| 1 | 1008 KVAR, 7.2 KV, 3 PHASE, 50HZ CAPACITOR BANK COMPRISING WITH 6 NOS OF 168 KVAR, 4.15 KV, 1 PHASE EXTERNAL FUSE DESIGN CAPACITOR UNITS CONNECTED IN STAR FORMATION. THE CAPACITOR BANK SHALL BE PROVIDED WITH 3 NOS OF HRC FUSES IN LINE SIDE IN TERMINAL COVER ARRANGEMENT. THE CAPACITOR UNIT SHALL CONFORM TO AS PER LATEST IS: 13925 (PART-1)/1998 STANDARDS, (OUTPUT-700 KVAR @ 6 KV ) |
| 2 | SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF MICOM 220 NUMERICAL RELAY FOR MOTOR PROTECTION FEEDER.( MAKE- SCHNEIDER) |
| 3 | NUMERICAL OVER & UNDER VOLTAGE RELAY PROK DVSR ( PNVNSP)TYPE STATIC RELAY WITH OUTPUT CONTACTS, IMPULSE VOLTAGE WITHSTAND TEST CLASS II, RATED VOLTAGE DC IN VOLT - 110, RATED VOLTAGE AC IN VOLT- 220, RATED CONTINUOUS CURRENT AC IN A - 10, RATED CONTINUOUS CURRENT IN DC IN A- 10, RATED INSULATION VOLTAGE IN VOLT- 1000, FREQUENCY OF OPERATION IN CYCLES PER HOUR- 36000, IP RATING- IP50, OPERATING TEMPERATURE- 0 C TO 60 C |
| 4 | SCHEDULE OF RATES FOR EARTHING INSTALLATIONS.Earthing Installation by GI pipe ... (FOR Sub(stationNeutral/Equipment earthing)Earthing with 80 mm dia GI pipe (TATA(Medium)x 3.0 Mts. long and 1 x 19/8 stranded GI (HOT Dip) wire (4 Mts. long), 25 mm dia x 150 mm long galvanized bolt, double nuts, double washers including socketing at both ends of stranded GI (h)ot Dip) wire by crimping sockets/ thimbles and S & F 40 mm dia GI pipe (ISI Medium) protection (3 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level to an average depth of 3.65 Mts |
| 5 | Earth busbar Supplying & fixing earth busbar of galvanized (HOT Dip) MS flat 50 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required |
| 6 | Supplying of the following HIGH TENSION XLPE Cables (make:Polycab/Gloster/Havells):3Core x 150 sq mm 6.6 KV (E)XLPE |
| 7 | Laying through Masonry Trench.(b)Laying of one cable above 150 sqmm and upto 300 sqmm through existing covered masonry trench incl. taking out RC covers, setting them in order, mending good the damages filling the trench with fine dry sand incl. supplying sand |
| 8 | Laying on Wall / surface with Saddles / clamps.(e)Laying of cable above 3... core 90 sqmm and upto 3... core 150 sqmm on wall/surface including S & F MS clams with earthing attachment in 2 x10 SWG GI (HOT Dip) Wire, making hole etc. as necy., mending good damages and painting |
| 9 | Laying through RCC/Hume/GI Pipe.(b)Laying only Cable above 50 sqmm but not exceeding 400sqmm through existing RCC/ Hume/GI Pipe/open masonary trench FOR single, 2, 3, 3... and 4 core |
| 10 | A N N E X U R E - I Basic Rate of Materials: (All Rates of materials from K-1 to K-14 are excluding VAT) 128. 100mm GI pipe (ISI-Medium) |
| 11 | Making Indoor type End termination Joint by providing all required terminal joints accessories {viz Heat Shrink Type End Termination Jointing Kits complete with all accessories for 3 core 6.6KV(UE)-11KV (E) XLPE Screened Cable, Aluminium Conductor}& man/equipments tools & tackles etc with the relevant Switch Gear inside the Pumping Station or Switch Room with care & caution including compliance of relevant safety norms & conforms to the relevant IS and complete in all respect as per direction of EIC. 3 core 6.6KV (UE)-11KV (E) XLPE Screened Cable, Aluminium Conductor of following Sizes 120-185 Sq mm Indoor type Heat Shrinkable Joint (Rechem KIT No- EPKT 3111) |
| 12 | Supplying of 1.1 KV. Grade PVC insulated Conductor of following cables (make: Polycab/ Gloster/Havells/):Size in Sq. mm, No & dia. of wire in mm , No of Core - 4 1/2.24 4 |
| 13 | Laying through Underground Trech.(a)Laying of one No. cable upto 35 sqmm in underground trench 460 mm wide x 760 mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per metre, including filling the space between the brick & cable and also the trench with shifted soil, leveling up and restoring surface duly rammed |
| 14 | Laying through Floor/ Pavement/Wall.Laying of cable as below, after cutting floor/pavement/wall/ and making holes incl., embedding the cable at an average depth as below and mending good the damages to original finish incl. removing the rubbish.(i)From 2.5 sqmm to 35 sqmm at an average depth of 75 mm in floor/pavement/wall etc. |
| 15 | A N N E X U R E - I Basic Rate of Materials: (All Rates of materials from K-1 to K-14 are excluding VAT) 70. 1.5 sq.mm 'FR' stranded Copper Wire |
| 16 | A N N E X U R E - I Basic Rate of Materials: (All Rates of materials from K-1 to K-14 are excluding VAT) 71. 2.5 sqmm'FR' stranded Copper Wire |
| 17 | Supply and delivery of Electronic Timer suitable for 240/ 360/415V, 50 Hz(Make: L&T/ABB/Schneider/Simence/ GE/Minilic) of the following time (Second) range: 12.0 to 120.0 |
| 18 | Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connection Seimens 6-32 A DP |
