Tendering Authority Military Engineer Services
Tender No 89848/SIL/E8
Tender ID 2026_MES_752603_2
Tender Brief Tender For Provision Of Single Living Accn With Sanitary Block And Allied Works At Aizawl Under Ge Silchar.
City Aizawl
State Assam
Document Fees INR 3000 /-
EMD INR 686050.0 /-
Tender Value INR 7.22 Crore /-
Tender Type Tender
Bidding Type Open Tender
Competition Type Indian

Tender Details

Tender for Provision Of Single Living Accn With Sanitary Block And Allied Works At Aizawl Under Ge Silchar.

Key Dates

Publish Date 23-05-2026
Last Date of Bid Submission 13-06-2026
Tender Opening Date 15-06-2026

Contact Information

Company Name Military Engineer Services
Contact Person CE SHILLONG ZONE
Address HQ CE SHILLONG ZONE, SPREAD EAGLE FALLS, SHILLONG MEGHALAYA 793011

BOQ Items

Name of Work:- PROVISION OF SINGLE LIVING ACCN WITH SANITARY BLOCK AND ALLIED WORKS AT AIZAWL UNDER GE SILCHAR.
Sl. No. Item Description
1\\" BOQ \\" BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority : Chief Engineer Shillong Zone NAME OF WORK: PROVISION OF SINGLE LIVING ACCN WITH SANITARY BLOCK AND ALLIED WORKS AT AIZAWL UNDER GE SILCHAR. Contract No: CESZ/SIL/ OF 2026-2027 Bidder Name : GENERAL SUMMARY (SCHEDULE OF WORKS) (This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # NUMBER # Sl.No. Description of Parts/ Item Item Code / Make No. orQty. Unit Pre Priced Rate (in. Rs.) as Defined by MES Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency RATE In Figures To be entered by the Bidder Rs. Ps. Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT in Figure TOTAL AMOUNT With Taxes TOTAL AMOUNT In Words Represent (%) Percentage having Above/ Below ( + or - denomination) the Lump sum pre price inserted by MES
2NOTE:- (Applicable for all parts/items/):- The bidders/contractors are advised to read tender document, all drawings & all corrigendum/ amendments and General conditions of contracts before entry/quoting the rates.
3Lumpsum price workedout by the tenderer for BUILDING & STRUCTURE WORKS as listed in Schedule ‘A’ Part-I
4Lumpsum price worked out by the bidder/ tenderer for SITE CLEARANCE, SITE DEVELOPMENTS & EARTH WORKS as listed in Schedule 'A' Part-II.
5Lumpsum price worked out by the bidder/ tenderer for INTERNAL ELECTRIFICATION as listed in Schedule 'A' Part-III
6Lumpsum price worked out by the bidder/ tenderer for ROAD, PATH, CULVERT AND HARDSTANDING as listed in Schedule 'A' Part-IV.
7Lumpsum price worked out by the bidder/ tenderer for SEWAGE DISPOSAL as listed in Schedule 'A' Part-V.
8Lumpsum price worked out by the bidder/ tenderer for AREA DRAINAGE as listed in Schedule 'A' Part-VI.
9Lumpsum price worked out by the bidder/ tenderer for FENCING AND GATE as listed in Schedule 'A' Part-VII.
10Lumpsum price worked out by the bidder/ tenderer for RCC/STONE MASSONRY RETAINING WALL as listed in Schedule 'A' Part-VIII
11Lumpsum price worked out by the bidder/ tenderer for SUMMER APPLIANCE as listed in Schedule 'A' Part-IX.
12Lumpsum price worked out by the bidder/ tenderer for LIGHTNING PROTECTOIN as listed in Schedule 'A' Part-X.
13Lumpsum price worked out by the bidder/ tenderer for EXTERNAL WATER SUPPLY as listed in Schedule 'A' Part-XI.
14Lumpsum price worked out by the bidder/ tenderer for EXTERNAL ELECTRIC SUPPLY as listed in Schedule 'A' Part-XII.
15Lumpsum price worked out by the bidder/ tenderer for INTERNAL WATER SUPPLY as listed in Schedule 'A' Part-XIII.
16Sch 'A' Sec-XIV (Miscellaneous Items) Note : This schedule is not pre-priced by MES and the pre-priced rate indicated as \\"Rs 0.00\\" under Col. 5 siginifies this fact only.
17S&fx electric water heater storage type, steel body with copper inner tank and heating element upto 2 kW capacity 50 litres, BEE 5 star rated complete with all accessories such as safety valve, thermostate, NRV, connection pipe complete all as specified and directed.
18S&F, testing and commissioning of voltage stablizer for automatic operation, single phase, naturally air cooled, indoor type, designed for input variation between 170V to 250V with stablized output voltage at 230V with accuracy of ±2.5% and of capacity 1.0 kVA complete all as specified and directed.
