| 1 | Taking down old unserviceable ACSR Conductor and GI wire of any size from LT Poles and removing from site complete all as specified and directed. |
| 2 | Taking down old unserviceable GI Earth wire/Guard wire etc of any size from LT Poles and removing from site complete all as specified and directed. |
| 3 | Dismantling and taking down of old unserviceable pin type/ shackle type insulators from any height of electric pole complete all as specified and directed. |
| 4 | Taking down old unserviceable cross -arms/Clamps/nut bolts and Angle section etc from LT Pole any size complete all as specified and directed. |
| 5 | Dismantling and taking down old unserviceable stay assembly from LT Poles and removing from site complete all as directed. |
| 6 | Dismantling and taking down of old unserviceable PCC LT pole complete all as directed. |
| 7 | Demolition of plain cement concrete of any description and in any position not otherwise specifically provided for in this Schedule complete all as specified. |
| 8 | Dismantling and taking down old unserviceable APFC Panel removing from site complete all as directed. |
| 9 | Supply, install, testing and commissioning automatic intelligent power factor corrector (APFC) capacitor bank LT 3 phase, 440 volts, system 50 cycles, AC supply to improve PF 0.98 or unity automatically step wise switch capacitor panel floor mounted ourdoor type weather proof dust/vermin proof type made out of MS sheet 16 SWG and angle iron 40 x 40 x 6 mm frame. Factory made fabricate as modular in construction duly powder coated light grey colour, front openable panel shutter with locking arrangement to faciliate ease of maintenance complete natural air cooled cable entry with gland plate iwth provision of PCC 1:3:6 type C1 450 mm below ground and 300 mm above ground level all around legs complete of cap 80 KVAR and consisting of items are as under :(i) Incom MCCB 4 pole 160 Amps 36 KA - 01 Nos(ii) MCB TP 63 Amps `C' curve - 06 Nos(iii) Contactor 3 pole (25-63)Amps - 06 Nos(iv) Cylinderical type cap 20 KVAR - 03 Nos(v) Cylinderical type cap 10 KVAR - 01 Nos(vi) Cylinderical type cap 5 KVAR - 02 Nos(vii) APFC relay 7 stage - 01 Nos. |
| 10 | Supply, lay, jointing and testing XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 185 Sqmm 3.5 Core cable laid in trenches/passing through pipe under road crossing etc all as specified and directed. |
| 11 | All as per item No 10 but size 150 Sqmm 3.5 Core. |
| 12 | All as per item No 10 but size 120 Sqmm 3.5 Core. |
| 13 | All as per item No 10 but size 95 Sqmm 3.5 Core. |
| 14 | All as per item No 10 but size 70 Sqmm 3.5 Core. |
| 15 | All as per item No 10 but size 50 Sqmm 3.5 Core. |
| 16 | All as per item No 10 but size 16 Sqmm 4.0 Core. |
| 17 | All as per item No 10 but size 16 Sqmm 2.0 Core. |
| 18 | Excavation in trenches n. exc 1.5Mtr width n.exc 1.5 Mtr in depth for laying of cables & foundation of poles, stay assembly and getting out soft/loose soil. |
| 19 | M&L sand cushioning to PVC under ground cable with screened and washed sand and punning to provide a required cover complete all as specified and directed. Note :- Thickness after punning shall be considered for payment. |
| 20 | M&L brick work with fly ash bricks (as per IS-13757(1993) burnt clay fly ash building bricks), (Old size bricks) with width equal to the length of the brick laid dry & flat abutted with each other with gap between adjacent bricks not exc 10mm over UG cable for protection and complete all as specified & directed. |
| 21 | Returning, filling in including spreading levelling, watering and well ramming in layers not exc 25 cm in any type soil. |
| 22 | Removing of surplus excavated soil to a distance not exc. 50m and depositing where directed at a level not exc 1.5 Mtr above the starting point. |
| 23 | Boring of holes under road,pavement, hard standing by trenchless technology using ultrasound technique and necessary machine including HDPE pipe of 80mm dia suitable for 0.4 mpa working pressure. |
| 24 | M&L galvanized iron tubing, 50mm bore medium grade, ISI marked, including all fittings and laid in trenches/under road/drains, fixed to poles/walls with required size of flat iron (25mmx3mm) clamps, bolts, nuts and washers for protection of LT electric cable including taking down old unserviceable GI tube complete. |
| 25 | Supply & eracting cable path indicators for LT Cable made of CI plate fixed on MS angle iron size 25x25x5mm and 60 Cm long. and fixing in ground 30 Cm below ground level in PCC 1:3:6 type B-1 using 40mm grade stone aggregate of size 30x30x30cm. Cable path indicators shall be provided at distance of every 30 meters and at cable joints and turning of all cables and incorporated LT 1100 Volts on it, including PCC & earth work complete all as specified and directed. |
| 26 | Supply, installing, testing and commissioning factory made, floor mounted outdoor type of sizes 85x75x45cm, LT panel board, cubicle type, suitable for 415 Volts, 3 Phase, 4 wire, 50 Hz, AC supply system, and tested at CPRI, having bus bar chamber with insulated Aluminium bus bar four wire system, colour coded for each phase and neutral, insulated on epoxy type insulators. The bottom of the outer shell contains a detachable plate having provn for entry of cable of adequate size with glands, The panel shall be dust and vermin proof, IP-65 class protection and made 3.0 mm CRCA MS sheet, powder coated finish over one coat of red oxide primer on outside surface and painted inside with two coats of red oxide primer, both side opening type, including internal wiring with PVC insulated solid copper conductor cable, IS-694 marked, 1100 volts grade of appropriate size (but not less than 2.5 sqmm) including grouting of panel 45 cm above ground level by providing 90 cm long angle iron frame of size 50x50x6 mm, welded on all the four corners, embedded in pcc 1:2:4 using 20 mm stone aggregate upto 45 cm above ground level complete all as specified and directed including the following accessories :- INCOMING(i) Adjustable thermal magnetic MCCB 4 pole 250 Amps 36 KA -01 Nos(ii) Aluminium bus bar 400 Amps with insulator - 04 Nos(iii) Combined Ammeter & Voltmeter (10/0-400/500) A/V rating - 01 No(iv) Instrument control fuses and indication lamp(RYB) with selector switch – 01 setOUTGOING(i) MCB TPN 63 Amps 10 KA - 03 Nos |
| 27 | All as per Item No 26.00 but sizes 85x75x45cm and the following accessories:- INCOMING. (i) Adjustable thermal magnetic MCCB 4 pole 200 Amps 36 KA -01 Nos (i) Aluminium bus bar 400 Amps with insulator - 04 Nos(ii) Combined Ammeter & Voltmeter (10/0-400/500) A/V rating - 01 No(iii) Instrument control fuses and indication lamp(RYB) with selector switch – 01 setOUTGOING(ii) MCB TPN 63 Amps 10 KA -03 Nos + (Space 1 nos. MCB) |
| 28 | All as per Item No 26.00 but sizes 85x75x45cm and the following accessories:- INCOMING. (i) Adjustable thermal magnetic MCCB 4 pole 200 Amps 36 KA -01 Nos (i) Aluminium bus bar 400 Amps with insulator - 04 Nos(ii) Combined Ammeter & Voltmeter (10/0-400/500) A/V rating - 01 No(iii) Instrument control fuses and indication lamp(RYB) with selector switch – 01 setOUTGOING(i) MCB TPN 63 Amps 10 KA -03 Nos +(Space 1 nos. MCB). (ii) MCCB 4Pole 160 Amps 36 KA -01 Nos |
| 29 | All as per Item No 26.00 but sizes 85x75x45cm and the following accessories:- INCOMING. (i) Adjustable thermal magnetic MCCB 4 pole 160 Amps 36 KA -01 Nos (i) Aluminium bus bar 400 Amps with insulator - 04 Nos(ii) Combined Ammeter & Voltmeter (10/0-400/500) A/V rating - 01 No(iii) Instrument control fuses and indication lamp(RYB) with selector switch – 01 setOUTGOING(i) MCB TPN 63 Amps 10 KA -03 Nos + (Space 1 nos. MCB) |
| 30 | All as per Item No 26.00 but sizes 85x75x45cm and the following accessories:- INCOMING. (i) Adjustable thermal magnetic MCCB 4 pole 125 Amps 16 KA -01 Nos (i) Aluminium bus bar 200 Amps with insulator - 04 Nos(ii) Combined Ammeter & Voltmeter (10/0-400/500) A/V rating - 01 No(iii) Instrument control fuses and indication lamp(RYB) with selector switch – 01 setOUTGOING(i) MCB TPN 63 Amps 10 KA -03 Nos + (Space 1 nos. MCB) |
| 31 | All as per Item No 26.00 but sizes 85x75x45cm and the following accessories:- INCOMING. (i) Adjustable thermal magnetic MCCB 4 pole 100 Amps 16 KA -01 Nos (i) Aluminium bus bar 200 Amps with insulator - 04 Nos(ii) Combined Ammeter & Voltmeter (10/0-400/500) A/V rating - 01 No(iii) Instrument control fuses and indication lamp(RYB) with selector switch – 01 setOUTGOING(i) MCB TPN 63 Amps 10 KA -03 Nos + (Space 1 nos. MCB) |
| 32 | S&F pole mounted juction box made out of one piece moulded SMC IP-65 protection having aluminium bus bars 100 Amp three phase and neutral with one No MCB SPN 6 Amp for street light, cable entry from bottom, maintenance free size 300x200x100 mm fixing on pole with MS flat 25x3mm clamp including nut bolts front openable all as specified and directed. |
| 33 | S&F 2.5 Sqmm PVC insulated & sheathed cable three core copper conductor cable from street light junction box/feeder piller to street light fittings complete all as specified and directed. |
| 34 | S&F steel conduit pipe of size 20mm dia (fixed to poles with required size of flat iron 25mm x 3mm clamps, bolts, nuts) from junction box to street light fitting and making necessary connection at street light pole and fixing accessories complete. |
| 35 | S&F street light bracket made to shape at required angle made out of 40mm dia (light grade) GI tubing of length not less than 1.5m long fixing on wall/pole suitable for holding street light fittings including mild steel flat iron 25 x 3 mm clamp 02 Nos with nuts, bolts & washers complete all as specified and directed. |
| 36 | M&L PCC 1:3:6, type C1, (using 20mm graded crushed stone aggregate) as in coping/pedestal of poles including providing necessary form work for fair finished exposed concrete surfaces complete all as specified and as directed. |
| 37 | M&L earthing complete as per electric plate No 3 of MES SSR Part-I with galvanised steel earth plate electrode 60x60cmx6.3mm thick burried directly in ground ( earth pit not less thanb 2.25 Mtr deep below ground level ) with top edge of the plate not less than 1.5 Mtr below normal ground level, connected to galvanised strip 25 x 4 mm earth lead by means of bolts, nuts, check nuts and wathers of GI or steel . Earthing strip shall be protected by galvanised iron pipe 40 mm bore light grade and connected to continous earth lead on pole/test point, Watering pipe shall be 20 mm bore GI medium grade. The unit rate quoted for earthing shall be inclusive of excavation and earth work in any type of soil, charcoal, salt, funnel, PCC pit and RCC cover complete all as specified and directed. Please Enable Macros to View BoQ information |