| 1 | Taking down of old UG Cable of any size/core and any type complete from trenches/cable duct/on wall/roof carefully, identifying for faults, dismantling unserviceable cable and saggregating serviceable cable for reuse all as specified and directed . |
| 2 | Suppy and laying in trenches, fixed on walls, passing through pipes, jointing and testing of electric LT cables, PVC insulated, PVC sheathed, galvanised steel strip or wire armoured electric power cables 4 Core 6 Sqmm with stranded aluminium conductors 1100 Volts grade complete all as specified and as directed by Engineer-in-Charge.Note: Earth work/HDPE pipe/straight through joints if required will be measured and paid separately. The rates should be includs in Cable lugs, Cable Gland and necessary insulation taping. |
| 3 | Suppy and laying in trenches, fixed on walls, passing through pipes, jointing and testing of electric LT cables, PVC insulated, PVC sheathed, galvanised steel strip or wire armoured electric power cables 4 Core 10 Sqmm with stranded aluminium conductors 1100 Volts grade complete all as specified and as directed by Engineer-in-Charge.Note: Earth work/HDPE pipe/straight through joints if required will be measured and paid separately. The rates should be includs in Cable lugs, Cable Gland and necessary insulation taping. |
| 4 | Suppy and laying in trenches, fixed on walls, passing through pipes, jointing and testing of electric LT cables, PVC insulated, PVC sheathed, galvanised steel strip or wire armoured electric power cables 4 Core 16 Sqmm with stranded aluminium conductors 1100 Volts grade complete all as specified and as directed by Engineer-in-Charge.Note: Earth work/HDPE pipe/straight through joints if required will be measured and paid separately. The rates should be includs in Cable lugs, Cable Gland and necessary insulation taping. |
| 5 | Suppy and laying in trenches, fixed on walls, passing through pipes, jointing and testing of electric LT cables, PVC insulated, PVC sheathed, galvanised steel strip or wire armoured electric power cables 3.5 Core 25 Sqmm with stranded aluminium conductors 1100 Volts grade complete all as specified and as directed by Engineer-in-Charge.Note: Earth work/HDPE pipe/straight through joints if required will be measured and paid separately. The rates should be includs in Cable lugs, Cable Gland and necessary insulation taping. |
| 6 | Suppy and laying in trenches, fixed on walls, passing through pipes, jointing and testing of electric LT cables, PVC insulated, PVC sheathed, galvanised steel strip or wire armoured electric power cables 3.5 Core 35 Sqmm with stranded aluminium conductors 1100 Volts grade complete all as specified and as directed by Engineer-in-Charge.Note: Earth work/HDPE pipe/straight through joints if required will be measured and paid separately. The rates should be includs in Cable lugs, Cable Gland and necessary insulation taping. |
| 7 | Supply & Laying in repair of Telerex DWC (Double Wall corrugated) HDPE pipe ISI marked of outer dia of 40 mm and inner dia 32 mm polythylene including coupler & Bend with smoooth inernal and profiled external surface for non pressue under ground cable complete all as specified and as directed by Engineer-in-Charge. Make : REX POLYEXTRUSION LTD, Prince or its equivalent as approved. |
| 8 | Relaying/ Rerouting old serviceable UG cable of size 10 to 25 Sqmm any core retrieved from item No above in trench/pipe/DWC pipes /on wall /cable duct with necessary saddles/clamps of suitable size complete all as directed. Note: Earth work, DWC pipe/GI pipe will be measured and paid separately |
| 9 | S&F GI pipe of medium grade 40 mm dia all fitting fixture for fixing with wall and road crossing etc. complete all as specified and as directed by Engineer-in-Charge |
| 10 | Excavation in trenches any type of soil (soft/loose/hard/dense) not exc 1.5 mtr wide and not exc 1.5 mtr in depth for foundation, pipe, laying of cable etc not exc 10 Sqmtr on plan and not exc 1.5 mtr in depth and getting out complete all as specified and as directed by Engineer-in-Charge |
| 11 | - Ditto - all as per item No 10 here in before but exc 1.5 mtr or part there of in depth beyond 1.5 mtr depth. |
| 12 | Returning filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25 cm in soft/loose soil all as specified and as directed by Engineer-in -charge. |
| 13 | Removing excavated materials (soil) to a distance not exceeding 50 meters and depositing where directed at a level not exceeding 1.5 meters above the starting point all as specified and as directed by Engineer-in -charge. |
| 14 | M&L for road cutting, removing of material , returning filling and pcc 1:2:4 for laying of LT UG cable /Galvanised Iron Pipe/DWC Pipe all as specified and as directed by Engineer-in -charge. |
| 15 | S & F in repair for cable jointing kit for 1100Volt grade cable for Straight through, heat shrinkable type joint complete with jointing materials and accessories suitable for LT, XLPE armoured aluminium conductor cable of size 10 to 25 Sqmm 3.5 core as in repairs complete all as specified and as directed by Engineer-in -charge. Make : DENSON / M Seal / RAYCHEM |
| 16 | Dismantling old RCC / rusted poles including PCC and supply & erect minimum 7 mtr height above GL / foundation made out of Hot dip Galvanized single section octogonal pole with foundation base plate of size 250x250x16 mm, foundation bolts 04 Nos of size 24 x 700/750 mm,with signle type arm bracket 1500 mm long, the pole shaft shall be tapered with single longitudinal welding and door opening for cable with 01 No MCB SP 6 Amp and 32 Amp connector and 03 run of 1.5 sqmm PVC wire for connecting street light fitting from MB complete all as specified and as directed by Engineer-in -charge.Note : Earth work, cement concrete in foundation, coping etc will be measured and paid seperately under relevant item. |
| 17 | M&L for Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint complete including dismantling existing rusted/ unserviceable cross arms. |
| 18 | M&L Reinforced cement concrete (nominal mix) Foundations M-30 Grade, including rafts, footings, foundation beams, plinth beams, bases for columns, etc,basement slabs, under-reamed piles and mass concrete complete all as specified and directed by Engr in charge. |
| 19 | M&L for PCC 1:4:8 type D2 with 40 mm graded aggregate as in foundation complete. |
| 20 | M&L for PCC 1:3:6 type C1 with 20 mm graded aggregate for coping of poles and stay including form work. |
| 21 | M&L for TMT bars from but 5mm dia and over upto and including 10mm dia in stirrups, spacers and binders, cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9mm dia or securing with clips for foundation work complete all as specified and as directed by Engr in charge. |
| 22 | M&L for fixing in repair bracket for street light fitting made out of 25 mm bore pipe light grade GI tube bent to shape required,not less than 1.20 meter long, fixed with and including MS flat iron clamps made out of 40x6 mm FI, bolts, nuts, washers etc complete including dismantling old defective.all as specified and as directed by Engineer-in -charge. |
| 23 | Supply and fixing in repair of GI clamp made out of 50x6 mm flat iron of suitable size for steel tabular poles all as specified and directed by Engineer-in-charge. |
| 24 | Suppy and laying in high mast lights Elastomer LT cables, PVC insulated, PVC sheathed, 2.5 Sqmm 3 core steel strip or wire armoured electric power cable with stranded copper conductor, 1100 Volts grade complete all as specified and as directed by Engineer-in-Charge for the following size :-Note: The rates should be include thimbles and connectors complete where ever required. |
| 25 | S&F in repair PVC copper cable insulated shealthed of size 1.5sqmm x 3 core complete all as specified and as directed by engineer in charge. Make- Havells or equivalent. |
| 26 | Supplying and laying on wall/ on pole of CPVC pipes outer diameter 20mm SDR 13.5 pipes & plain CPVC SDR 11 fittings complete all as specified and as directed including dismantling old one. |
