| 1 | Item Rate BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: GE(I) Kanpur Name of Work : REPAIR/MAINT OF HT CABLE DISTRIBUTION NETWORK BUSBARS ALONGWITH ALLIED SERVICES AT CANTT AREA UNDER GE (I) KANPUR Contract No : GE(I)/KAN/T-11 OF 2026-27 Bidder Name : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Sl.No. Description of Items/Works Item Code / Make Quantity Units Estimated Rate Addition / Deduction Addition / Deduction Values Currency Conversion against each Item Quoted Currency in INR / Other Currency BASIC RATE In Figures To be entered by the Bidder Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT TOTAL AMOUNT With Taxes TOTAL AMOUNT In Words |
| 2 | Excavation in trenches / foundation in soft / loose soil not exc. 1.5 metre wide and n'exc. 1.5 m deep for HT / LT underground cable / pole foundation and getting out including forming bottom surface to required level or slope complete all as specified and directed. |
| 3 | Returning filling of excavated soil after laying the cable with spreading leveling watering and well ramming in layers not exceeding 25cm thick in loose/soft soil complete all as specified and directed. |
| 4 | Removal of surplus soil/excavated material obtained from ground level to a distance not exceeding 50 metre and depositing where directed at a level not exceeding 1.5 metre above from the starting point complete all as specified and directed. |
| 5 | M&L for sand cushning to U/G cable in layers of 23cm thick (8 Cm before laying the cable and 15 cm thick after laying the cable) in trenches including watering and consolidation, complete all as specified and directed. Note: Only punned thickness 18 cm shall be measured and paid. |
| 6 | Supplying and laying un-reinforced precast concrete cable cover, class HVP, type 1 with peak, size 300mm x 180mm x 40mm complete all as specified and directed. |
| 7 | M&L for drilling manually in soft/loose/ hard soil under road ,pavement hard standing for protection of GI pipe up to 80mm dia complete all as specified and directed. Note Depth of bore shall not be more than 1 Mtr from ground level. |
| 8 | Supply & laying in replacement of GI tubing of 80 mm bore dia, light grade conforming to IS 1239- Part-I and ISI marked in trenches, across the road, on wall or pole incl fixing arrangement as directed, culvert etc of required length for cable protection complete all as specified and directed. |
| 9 | Supply, laying in trenches or passing through pipe/ducts, fixed to wall or poles XLPE insulated screened PVC sheathed galvanized steel strip or wire armoured electric power cable with alumn conductor of cross sectional area 95 Sqmm 3 core 11 KV rated suitable for earthed system including testing and commissioning all as specified and directed Note : (Excavation and earth work, sand cushioning brick covers and GI pipe etc shall be measured and paid separately. |
| 10 | All as per item No 8.00 above but HT 11 KV cable of size 120 Sqmm complete all as specified and directed. |
| 11 | All as per item No 8.00 above but HT 11 KV cable of size 185 Sqmm complete all as specified and directed. |
| 12 | Supply and fix cable end jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and all accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 70 to 95 Sqmm complete all as specified and directed. |
| 13 | Supply and fix cable end jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and all accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 to 185 Sqmm complete all as specified and directed. |
| 14 | Supply and fix cable end jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and all accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 70 to 95 Sq mm complete all as specified and directed. |
| 15 | Supply and fix cable end jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and all accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 to 185 Sqmm complete all as specified and directed. |
| 16 | Supply and fix cable straight through jointing kit for 11 KV (Earthed) grade cable termination heat shrink type joint complete with jointing material and all accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 to 95 Sqmm complete all as specified and directed. |
| 17 | Supply and fix cable straight through jointing kit for 11 KV grade cable termination heat shrink type joint complete with jointing material and all accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 to 185 Sqmm complete all as specified and directed. |
| 18 | S&F in replacement of Power / Control Copper Cables, with solid copper conductor, XLPE insulated, 2.5 sqmm, 08 core cut to pieces including making all necessary connections as per site requirement and removing the old unsv control cables from ducts etc complete all as specified and directed. |
| 19 | S&F in replacement of Power / Control Copper Cables, with solid copper conductor, XLPE insulated, 2.5 sqmm, 10 core cut to pieces including making all necessary connections as per site requirement and removing the old unsv control cables from ducts etc complete all as specified and directed. |
