Indian Tenders

Tender Notice

TDR 55644040
Tendering Authority Military Engineer Services
Tender No 753049A PROVN OF MI ROOM FOR MIL STN MUZAFFARPUR
Tender ID 2026_MES_767054_1
Tender Brief Tender For Provn Of Mi Room For Mil Stn Muzaffarpur
City Danapur
State Bihar
Document Fees INR 1000 /-
EMD INR 244380.0 /-
Tender Value INR 1.69 Crore /-
Tender Type Tender
Bidding Type Open Tender
Competition Type Indian

Tender Details

Tender for Provn Of Mi Room For Mil Stn Muzaffarpur

Key Dates

Publish Date 22-05-2026
Last Date of Bid Submission 26-06-2026
Tender Opening Date 03-07-2026

Contact Information

Company Name Military Engineer Services
Contact Person HQ CHIEF ENGINEER JABALPUR ZONE
Address HQ CHIEF ENGINEER JABALPUR ZONE RIDGE ROAD JABALPUR 482001

BOQ Items

Name of Work:- PROVN OF MI ROOM FOR MIL STN MUZAFFARPUR
Sl. No. Item Description
1SCHEDULE \\"A\\" Part-I (Building/Structures) (To be quoted by the tenderer)
2Item No 01 A : Design and construction of MI Room incl ambulance bldg all as per drawing and specified
3Item No 01 B : Design and construction of cycle/ scooter shed bldg all as per drawing and specified
4Sch 'A' Part-II (Internal Electrification) Lump sum price worked out by the contractor for (Internal Electrification) as listed in Schedule 'A' Part-II against the lump sum price inserted by the MES.
5Sch 'A' Part-III (Internal Water Supply) Lump sum price worked out by the contractor for (Internal Water Supply) as listed in Schedule 'A' Part-III against the lump sum price inserted by the MES.
6Sch 'A' Part-IV (External Electric Supply) Lump sum price worked out by the contractor for (External Electric Supply) as listed in Schedule 'A' Part-IV against the lump sum price inserted by the MES.
7Sch 'A' Part-V (External Water supply) Lump sum price worked out by the contractor for (External Water supply) as listed in Schedule 'A' Part-V against the lump sum price inserted by the MES.
8Sch 'A' Part-VI (Road, Path Curvert) Lump sum price worked out by the contractor for (Road, Path Curvert) as listed in Schedule 'A' Part-VI against the lump sum price inserted by the MES.
9Sch 'A' Part-VII (Air Conditioning) Lump sum price worked out by the contractor for (Air Conditioning) as listed in Schedule 'A' Part-VII against the lump sum price inserted by the MES.
10Sch 'A' Part-VIII (Water Cooler) Lump sum price worked out by the contractor for (Water Cooler) as listed in Schedule 'A' Part-VIII against the lump sum price inserted by the MES.
11Sch 'A' Part-IX (Hot Water) Lump sum price worked out by the contractor for (Hot Water) as listed in Schedule 'A' Part-IX against the lump sum price inserted by the MES.
12Sch 'A' Part-X (FIRE Alarm and Extingusher) Lump sum price worked out by the contractor for (FIRE Alarm and Extingusher) as listed in Schedule 'A' Part-X against the lump sum price inserted by the MES.
13Sch 'A' Part-XI (Sewage Disposal) Lump sum price worked out by the contractor for (Sewage Disposal) as listed in Schedule 'A' Part-XI against the lump sum price inserted by the MES.
14Sch 'A' Part-XII (Area Drainage) Lump sum price worked out by the contractor for (Area Drainage) as listed in Schedule 'A' Part-XII against the lump sum price inserted by the MES.
15Sch 'A' Part-XIII (Site Clearance) Lump sum price worked out by the contractor for (Site Clearance) as listed in Schedule 'A' Part-XIII against the lump sum price inserted by the MES.
16Note for Srl No 2 to 15The percentage above / below the SSR -2020 (part-II) rates shall be derived from the amount quoted by the contractor against Srl No. 2 to 15 by comparing it with the amount inserted / pre- priced by the department and the same shall be applicable for the items of respective schedule
17Schedule 'A' Part-XIV (Miscellaneous items of works)
18INTERNAL ELECTRIFICATION
19Item No 02 : S & F for sheet metal enclosure MCCB DB VTPN 6 way Vertical type with 200 Amps rated bus bar 415 volts for incomming MCCB 4 pole -01 Nos and out going 18 Nos MCB Modules with double door with magnitic locking system including necessary provision for inserting the DBs in wall by cutting the brick/stone masonary etc and making good of distrubed surface to match with existing colour of wall complete all as specified and as directed. Note :-The rate of dummy plate shall be deemed to be included in unit rate of item.
20Item No 03 : S & F for MCCB 4 pole rated capacity 100 Amps, 415 Volts breaking capacity 16 KA, 'C' curve complete all as specified and as directed.
21External Electric supply
22Item No 04 : Labour for boring, holes for inserting of 50/80 mm bore GI pipe under the road/hard standing or any other location not less than 1200 mm deeep complete all as specified and ditected.
23Item No 05 : Supply laying fixing or passing through pipe 1100 Voltage grade heavy duty cable with PVC insulated and sheathed aluminium conductor comfirming to relevent IS size 6 sqmm 2 core unarmoured and connecting to system complete all as specified and directed.
24Item No 06 : Supply and fix FRP , hot press moulded SMC pole box 270 X225 X135 mm comprising of 100 Ams aluminium bus bar 4 strips ( IP 55 protection ) with one MCB SP 6 Ams to be fixed inside the box and box will be clamped bottom of the pole with FI clamps (duly painted ) nut bolt washers of required size.
25Item No 07 : S & F bracket made with GI tube light grade (not less than 1.2 RM) in length of 40 mm bore size and fixed to the LT pole with the help of two Nos FI Clamps of size 50X6 mm nut bolt and washers,complete all as specified and directed.