| 27 | M & L for servicing of High Mast of less than 15 Mtrs height by lowering, checking, rectifying the defects, over hauling of winch drum assembly, motor including checking and replacing of gears, winch motor, wire ropes, trailing cable along with lugs, lubricating the moving mechanism and raising the high mast upto its height complete all as specified and as directed by Engineer in Charge.Note: The items gears, winch motor, wire ropes and trailing cable will be measured and paid separetely under relevant item. |
| 28 | Supply only gear mechanism complete all as specified and directed by Engr-in-Charge. |
| 29 | Supply only stainless steel wire rope 6mm dia (7/19 construction). |
| 30 | M & L for dismantling the defective induction motor of capacity upto 1 HP any make/class of insulation from foundation bed, disconnecting all electric supply connections, duly coupled with pump/compressor, trasnporting to workshop removing burnt out widing from stator/rotor, rewinding with suitable gauge of super enamelled copper wire of approved make and replacing DE /NDE bearings, insulation materials, varnishing , heating, greasing of bearings etc complete, re-assembling, testing and commissioning of following capacity motors all as directed. Note : Terminal block, Bearings of motor if required will be measured & paid separately under relevant schedule items. |
| 31 | S&F loop-in/loop-out box of outer size size 250x210x115 mm made out of FRP(Hot moulded type), IP 54 with weather proof canopy and locking screws along with with 5/6 Amps MCB - 01 No, 50 Amps rated 3 pole connector- 01 Nos, neutral link mounted and Din rail suitable size for mounting MCB/Connector etc complete in the box, duly fixed to to steel tubular/rail/PCC/RCC pole using 25 x 3mm FI clamp, including suitable gland and lugs for connecting cable complete all as directed including dismantling old one. |
| 32 | Supply & fixing IP 65/66 thermoplastic-polycarbonate cable junction box of size 205X255X112mm with terminal which is totally shock proof, water proof, halogen free, silica and having internally embedded gasket technology fixing on pole / surface / frame with the help of Two nos of GI calmp of size 25X3 mm including 40Amps connector, lugs and equivalent MCB complete all as directed. |
| 33 | Supply & fixing IP 65/66 thermoplastic-polycarbonate cable junction box of size 130X180X77mm with terminal which is totally shock proof, water proof, halogen free, silica and having internally embedded gasket technology fixing on pole / surface / frame with the help of Two nos of GI calmp of size 25X3 mm including 40Amps connector, lugs and equivalent MCB complete all as directed. |
| 34 | S&F in replacement of LED street light fittings comprising of epoxy powder coated housing,enclosed with glass cover in frame,with lumen output not less than 10800 lumens suitable watt for efficiency not less than 120 lumens/watt,having secondary optics,min wattage 120 watt ,with ingress protection IP 65/66 and potted electronic driver of miniumum IP 67 with THD less than 10 % ,CRI>80,P.F>0.9,IK>08 SPD of capacity 10 KV etc complete all as specified and as directed by Engineer in charge |
| 35 | S&F in replacement of LED street light fittings comprising of epoxy powder coated housing,enclosed with glass cover in frame,with lumen output not less than 8400 lumens suitable watt for efficiency not less than 120 lumens/watt,having secondary optics,min wattage 90 watt ,with ingress protection IP 65/66 and potted electronic driver of miniumum IP 67 with THD less than 10 % ,CRI>80,P.F>0.9,IK>08 SPD of capacity 10 KV etc complete all as specified and as directed by Engineer in charge |
| 36 | S&F in replacement of LED street light fittings comprising of epoxy powder coated housing,enclosed with glass cover in frame,with lumen output not less than 7200 lumens suitable watt for efficiency not less than 120 lumens/watt,having secondary optics,min wattage 60 watt ,with ingress protection IP 65/66 and potted electronic driver of miniumum IP 67 with THD less than 10 % ,CRI>80,P.F>0.9,IK>08 SPD of capacity 10 KV etc complete all as specified and as directed by Engineer in charge |
