Tender Brief Corrigendum : Tender For Proposed (G + 9) Storied Private Cabin Building Within The Premises Of Ipgmer- Sskm Hospital, Kolkata ------ Electrical Installation Works & Other Utility Services --- Supply Installation Testing and Commissioning of Silent Dg Set With All
City Kolkata
State West Bengal
Document Fees Refer document
EMD INR 231000.0 /-
Tender Value INR 1.15 Crore /-
Tender Type Tender
Bidding Type Open Tender
Competition Type Indian

Tender Details

Tender for Proposed (G + 9) Storied Private Cabin Building Within The Premises Of Ipgmer- Sskm Hospital, Kolkata ------ Electrical Installation Works & Other Utility Services --- Supply Installation Testing and Commissioning of Silent Dg Set With Allied Installation Work .

Corrigendum Details

Sr No CorrigendumDate Corrigendum CorrigendumType NewSubmissionDate
1 21-05-2026 Other Corrigendum Other 12-06-2026

Key Dates

Publish Date 21-05-2026
Last Date of Bid Submission 12-06-2026

Contact Information

Company Name Public Works Department
Contact Person Office of the SSE,KHEC,PWD
Address Kolkata Health Electrical Circle, P.W.Dte KIT Annex Building, 5th Floor KOLKATA.

BOQ Items

Name of Work:- Proposed (G + 9) storied Private Cabin Building within the premises of IPGMER- SSKM Hospital, Kolkata ------ Electrical Installation Works & Other Utility Services --- SITC of Silent DG Set with allied installation work .
Sl. No. Item Description
1SITC of 1010 KVA ,415V,50Hz 3Phase Silent aiesel Generator Set incl full tank HSD oil,comprising of Engine,Alternator, separate AMF panel ,Base frame ,Fuel tank,Battery,CPCB-Vl+ approved Engine & Acoustic Enclosure having following specifications, Engine deration calculation require to submit from Engine Manufacturer Only. Engine should not derate at 50 deg C.
2ENGINE :
3Make: VOLVO Penta/ Cummins/ CATTERPILLAR
4Engine Type : 4 Stroke Diesel Engine
5RPM : 1500
6Rated Output : 1180 BHP or Higher
7Duty : PRIME POWER
8Cooling : Coolant with radiator
9Cylinder : 12/16 \\"Vee\\"
10Aspiration : Turbo Charged after cooled.
11Type of Governer : Electronics/A1
12Fuel Tank Capacity : Minimum capacity 990 Liters Diesel Tank , with Inlet & outlet arrangement with Drain Plug and Air vents.
13Fuel Consumption at 50% rated Load with Radiator or Fan : 116.1 Ltr./ Hr. or Less
14Fuel Consumption at 75% rated Load with Radiator or Fan : 153.3 Ltr./ Hr. or Less
15Fuel Consumption at 100% rated Load with Radiator or Fan : 203.8 Ltr./ Hr. or Less
16Over Load Capacity: 10% Overload for one hour for every 12 hours continuous running at Full load or better
17Engine instrument Panel : Consisting of starting switch with Key, Lube Oil Indicator, water temperature Indicator, RPM indicator and hour mete.
18Safety Controls : Emergency Stop, Low Lube Oil Pressure warning/ Shutdown, High Engine Water Temp. warning/ Shutdown, Sensor failure Indicator, Engine overspeed indicator, Battery charging and low battery indicator
19Exhaust Silencer : Hospital grade
20Starting system : 12V/24V, srtarting system complete with starter motor, charging alternator with rectifier and Cutout as per manufacturer standard.
21Battery : Lead Acid, Low Maintenance or SMF and conforming to relevant IS Specification with Low/High Battery Voltage and Weak Battery warning
22ALTERNATOR:
23Make: Stamford /Crompton/ Leroy Somer
24Rating : 415 V., 3Ph. 50 Hz., 1010 KVA, 1500 rpm, 0.8 PF
25Type : Brushless, self excited and self regulated
26Insulation : Class High (Tempt.150 deg. to 270 deg.)
27Protection : screen-protected drip proof with Min.IP-23 degree of protection
28RPM : 1500
29Voltage Regulation (max) : ± 1/2% (Steady State) & Less than ± 1% (No load to full load). (Integrated Digital Electronic Voltage Regulator)
30Winding Connection: Star with Neutral (2/3 .Pitch, Stator- Double layer & Rotor - Dynamically balanced)
31Power Factor : 0.8 pf (lag)
32Total Harmonic distortion in output waveform: Less 5%
33Extended Busbar chamber for cable termination AMF to Alternator
34ACOUSTIC ENCLOSURE
35The DG set should have integrated acoustic enclosure at the manufacturing state itself with 11 tank process. High quality acoustict enclosure must be certified as per CPCB-II norms.
36BASE FRAME: Rugged in construction fabricated out of ISMC Channel for mounting the Engine, Alternator, Acoustic Enclosure etc. mounted on AVM pads and having provision for lifting Hook.
37AMF Panel
38Fabricating, Installing, Testing & Commissioning of weather proof AUTO-MATIC MAINS FAILURE of IP- 65 CUBICAL PANEL made from 14 SWG Sheet Steel, duly pretreated, powder coated painted and aesthetically finished, for operation of DG sets including auto bypass panel, suitable for 1010 KVA silent type DG set complete with relays, timers, set of CTs for metering & protection and energy analyser to indicate currents, phase and line voltages, frequency, power factor, KWH, Kilo Volt Ampere Reative Hour (KVARH), KVA (Phase & Total), KW & provision for overload, short circuit, restricted earth fault, under frequency, power (aluminum) and control (copper ) cabling of suitable size upto 15 meter between AMF panel, LT Panel and DG Set including connection interconnection etc. as required,
39all complete and inter locking and communication/ Ethernet /RS485/SNMP port open protocol for BMS integration including suitable software, the panel shall be of DG Set OEM make etc. as per approved by Engineering in charge and including the following:
40i) 415V, 1600 A (Full Load Current), 50KA, EDO type ACB with O/L, S/C, E/F protection and microprocessor based protection release , U/V release etc. (Master Pact ) NW/LK ('U Power\\" Series)/ABB Emax)-2 Sets
41ii) S&F of 2500 Amp capacity of Suitable size of Aluminium Bus Bar for 1010 KVA DG set having current carrying capacity 1.3 A / sqmm and also suitable for controlling of DG set having following specification/ features. Manufactured by the OEM/CPRI/Approved Panel builder & remote monitoring of internal temperature for every bus section & cable alley should be provided - 1 Set.
42iii) 415V, 1000 A , 50KA, EDO type ACB with O/L, S/C, E/F protection and microprocessor based protection release etc as outgoing to Chiller Panel. [Make: ABB, Legrand, Schneider] - 1 Set.
43iv) 415V, 1000 A , 50KA, EDO type ACB with O/L, S/C, E/F protection and microprocessor based protection release etc. as outgoing to Main Panel. [make: ABB, Legrand, Schneider] - 1 Set.
44v) In Built By-Pass switch for rated capacity for Engine & mains bypass.
45vi) On -delay timer for load change over
46vii) On-delay timer for engine shut off
47viii) Engine On-Off switch (Push button type), Emergency stop, nRemote Start/Stop Control. , Manual Run / Stop Control switch , Panel Lamp/ Lamp Test Control Switch
48ix) Mode selector for setting the panel on Auto/ Man/ Test Mode
49x) Battery charger completer with voltage regulator, booster selector switch, on-off- switch, voltmeter and ammeter for charging the battery from mains. This will be in addition to the battery charging alternator fitted on the engine.
50xi) Minimum five number indicating lamps to indicate 'mains ON', 'load on mains', Set running', 'load on set' and 'battery charger on'.