26Item No 08 : Supply ,fabrication, installation and testing of LT Panel out door type factory made CPRI Approved, water and vermin proof protection of size min 1500 mm x 1000 mm x 500 mm (min over all dimension) made out of 3.00 mm thick CRCA sheet dully supported with mild steel angle iron of size 50 x 50 x 6 mm vertical frame and legs with mild steel flat iron 25 x 5 mm in horizontal sides of the frame with front and back side openable ,single hinged door / shutter with locking arrengement and powder coated finish both internal and external steel surfaces after necessary preparation of steel surfaces including providing PCC (1:3:6) type C2 foundation of suitable size and connections of all outgoing / incomming cable inclusive of necessary excavation and earthwork as required including the following fitment accessories and also including removing old exisisting one complete all as specified and as directed. . NOTE:- Rate of earthwork and PCC work are deemed to be inclusive in this item.
27INCOMMING(a) Aluminium strip busbar of 300 amps rated capaacity wrapped with PVC sleeves with maintained the colour code and provision of making holes with Copper nuts, bolts & washers for cable connections including hydrograpic insulators with nuts & bolts at both ends = 04 Nos(b) 4 Pole MCCB 200 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links -01 Nos
28(c) LED Neon indicator lamp (RYB) with holder and fuse holder 230/250 volts, AC -01 set (set of three) Make :- Legrand/L&T/Schneider.(d) Digital Ammeter of range (0- 300) Amps, flush mounting type with CT’s of ratio 350/5 and selector switch – 01 set. (e) Digital voltmeter of range (0-500) volts, flush mounting type with selector switch – 01 No.
29OUTGOING(a) 4 Pole MCCB 125 Amps with rotary handle, adjustable thermal magnetic release type, 4 poles, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links -01 No(b) 4 Pole MCCB 63 Amps with rotary handle, adjustable thermal magnetic release type, 4 poles, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links -02 Nos(c) Enamelled iron danger notice plate of 1.60 mm thick mild steel sheet of size 200 mm x 150 mm , white with letters , figures and conventional skull and bones in signal red and fixed with nuts and bolts on door / shutter of JB for LT -01 No
30Item No 09 : Supply ,fabrication, installation and testing of LT Panel out door type factory made CPRI Approved, water and vermin proof protection of size 1000mm x 1000mm x 500 mm (over all dimension) made out of 3.00 mm thick CRCA sheet dully supported with mild steel angle iron of size 50 x 50 x 6 mm vertical frame and legs with mild steel flat iron 25 x 5 mm in horizontal sides of the frame with front and back side openable ,single hinged door / shutter with locking arrengement and powder coated finish both internal and external steel surfaces after necessary preparation of steel surfaces including providing PCC (1:3:6) type C2 foundation of suitable size and connections of all outgoing / incomming cable inclusive of necessary excavation and earthwork as required including the following fitment accessories and also including removing old exisisting one complete all as specified and as directed. Note: Rate of earthwork and PCC work are deemed to be inclusive in this item.
31INCOMMING(a) Aluminium strip busbar of 200 amps rated capaacity wrapped with PVC sleeves with maintained the colour code and provision of making holes with Copper nuts, bolts & washers for cable connections including hydrograpic insulators with nuts & bolts at both ends = 04 Nos(b) 4 pole MCCB 125 Amps with rotary handle, adjustable thermal magnetic release type 415 Volts, Ics = 100% Icu, breaking capacity 35 KA including all fixing accessories with both ends spreader links - 01 No.
32(c) LED Neon indicator lamp (RYB) with holder and fuse holder 230/250 volts, AC -01 set (set of three) Make :- Legrand/L&T/Schneider.(d) Digital Ammeter of range (0- 250) Amps, flush mounting type with CT’s of ratio 250/5 and selector switch – 01 set. (e) Digital voltmeter of range (0-500) volts, flush mounting type with selector switch – 01 No.
33OUTGOING(a) 4 Pole MCCB 100 Amps with rotary handle, adjustable thermal magnetic release type, 4 poles, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links -01 Nos (b) 4 Pole MCCB 63 Amps with rotary handle, adjustable thermal magnetic release type, 4 poles, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links -01 Nos (c) 4 Pole MCB 20 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links -02 Nos(d) Multifunctional Digial type timer Switch (Astro type having longitude and latitude of Indian cities memory) 240 volts AC Single Phase - 01 No(e) Power contractor 4 Pole, 40 Amps, 415 Volts, 50 Hz - 01 No (f) Enamelled iron danger notice plate of 1.60 mm thick mild steel sheet of size 200 mm x 150 mm , white with letters , figures and conventional skull and bones in signal red and fixed with nuts and bolts on door / shutter of JB for LT -01 No.
34Item No 10 : Supply and installation of silent Diesel Engine driven generating set of capacity 58.5 KVA(or nearest higher standard size) CPCB IV+ , 415 volts, 3 phase 4 wire,50 Hz engine as per IS:10001/ 10002 and Alternator as per IS: 13364 at power factor 0.8, noise level below 75dB at 1mtr distance, fuel tank capacity at least 165 litres, battery 150 AH or higher X 1 Nos, 12 Volt including suitable battery charger complete with as specification For Engine -4 nos. of cylinder, 1500 RPM rated speed, with Lube oil capacity of 10 litres (approx), and coolant tank capacity of 12.7 liters (approx) litres,For Alternator- Self - excited brushless with AVR ,insulation class-H, IP-23 protection, efficency at full load not below 93.6%, permissible voltage drop less than 20%, short circuit ratio is 0.629 and with foundation (as per OEM design) with advance digital controller relay panel and switch gears for automatic starting on main failure, control panel (AMF Panels), having meter and sound proof canopy as per CPCB IV+ norms & including necessary PCC plateform of suitable size as per OEM recommendation and Cover shed as per MES Practice as approved by GE for installation of DG set complete all as specified.
35External Water Supply
36Item No 11 : M & L for Construction of brick masonry valves pits , of the following internal dimension complete with 3.15 mm thick MS sheet cover angle iron frame duly painted with locking arrangement including all necessary excavation and earth work PCC wok complete for following size:
37(a) 900mm x 900mm x 900mm
38Refrigeration System
39Item No 12 : Supply , installation, testing and commissioning refrigerator electric driven single phase 230 Volt AC, 50 Hz freestanding, single door, inverter, direct cool 5 star rating of capacity 224 Ltrs(or nearest higher standard size) .
