| 1 | Supply and laying of 3.5CX 185 sq.mm Armoured Aluminium cable 650/1100V grade as per IS 7098(Part 1) 2011,Double run (2 Run) PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering. Make: KEI/ Gloster/ Universal/Polycab |
| 2 | Above 95 sq. mm and upto 185 sq. mm |
| 3 | Supply and laying of 3.5CX 185 sq.mm Armoured Aluminium cable 650/1100V grade as per IS 7098(Part 1) 2011,Double run (2 Run) PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. Make: KEI/ Gloster/ Universal/Polycab |
| 4 | Above 95 sq. mm and upto 185 sq. mm |
| 5 | Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep) and re-filling etc. as required |
| 6 | 100 mm dia |
| 7 | Supply, Installation ,testing & Commisionioning (SITC) of outdoor CPRI certified cubical Feeder pilar with EC grade Al busbar capacity 630Amp. 100% netural suitable >25ka for 3 sec for fault level ,compatiable for following incomming & outgoing . Custum built self fabricated out of 16SWG , CRCA sheet Foot mounted type Panel Furnished with siemen gray shade powder coated paint after necessary pre treatment fully dust & vermin proof, Copper wire ,Lugs and Netural & Insulating Material Engineering and Labor Charges ,Panle size (H-W-D)mm. Details as Incoming-SFU400 Amp. 2 nos. & 6 nos-HRC fuse, Incomer All Busbar capacity 500 Amp. Phase indicating light shall be protected by 6 amps MCB‟s. - 3 Sets, AVF Meter - 01 No Outgoing Deatils TP MCCB-160 Amp. 02 Nos, TP MCCB-100 Amp. 03 Nos, (Range 40A -630A , Protaction against overload, and short circuit) , 01 No of Timer 63A FP MCB 0-24 hours Astronomical timer auto / manual by pass selector switches Cubicle Type 1 nos. Note-MCCB Make Legrand, L& T, Simenice,Schneider etc. Electrical Panel.Make : Allied Engineers/Electrocare/Electro craft |
| 8 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 Kv grade as required. |
| 9 | 3½ X 185 sq. mm (57mm) |
| 10 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 11 | Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) |
| 12 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required. |
| 13 | 160 mm dia (OD-160 mm & ID-135 mm nominal) |
| 14 | Supplying and making cable route marker with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size ) of size 60 cm X 60 cm at the bottom and 50 cm X 50 cm at the top with a thickness of 10cm including inscription duly engraved as required. Please Enable Macros to View BoQ information |