19Supply, install, testing and commissioning of 11kV 630 Amps 21 KA for 3 Sec. SF6 insulated, both side extensible, outdoor duty Ring Main Unit (RMU), fully motorized, in combination of 01 No VCB modules as incomer, 01 Nos Load Break Switch as Outgoing consisting of copper busbar in SF6 insulated 304 (Non-Ferrite Non-Magnetic Grade) stainless steel enclosure of thickness 2.5 mm with manometer fixed on the tank. The Breaker shall have mechanical ON /OFF indicator with hand trip device and control spring charging, spring release coil. The HV switchgear and gear should be confirming to IEC-62271-1,100,200. The RMU with gas tank should be internal arc tested for 21KA for 1 second with IAC-AFLR classification for gas tank. The complete RMU mimic and cable chamber should be covered by single door to have ingress protection IP) of minimum IP54. The RMU design should support site replaceable HT cable bushing and VI of VCB should be RMU Manufacturer’s own make. (At 457 FD Hospital Area)RMU Should have followings: • 01 no. microprocessor based self-powered numerical relay with over Current/ earth fault & short circuit protection (with RS 485 port and Modbus protocol) in each VCB feeder. Relay should display each phase current. • 03 Nos Protection CT shall be of Burden 2.5VA, Ratio 200-100/1A, Class of Accuracy class 5P10 for O/C and E/F protection for each VCB outgoing feeder (CT ratio is indicative and may vary during detailed engineering) monitoring On/Off/Trip, VCB, relay, energy meter, Gas pressure monitoring & other parameter etc., to brought to a dedicated set of Terminal block and sufficient space to be left to mount FRTU
20Serial item No. 14.003 continued--- • 01 No Manometer for each tank • 01 Nos Voltage passage indicator for each feeder • There must be mechanical interlock between Incomers and bus sectionalizer • Completely touch proof screen separable termination kit for all the feeder Modules considering installation shall be above 1200-meter altitude• Vacuum Interrupter & RMU should be of same make for better life cycle optimization • Basic insulation level of complete RMU shall be 28KV(RMS)/75KV(Peak) • The VCB operating sequence must be O-0.3-CO- 3MIN-CO & tested for 10000 CO mechanical operation • Set 24V Battery & Charger for indication, operation of VCB and load break switch. There must battery and charger health monitoring system for SCADA • Complete RMU must be SCADA ready and all the wirings for control and Indication of each module, forNote :- (i) Cost of supply and fix of Switchgears / Breakers having terminals / disconnecting links for termination of CT wiring including fuses complete all as required at site are deemed to be included in the quoted rate.(ii) Cost of Foundation including construction material as per manufacture design complete is deemed to be included in the quoted rate. (iii) Rate is inclusive for dismantling, taking down existing HT cable from 4 pole / 2 pole structure and connecting Switchgears / Breakers.(iv) Rate of cable end joint shall be measured and paid seperately under relevant item. (v) Cost of additional base channel required at site shall be measured and paid seperately. (vi) Rate is inclusive for any other works which are not included in item but required at site for commissioning of Switchgears / Breakers / VCB including marking, numbering, by synthetic enamel paint, providing danger board etc.
21Serial item No. 14.003 continued--- (vii) Contractor shall provide AMC include callibration of HT panels, VCBs, CT / PTs, Relay settings for the Switchgears / Breakers here in above under defect liability period (DLP) i.e 24 months by engaging Service Engineer from OEM of eqpts without any extra cost and site inspection, testing and callibration report will be submitted on before commissioning and subsequently once in six months to Engr-in-charge . Compensation @ Rs 80000.00 shall be recovered from contractor due in case failure.(viii) Rate is inclusive for submitting completion Drg and network details after testing & commissioning but before completion of work. Display board (illuminated) of size not less than 2.0 Mtr x 1.5 Mtr shall also be provided by the contractor at MRS Sub Stn without any extra cost.