| 20 | S&F in replacement of Power / Control Copper Cables, with solid copper conductor, XLPE insulated, 2.5 sqmm, 12 core cut to pieces including making all necessary connections as per site requirement and removing the old unsv control cables from ducts etc complete all as specified and directed. |
| 21 | Detection of any type of fault in HT underground Line (laid in soil at plane area or forest area) with the help of Cable fault locator machine. Cable fault locator with carring vehicle will be brought by the cable fault detection agencies. Span of faulty cable will be trace out by the agencies by meggering HT cable complete all as specified and directed. Note : 1. Detection of fault in one span of length will be measured as one Job either machine placed from one side or both side of the cable. 2. Technicians will be employed by the working agencies. 3. Earth work and taking out will be measured and paid seperately. 4. Material for repair and replacement measured and paid saperately. 5. One job shall be measured if the fault has successfully identified by the fault locator machine or removing moisture in the cable if required. |
| 22 | M&L for earthing with GI plate electrode of size 60cm X 60cm X 6mm buried directly in ground vertically at a depth not less than 2.25 metre below normal ground level with top edge of earth plate at a depth not less than 1.5 metre below normal ground level surrounded from all sides by 15 cm thick and packed layer of charcoal dust and common salt filling in alternate layers etc and connected to and including GI strip of size 32x6 mm up to 7.5 mtr by means of bolts, nuts, check nuts and washers made of brass and protected by light grade 40mm dia upto 7.5 mtr long GI pipe connected to main control board and GI pipe light grade 20mm bore for watering and including funnel, wire mesh, RCC pit cover 50mm thick and PCC chamber pit with PCC 1:2:4 type C2 (including excavation and earth work disposal of surplus soil to a distance not exceeding 50 metre) and testing after completion all as specified and shown on plate No 3 of SSR Part-I 2009 including taking down old unserviceable and making test point and all connections complete all as specified and directed. |
| 23 | S&F in replacement of HT 11 KV bus bar outdoor type weather and vermin proof factory fabricated CPRI approved duly painted with two coat of enamelled paint, pedestal type made out of mild steel sheet 3.15mm thick, factory made, using angle iron 40mm x 40mm x 6mm and 500mm high, front opening double shutter weather proof , rust proof, dust proof with provision of rubber gasket and locking arrangement including HT bush, insulator & bus bar color code - 03 Nos and making connection with suitable size of thimbles, nuts, bolts and washers etc incl necessary earth work complete all as specified and directed. |
| 24 | M&L for advance maintenance free chemical earthing with enviornment friendly ring earthing system consisting each set of 03 (three) Nos of 10 (ten) feet length 40 mm dia earth eletrode made out by copper, maintenance free electrolytic grade copper earthing system based on flat in pipe technology of 3 Mtrs length , 40 mm dia with crystalite conductive mixture COMPOUND filled withthe permanent sealings at the top & bottom with the lead terminal / strip in 25x4 mm size copper with 2 holes of 10 mm dia at the top , to be lowered in 150 mm dia bore including filling of back fill ecofriendly earth enhancing compound tested by ROHS comply to IEC 62651-7 which should have passed leaching ,corrosion, supphur & resistivity test as per IEC 62651-7 by NABL accredit LAB/JAM plus compound in 150 mm bore in immediate contract around the earth electrode and top of the bore shall be finished with 40 mm thick PCC in 1:2:4 type B 1 over 75 mm thick PCC in 1:4:8 type D-2 and backfilly/ JAM compound shall be covererd with FRP pit cover of suitable size for each earth electrode , joint to be made by JAM weld exothermically welded technology including copper strip size 32 x 6 mm for earthing ring system and copper strip 32x6 mm size for earthing electrode to test point with saddles & porcelain insulators suitable size on wall ,earth strip protected by light grade GI pipe 40 mm dia in case of plinth protection / floor/ hard standing crossing complete all as specified and directed. Note :- Earth work , PCC work, PCC cutting work by cutter, earth chamber in suitable size with testing on suitable value etc rate shall deemed to be included in quoted rate |
| 25 | Removing the cover of cable duct for removal of unwanted vegetation/bushes/small plants/ shrubs/soil from cable duct not exc 3' wide and 3' deep at 33 KV sub station and removing the excavated material to a distance exceeding 50 M and placing the cover after completion complete all as specified and directed. |