51xii) Audio visual alarm for Low lubricating oil pressure, \\"High,' coolant temperature Start failure ,and DG over load\\".
52xiii) Microprocessor based relay with composite meter for digital display of following
53a) Generator voltage/AC Mains voltage.
54b) Generator & Mains Current in all phases incl neutral current. Harmonic etc
55c) Frequency
56d) Power Factor
57e) Indication for alternator supply
58f) Running time indication number of hoursof operation and service intervals, service due indication
59The AMF panel must be designed to ensure trouble free performance and ensure switching over Electrical Load to DG within 15 (fifteen) second from the instant of mains failure.
60Supply & Installation of exhaust pipe line (thickness minimum 4 mm) connection with MS black pipe ISI approved necessary flange, nuts, bolts, washers & gasket incl electrical welding where necessary for following sizes:
61350 mm NB MS heavy type black pipe
62250 mm NB MS heavy type black pipe
63350 mm NB MS heavy type long bend
64250mm NB MS heavy type long bend
65350 mm x 250mm NB MS heavy type reducing \\"T / \\"Y\\" piece
66350 mm NB MS Plug incl socket with short piece
67S & F rain protection canopy suitable for 350 mm dia MS exhaust pipe
68Making insulation by wrapping with 3\\" thick glass wool including netting arrangement and covered with 26 SWG aluminium clading as per direction of the EIC for following sizes:
69For 350 mm NB exhaust pipe
70For 250 mm NB exhaust pipe
71For Residential type silenser pipe for 1010 KVA.
72Painting the MS black pipe by Aluminum paint (for high temperature application) of two coat over the R.O. primer (Approved paint) for following sizes:
73for 350 mm NB exhaust pipe
74for 250 mm NB exhaust pipe
75S & F MS angle iron structure made of (80x80x6)mm / (50x6)mm MS angle / Flat to support Exhaust pipe / Chair for AMF panel, etc. Incl painting and foundation if any as per GS. [for continuous vertical suuport of 1 set exhaust pipe along G+9+1 storied building wall and vertical supports of horizontal run at suitable interval]
76S & F special type MS angle iron bracket support made of 40x40x6mm MS angle with flat iron clamp with nut bolts washers etc suitable for 350mm dia (vertical run).
77S & Delivery of 200 ltr capacity barrel made of 2mm thick MS sheet.
78Supply, transporation & pouring of HSD Oil
79Supply, transporation & pouring of Engine Oil
80Supply & delivery of best quality hand pump for pumping diesel with 1\\" dia PVC flexible pipe (10 mtrs) (Brand approved by EIC)
81Hiring charges for scaffolding by bamboo, coir rope by square type arrangement for smooth working and lifting of MS black pipe for vertical installation including dismantling after completion of work.
82Supply & Laying of 1.1 kV grade 16 core 2.5 sq.mm. PVC Armoured Copper conductor cable (RR Kabel/ KEI/Havells/ Gloster/Polycab) through masonery trench/prelaid pipe for control wiring & interconnection of DG set with AMF panel.
83Supply & Laying of 1.1 kV grade 3 core x 4 sqmm PVC Armoured Copper conductor cable (RR Kabel/ Havells /KEI/Gloster/Polycab) through masonery trench/prelaid pipe for auxiliary AC & DC power supply of battery charging between DG set & AMF panel.
84S & F compression type brass cable gland & finishing the cable end for 16 core 2.5 sqmm PVC/A copper cable
85S & F compression type brass cable gland & finishing the cable end for 3 core 4 sqmm PVC/A copper cable
86Supply & Laying of 1.1 kV Grade 2 run x 800 sqmm single core PVC/XLPE Ar. Aluminium cable (Make: Polycab/ RR Kabel/ KEI/ Havells/Gloster) from 1010 KVA DG Alternator terminal to AMF panel through HDPE pipe incl. S/F HDPE pipe in masonry cable trench as per direction of EIC.
87Supply & Laying 1.1 kV GR 2 run x 300 sqmm single core PVC/XLPE Ar./Copper conductor cable (Make: Polycab/ RR Kabel/ KEI/ Havells/Gloster) through HDPE pipe incl. HDPE pipe on wall / floor from neutral earth bus to DG set neutral point including both side socketing gland and finishing as per direction of EIC. (Make: Havells/ Polycab/ RR Kabel)
88Supply & making end termination with Brass double compression gland and finishing the end of conductor by crimping method by aluminium lugs for 800 sqmm XLPE 2v insulated aluminium conductor cable ofl .1 kv Grade as required.
89S & F EI danger board. (size : 20 cm x 30 cm)
90S & F 2 Kg capacity Gas pressure (DCP) fire extinguisher on wall by suitable size of iron bracket (Make - Fire Shield / Surex)
91Terms and Condition:
92Rate should be quoted inclusive of all applicable taxes and duty etc.
93All materials, equipments & accessories must confirm to relivent IS Specification. The DG set to be supplied must be from the authorized OEM of the respective Engine Manufacturer.
94Necessary Manufacturer's test certificate for Diesel Engine,Alternator etc. will have to submit in triplicate copy during delivery for the equipment.
95Copy of \\"Type Approval Certificate\\" and Certificate of \\"COP\\" must be produced at the time of delivery issued from component Authority (As per COP-II)
96Cicuit Diagram for AMF panel must be submitted from the Manufacturer / OEM
97The entire set must be warranted at least 15 months from the date of Delivery/12 months / 5000 Hrs from the date of commissioning whichever is latter. However Engine & Alternator should be warranted of 2 years/5000Hrs, whichever is earlier.
98Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/submission of bill.
99If any refurbished material is supplied and installed, penal action will be taken as per existing rules
100(Rates should be Quoted inclusive of all taxes & duities and L.W.C. @ 1% as applicable) Please Enable Macros to View BoQ information

Other Detail

Information Source https://tenders.wb.gov.in/nicgep/app
Download FileName File Description File Size
Download 3c59a526-1a00-4ef9-a970-c4bd75e21e3f.html Tender Documents 0 KB
Download BOQ_5081938.xls Tender Documents 0 KB
Download tech_prebid_5081938.pdf Tender Documents 0 KB
Download Tendernotice_1 (11).pdf Tender Documents 0 KB
Download Tendernotice_2 (2).pdf Tender Documents 0 KB
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.