22Shifting and installation of existing distribution transformer upto 200 kVA, 11/0.433V / nearest available capacity / through existing station rationalisation source complete including connection at proposed location all as specified and directed.
23S&F Cast iron cable route indicator width 4\\" with embossing mark as HT/LT cable, shall be directly burried into the ground and having withstand capacity in all type of weather conditions and physical impact and painted with bright colour complete as specified and directed.
24Supplying and laying of DWC HDPE pipe ISI marked of size 120 mm dia (OD-120 mm & ID-103 mm nominal) along with all accessories like socket, bend, couplers etc. conforming to IS:14930, Part Il including fittings and cutting, jointing etc. in the existing trench complete all as specified and directed.
25Supplying and laying of DWC HDPE pipe ISI marked of size 50 mm dia (OD-50 mm & ID-38 mm nominal) along with all accessories like socket, bend, couplers etc. conforming to IS:14930, Part Il including fittings and cutting, jointing etc. in the existing trench complete all as specified and directed.
26S & F loop in loop out junction box of size 300 x 200 x 110 mm made out of 1.6mm thick SMC sheet weather proof dust and vermin proof with hinged door and locking arrangements with slanting cover on top and provision of 04 nos aluminium bus bar of size 20x5 mm fixed on insulator and one MCB of capacity 10 Amp complete fixed on pole with and including suitable size MS flat iron clamp nut, bolt and washers complete all as specified and as directed.
27Fabrication, supply, installation, testing & commissioning of electrical cubical control panel board (PTTA Panel) factory assembled weather, Dust & Vermin proof, totally enclosed IP-54 protection Plinth mounted Outdoor factory fabricated of 3.15 mm CRCA MS sheet of suitable size, 3 phase, 4 wire, 415 Volt AC, 50 Hz complete duly painted with powder coating complete with locking arrangement, earthing terminals with suitable rating aluminium bus bar insulated with FRP heat shrinkable sleeves of relevant colour wit necessary insulators for incoming/outgoing Circuit breakers including and mounting measuring instrument such as voltmeter, Ammeter, CT’s Phase LED indicator lamp R-Y-B, selector switch for incoming, cables connection with suitable cable glands, lugs including grouting of feeder pillar box 60 cm above ground level by providing 90 cm long angle iron size 50x50x6 mm welded on all four corner embedded in PCC (1:2:4) using 20mm graded up to 30 cm as latest edition of IS 8623, IS 13947 & IS 2147 complete all as specified and directed(Near Single liv OR bldg)INCOMING:-MCCB 4 pole, 100 Amps, 16 kA, Thermal Magnetic based, adjustable range 0.7 to 1 In - 01 No OUTGOING:-(a) MCCB 4P 40A, 16kA, Thermal Magnetic based, adjustable range 0.7 to 1 In - 03 No (b) TPN MCB 6-32A, 10kA, 'C' curve - 01 No (Street light)(c) Intelligent panel meter to measure voltage, current frequency, power factor, kWH, etc with all connected CTs -01set(d) LED indicating lamps with colour R,Y,B - 01 set
28Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 150 mm dia suitable for 0.4 Mpa working pressure complete all as specified and directed
29Fabrication, supply, installation, testing & commissioning of IP-66, IK10 protection, outdoor type, double door pedestal, Street light timer controlled panel of 5kW, 3 phase, 4 wire, 415 Volt AC, 50 Hz with an astronomical timer driving two three phase feeders complete with floor mounted, fabricated of 3.15 mm CRCA MS sheet of suitable size with UV-stable gasket, duly powder coated complete with locking arrangement, earthing terminals, with FRLSH control wiring including mounting Phase LED indicator lamp R-Y-B, selector switch for incoming, cables connection with suitable cable glands, lugs with all complete accessories. Complete panel unit grouting 60 cm above ground level by providing necessary angle iron support on all four corner embedded in PCC (1:2:4) using 20 mm graded up to 30 cm complete with the following:-