| 19 | S/F 230V, LED indicating lamp, (other colurs) |
| 20 | S/F 230V, LED indicating lamp, (Blue & White) |
| 21 | Supply and delivery Modular Push button actuators(with plastic front ring),Illuminated actuator (with holder for contact block) (Make: L & T/ABB/ Schneider/Simence/ GE)Rised, colour: Red,green,blue, Amber, white, yellow, clear |
| 22 | Supply, and fixing of HT insulation rubber Mat of the following sizes :-2.5 mm thick (upto 11 KV) |
| 23 | S UPPLY, INSTALLATION & COMMISSIONING OF POWER PACK WITH BATTERY BACK UP I/P- 240V AC, 50 HZ O/P- 110 V DC MODEL- APP230110SNS STORED 110 WATT SEC & NON STORED 110 WATT SEC ( HSN CODSE 85044090) , MAKE: ALAN ELECTRONICS SYSTEM PVT LTD |
| 24 | SURGE ARRESTERS, 240/415 V, PROTECTION LEVEL UPTO 1.5- 1.9 KV, RATED DISCHARGE CURRENT UPTO 40 KA, 3P+ N POLE, TYPE- SSD74 RATE IS COLLECTED FROM APROVED RATE , APPROVAL DONE BY D.G.(W.S.) DATED ON 21/08/2019 |
| 25 | BUILDING WORKS (B) DISMANTLING, CUTTING CHASE, HOLES ETC. 1. Dismantling all types of masonry excepting cement concrete plain or reinforced, stacking serviceable materials at site and removing rubbish as directed within a lead of 75 m. (a) In ground floorincluding roof. |
| 26 | BUILDING WORKS (B) DISMANTLING, CUTTING CHASE, HOLES ETC 2. Dismantling all types of plain cement concrete works, stackingserviceable materials at site and removing rubbish as directed within a lead of 75 m In ground floor including roof. (a) upto 150 mm. thick |
| 27 | BUILDING WORKS ( C ) Brickworks,Concrete Works etc A. BRICK WORKS 5. Brick work with 1st class bricks in lime and surki mortar (1:2) (1 lime putty/paste: 2 surki) lime to be slaked at site and the mortar to be prepared with such lime putty and first class surki made from kiln burnt bricks having its fineness modulus between 2 and 2.5 and which passes through B.S. sieve No 8 with correspondes to I.S sieve No 200 with considerable grinding and pugging it complete. a) In foundation and plinth |
| 28 | SECTION 1. ------------BUILDING WORKS (I) PLASTERING, POINTING ETC. A. ORIGINAL WORKS 1.Plaster (to wall, floor, ceiling etc.) with sand and cement mortar including rounding off or chamfering corners as directed and raking out joints including throating, nosing and drip course, scaffolding/staging where necessary (Ground floor).[Excluding cost of chipping over concrete surface] i) With 1:6 cement mortar (a) 25 mm thick plaster |
| 29 | BUILDING WORKS (F) STRUCTURAL STEEL WORKS, GRILLS, GATES ETC. A. ORIGINAL WORKS 1. M.S. structural works in columns, beams etc. with simple rolled structural members (e.g. joists, angle, channel sections conforming to IS: 226, IS: 808 & SP (6)- 1964 connected to one another with bracket, gussets, cleats as per design, direction of Engineer-incharge complete including cutting to requisite shape and length,fabrication with necessary bolting, metalarc welding conforming to IS: 816- 1969 & IS: 1995 using electrodes of approved make and brand conforming to IS:814- 2004, haulage, hoisting and erection all complete. The rate includes the cost of rolledsteel section, consumables such as electrodes, gas and hire charge of all tools and plants and labour required for the work including all incidental chages such as electricity charges, labour insurance charges etc. Payment to be made on the basis of calculated weight ofstructural members only in finished work as per IS specified weight. Payment for gusset, bracket, cleat, rivets, bolts and nuts may be make by adding the actual weight of such items with the weight of finished structural members or 7% of weight for finished structural members weighing not less than 22.5 Kg. / m. or 15 % of weight for finished structal members weighing less than 22.5 Kg. / m. may be increased allow for bracket, cleat, rivet, bolts and nuts etc. and no seperate payment being made for these items, as per direction of Engineer In Charge. The rates are considered for a height of erection 8m. / 2nd floor level from the ground. Add 1.5% extra over the rate foreach additional floor or 4m. beyond initiial 8m. or part thereof. I) For structural members of specified sections weighing less than 22.5 Kg./m |
| 30 | SR. ELECTRICIAN GRADE-I |
| 31 | MATERIALS AND LABOUR (B) Labour Rates Per Diem 3. Mazdoor (Male) Note: (I)The above rates of labour are exclusive of 10% contractors profit and 1% Labour welfare cess which would be admissible to the Contractors, but contractual percentage will not be applicable.(II) The workersemployed on high rise building or any structure over 30 ft in height and also workers engaged in Tunnel shall be paid 20% extra wages |
| 32 | TOTAL ESTIMATED AMOUNT |
| 33 | ADD : 9% SGST |
| 34 | ADD : 9% CGST |
| 35 | ADD : 1% LWC Please Enable Macros to View BoQ information |