40Item No 13 : Supply and fixing voltage stabilizer for automatic operation single phase naturally air cooled indooor type and designed for input voltage between 130 volt to 280 volts with output voltage stabilized at 230 V +/- 2.5% with time delay relay and suitable for fixing / mounting on wall of capacity 1 KVA suitable for refrigerator copper wound complete for refrigerator all as specified and directed.
41Water cooler
42Item No 14 : Supply and fixing voltage stabilizer for automatic operation single phase naturally air cooled indooor type and designed for input voltage between 130 volt to 280 volts with output voltage stabilized at 230 V +/- 2.5% with time delay relay and suitable for fixing / mounting on wall of capacity 6A suitable for refrigerator copper wound complete for refrigerator all as specified and directed.
43Air Conditioning
44Item No 15 : Supply and fixing wall mounting voltage stabilizer for automatic operation single phase naturally air cooled indooor type and designed for input voltage between 150 volt to 285 volts with output voltage stabilized at 230 V +/- 2.5% with time delay relay and suitable for fixing / mounting on wall of capacity 4 KVA copper wound complete all as specified and directed.
45Item No 16 : Supply and fixing wall mounting voltage stabilizer for automatic operation single phase naturally air cooled indooor type and designed for input voltage between 130 volt to 280 volts with output voltage stabilized at 230 V +/- 2.5% with time delay relay and suitable for fixing / mounting on wall of capacity 5 KVA complete all as specified and directed.
46Item No 17 : Supply & fixing factory made,universal bracket / wall mounting stand ,made with galvanized structural steel,high strenth,weather proof,powder coated,modular construction and not less than 5 Kg and suitable upto 2 TR capacity split type AC.
47Dessert Cooler
48Item No 18 : Supply & fixing heavy duty desert cooler stainless steel 5000 cum/hr, with front grill and directional grills of suitable size and bottom water tank of capacity minimum 80 Ltrs with submersible pump motor 40 watt single phase complete all as specified and directed
49Shadowless light
50Item No 19 :Supply and installation, commissioning Shadow less light of 48X2 Watts fitting complete with emergency power unit & battery back up for min 30 minutes (3 KVA) and 48 nos. of LED light in each dome, 160000X2 lux intensity, dia of light 500mm, spot dia 100-150mm, depth of illumination 10-15cm, with colour temp. 3800-5200K, CRI 95Ra, adjustable focusing mode, digital intensity control, average life of LED light minimum 50000Hrs with memory functional remote control, fully counter balanced moveable on ceiling trolley having axial rotation of 360 degree. The unit to be suitable for operation on 230V, single phase 50 cycles mains supply complete all as specified and as directed.
51Item No 20 :Supply installation testing and commissioning online UPS for 40 min back up single phase AC input 160 to 260 V and out put 230 ± 1% of capacity 6 KVA complete with SMF batteries capacity 42Ah Qty 10 Nos complete as specified and as directed..
52FIRE ALARM & EXTINGUISHER
53Item No 21: Supply, installation, testing, and commissioning of Fully automatic DOL starter, suitable for the booster pump, complete with contactors, push button, LED type indicators, auto/manual selector switch, overload protection, current sensing type single phase preventer complete with all accessories and wiring etc.with ncomplete all as specified and directed by the engineer-in-charge.
54Item No 22 : S & Fof Pressure Gauge suitable for 0-14 kg pressure range with 4\\" dial, die cast aluminium body with white background & black marking, 1/2\\" Male NPT threaded connection, suitable to work in service temp. of -20 °C to 80 °C having accuracy of ± 1 % FSD assembled with ball valve, nipple, socket, etc. for pump suction & delivery lines of fire pump sets near the flow switches all complete as specified and directed by the engineer-in-charge.
55Item No 23 : M & L for low smoke zero halogen (LS0H)FRLSH fire alarm cable, 2 core, 1.5 mm² conforming to BS 7629-1, BS 6387 & BS EN 50200 and rated for 500 V, drawn through concealed PVC conduit and having plain annealed stranded copper conductor with primary insulation of glass mica fire resistant tape and secondary insulation of high performance silicone rubber, earth/drain wire of annealed tinned copper, electrostatic screen of aluminium fire barrier and type LTS3 outer sheath conforming to BS 7655, suitable for operating temperature range -30 ˚C to +70 ˚C and minimum bending radius being 6 times the overall cable diameter, RED in colour, including laying, termination and ferruling complete all as specified and directed by the engineer-in-charge
56Item No 24 : S & F PREMIUM Powder Fire Extinguisher (Stored Pressure type) Capacity 06 Kg duly ISI marked conforming to IS: 15683:2018, with IS 4308, ISI marked MAP 90% ABC powder complete with squeeze grip release valve, discharge pipe, locking arrangement, pressure gauge, operation manual and bracket. Operating Temperature: -30ºC to + 60ºC. along with suitable signage, etc. complete all as specified and directed by the engineer-in-charge. Make LIFEGUARD, Kanex, Minimax, Safeguard.
57Item No 25 : S & F of CO2 type Fire Extinguisher ISI marked conforming to IS: 15683. Capacity 4.5 Kg. Complete with delivery hose horn, wheel type release valve, locking arrangement, operation manual and bracket. Operating Temperature:- 30ºC to +60ºC.mounting accessories along with suitable signage complete all as specified and directed by the engineer-in-charge.Make LIFEGUARD, Kanex, Minimax, Safeguard.
58Item No 26 : S & F Mechanical Foam (AFFF) Fire Extinguisher Gas Cartridge type ISI marked conforming to IS: 15683. Capacity 9 litre. Complete with gas cartridge, delivery hose, squeeze grip release valve, locking arrangement, operation manual and bracket. Operating Temperature: +5ºC to + 60ºC.along with suitable signage, etc. complete all as specified and directed by the engineer-in-charge. Make LIFEGUARD, Kanex, Minimax, Safeguard.