| 37 | S&F in replacement of LED street light fittings comprising of epoxy powder coated housing,enclosed with glass cover in frame,with lumen output not less than 5400 lumens suitable watt for efficiency not less than 120 lumens/watt,having secondary optics,min wattage 70 watt ,with ingress protection IP 65/66 and potted electronic driver of miniumum IP 67 with THD less than 10 % ,CRI>80,P.F>0.9,IK>08 SPD of capacity 10 KV etc complete all as specified and as directed by Engineer in charge |
| 38 | S&F in replacement of LED street light fittings comprising of epoxy powder coated housing,enclosed with glass cover in frame,with lumen output not less than 3000 lumens suitable watt for efficiency not less than 120 lumens/watt,having secondary optics,min wattage 25 watt ,with ingress protection IP 65/66 and potted electronic driver of miniumum IP 67 with THD less than 10 % ,CRI>80,P.F>0.9,IK>08 SPD of capacity 10 KV etc complete all as specified and as directed by Engineer in charge. |
| 39 | Taking down old unserviceable flood light fittings from any height and Supply & fixing LED flood light fittings 50 Watt comprising of epoxy powder coated housing, enclosed with glass cover in frame,(with total lumen output not less than 6000 lumens and suitable wattage for efficiency not less than 120 lumens/Watt) min wattage 50 watt, with ingress protection IP 65/66 and SPD of capacity 10 KV etc incl necessary clamps etc complete and testing on completion all as specified and as directed. Make:Crompton /Phillips/C&S /Havells/ Wipro/ Henolix/Luker. Note: The GI pipe bracket if required will be measured and paid separately under relevant schedule items |
| 40 | Taking down old unserviceable flood light fittings from any height and Supply & fixing LED flood light fittings comprising of epoxy powder coated housing, enclosed with glass cover in frame,(with total lumen output not less than 14250 lumens and suitable wattage for efficiency not less than 18000 lumens/Watt) min wattage 150 watt, with ingress protection IP 65/66 and SPD of capacity 10 KV etc incl necessary clamps etc complete and testing on completion all as specified and as directed. Make:Crompton /Phillips/C&S /Havells/ Wipro/ Henolix/Luker . Note: The GI pipe bracket if required will be measured and paid separately under relevant schedule items |
| 41 | Taking down old unserviceable flood light fittings from any height and Supply & fixing LED flood light fittings comprising of epoxy powder coated housing, enclosed with glass cover in frame,(with total lumen output not less than 14400 lumens and suitable wattage for efficiency not less than 120 lumens/Watt) min wattage 120 watt, with ingress protection IP 65/66 and SPD of capacity 10 KV etc incl necessary clamps etc complete and testing on completion all as specified and as directed. Make:Crompton /Phillips/C&S /Havells/ Wipro/ Henolix/Luker. Note: The GI pipe bracket if required will be measured and paid separately under relevant schedule items |
| 42 | Taking down old unserviceable flood light fittings from any height and Supply & fixing LED flood light fittings comprising of epoxy powder coated housing, enclosed with glass cover in frame,(with total lumen output not less than 24000 lumens and suitable wattage for efficiency not less than 120 lumens/Watt) min wattage 200 watt, with ingress protection IP 65/66 and SPD of capacity 10 KV etc incl necessary clamps etc complete and testing on completion all as specified and as directed. Make:Crompton /Phillips/C&S /Havells/ Wipro/ Henolix/Luker. Note: The GI pipe bracket if required will be measured and paid separately under relevant schedule items |
| 43 | Taking down old unserviceable flood light fittings from any height and Supply & fixing LED flood light fittings comprising of epoxy powder coated housing, enclosed with glass cover in frame,(with total lumen output not less than 30000 lumens and suitable wattage for efficiency not less than 120 lumens/Watt) min wattage 250 watt, with ingress protection IP 65/66 and SPD of capacity 10 KV etc incl necessary clamps etc complete and testing on completion all as specified and as directed. Make:Crompton /Phillips/C&S /Havells/ Wipro/ Henolix/Luker. Note: The GI pipe bracket if required will be measured and paid separately under relevant schedule items |