30Serial item No. 14.011 continued...Bus-bar : 3P+1N - Aluminium busbar, 40 A mounted on 1.2 kV insulation sleeves, form-2bIncomer : TPN MCB 6-32A, 10kA, 'C' curve - 01 NoOutgoing : (i) MCB 4P 16 A, 10kA 'C' curve - 02 Nos(ii) Power contactor - 4P, 16-20 A AC - 01 No(iii) Surge Protection device Type 2, 3P+N, Uc 275 V (N-PE)/320-350 V (L-PE), Imax≥20 kA per pole, with thermal disconnector and remote contact - 01 NoControl & automation:-(i) Astronomical timer : Legrand Astro Rex or equivalent, 2 channel, 230V AC, ≥per chan(pilot duty), lay/long programmable, DST auto, ±120 min offset - 01 No(ii) 3 position (Hand-Off-Auto) selector - 01 No(iii) Master bypass : AUTO/BYPASS selector to force panel ON irrespective of timer - 01 No(iv) Manual OFF pushbutton -02 (per outgoing feeder)(v) LED indicating lamps with colour R,Y,B - 01 setNote: (i) Clearance for 25% future feeders shall be made provisioned(ii) The cost of earthwork, panel foundation is deemed to be included in the quoted rate of contractor
31Supply, install, testing and commissioning of Smart energy meter (IS-16444), AC whole current, three phase, 4 wire, CT operated Smart Energy meter of Class 0.5 S, 415 V, 50 Hz, 1b 5A complete all as specified. The meter shall communicate with Head End System (HES) on any of the communication technologies mentioned in IS-16444 Part-I in a secure manner. The selection of communication technology should be as per the site condition and as per design consideration of AMI implementing agaency to meet the performance. The smart meter can based on RF Mesh communication technology or Cellular communication technology. The meter shall be provided with transparent polycarbonate ABS thermoplastic box with sealing arrangemenrs of suitable size as per the requirement of OEM of electric meter. The cost of meter would include the supply of current transformer, rated burden 15VA, accuracy class 0.5S, frequency 50Hz and voltage class 660V, effectively earthed and CT ratio suitable as (60/5 to 1000/5) completecomplete all as specified and as directed
32Fabrication, supply, installation, testing & commissioning of electrical cubical busbar control panel board factory assembled weather, Dust & Vermin proof, totally enclosed IP-54 protection Plinth mounted Outdoor factory fabricated of 3.15 mm CRCA MS sheet of suitable size, 3 phase, 4 wire, 415 Volt AC, 50 Hz complete duly painted with powder coating complete with locking arrangement, earthing terminals with 300A, 4way aluminium bus bar, insulated with FRP heat shrinkable sleeves of relevant colour with necessary insulators for incoming/outgoing controls including 01 x MCCB 250A, 4P, 36kA, Miroprocessor based electronic release with LSIG protection as incoming, cables connection with suitable cable glands, lugs including grouting of feeder pillar box 60 cm above ground level by providing 90 cm long angle iron size 50x50x6 mm welded on all four corner embedded in PCC (1:2:4) using 20mm graded up to 30 cm complete all as specified and directed
33M&L for construction of 100 users septic tank in hard / dense soil, foundation in PCC (1:2:4) type B1 using 20 mm graded crushed stone aggregate, brick construction wall in CM (1:4), M-20 grade RCC cover slab , RCC pre-cast manhole cover 100 mm thick of M-20 grade concrete having 6 mm plate embedded all around / fibre reinforced cover with angle iron frame , vent shaft and sludge chambers complete all as specified and as shown on TD drawings.
34M&L for construction of sokage well of size 3.60 m internal dia and 6.00 m effective depth in odinary soil, foundation in PCC (1:3:6) type C1 using 20 mm graded crushed stone aggregate, honey comb brick construction wall in CM (1:4), M-25 grade RCC cover slab , including intercepting chamber, screen chamber with brick wall construction in CM(1:4) ,RCC pre-cast cover cover slab 100 mm thick of M-25 grade concrete, brick bats filling complete all as specified and as shown on TD drawings.