59Item No 27 : Sign of size 450 MM X 150 MM reading 'FIRE POINT' in 12.5 mm block letters in White and Red background, properly spaced to provide good legibility located directly in corridor near to each Manual call point/Fire Extinguisher and squarely attached to the wall or partition in a way that the top of the sign is not above 2 m from the finished floor level
60Sewage Disposal
61Item No 28 : M&L for DWCPE (SN8) pipes 180 OD/163 ID, laid and jointed complete complete all as specified and directed for the following internal dia of pipes.
62Item No 29 : Construction of conventional septic tank designed to carry sewage and sullage water, excavation in any type of soil, PCC 1:4:8 below foundation, Brick wall, RCC 1:2:4 in slab with vent, manhole openings with cover construction etc, complete efective depth of 1.4m and overall depth 2.1 m for 25 users
63Item No 30 : Construction of soakage well excavation in any type of soil, foundation in PCC 1:4:8, wall of 1 bk thick and honeycombed masonary with top ring of RCC 1:2:4 concrete including RCC cover slab, interconnecting pipes complete filled with brick bats of size 1.8m dia and 3.0 m effective depth. Please Enable Macros to View BoQ information Schedule 'A' Part-II (Internal Electric Supply) Item Description of Item Unit Rate per unit(Rs.) Qty Amount (Rs.)
64M & L for Point wiring using approved colour coding as per IS, with multistranded copper conductor 1.5 Sq. mm (nominal area), two single core, PVC insulated and unsheathed FRLSH cable 1100 volts grade ISI-694 marked drawn through in and including heavy duty, PVC concealed conduit of white/ ivory colour including all accessories after chasing in wall/ceiling etc, heavy duty ISI marked, with mudular metal box min 1.2mm thick, duly covered with modular white colour plate with frame and other necessary accessories ncluding PVC insulated multistranded copper conductor 1.5 Sqmm (nominal area) single core FRLSH cable as earth continuity conductor to common earth and connecting to earth dolly including cutting, chasses and making good disturbed surface to match with existing finish with plaster complete all as specified and directed for the following :- Note :- a) One circuit should have maximum 8 to 10 pointsb) Circuit wire from MCB to switch board is deemed to be included with unit rate of item point wiring and the size of circit wire should be 2.5 sqmm for L, N, Earth point .c) Core coding for phase wires are RYB maintain, for neutral black colour and for Earth Green (a) One light point controlled by one, one way switch 5 Amps Point 992.75 44.0 43681.0 (b) One fan point/ exhaust fan point controlled by one, one way switch 5 Amps and regulator Point 992.75 24.0 23826.0 (c) One 3 point 5 Amps switch socket outlet point controlled by one switch on the same board. Point 284.1 20.0 5682.0 (d) One 3 pin 5 Amps switch socket outlet point controlled by one switch on independent boad. Point 1070.4 31.0 33182.4
65Description all as per item No 1 here in before but using 2.5 sq mm single core copper conductor two nos cables of multistranded flame retardant PVC insulated unsheathed 1100 volts grade for 5/15 amps switch socket cobmination point including necessary running of 2.5 sq mm copper conductor flame retardant PVC wire as earth continuity conductor along with wiring and connecting to the common eath dolly.Note :- a) Circuit wire from MCB to switch board is deemed to be included with unit rate of item point wiring and the size of circit wire should be 4.00 sqmm for L, N, E
66Description all as per item No 1 here in before but using 4 sq mm single core copper conductor two nos cables of multistranded flame retardant PVC insulated unsheathed 1100 volts grade for industrial socket point including necessary running of 4 sq mm copper conductor flame retardant PVC wire as earth continuity conductor along with wiring and connecting to the common eath dolly. Note connections to be drawn for segregated 4 way DBs in each dwelling unit for Ac and Geyser points .Note :- a) Circuit wire from MCB to switch board is deemed to be included with unit rate of item point wiring and the size of circit wire should be 4.0 sqmm for L, N, E
67M & L for Sub main wiring with approved colour coding as per IS with two single core PVC insulated FRLSH cable with stranded copper conductor of size 6 Sq mm nominal area and drawing into suitable size of PVC non metallic rigid heavy duty PVC conduit of white/ ivory colour and its accessaries ISI marked heavy duty of suitable size including concealed in wall etc one run of PVC insulated with 6.0 Sqmm (nominal area) stranded copper conductor FRLSH cable as earth wire complete all as specified and as directed. Note:- Two runs of 6 sqmm cable,one run of 6 sqmm cable and one run of PVC conduit will be measured as one unit .Note:- Each SPN DB separate ciruits are drawn from VTPN located on Entrance of MI Room.
68S & F ceiling rose, surface Bakelite with 3 terminals, ISI marked for batten fitting complete.
69S & F modular switch piano flush type, single pole, one way, and 5/6 Amp single module complete all as specified.
70S & F modular switch piano flush type, single pole, one way, and 15/16 Amp single module complete all as specified.
71S & F modular socket outlet multipurpose having provision for 3 pin, 5/6 Amp and 2 pin, 5/6 Amp, 2 module piano flush type complete all as specified.
72S & F modular socket outlet multipurpose having provision for 3 pin, 15/16 Amp and 3 pin, 5/6 Amp, 2 module piano flush type complete all as specified.
73S & F for sheet metal enclosure with socket plug top and MCBs 20 Amps 240v single pole and neutral enclosure with a two pin and earth plug and socket complete with necessary provision for inserting the metal enclosure box in wall by cutting the brick/stone masonary etc and making good of distrubed surface to match with existing colour of wall complete all as specified and as directed.
74S & F for sheet metal enclosure MCB DB SPN 12 way withsuitable Amps rated bus bar 240 volts double door including blanking plate for dummy space with magnitic locking system including necessary provision for inserting the DBs in wall by cutting the brick/stone masonary etc and making good of distrubed surface to match with existing colour of wall complete all as specified and as directed. Note :-The rate of dummy plate shall be deemed to be included in unit rate of item.
75S & F for MCB DP rated capacity 40 Amps, (nearest standard size ) 240 Volts breaking capacity 10 KA, 'C' curve complete all as specified and as directed.