| 44 | S&F in replacement energy efficient LED Two way wall washer light fitting with IP 65 protection high quality integerated LEDs assuring soothing warm white light all night long 10W with THD less then 10%, CRI > 80, P.F> 0.9, IK> 08, black case aluminuim including all necessary wiring clamps, nut and bolts mounting acessories etc and providing connection all as specified and directed by Engineer-in-Charge. |
| 45 | Supply & fixing LED Rope light of length not less than 50mtr and having 120 LEDs per mtr with total lumen output not less than 22500 lumens and suitable wattage for efficiency not less than 450 lumens per mtr min wattage 450 watt, with ingress protection IP 65/66 and SPD of capacity 10 KV etc incl 2 set of strip connector and 1 set of driver, necessary clamps etc complete and testing on completion all as specified and as directed. Make:Crompton /Phillips/C&S /Havells/ Wipro/ Helonix/Luker . |
| 46 | Supply & fixing in replacement of LED Rope light 18 mtr comprising of transparent silicon coating,tricolour specified as orange, white, green colour 240V, 50Hz suitable wattage for efficiency not less than 6W/mtr , having secondary optics, min wattage 108 watt, with ingress protection IP 65/66 and potted electronic driver of minimum IP 67 with THD less then 10%, CRI > 80, P.F> 0.9, IK> 08, SPD of capacity 10 KV etc incl fixing accessories on wall, poles etc and 2 set of strip connector and 1 set of driver, necessary clamps etc complete and testing on completion all as specified and as directed. . |
| 47 | Supply and fix LED aviation lamp of minimum 10 watts with total lumen output not less than 1000 lumens and suitable wattage for efficiency not less than 100 lumens / watt made up of die-cast aluminum housing with red polycarbonate dome for better illumination, Integral driver, Ingress Protection : IP65, protection against short-circuit, protection against surge, wide operating input voltage range 100 – 270VAC complete all as specified and as directed by Engineer in Charge. |
| 48 | Supply & fixing in replacement of LED bay light fittings comprising of epoxy powder coated housing, enclosed with glass cover in frame, (with total lumen output not less than 9600 lumens and suitable wattage for efficiency not less than 120 lumens/Watt, having secondary optics, min wattage 80 watt, with ingress protection IP 65/66 and potted electronic driver of minimum IP 67 with THD less then 10%, CRI > 80, P.F> 0.9, IK> 08, SPD of capacity 10 KV etc incl necessary clamps etc complete and testing on completion all as specified and as directed. Make:Crompton /Phillips/C&S /Havells/ Wipro/ Henolix/Luker . |
| 49 | Supply & fixing in replacement of LED bay light fittings comprising of epoxy powder coated housing, enclosed with glass cover in frame, (with total lumen output not less than 14400 lumens and suitable wattage for efficiency not less than 120 lumens/Watt, having secondary optics, min wattage 120 watt, with ingress protection IP 65/66 and potted electronic driver of minimum IP 67 with THD less then 10%, CRI > 80, P.F> 0.9, IK> 08, SPD of capacity 10 KV etc incl necessary clamps etc complete and testing on completion all as specified and as directed. Make:Crompton /Phillips/C&S /Havells/ Wipro/ Henolix/Luker . |
| 50 | Supply fixing as in repair connection and testing of MCB SP 6-32Amps Amps Make : Legrand / L&T/Schiender. |
| 51 | Supply and fixing as in repair of Service wire Al Conductor Weather Proof 10 Sqmm 2core complete all as specified and as directed by Engineer-in -charge. |
| 52 | Supply and fixing as in repair of Service wire Al Conductor Weather Proof 6 Sqmm 2core complete all as specified and as directed by Engineer-in -charge. |
| 53 | Supply and fix as in repair Digital Timer with Digital time switch ,contactor pre wired Distribution Board complete time lite 40A 3 Pole 415 V complete as specifed and directed by Engineer-in -charge. |
| 54 | Cutting vegetation and surface dressing not exceeding 15 cm deep including removing the materials to a distance not-exc 60 mtr around each pole upto 1.0X1.0Mtr from each pole coping of pole complete all as specified and directed by Engineer-in -charge. |
