| 1 | Safe carriage of following material from store center PVVNL to site of work with loading and unloading at both ends. |
| 2 | 13 Mtr./11 Mtr./9 Mtr./8.5 Mtr Long PCC Pole. |
| 3 | 11 KV VCB O/G CTR 200/100/5A, 350MVA 1250A |
| 4 | Cable Jointing Kit 3x185 I/D & O/D |
| 5 | ACSR Weasel/Rabit Conductor. |
| 6 | 11 KV XLPE Cable Size (3x185)sqmm |
| 7 | 11 KV Disc Insulator with fitting/11 KV Pin insulator with pin. |
| 8 | Earthing set complete/Stay Rod set Complete. |
| 9 | 11 KV V-Type cross Arm. |
| 10 | Erection/Fixing & laying/Installation of following materials as per RESPO manual and as per direction to Supervising Engineer (complete in all respect). Work includes the cost of labour, T&P by providing nut, bolt, Stone pad, G.I. Pipe 6\\" dia and all other acessaries/material for proper completion of work. |
| 11 | For 11 KV Line, Double Pole structure with 13/11/9/8.5 Mtr. long PCC Poles :- Excavation of foundation pit in size of 75x45 cm. having depth of 1/6th of the full length of the support (pole). Erection of support (pole) complete work by fixing of D.P. Clamps and all other accessories. The work includes fabrication work and fixing of cross bracing sets, cutting holes complete work as per RESPO Norms. |
| 12 | For LT/11 KV Line, Single Pole structure with 13/11/9/8.5 Mtr. long PCC Poles :- Excavation of foundation pit in size of 75x45 cm. having depth of 1/6th of the full length of the support (pole). Erection of support (pole) complete work by fixing of all other accessories. The work includes fabrication work and fixing of cross bracing sets, cutting holes complete work as per RESPO Norms. |
| 13 | Grouting of Poles Single line support :- Grouting of support in CC 1:4:6 (cement, sand and 40 mm. brick ballast) Grouting will be done in the block of size 45cm x 45cm x 1/6th of full length of the support upto ground level as per RESPO Norms. |
| 14 | Fixing and Grouting of stay rods (20x1800mm.) including all works of excavation, cement concrete in size of (0.60x0.60x0.30)M in the ratio of 1:4:6 (cement, sand and 40 mm. brick ballast) including back filling of soil and proper ramming etc.Fixing, tightening and nozelling of stay wire with stay rod and stay insulators with the pole of required tension by providing stay clamps, nuts, bolts etc. |
| 15 | Earthing of support with MS Earth Rod of (20x2500)mm. long including excavation of pit and driving MS Rod 3.0M apart from support and 0.5M below the ground level and connecting below the earth electrodes with the help of G.I. Wire No.6 SWG tightening with nuts and bolts. |
| 16 | Installation of VCB & Testing Comissioning as per respo norms. |
| 17 | Laying, sagging, stringing and binding of ACSR/Dog/Rabbit/weasel conductor with all other accessories on pole as per respo norms. |
| 18 | Laying of 11 KV XLPE Cable by digging/driling under Railway Track as per respo norms. |
| 19 | Making of trench for XLPE Cable as per respo norms. |
| 20 | Laying of Double Circuit 11 KV XLPE Cable Size 3x185sqmm with making proper connection as per respo norms. |
| 21 | Guarding of 11 KV Line as per respo norms. |
| 22 | Providing and Fixing of Holding/F-bracket clamps with bolts & nuts. |
| 23 | Providing and fixing of Different size clamp. |
| 24 | Providing and fixing of Stonepad of size 300x300x75 |
| 25 | Providing and fixing Barberd wire. |
| 26 | Provide and fitting of MS Dropper Channel/Top Channel |
| 27 | Provide and fitting of MS T-off channel/MS angle |
| 28 | Providing and fixing of Number Plate and Danger Board with Nut and Bolts. |
| 29 | Providing and fixing of HDPE Pipe (120mm) as per respo norms. |
| 30 | Safe carriage of following material from site to PVVNL store centre work with loading and unloading at both ends. |
| 31 | Weasel Conductor scrap. |
| 32 | Iron scrap. |
| 33 | Old VCB Please Enable Macros to View BoQ information |