76S & F for MCB Single pole rated capacity 6 Amps, 240 Volts breaking capacity 10 KA, 'C' curve complete all as specified and as directed.
77S & F for MCB Single pole rated capacity 10 Amps, 240 Volts breaking capacity 10 KA, 'C' curve complete all as specified and as directed.
78S & F for MCB Single pole rated capacity 16 Amps, 240 Volts breaking capacity 10 KA, 'C' curve complete all as specified and as directed.
79S & F for MCB Single pole rated capacity 20 Amps, 240 Volts breaking capacity 10 KA, 'C' curve complete all as specified and as directed.
80S & F for MCB Single pole rated capacity 40 Amps, 240 Volts breaking capacity 10 KA, 'C' curve complete all as specified and as directed.
81Supply and fixing ceiling fans complete with blades, down rods, remote controlled with battery and accessories, 230 V, 1200 mm sweep. Min air delivery 210 CFM with service value 6.0 BEE. Five star rated with brushless direct current motor (BLDC) complete all as specified and as directed.
82Supply and fix exhaust fan, steel body AC single Phase. 230V of size 380mm sweep with, blades, and frame and louvers with louvers shutter, 1200 RPM , copper winding fan single phase including making of hole suitable size fan base after cutting of brick/stone wall /suitable size of water proof ply wood complete all as specified and directed by Engineer in charge.
83S & F for wall mounted LED tube light fitting 1x 10 watts batten for surface mounted, anodized extruded aluminium housing, high transmissitivity diffuser, high lumen ouput box type fitting,luminous efficiency not less than 120 lumen/watt, CRI > 80% , THD < 30% , driver Efficiency > 85% , PF > 0.9. Correlated Color Temperature 6500K (cool daylight) 170 Volts to 230 volts and LED Chip, Diver and Housing should of same make with warranty option of 2 years from date of installation complete with all accessories internally pre wired and necessary mounting arrangements, provision of new 3 core multistranded copper conductor and flexible conduit of size 23/0.193 from ceiling rose to fitting complete all as specified and as directed.Make : Philips or equivalent in OSRAM/GE
84S & F for wall mounted LED tube light fitting 1x 20 watts batten for surface mounted, anodized extruded aluminium housing, high transmissitivity diffuser, high lumen ouput box type fitting,luminous efficiency not less than 120 lumen/watt, CRI > 80% , THD < 30% , driver Efficiency > 85% , PF > 0.9. Correlated Color Temperature 6500K (cool daylight) 170 Volts to 230 volts and LED Chip, Diver and Housing should of same make with warranty option of 2 years from date of installation complete with all accessories internally pre wired and necessary mounting arrangements, provision of new 3 core multistranded copper conductor and flexible conduit of size 23/0.193 from ceiling rose to fitting complete all as specified and as directed.Make : Philips or equivalent in OSRAM/GE
85S & F for Energy saving new generation environmental friendly long life versatile presure die cast aluminium IP 66 for security light fitting luminaire with high power LEDs as light source and electronic driver of capacity 35 watts(or nearest standard size) , luminous efficacy not less than 110 lumen/watt, LED Chip, Diver and Housing should of same make with pre wired and necessary mounting arrangements and provision of 2.5 sq mm three core copper conductor cable multi stranded from ceiling rose to light fitting including necessary dia GI pipe medium grade bracket 1.5 mtr long bend to required shape with clamps, nut, bolts complete all as directed by Engineer- in-charge. Make : Philips or equivalent in OSRAM/GE
86M & L for earthing complete with galvanized earth plate electrode 600mmx 600mm x 6mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below ground level) with top edge of the plate not less than 1.5mtr below ground level connected to galvenised earth lead wire of 4 mm dia by means of nuts, bolts, washes of galvanized iron or steel all as shown in electrical plate No 3 and testing on completion including adequate charcoal dust comman salt necessary excavation & earth work PCC(1:3:6) type C-1 pit with precast RCC Cover slab 40 mm thick in PCC(1:2:4) type B-1 reinforced with 6 mm dia MS bars @ 100 mm c/c both ways with funnel wire mesh and 20 mm dia GI pipe medium grade as watering pipe and 15 mm dia GI pipe for protection of GI wire up to 7.5 mtr connected to earthing point complete all as specified and as directed.
87M & L for Sub main wiring with approved colour coding as per IS with two single core PVC insulated FRLSH cable with stranded copper conductor of size 1.5 Sq mm nominal area and drawing into suitable size of PVC non metallic rigid heavy duty PVC conduit of white/ ivory colour and its accessaries ISI marked heavy duty of suitable size including concealed in wall etc one run of PVC insulated with 1.5 Sqmm (nominal area) stranded copper conductor FRLSH cable as earth wire complete all as specified and as directed. Note:- Two runs of 1.5 sqmm cable,one run of 1.5sqmm cable and one run of PVC conduit will be measured as one unit . Total carried over to BOQ Rs. 509746.4 Signature of Contactor DY Dir(Contracts) Date: For Accepting Officer Schedule 'A' Part-III (Internal Water Supply) Item Description of Item Unit Rate per unit(Rs.) Qty Amount (Rs.)
88Galvanised steel water tubing, medium grade, with all fitting 15mm bore and fixed complete to walls and ceilings or laid in floors
89Galvanised steel water tubing, medium grade, with all fitting 20mm bore and fixed complete to walls and ceilings or laid in floors
90Galvanised steel water tubing, medium grade, with all fitting 25mm bore and fixed complete to walls and ceilings or laid in floors
91S&F Bib taps, cast copper alloy with crutch or butterfly handle, chromium plated, fancy type screwed down, screwed for iron pipe or for brass ferrule of 15mm bore
92S&F Pillar taps, cast copper alloy, with capstan heads, chromium plated, fancy type screwed down high pressure, with or without lettered 'Hot' or 'Cold' with long screwed shanks and fly-nuts, screwed for iron pipe of 15mm bore
93S&F Angle Stop valves, cast copper alloy,fancy type, chromium plated screwed down, high pressure, with crutch or butterfly handle, screwed both ends for iron pipe or for unions of 15mm bore
94S&F Ball brass valves, high pressure, with polythene float and flynut complete, screwed for iron pipe or brass ferrule of 20mm bore
95S&F Gun-metal, globe or gate valves, with iron wheel head, screwed both ends for iron pipe of 20mm bore
96S&F Gun-metal, globe or gate valves, with iron wheel head, screwed both ends for iron pipe of 25mm bore
97S&F PVC connections 15mm size with PTMT nuts of length 450mm Total carried over to BOQ Rs. 24032.56 Signature of Contactor DY Dir(Contracts) Date: For Accepting Officer Schedule 'A' Part-IV (External Electric Supply) Item Description of Item Unit Rate per unit(Rs.) Qty Amount (Rs.)
98Excavation in trenches n.exc. 1.5 m deep and n.exc.1.5 m wide in any type of soil and forming bottom surfaces for laying of cable/ foundation of polescomplete all as specified and directed.
99Supply & laying sand cushioning for cable protection in trenches 8 cm before laying cable and 15 cm thick over the cable complete all as specified and ditected.
100Supply & laying brick for protection of cable sub class 'B' laid dry flat across the cable with width equal to the length of whole bricks complete all as specified and ditected.
101Returning filling in including spreading leveling watering and well ramming in layers n. exc. 25 cm complete all as specified and directed.
102Removal surplus soil at a distance n. exc. 50 m and deposited where diredted at a lavel not exc. 1.50 m above the starting pont complete all as specified and directed.
103M & L GI pipe 20 mm bore light grade fixed on pole/under road/on wall for protection of cable including all fittings complete all as specified and directed.
104M & L GI pipe 40 mm bore light grade fixed on pole/under road/on wall for protection of cable including all fittings complete all as specified and directed.
105M & L GI pipe 50 mm bore light grade fixed on pole/under road/on wall for protection of cable including all fittings complete all as specified and directed.
106M & L GI pipe 80 mm bore light grade fixed on pole/under road/on wall for protection of cable including all fittings complete all as specified and directed.
107Supply and laying in replacement ,jointing and testing XLPE insulated extruded PVC outer sheath and inner sheath galvanized steel armoured cable with aluminium conductor suitable for rated voltage of 1100 Volts grade conforming to IS 7089 (Pt I of 1988) laid in tranches/ pipe/duct/pole complete all as specified and directed size 150 sq mm 3.5 core.
108All as per item No 11 above but size 50 Sqmm 3.5 core.
109All as per item No 11 above but size 16 Sqmm 4 core.
110All as per item No 11 above but size 10 Sqmm 4 core.
111Supply and fix roadway luminaire LED light fittings of 70 watts luminious efficacy not less than 140lm/watt, [ron of inbuilt surge protection device and including necessary electric connection with 2.5 Sqmm twin core Copper conductor unarmoured cable, complete all as specified and directed.
112Supply, erecting and fixing in true vertical position steel tubular swaged pole 9.0 Mtr long type (410 SP -31) conforming to IS 2713 part I & III - 1980 complete with cast iron base plate, pole cap, mild steel, bolts, nuts and screws, welded and reduced section and longitudinal weld seam throughtout entire length of pole including two coats of black bituminous paint throughtout internally and externally upto planting depth and remaining exterior portion of pole with two coats of aluminium paint over a coat of red oxide primer complete including transporting the poles to plating & providing three bends/strap with paint red signal/post office colour 300 mm apart from plinth block & numbering of poles complete all as specified and directed. ( Note:- Earth work & PCC will be measured and paid separately under respective item )
113M&L for cement concrete (1:4:8 ) type D2 using 40 mm graded stone aggregate as in foundation filling and mass concrete complete all as specified and directed.
114M&L for cement concrete (1:3:6 ) type C2 using 40 mm graded stone aggregate as in foundation filling and mass concrete complete all as specified and directed.
115M&L for cement concrete (1:2:4) type B-1 using 20 mm graded stone aggregate as in coping , including necessary form work complete all as specified and directed.
116M&L earthing complete with galvanised steel earth plate 600X600X6 mm thick buried directly in ground (earth pit not les than 2.25 M deep below GL with top edge of plate not less than 1.5 m below GL) connected with GI earth strip of 32X6 mm as earthing leads by means of bolts, nuts, check nuts and washers beside brazing at all joints as shown on drawings and including excavation, earth work. GI pipe light grade 40 mm bore for protection of GI earth strip from earth electrode to and including the earth test point, supplying and laying charcoal dust, common salt PCC (1:2:4) type B1chamber and MS angle iron frame of 40mmx40mm x3 mmand RCC cover 40 mm thick (1:2:4) type B1 using 20 mm graded stone aggregate reinforced with 8 mm dia TMT bars @ 75 mm C/C both ways with MS handle 12 mm dia, PGI funnel and wire mesh, 20 mm dia GI pipe light grade for watering all as shown in electrical plate No 3 of SSR Part -I and conected to earth test point including testing complete all as secified and directed. Total carried over to BOQ Rs. 1088426.23 Signature of Contactor DY Dir(Contracts) Date: For Accepting Officer Schedule 'A' Part V (External Water supply) Item Description of Item Unit Rate per Unit (Rs.) Qty Amount (Rs.)
117Excavating in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth for laying of cables & foundation of poles , stay assembly and getting out in any type of soil complete all as specified and directed .
118Returning, filling in excavated approved soil, including spreading, leveling, watering and well ramming in layers not exceeding 25cm each complete.
119Removing excavated soil not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete.
120Supply and laying for galvanised iron tubing medium grade with and including all fittings such as bends, elbows, tees, short pieces, union etc in trenches complete all as specified and as directed of following sizes :-. (a) 80 mm (3”) dia. RM 771.0 416.0 320736.0 (b) 25 mm (1.0”) dia RM 196.0 50.0 9800.0
121Supply and fix cast iron flanged sluice valve of class 1.6 PN installed complete with ISI marked (IS-14846) with gun metal spindle and hand wheel all as specified and directed by EIC including taking down old unserviceable one of following size (a) 80 mm bore Each 9500.0 2.0 19000.0
122S & F for gun metal gate valve with iron wheel head screwed both ends ISI marked fixed to GI pipe complete all as specified and as directed of following sizes :- (a) 25 mm bore GI pipe Each 1556.0 4.0 6224.0
123M & L for cutting existing CI water mains 150 mm dia in position for insertion of tee, branch line etc to new water connection complete all as specified and directed.
