| 1 | Dismantaling,reinstallinig & commissioning of Floor Mounted/Celing Suspended Chilled water Air Handling Unit at different floor of Chest & cancer building,AHU capacity Upto 5400CFM |
| 2 | Dismantaling,reinstallinig & commissioning of Celing Suspended Refrizerant IDU/ Air Handling Unit with proper Gas locking,Nitrozen pressuring & vaccum at 2nd floor of Chest & cancer building,AHU capacity Upto 2200CFM |
| 3 | Dismantaling,reinstallinig & commissioning of Celing Suspended Indoor Unit with proper Gas locking,Nitrozen pressuring & vaccum at Different floor of Chest & cancer building, capacity Upto 2TR . |
| 4 | Dismantaling,reinstallinig & commissioning of Out Door Unit of Concealed split type with proper Gas locking,Nitrozen pressuring & vaccum at Different floor of Chest & cancer building, capacity Upto 2TR . |
| 5 | Dismantaling,reinstallinig & commissioning of split type air conditioner both indoor & Out Door Unit with proper Gas locking,Nitrozen pressuring & vaccum at Different floor of Chest & cancer building, capacity Upto 2.2TR . |
| 6 | Dismantaling,reinstallinig & commissioning of Window type air conditioner at Different floor of Chest & cancer building,capacity Upto 2TR. |
| 7 | S&F of Copper Refrigeration pipe line for liquid and suction line with hard/soft drawn copper piping with supports & brackets (Make:Rajco/Ryoku/Nippon) |
| 8 | Liquid Line ( 1/4\\" dia) with 19mm thick nitrile insulation |
| 9 | Liquid Line ( 3/8\\" dia) with 19mm thick nitrile insulation |
| 10 | Suction Line (1/2\\" dia) with 19mm thick nitrile insulation |
| 11 | Suction Line (5/8\\" dia) with 19mm thick nitrile insulation |
| 12 | S& L of 4 Core 2.5sq. mm. copper control Cable (As Control Cable from ODU to IDU ) (Make : Havells/ Gloster/ Polycab/KEI). |
| 13 | Supply,Design,Fabrication & Installation of GI Duct, Class - VIII grade (120 GSM) supply & return air duct as per approved drawing along with necessary supports, hangers, flanges etc. as required and as per IS 655 and IS-277 standards of following gauges. (As per direction of E.I.C) (Make- SAIL/TATA/JINDAL) |
| 14 | 24 SWG thick . |
| 15 | 22 SWG thick . |
| 16 | Supply & fixing of milky while powder coated Aluminium extruded supply air diffusers/grilles with VCD (As per direction of E.I.C) (MAKE: SYSTEMAIR/DYNACRAFT/AIR ENT/RUSKIN) |
| 17 | Supply & fixing of milky while powder coated Aluminium extruded return air diffusers/grilles without VCD(As per direction of E.I.C) (MAKE: SYSTEMAIR/DYNACRAFT/AIR ENT/RUSKIN) |
| 18 | Supply and fixing of GI Duct Damper (MAKE: SYSTEMAIR/DYNACRAFT/AIR ENT/RUSKIN) |
| 19 | Supply & fixing of Fresh air package with damper, cowl and bird net arrangements (As per direction of E.I.C) |
| 20 | Supply & fixing of fire-retardant Canvas Connections for AHU/IDU and Duct. |
| 21 | Supply and fixing of 10 mm thick Acoustic insulation of duct with fire retardant, open cell class 1 tri-dimensional chemically crosslinked polyethylene foam insulation and having minimum density of 140-180 kg/cum. Insulation material including applying OEM recommended suitable adhesive on the inner side of duct (As per direction of E.I.C).(MAKE: KFLEX/ARMACELL/AFLEX) |
| 22 | Supply and fixing of 19 mm thick duly laminated Aluminium foil of mat finish closed cell Nitrile rubber Insulation, class “O” insulation on supply and return duct after applying OEM recommended suitable adhesive for Nitrile rubber. The joints shall be sealed with 150 mm wide same nitrile rubber insulation materials and Aluminium tape wherever required (As per direction of E.I.C).(MAKE: KFLEX/ARMACELL/AFLEX). For INDOOR Area & Out side Drop celing. |
| 23 | Supply and fixing of 75 mm thick TF quality, 16 Kg/CuM density Expanded Polystyrene slab by using suitable bituminous compound, sealant, GI washer, GI wire and complete facing with 22 SWG GI Chicken wire mesh having maximum 1-inch hexagonal gap and finally with 12 mm thick sand cement and plaster (As per direction of E.I.C). (MAKE: BEARDSEL/ASTHA/OWENSCORNING). For OUTDOOR Area. |