| 55 | Supply and fix as in repair contactors of capacity 40-63 A 3 Pole 415 V with 2NO+2NC complete all as specified and as directed by Engineer-in -charge. Make Legrand/L&T |
| 56 | Supply and fix as in repair NO/NC auxillary contacts of capacity 40A of 415 V complete all as specified and as directed by Engineer-in -charge. |
| 57 | Supply and fix as in repair digital timer switch, current capacity 16A, with 1 changeover complete all as specified and as directed by Engineer-in -charge. Make Legrand/L&T /Indoasian |
| 58 | Material and labour for painting to Steel tublar pole 9 m long with one coat of aluminium paint including preparation of old painted surfaces and painting the pole terminal and lettering the pole details with adhesive sticker of dia 125 mm with white letters (indicating pole No/location code) on blue background blackground etc complete all as specified and as directed. |
| 59 | M&L for preparation of old painted surfaces of 9 m long RCC poles incl removing oily/greasy spots and applying one coat of synthetic enamel paint of black and yellow in alternate strips of 30 cm width upto 1.0 mtr height including applying a coat of white distamper on pole, pole coping and lettering the pole details with adhesive sticker of dia 125 mm with white letters (indicating pole No/location code) on blue background blackground |
| 60 | Material and labour for fixing in repair radium reflective, water proof adhesive sticker of width not less than 50 mm wrapped around the street light pole of approved colour by Engineer in Charge complete all as specified and as directed. |
| 61 | Supply and fix in repair for aluminium cable lugs for fixing of armoured cables 6 Sqmm in panels complete all as specified and as directed by Engineer-in-Charge . |
| 62 | Supply and fix in repair for aluminium cable lugs for fixing of armoured cables 10 Sqmm in panels complete all as specified and as directed by Engineer-in-Charge . |
| 63 | Supply and fix in repair for aluminium cable lugs for fixing of armoured cables 16 Sqmm in panels complete all as specified and as directed by Engineer-in-Charge . |
| 64 | Supply and fix in repair for aluminium cable lugs for fixing of armoured cables 25 Sqmm in panels complete all as specified and as directed by Engineer-in-Charge . |
| 65 | Supply and fix in repair for aluminium cable lugs for fixing of armoured cables 35 Sqmm in panels complete all as specified and as directed by Engineer-in-Charge . |
| 66 | S&F in replacement Decorative Verbena Square Bollard Lights fitting 12 Watt with IP 65 protection high quality integerated driver LEDs assuring soothing warm white light all night long 12W with THD less then 10%, efficiency -80% , Surge protection -4 KV ,CRI- 90, P.F> 0.9, IK> 08, black case aluminuim including all necessary wiring clamps, stainless stell screw ,nut and bolts mounting acessories etc and providing connection all as specified and directed by Engineer-in-Charge. Make K - Lite Model No-24735Note: (i) Earth work, Foundation for pole, shall be measured and paid seperately under relevant item. |
| 67 | S&F in replacement Decorative Verbena Round Bollard Lights fitting 12 Watt with IP 65 protection high quality integerated driver LEDs assuring soothing warm white light all night long 12W with THD less then 10%, efficiency -80% , Surge protection -4 KV ,CRI- 90, P.F> 0.9, IK> 08, black case aluminuim including all necessary wiring clamps, stainless stell screw ,nut and bolts mounting acessories etc and providing connection all as specified and directed by Engineer-in-Charge. Make K - Lite Model No-24597 or equivalent in Philips / Havells/ CGNote: (i) Earth work, Foundation for pole, shall be measured and paid seperately under relevant item. |
| 68 | Supply & fix as in repair hot dipped galvanised marine grade powder coated mild steel step pole of height 5 mtr with black and gold powder finish, compatible for all standard post top lights, plasma cut having bottom of approximately 139 mm and top approximately 88 mm, fixed to the foundation with GI nuts and bolt including 3 core 1.5 Sqmm PVC wire for post lamp connection with inbuilt junction connection box complete suitable for single arm accessory of 38 mm Dia all as specified and as directed.Note: (i) Earth work, Foundation for pole, Post top light shall be measured and paid seperately under relevant item.Make : Cat Part No. 12028-500-G25-SA-NA-L0188-MGP-310-055 of Klite or eqevalent in Havells/ Philips/ CG/ Bajaj |