124S & F CI fittings for spigot, socket pipes such as, bends( any type radius and angle) , tapers any type (straight bends in increasing , decreasing or double socket etc.) Tee pieces ,single branch, 'Y' junctions , double branch, cross ( all sockets or socket and spigot), collars , caps and plugs suitable up to 150 mm bore complete all as specified . Total carried over to BOQ Rs. 432792.51 Signature of Contactor DY Dir(Contracts) Date: For Accepting Officer Schedule 'A' Part VI (Road, Path Curvert ) Item Description of Item Unit Rate per unit (Rs.) Qty Amount (Rs.)
125Surface dressing n exc 15 cm deep and getting out in soft/loose soil all as spd.
126Excavating in trenches, n exc 1.5 m wide and n exc 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. n exc 10 sq m on plan and n exc 1.5 m in depth and getting out in Soft/Loose Soil.
127M&L for Brickwork with old size fly ash bricks, straight or curved on plan in CM 1:6 complete.
128M&L 15mm thick cement plaster on fair faces of bricks work or concrete surfaces with cement mortar 1:6 finished even and smooth (without using extra cement) complete.
129M&L for Moorum/red bajri filling in floors or pavings, laid in layers n exc. 15 cm thick, spread, levelled and rammed including watering (for floor rising due to water loginig area).
130M & L for Hardcore of gauge exc. 63 mm but not exc. 100 mm, deposited, spread and leveled in layers not exc. 15 cm thick, watered and rammed to a true surface using broken bricks complete all as specified and directed.
131M&L cement concrete 1:4:8 type D-2 using 40mm graded aggregate in foundation, filling and mass concrete complete.
132M&L for sand filling under floors or in foundations, laid in layers n exc 15 cm thick, spread levelled including watering and consolidation complete all as specified and directed
133M&L for Machine pressed precast concrete interlocking paver block with gray cement and pigment any shape and size confirming to IS 15658-2006 of 80 mm thickness M-40 Grade
134M&L for PCC 1:2:4 type B1 (using 20mm graded stone aggregate),as in coping Total carried over to BOQ Rs. 1104266.39 Signature of Contactor DY Dir(Contracts) Date: For Accepting Officer Schedule 'A' Part VII (Air Conditioning) Item Description of Item Unit Rate per unit (Rs.) Qty Amount (Rs.)
135Supply & Fixing split type air conditioner of capacity 2.0 TR 5 star rating and EER 3.2. with cordless remote control unit and in built air ioniser ,plasma filter for better indoor air quality, suitable for wall mounted,single phase, 230/250 volt AC including breaking necessary hole in wall for fixing indoor and outdoor unit and making good to disturbed surfaces with cement mortar to match with existing after commissioning as required at site, making necessary connections and M & L for unplasticised PVC pipes medium duty 20 mm dia for draining out condensed water all as required and directed including necessary connection through voltage stabilizer,testing of AC complete all as specified and directed.
136Supply & Fixing split type air conditioner of capacity 1.5 TR 5 star rating and EER 3.2. with cordless remote control unit and in built air ioniser ,plasma filter for better indoor air quality, suitable for wall mounted,single phase, 230/250 volt AC including breaking necessary hole in wall for fixing indoor and outdoor unit and making good to disturbed surfaces with cement mortar to match with existing after commissioning as required at site, making necessary connections and M & L for unplasticised PVC pipes medium duty 20 mm dia for draining out condensed water all as required and directed including necessary connection through voltage stabilizer,testing of AC complete all as specified and directed. Total carried over to BOQ Rs. 304485.1 Signature of Contactor DY Dir(Contracts) Date: For Accepting Officer Schedule 'A' Part VIII (Water Cooler) Item Description of Item Unit Rate per Unit (Rs.) Qty Amount (Rs.)
137Supply, installation, commissioning of Water cooler fully stainless steel, electric driven single phase having approx storage and nominal cooling capacity 60/120 Ltrs with proper platform of PCC and drain out waste water arrangement complete all as specified and directed. Total carried over to BOQ Rs. 55657.83 Signature of Contactor DY Dir(Contracts) Date: For Accepting Officer Schedule 'A' Part IX (Hot Water) Item Description of Item Unit Rate per Unit (Rs.) Qty Amount (Rs.)
138Supply and fix electric water heater, storage type steel body with copper inner tank and heating element upto 2 KW capacity 25 litre, BEE 5 Star rated complete with all accessories such as safety valve, thermostate, NRV, connection piece etc. complete all as specified and directed.. Total carried over to BOQ Rs. 10029.54 Signature of Contactor DY Dir(Contracts) Date: For Accepting Officer Schedule 'A' Part X (FIRE ALARM AND EXTINGUSHER) Item Description of Item Unit Rate per unit (Rs.) Qty Amount (Rs.)
139Supply, installation, testing and commissioning of electric driven Booster Pump to deliver 450 LPM flowrate at 30 m head and suitable for automatic operation , necessary mounting base with iron and PCC and consisting of complete with accessories with cover shed as directed by GE all as specified and directed by the engineer-in-charge.
140M & L for ISI marked MS ERW Pipes with all accessories like all fittings including tees, elbows, reducers, union, flanges, rubber gaskets, GI nuts bolts, washer, including supporting / fixing the pipe on floor / wall / ceiling with clamps, hangers, angles, channels (using anchor fastners) with painting of one coat primer and 2 or more coats of synthetic enamel paint complete all as specified and directed by the engineer-in-charge for bore size 25 mm .
141S & F of rated three-piece design 25 mm NB Cast Steel (CS) Straight pattern ball valve, conforming to IS 9890: 1981 and tested as per BS 6755-1, having Cast iron body, Stainless steel AISI 304 ball, renewable PTFE seat & gland packing, CS fastners & lever having screwed / socket weld end connection with accessories complete all as specified and directed by the engineer-in-charge.