| 24 | Supply, fabrication & fixing of 2 Nos. M.S Angle (45x45x5mm) with supporting angle (25x25x5mm) incl. 4\\" bullet fastener, washer etc. for Window AC Machine incl. Painting with 2 coat of synthetic enameled paint over 2 coat of RO primer (Asian/ICI/ Baerger) support with all accessories and also S&F 20 SWG galvanized base tray for WRAC type AC machine & outside covering of refrigerant pipe if required for water Storage with 1/2 inch ripple fixing by Clamping arrangment as per direction of EIC incl. scafolding, welding, carriage and transportation, dismantling, cutting, fabrication & re-installing window grill with 2 nos. window type Air condition machine support with all accessories. |
| 25 | Supplying, fitting and fixing PVC pipes of approved make of Schedule 80 (medium duty) conforming to ASTMD - 1785 and threaded to match with GI Pipes as per IS : 1239 (Part - I). with all necessary accessories, specials viz. socket, bend, tee, union, cross, elbo, nipple, longscrew, reducing socket, reducing tee, short piece etc. fitted with holder bats clamps, including cutting pipes, making threads,fitting, fixing etc.complete in all respect including cost of all necessary fittings asrequired,jointing materials and two coats of painting with approved paint in any position above ground. |
| 26 | (a) For Exposed Work (PVC Pipes) (25 mm)(Make:Supreme/Finolex/Approved make) |
| 27 | Supply & Fixing of perforated GI drain tray with perforation not more than 17.5% suspended from ceiling incl. S&F GI connector, 6mm dia MS suspender, bolts & nuts, steel fastener etc. as required of the following size. Incl. Al painting of MS support |
| 28 | With 25x25x3mm angle iron support200x50x1.25mm (18 SWG) |
| 29 | Supplying, fitting & fixing in position suspended boxing for return /supply air arrangement for ducting with frame work of aluminium hollow section of size 50mm x25mm (2.0mm thickness) combined with aluminium corners of size 38mm x 25mm, suspended by aluminium hollow tube section of size 38mm x 25mm ,25mm x 25mm powder coated wall angle with aluminium composit panel of thickness 3.0mm comprising of protective film, polyester coating, primer, aluminium coil, adhesive film, polyethylene core again with one layer adhesive film, aluminium bottom coating and finally service coating as per manufacturer's specification finished with aluminium screw and silicon sealent including suitable arrangement for grill fixing complete in all respect as per direction of EIC. |
| 30 | a) Drop Celing |
| 31 | b) Trap door |
| 32 | Supply and fixing 50 mm thick TF for Underdeck, quality 16 Kg/CuM density Expanded Polystyrene slab on the ceiling by using suitable bituminous compound, sealant, GI washer, GI wire and complete facing with 22 SWG GI Chicken wire mesh having maximum 1-inch hexagonal gap. (As per direction of E.I.C).(MAKE: BEARDSEL/ASTHA/OWENSCORNING) |
| 33 | Hiring charges for scaffolding arrangement including dismantling at the end of work and carriage. |
| 34 | Carring Cost of the above Materials from Co's workshop to Site by own transportation cost incl. loading and unloading of the materials by own manpower. |
| 35 | Supply, design, fabrication, installation of MS structural work for IDU/AHU supports,ODU Platform etc as per site requirement (As per direction of E.I.C) |
| 36 | Less Cost for old dismantled iron structures of AC System Rs.10,000.00 |
| 37 | The Agency must procure the materials from the Manufacturer / OEM or from their authorised sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them. Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/ submission of bill.If any refurbished material is supplied and installed, penal action will be taken as per existing rules |
| 38 | Defect Liability Period - 1 (One) year after completion of work |
| 39 | Make & model of each and every material to be approved by EIC Please Enable Macros to View BoQ information |