| 69 | S&F in replacement energy efficient hanging type LED post top light fitting with marine grade M-30 powder coating in black and gols colour galvanished mild steel arm bracket IP 67/68 protection high quality integrated LEDs assuring soothing warm white light all night long 30W with THD less than 10%, CRI>80, P.F>0.9, IK>08, 3000K black case aluminium including decorative mild steel arm for hanging post top, all necessary wiring, clamps, nut and bolts mounting accessories etc and providing connection complete all as specified and as directed.Make : Cat Part No. 24395-054-30-57-T2-A9-L0188-PCP-322-055 of Klite or eqevalent in Philips/ Bajaj /Havells |
| 70 | Supply & fix as in repair Decorative pole of height 3 mtr long, body extruded Aluminium with black RAL-9004 finish, compatible for all standard for 2 Nos Lights top lights 30 W & 40 W & inbuild 50 W light with IP 65/67 protection high quality integerated LEDs assuring soothing warm white light all night long 50W with THD less then 10%, CRI > 70, P.F> 0.9, IK> 08, & for terminal connections, fixed to the foundation with SS nuts and bolt, designed body including 3 core 1.5 Sqmm pvc wire for post lamp connection complete all as specified and as directed by Engineer in Charge.Note: (i) Earth work, Foundation for pole, Flood focus light shall be measured and paid seperately under relevant item. |
| 71 | S&F in replacement energy efficient LED Round type flood light fitting 30 W with IP 65 protection high quality integerated LEDs 30W for mounting on Decorative pole with THD less then 10%, CRI > 80, P.F> 0.9, IK> 08, black case aluminuim including all necessary wiring clamps, nut and bolts mounting acessories etc and providing connection all as specified and directed by Engineer-in-Charge. |
| 72 | S&F in replacement energy efficient LED Round type flood light fitting 40 W with IP 65 protection high quality integerated LEDs 30W for mounting on Decorative pole with THD less then 10%, CRI > 80, P.F> 0.9, IK> 08, black case aluminuim including all necessary wiring clamps, nut and bolts mounting acessories etc and providing connection all as specified and directed by Engineer-in-Charge. |
| 73 | Material and labour for earthing with galvanised earth plate electrode 600 mm x 600 mm x 6 mm thick, burried directly in ground vertically to a depth of not less than 2.25 mtr below ground level connected to galvanised iron strip 25 mm x 4 mm by means of GI Welding made out of galvanised iron mild steel and 40 mm dia GI pipe \\"light grade\\" for protection of earth lead and connected to control board or transformer neutral earth or as directed including earthing pit in PCC (1:3:6) type C-1, pre-cast reinforced cover with MS XPM Jalli, RCC 1:1.5:3 cover slab of size 300 x 300 x 100 mm with one handle made out of 8 mm dia round bar 20 mm dia GI pipe medium grade for watering funnels , wire mesh and provided charcoal or coke of alternative layers of 15 cm including necessary earth work complete shown in electrical plated No 3 and testing complete all as specified and as directed by Engineer-in -charge.NOTE : (i) The earthing pit should be provided with proper earth pit and pit cover.(ii) If the desired earth resistance is not achive during testing as per IS the complete earthing shall be carried out by the contractor at his own cost and no extra claim shall be admissable. |
| 74 | S&F in replacement energy efficient LED Post top light fitting with IP 66/67 protection high quality integerated LEDs assuring soothing warm white light all night long 35W with THD less then 10%, CRI > 80, P.F> 0.9, IK> 08, black case aluminuim including all necessary wiring clamps, nut and bolts mounting acessories etc and providing connection all as specified and directed by Engineer-in-Charge. Please Enable Macros to View BoQ information |