142S & F of sprinkler glass bulb type (standard response) a per IS : 15106/TAC guidelines 68 degree temperature rating pendent type complete all as specified and directed by the engineer-in-charge.
143Supply, installation, testing and commissioning of Fire Alarm Control Panel (FCAP) complying with BS EN 54 single loop panel of capacity from 99 detectors & 99 modules upto 200 detector and modules, with required accessories complete all as specified and directed by the engineer-in-charge. (Note:- The FACP shall have four access levels, flash EPROM, 240 VAC power supply, automatic battery charger, 24 V sealed lead acid batteries, sufficient for 24 hrs normal working and 30 min in alarm condition.)
144Supply, installation, testing and commissioning of FM approved and UL listed surface / semi- flush mounted Dual Action Manual Pull Station \\"Push In & Pull Down\\" including an addressable interface for the intelligent FACP having built-in bicolour LED which is visible, flashing in normal operation and latching steady red in alarm condition, captive screw terminals wire-ready for easy connection to SLC loop complete all as specified and directed by engineer-in-charge.
145Supply, installation, testing and commissioning of UL listed of Horn Strobe, wired as a primary notification appliance, flashing 75 cd at 1 Hz over the strobe's entire operating voltage range, xenon flash tube and associated lens / reflector system, built-in synchronization feature keeping strobes in sync for up to 30 minutes, horn producing audible annunciation of 75 dBA at 3 m distance complete all as specified and directed by engineer-in-charge. Total carried over to BOQ Rs. 196355.62 Signature of Contactor DY Dir(Contracts) Date: For Accepting Officer Schedule 'A' Part XI (Sewage Disposal) Item Description of Item Unit Rate per unit (Rs.) Qty Amount (Rs.)
146Excavating over areas n exc 1.5m in depth for foundation etc. and getting out in soft/loose soil.
147Returning, filling in, including spreading, levelling, watering & well ramming in layers n. exc 25 cm in soft/loose soil.
148Removing excavated soil n exc. 50m & depositing where directed at a level n exc. 1.5 m above the starting point
149M&L for PCC (1:4:8) type D-2 (using 40mm graded stone aggregate) as in foundation, filling & mass concrete complete all as specified
150M&L Brick work with sub class ‘B’ bricks straight or curved on plan exc 6m mean radius built in CM 1:6
151M&L for concrete bed in PCC 1:4:8 type D2 (using 40mm graded Aggr) to drain pipes including packing under and haunching against the sides of the 150mm dia pipes after laying and testing complete all as specified
152M&L for PCC 1:2:4 type B1 using 20 mm graded aggr as in roof curb & mud stops, coaping benching and surface channel and for similar work including necessary formwork complete all as specified and directed.
153M&L for rendering 15mm thick in cement mortar 1:4 on concrete surfaces specified and directed.
154Extra for forming fair finished drain or channel 30 cm inner girth in cement concrete, using ex- tra cement, including forms, moulds, mi- tred/stopped ends etc.
155S&F Mild steel TMT bars, 10 mm dia and over, cut to length, bent to shape required, including cranking, bending spirally for hoopinbg for columns, hooking ends and binding with and including MS wire (annealed) not less than 0.9 mm dia or securing with clips all as specified
156M&L for precast cement concrete in landing, cover slabs (for manholes etc) 1:2:4 type B1 all as specified and directed by Engr-in-Charge. Total carried over to BOQ Rs. 69006.67 Signature of Contactor DY Dir(Contracts) Date: For Accepting Officer Schedule 'A' Part XII (Area Drainage) Item Description of Item Unit Rate per unit (Rs.) Qty Amount (Rs.)
157Excavation over area n. exc 1.5 mtr deep and getting out soft / loose soil complete all as specified and directed.
158M&L PCC 1:4:8 as in bed to drain, type D2 with 40mm aggregate
159M&L Brick work with subclass 'B' Bricks, straight or curved on plan exc 6m mean redius built in CM 1 :6
160M&L for PCC 1:2:4 type B-2 using ( 40 mm graded stone Agg ) in surfaces channel and drains complete all as specified and directed
161M&L for PCC 1:2:4 type B-1 using ( 20 mm graded stone Agg ) as in coping including rounded or chamfered angles complete all as specified and directed
162M&L for Moorum/red bajri filling in floors or pavings, laid in layers n exc. 15 cm thick, spread, levelled and rammed including watering (for floor rising due to water loginig area).
163Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cm. thick all as specified and as directed at site by Engineer-in Charge.
164Removing surplus excavated material to a distance exc. 250m and and n.exc 500 mtr and depositing where directed as specified and as directed .
165Extra for forming fair finished drain or channel 30 cm inner girth in cement concrete, using ex- tra cement, including forms, moulds, mi- tred/stopped ends etc.
166Add or deduct for each 25 mm girth or part thereof over or under 30cm ditto
167Supply and fixing 75 mm dia PVC (SWR) pipes single socketed, in any length for weep hole in drain at 3.0 mtr c/c in alternate
168M&L for stone aggregate of 40 mm size Hand packing (any thickness) at back of walls over drain. and raising (or lowering) to the required level Total carried over to BOQ Rs. 170992.71 Signature of Contactor DY Dir(Contracts) Date: For Accepting Officer Schedule 'A' Part XIII (Site Clearance) Item Description of Item Unit Rate per unit(Rs.) Qty Amount (Rs.)
169Surface dressing n. Exc 15cm deep in soft/loose soil all as specified
170M&L for Moorum/red bajri filling in floors or pavings, laid in layers n exc. 15 cm thick, spread, levelled and rammed including watering (for floor rising due to water loginig area). Total carried over to BOQ Rs. 558642.57 SIGNATURE OF CONTRACTOR DY Dir (Contracts) DATED _________ FOR ACCEPTING OFFICER

Other Detail

Information Source https://defproc.gov.in/nicgep/app
Download FileName File Description File Size
Download BOQ_859175.xls Tender Documents 0 KB