35S&F LED type bed side wall mounted light fitting 9/10 Watt , housing- glass, frosted type, metallic frame, adjustable type complete all as specified and directed.
36S&F wall mounted type fans of 400 mm sweep, 03 blades aerodynamically balanced with 60 degree oscillation, working Voltage range 230 V, with service value not less than 1.2 BEE 5 star rated with brush less direct current motor(BLDC), the super efficient BLDC motor 50Hz and Noise level not more than 64 dB with 2 years warranty complete all as specified and directed.
37Supply, install, testing and commissioning of maintenance free chemical earthing with earth electrode minimum 17.0 mm diameter and minimum 3 Meter long, (In rocky area, a set of 3 electrodes of 1 Meter each of 17.0mm dia in grid form shall be installed in grid form) shall be made of high tensile low carbon steel circular rods, molecularly bonded with copper 250 microns of 99.9% electrolyte grade copper, on outer surface to meet the requirements of Underwriters Laboratories (UL) 467-2007 or latest as well as IEC 62561, a hole of 100mm to 125mm dia shall be augured /dug to a depth of about 3.0 meters, earth enhancement material minimum approx. 30-35 kg, with carbon based with min 95% of fixed carbon content premixed with corrosion resistant cement, cement shall not mix separately & shall not have bentonite to improve conductivity of the earth electrode and ground contact area, shall not pollute the soil or local water table and meets environmental friendly requirements for land fill, shall not be explosive & shall not cause burns, irritation to eye, skin, complete with a copper strip of 20mmX3mm shall be exothermically welded to main earth electrode for taking the connection to the main equi-potential earth copper busbar 25mm x 6mm x 300mm long fixed on water proof box on wall with insulator support incl Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc., including Inspection chamber of 300 x 300 x 300 mm (inside dimension) of RCC with 50 mm thick and fine finish, marking space should be present on RCC cover with date of testing and earth resistance value shall be written on the cover with black base with yellow paint, all to achive the earth resistance value below 1.0hms complete all as specified and as directed.Note :- (i) The ring main earth resistance shall be below 0.5 Ohms (ii) Soil resistivity shall be checked before design the earth rods accordingly design should be submitted.
38S&F modular type TV socket. RJ46, 1 module complete all as specified and directed.
39S&F modular blanking plate modular type suitable for fixing in modular switch board complete all as specified and as directed.
40S&F epoxy powder coated sheet metal enclosure for DBs, double door, Triple pole and neutral (VTPN) 415V, 4 ways suitable for fixing MCCB 4P/3P upto 160 Amps as incomer and MCB TP/SP as out going, fitted with 250 Amps rated copper bus bar for each phase with 02 Nos neutral bar & 02 NOs Earth bar and cable ties for cable management fully insulated busbar & shrouded Neutral bars pre-fitted with masking sheet, the DB shall be of IP-54 Protection complete all as specified and directed
41S&F Surge Protection Device (SPD) Single Phase and neutral, T2 -limb, Imax 20 KA per pole complete fixed in distribution board and making connections complete all as specified and directed. Total in Figures 0.0 0.0 INR Zero Only Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information

Other Detail

Information Source https://defproc.gov.in/nicgep/app
Download FileName File Description File Size
Download 223aab75-0adc-4702-bdcd-635335838643.html Tender Documents 0 KB
Download BOQ_859424.xls Tender Documents 0 KB
Download DRAWINGS.pdf Tender Documents 0 KB
Download tender.pdf Tender Documents 0 KB
Download Tendernotice_1.pdf Tender Documents 0 KB