| 26 | Removal coarse aggregate of any size from MES installation and segregate/removal of vegetation/ bushes/ small plants/ shrubs etc and after that spreading in the same location incl levelling and removing the vegetation/ bushes/ small plants/ shrubs to a distance exceeding 50 M complete all as specified and directed. |
| 27 | M&L for coarse aggregate not less than 40 mm graded nominal size without any vegetation or chemical incl levelling spreading all around complete all as specified and directed. |
| 28 | Supply & fixing PVC insulated sheathed aluminium conductor armoured cable with inner sheathing for service connection size 10 Sqmm 2 core 1100 Volt complete all as specified and directed. |
| 29 | Supply & fixing PVC insulated sheathed aluminium conductor armoured cable with inner sheathing for service connection size 6 Sqmm 2 core 1100 Volt complete all as specified and directed. |
| 30 | Supply & fixing self adhesive PVC insulation tape suitable for 11 KV, 25.1 MM x 9.1 Mtrs x 0.305 MM for HT Scotch-70 complete all as specified and directed. |
| 31 | Supply & fixing scotch Rubber mastic tape 2228, 2\\" (50 MM minimum) width and 10 feet in length suitable for 11 KV complete all as specified and directed. |
| 32 | Cable route indicator made out of RCC patties size 15cm x 15cm x 75cm in lengths duly engraved with (HT CABLE 11 KV) with projection of 45 cm above ground level and 30 cm grouted in foundation including PCC foundation, RCC shall be painted with yellow colour above ground and HT CABLE 11 KV will be marked with Red Colour Paint complete all as specified and directed. |
| 33 | Supply & fixing in replacement of 12 Volt 150AH,short tubular inverter battery with rugged construction maintenance free battery mounted on steel rack complete, testing and commissioning complete all as specified and directed. Make- Exide/Amarraja/Amron |
| 34 | Supply & replace battery lead of 1 mtre length, PVC insulated multistranded copper conductor of size 25 sqmm including one side cable lugs and other side battery terminal. complete suitable to connect starter of any sizes of DG set complete all as specified and directed. |
| 35 | Supply and fixing Inverter 12 volt 900 VA max load 756 watt, inverter type pure sine wave inverter with digital display, processor intelligent 32 bit DSP processor MCB for protection from input main complete with mounting stand suitable for inverter and Battery complete all as specified and directed. |
| 36 | M&L for RCC Nominal Mix 1:2:4 type B2 (using 12.5 mm coarse aggregate) for Cover of cable duct of size 1.5 ft width 3 ft length and 50 mm thickness using 10 mm steel reinforcement bar with 125x 125 mm distance of reinfocement on double side and 40x40x5mm angle on top edge of cover complete all as specified and directed. Note- Rate of panting of cover shuold be included in quoted unit rate . |
| 37 | Supply and fixing termination boots suitable size for RMU unit capacity 630 Amp including taking down old unsv termination boots complete all as specified and directed. |
| 38 | S&F Framed brackets of angles or tees with web and flanges cut to shape, drilled and countersunk for screw, including bending and welding angles, as necessary, gusset plates, riveting, etc.. n exc 10 kg each brackets, conforming to Fe.290.Gde-E-165 (Brackets over 10 kg each including necessary nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape and size as directed and including applying two coats of aluminium paint (under & finishing coats) over a coat of red oxide zinc chromate primer on exposed steel surfaces after preparation of surfaces, supplied and fixed in repair complete all as specified and directed.(Note: - (i) Sizes & types of members and shape of the cross arms etc shall be as required at site all as directed by the Engineer-in-Charge.(ii) Un-exposed steel surfaces shall be given one coat of red-oxide zinc chromate primer only. Cost of the same is included in unit rate of the item and nothing extra shall be paid on this account.)Framed brackets of angles or tees with web and flanges cut to shape, drilled and countersunk for screw, including bending and welding angles, as necessary, gusset plates, riveting, etc.. n exc 10 kg each brackets, conforming to Fe.290.Gde-E-165 (Bracketsover 10 kg each to be measured under 'Structural Steel') |
| 39 | S&F mild steel galvanised chain fencing made of galvanised steel wire of not less than 2.5 mm of fixed iron rails to flat iron rails with RCC/ angle iron post complete all as specified and directed. |
| 40 | M&L for cement concrete type B 2 in ratio 1:2:4 (using 40 MM graded aggregate) in foundation filling and mass concrete complete all as specified and directed. |
| 41 | M&L for cement concrete type C 2 in ratio 1:2:4 (using 20 MM graded aggregate) in foundation filling and mass concrete complete all as specified and directed. |
| 42 | Supply , installation, testing and commissioning and testing of power factor improvement panel of capacity 100 KVAR size of panel 1100 mm x 700 mm x 250 mm, fully type test according to IEC 61439-1&2,IEC 61921 including interconnection with LT panel with appropriate size of electric cable for Main panel, factory made, weather proof , dust and vermin proof (IP 65) suitable for Humidity: up to 95%,Average daily temperature: +35°C max,Ambient temperature: -5°C to 45°C, 1100 V/660 V grade 3 phase 50 HZ AC supply floor mounted , fabricated out of 14 SWG MS sheet welded on 40 x 40 x 3 mm angle iron frame / base of appropriate size and having four Nos angle iron legs made out of 40 x 40 x 6mm 60 cm long angle iron below frame with front door and back opening having locking arrangement prewired with copper conductor PVC insulated flexible wire size 1.5 sq mm / extension strips and connected with suitable size thimbles , lugs duly painted with grey epoxy powder coating after suitable chemical treatment , legs duly embedded in ground in PCC 1:3:6 of suitable size including locking arrangement suitable for mounting , with required sheet metal enclosures, thimbles , all as specified and directed by Engr-in-Charge and all other electric incoming and outgoing connections with PVC insulated multi stranded flexible copper NYVIN cable of suitable size and PVC flexible conduit medium quality as required , comprising of the following:- (A) Insulated Bus bar of aluminium of 250 Amps capacity for three phase, fixed on insulators, Busbar should be PVC sleeved with Red, Yellow & Blue Colour, Bus bar support should be of SMC/DMC, Rated Impulse Withstand Voltage 8KV -01 Set(B) Incommer MCCB 250 Amp , three pole, short circuit breaking capacity 36 KA Icu at 415 V (KA rms) Ics =100% , IEC 60947-2 Adjustable thermal and fixed magnetic setting ,frame LS type, Front Face, Isolation with Positive Break Indication with Double Break Contacts, Standard Extended Rotary Handle, Spreaders, Phase Barrier.Make:- Schneider/ Siemens / ABB/L&T/Havells -1 No.(C) Capacitor 100 KVAR (2 KVAR x 01 No, 3 KVAR x 01 No, 5 KVAR x 01 No, 10 KVAR x 01 No, 20 KVAR x 04 Nos), square type capacitor heavy duty rated, capacitor bank of rated 440 volt , 3 phase, Maximum over current: 1.8 In,Overpressure protection,Discharge resistance 50 V - 1 min, Capacitance Tolerance -5%, +10%,Maximum permissible over current(with thermal protection included)1.43 In ,Maximum permissible over voltage 1.1 x Un, 8 h every 24 h,of rated 440 volt with detuned Reactor of de-tuning factor (P) 7% and suitable output of 100 KVAr at 440 volt suitable output , Overheating protection by thermostat confirming to IS-13340-1993/, 13341-1992 & IEC -60831-1+2. .Make:- Schneider/ Siemens / ABB/L&T/Havells |
| 43 | (D)Intelligent Power factor controller relay 8 steps, seven segment LED Display, Augiliary power factor, Algotitham, Dual password protection 4 digit display, Alarm Indication on Display switching time programmable IS to 1809, 90V - 550V 50/60Hz 1A/5A with RS485 Make:- Schneider/ Siemens / ABB/L&T/Havells -01 No(G) SP MCB ,C-Curve, Control Circuit, .Make:- Schneider/ Siemens / ABB/L&T/Havells(H) CT 250/5A , 10 V.A,CL:1.0,Resin Cast , CT Secondary wire Size should be 2.5 Sq mm.Make : Kalpa /AE/ L&T/Kappa -03 Nos(L) Accessories for 100 KVAR capacitor Bank :- (1) Capacitor Duty Contactor (3 KVAR-02 Nos, 5 KVAR - 01 No, 12.5 KVAR- 01 No, 25 KVAR - 04 Nos) 440 volt with damping resistors which limit inrush Current,440 volt ,3ph,50 Hz, Coil-220 Vac, .Make:- Schneider/ Siemens / ABB/L&T/Havells(2) MCB TPN 10 Amp, 10 KA, 240 Volt(3) MCB TPN 16 to 25 Amp, 10 KA, 240 Volt(4) Digital Voltmeter of size 96x96mm (0-500V) with built in selector switch.(5) Digital Ammeter of size 96x96mm (0-400A) with built in selector switch. (6) Indication lamp 22.5mm dia LED type 240volts AC to show three phase availability-01Set.(N) Ventilating fans of required size to dissipiate the heat liberated by capacitor units complete with automatic switching ON and OFF of fans depending upon the temperature of the Panel. 230 V AC, 2650 rpm,160 Cu.m/h, Flying leads - 04 Nos (O) All accessories prewired with suitable size copper conductor cable insulated with fibre glass insulation to with stand high temperature, housed in cubical panel (CPRI approved) made out of 3.15 mm thick MS sheet factory made as per IEC 62208 duly powder coated front and rear door open able with locking arrangement complete with,IK 10 protection against mechanical Shocks as per IEC 62262 foundation as required or recommended by manufacturer. Make of APFC Panel Note: APFC Panel shall be manufactured by original manufacturer only. The firms specified cannot authorize any other vendors to manufacture APFC Panels on their behalf and the panels so manufactured will not be accepted. Total in Figures 0.0 23 INR Zero Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 Nos Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |