Indian Tenders

Tender Notice

TDR 55636515
Tendering Authority Hll Lifecare Limited
Tender No HLL/CMO/HCD/T-IV/AP/26-27
Tender ID 2026_HLL_278497_1
Tender Brief Tender For Civil & Electrical - Estimate For The Construction Of Type Iv Building At Aiims Mangalagiri
City Guntur
State Andhra Pradesh
Document Fees INR 2950 /-
EMD INR 1004750.0 /-
Tender Value INR 4.01 Crore /-
Tender Type Tender
Bidding Type Open Tender
Competition Type Indian

Tender Details

Tender for Civil & Electrical - Estimate For The Construction Of Type Iv Building At Aiims Mangalagiri

Key Dates

Publish Date 22-05-2026
Last Date of Bid Submission 30-05-2026
Tender Opening Date 01-06-2026

Contact Information

Company Name Hll Lifecare Limited
Contact Person ASSOCIATE VICE PRESIDENT
Address HLL Lifecare Limited, HLL Bhavan, No26/4, Tambaram-Velachery Main Road, Pallikaranai, Chennai 600 100, Tamilnadu

BOQ Items

Name of Work:- Civil & Electrical - ESTIMATE FOR THE CONSTRUCTION OF TYPE IV BUILDING AT AIIMS MANGALAGIRI
Sl. No. Item Description
1CIVIL WORKS
2SITE CLEARENCE
3Clearing jungle including uprooting of rank vegetation, grass, brush wood, trees and saplings of girth upto 30 cm measured at a height of 1 m above ground level and removal of rubbish upto a distance of 50 m outside the periphery of the area cleared.
4EARTH WORK EXCAVATION
5Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. All kinds of soil.
6Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m
7Filling with contractor's own earth ( excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m as per direction of site Engineer-in-charge
8Extra for every additional lift 1.5 m or part there of in excavation / banking excavated or stacked materials.All kinds of soil
9PLAIN CEMENT CONCRETE
10Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:4:8 (1 Cement : 4 coarse sand (zone-III) : 8 graded stone aggregate 40 mm nominal size)
11Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work above plinth level : 1:4:8 (1 Cement : 4 coarse sand (zone-III) : 8 graded stone aggregate 40 mm nominal size)
12Making plinth protection 50mm thick of cement concrete 1:3:6 (1 cement : 3 coarse sand (zone-III) derived from natural sources : 6 graded stone aggregate 20 mm nominal size derived from natural sources) over 75mm thick bed of dry brick ballast 40 mm nominal size, well rammed and consolidated and grouted with fine sand, including necessary excavation, levelling & dressing & finishing the top smooth.
13RCC WORK
14Providing and laying in position machine batched and machine mixed design mix M-30 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer - in-charge.All work upto plinth level.
15Providing and laying in position machine batched and machine mixed design mix M-30 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer - in-charge. Note:- Cement content considered in this item is @ 400 kg/ cum.All work above plinth level upto floor V level
16Providing concrete grade 1:5:10 upto floor V level to cast Dummy columns to cover the projecting reinforcement of columns just below finished floors (for a length equal to lap length in compression but not less than 24d) to lap reinforcement for future vertical extension of columns for subsequent floors so as to prevent rusting/corrosion of bars due to environmental influences. It should be ensured that the columns so casted will cover the full height of projecting bars and no part shall left uncovered. The concrete in Dummy columns so casted will be demolished prior to vertical extension of columns is susequent floors.
17Reinforced cement concrete work in beams, suspended floors, roofs having slope up to 15° landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral stair cases above plinth level up to floor five level, excluding the cost of centering, shuttering, finishing and reinforcement, with 1:1.5:3 (1 cement : 1.5 coarse sand (zone-III) : 3 graded stone aggregate 20 mm nominal size).
18Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete below plinth level. Thermo-Mechanically Treated bars of grade Fe-500D or more.
19Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete above plinth level. Thermo-Mechanically Treated bars of grade Fe-500D or more.
20Add for using extra cement in the items of design mix over and above the specified cement content therein
21FORM WORK
22Centering and shuttering including strutting, propping etc. and removal of form for : Foundations, footings, bases of columns, etc. for mass concrete
23Centering and shuttering including strutting, propping etc. and removal of form for Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc.
24Centering and shuttering including strutting, propping etc. and removal of form for : Suspended floors, roofs, landings, balconies and access platform
25Centering and shuttering including strutting, propping etc. and removal of form for : Lintels, beams, plinth beams, girders, bressumers and cantilevers
26Centering and shuttering including strutting, propping etc. and removal of form for : Edges of slabs and breaks in floors and walls Under 20 cm wide
27Centering and shuttering including strutting, propping etc. and removal of form for : Stairs, (excluding landings) except spiral-staircases
28Centering and shuttering including strutting, propping etc. and removal of form for : Edges of slabs and breaks in floors and walls Under 20 cm wide
29Centering and shuttering including strutting, propping etc. and removal of form for : Weather shade, Chajjas, corbels etc., including edges
30STEEL WORK
31Steel work in built up tubular (round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete.
32Providing and fixing stainless steel ( Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners , stainless steel bolts etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-incharge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.).
33Providing at all heights, levels and locations Aluminium profile industrial troughed sheet of Alloy 31500/31000/40800, conforming to IS 1254, IS 737, IS 2676. The sheet shall be fixed using self drilling/ self tapping SS screws of size 5.5x65 mm with EPDM seal complete upto required pitch in horizontal, vertical or curved surfaces i/c cutting to size and shape where required as per specifications, detail drawings and direction of Engineer-in-Charge. The rate shall be inclusive of all screws, seal, ridge, labour, scaffolding, machinery for fixing and approved sealent where required etc. but excluding the cost of purlins, rafters and trusses 0.71 mm thick, the profile detail width 1044/920 mm, cover width 1000/875 mm.
34STONE WORK
35Random rubble masonry with hard stone in foundation and plinth including levelling up with cement concrete 1:6:12 (1 cement : 6 coarse sand : 12 graded stone aggregate 20 mm nominal size) up to plinth level with:Cement mortar 1:6 (1 cement : 6 coarse sand)
36MASONRY WORK
37Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in :Cement mortar 1:4 (1 cement : 4 coarse sand)
38Half brick masonry with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level. Cement mortar 1:4 (1 cement :4 coarse sand)
39PLASTERING
4012 mm cement plaster of mix 1:4 (1 cement: 4 fine sand)
416 mm cement plaster of mix : 1:3 (1 cement : 3 fine sand)
42DOORS & WINDOWS
43Providing wood work in frames of doors, windows, clerestory windows and other frames, wrought framed and fixed in position with hold fast lugs or with dash fasteners of required dia & length (hold fast lugs or dash fastener shall be paid for separately). Sal wood or other similar quality wood
44Providing 40x5 mm flat iron hold fast 400 mm long including fixing to frame with 10 mm diameter bolts, nuts and wooden plugs and embedding in cement concrete block 300x100x150 mm 1:3:6 mix (1 cement : 3 coarse sand : 6 graded stone aggregate 20mm nominal size).
45Providing and fixing Fiber Glass Reinforced plastic (FRP) Door Frames of cross-section 90 mm x 45 mm having single rebate of 32 mm x 15 mm to receive shutter of 30 mm thickness. The laminate shall be moulded with fire resistant grade unsaturated polyester resin and chopped mat. Door frame laminate shall be 2mm thick and shall be filled with suitable wooden block in all the three legs. The frame shall be covered with fiber glass from all sides. M.S. stay shall be provided at the bottom to steady the frame.
4630 mm thick Glass Fibre Reinforced Plastic (FRP) panelled door shutter of required Colour and approved brand and manufacture, made with fire - retardant grade unsaturated polyester resin, moulded to 3 mm thick FRP laminate for forming hollow rails and styles, with wooden frame and suitable blocks of seasoned wood inside at required places for fixing of fittings, cast monolithically with 5 mm thick FRP laminate for panels conforming to IS: 14856, including fixing to frames.
47Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) decorative type, core of block board construction with frame of 1st class hard wood and well matched teak 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters. 35 mm thick including ISI marked Stainless Steel butt hinges with necessary screws
48Extra for providing ISI marked Stainless Steel butt hinges instead of M.S. pressed butt hinges bright finished of required size with necessary screws. (Shutter area to be measured)
49Providing and fixing bright finished brass tower bolts (barrel type) with necessary screws etc. complete : 200x10 mm
50Providing and fixing bright finished brass handles with screws etc. complete: 125 mm
51Providing and fixing bright finished brass hanging type floor door stopper with necessary screws, etc. complete.
52Providing and fixing aluminium extruded section body tubular type universal hydraulic door closer (having brand logo with ISI, IS : 3564, embossed on the body, door weight upto 36 kg to 80 kg and door width from 701 mm to 1000 mm) with double speed adjustment with necessary accessories and screws etc. complete.
53Providing and fixing bright finished 100 mm mortice lock with 6 levers without pair of handles of approved quality for aluminium door, with necessary screws etc complete as per direction of Engineer- in-charge.
54Providing and fixing 1mm thick M.S. sheet door with frame of 40x40x6 mm angle iron and 3 mm M.S. gusset plates at the junctions and corners, all necessary fittings complete, including applying a priming coat of approved steel primer.Using M.S. angels 40x40x6 mm for diagonal braces
55Providing and fixing factory made uPVC white colour casement/casement cum fixed glazed windows comprising of uPVC multi-chambered frame, sash and mullion (where ever required) extruded profiles duly reinforced with 1.60 ± 0.2 mm thick galvanized mild steel section made from roll forming process of required length (shape & size according to uPVC profile), uPVC extruded glazing beads of appropriate dimension, EPDM gasket, stainless steel (SS 304 grade) friction hinges, zinc alloy (white powder coated) casement handles, G.I fasteners 100 x 8 mm size for fixing frame to finished wall, plastic packers, plastic caps and necessary stainless steel screws etc. Profile of frame & sash shall be mitred cut and fusion welded at all corners, mullion (if required) shall be also fusion welded including drilling of holes for fixing hardware's and drainage of water etc. After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealant over backer rod of required size and of approved quality, all complete as per approved drawing & direction of Engineer-in-Charge. (Single / double glass panes and silicon sealant shall be paid separately) Note: For uPVC frame, sash and mullion extruded profiles minus 5% tolerancein dimension i.e. in depth & width of profile shall be acceptable.Casement window double panels with S.S. friction hinges (300 x 19 x 1.9 mm) made of (small series) frame 47 x 50 mm, sash 47 x 68 mm & mullion 47 x 68 mm all having wall thickness of 1.9 ± 0.2 mm and single glazing bead of appropriate dimension. (Area of window above 0.75 sqm upto 1.50 sqm).
56Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic item):With float glass panes of 5 mm thickness (weight not less than 12.50 kg/ sqm)
57Providing and fixing factory made uPVC white colour casement/casement cum fixed glazed windows comprising of uPVC multi-chambered frame, sash and mullion (where ever required) extruded profiles duly reinforced with 1.60 +/- 0.2 mm thick galvanized mild steel section made from roll forming process of required length (shape & size according to uPVC profile), uPVC extruded glazing beads of appropriate dimension, EPDM gasket, stainless steel (SS 304 grade) friction hinges, zinc alloy (white powder coated) casement handles, G.I fasteners 100 x 8 mm size for fixing frame to finished wall, plastic packers, plastic caps and necessary stainless steel screws etc. Profile of frame & sash shall be mitred cut and fusion welded at all corners, mullion (if required) shall be also fusion welded including drilling of holes for fixing hardware's and drainage of water etc. After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealant over backer rod of required size and of approved quality, all complete as per approved drawing & direction of Engineer-in-Charge. (Single / double glass panes and silicon sealant shall be paid separately) Note: For uPVC frame, sash and mullion extruded profiles minus 5% tolerance in dimension i.e. in depth & width of profile shall be acceptable.Casement window single panel with S.S. friction hinges (300 x 19 x 1.9 mm), made of (small series) frame 47 x 50 mm & sash 47 x 68 mm both having wall thickness of 1.9 +/- 0.2 mm and single glass pane glazing bead of appropriate dimension. (Area of window upto 0.75 sqm.)
58Providing and fixing casement handle made of zinc alloyed (white powder coated) for uPVC casement window with necessary screws etc. complete.
59Providing and fixing fire resistant door frame of section 143 x 57 mm having built in rebate made out of 16 SWG G.I. sheet (zinc coating not less than 120 gm/sqm) duly filled with vermuculite based concrete mix, suitable for mounting 60 minutes fire rated door shutters. The frame is fitted with intumuscent fire seal strip of size 10x4 mm (minimum) alround the frame and fixing with dash fastener of approved size and make, including applying a coat of approved brand fire resistant primer etc. complete as per direction of Engineer-in-charge (Dash fastener to be paid for separately).
60Providing and fixing 50 mm thick glazed fire resistant door shutters of 60 minutes fire rating conforming to IS:3614 (Part-II), tested and certified as per laboratory approved by Engineer-in-charge, with suitable mounting on door frame, consisting of vertical styles, lock rail, top rail 100 mm wide, bottom rail 200 mm wide, made out of 16 SWG G.I.sheet (zinc coating not less than 120 gm/m2) duly filled FR insulation material and fixing with necessary stainless steel ball bearing hinges of approved make, including applying a coat of approved fire resistant primer etc. all complete as per direction of Engineer-in-charge (panneling to be paid for separately).
61Providing and fixing glazing in fire resistant door shutters, fixed panels & partitions etc., with G.I. beading made out of 1.6 mm thick G.I. sheet (zinc coating not less than 120 gm/m²) of size 20 x 33 mm screwed with M4 x 38 mm SS screws at distance 75 mm from the edges and 150 mm c/c , including applying a coat of approved fire resistant primer/powder coating of not less than 30 micron on G.I. beading, & special ceramic tape of 5 x 20 mm size etc complete in all respect as per NBC 2016, IS 16231 (Part 3):2016 and as per direction of Engineer-in-charge with glass of required thickness having 60 minutes of fire resistance both integrity & radiation control (EW60) and minimum 20 minutes of insulation (EI20). The manufacturer have to give test report/certification of fire glass and the glass should have the stamp showing the value of E, EW & EI. The glass shall be tested in approved NABL accredited lab or by any other accreditation body which operates in accordance with ISO/IEC 17011 and accredits labs as per ISO/IEC 17025 for testing and calibration scopes shall be eligible. The maximum glazing size shall not be more than 1100x2200 mm (w x h) or 2.42 sqm.
62Providing and fixing panic bar / latch (Double point) fitted with a single body, Trim Latch & Lock on back side of the Panic Latch of reputed brand and manufacture to be approved by the Engineer- in- charge, all complete.
63Providing and fixing M.S. Grills of required pattern in frames of windows etc. with M.S. flats, square or round bars etc. including priming coat with approved steel primer all complete.Fixed to openings/ wooden frames with rawl plugs screws etc
64WALL TILE
65Providing and laying Vitrified tiles in different sizes (thickness to be specified by the manufacturer), with water absorption less than 0.08% and conforming to IS: 15622, of approved brand & manufacturer, in all colours and shade, in skirting, riser of steps, laid with cement based high polymer modified quick set tile adhesive (water based) conforming to IS: 15477, in average 6 mm thickness, including grouting of joints (Payment for grouting of joints to be made separately).Size of Tile 600x600 mm
66Providing and fixing first-quality vitrified glazed wall tiles of approved make and size 300 × 600 mm, as approved by the Engineer-in-Charge, in skirting, step risers, and dado areas. The tiles shall be laid over a 12 mm thick cement mortar bed in the proportion of 1:3 (1 cement : 3 coarse sand). Joints shall be filled using grey cement slurry at the rate of 3.3 kg per sqm, and finished with white cement pointing mixed with matching pigment, complete in all respects.
67FLOORING
68Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS: 15622, of approved make, in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand), jointing with grey cement slurry @ 3.3 kg/ sqm including grouting the joints with white cement and matching pigments etc., complete. Size of Tile 600x600 mm
69Providing and laying Vitrified tiles in floor in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS:15622, of approved brand & manufacturer, in all colours and shade, laid on 20 mm thick cement mortar 1:4 (1 cement: 4 coarse sand) jointing with grey cement slurry @3.3 kg/sqm including grouting the joints with white cement and matching pigments etc. The tiles must be cut with the zero chipping diamond cutter only . Laying of tiles will be done with the notch trowel, plier, wedge, clips of required thickness, leveling system and rubber mallet for placing the tiles gently and easily.Glazed Vitrified tiles Matt/Antiskid finish of size of Tile 600 x 600 mm
70Providing and fixing 18 mm thick gang saw cut, mirror polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills, facias and similar locations of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 (1 cement : 4 coarse sand), joint treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels. Granite of any colour and shade. Area of slab over 0.50 sqm
71Extra for providing opening of required size & shape for wash basins/ kitchen sink in kitchen platform, vanity counters and similar location in marble/ Granite/ stone work including necessary holes for pillar taps etc. including moulding, rubbing and polishing of cut edges etc. complete.
72Chequered terrazo tiles 22 mm thick with graded marble chips of size up to 6 mm in floors, jointed with neat cement slurry mixed with pigment to match the shade of the tiles, including rubbing and polishing complete, on 20 mm thick bed of cement mortar 1:4 (1 cement :4 coarse sand) : Dark shade pigment using ordinary cement
73PAINTING
74Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete.
75Finishing walls with Premium Acrylic Smooth exterior paint with Silicone additives of required shade: New work (Two or more coats applied @ 1.43 ltr/10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/10 sqm)
76Finishing with Deluxe Multi surface paint system for interiors and exteriors using Primer as per manufacturers specifications : Two or more coats applied on walls @ 1.25 ltr/10 sqm over and including one coat of Special primer applied @ 0.75 ltr /10 sqm
77Finishing with Deluxe Multi surface paint system for interiors and exteriors using Primer as per manufacturers specifications :Painting Steel work with Deluxe Multi Surface Paint to give an even shade. Two or more coat applied @ 0.90 ltr/10 sqm over an under coat of primer applied @ 0.80 ltr/10 sqm of approved brand and manufacture
78Finishing walls with water proofing cement paint of required shade New work (Two or more coats applied @ 3.84 kg/10 sqm)
79PLUMBING & SANITARY FITTINGS
80Providing and fixing 600x450 mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete.
81Providing and fixing PTMT towel rail complete with brackets fixed to wooden cleats with CP brass screws with concealed fittings arrangement of approved quality and colour.450 mm long towel rail with total length of 495 mm, 78 mm wide and effective height of 88 mm, weighing not less than 170 gms
82Providing and fixing PTMT liquid soap container 109mm wide, 125mm high and 112mm distance from wall of standard shape with bracket of the same materials with snap fittings of approved quality and colour. weighing not less than 105 gms.
83Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge 25 mm dia 10 Kgf/cm2- External work - Exposed on wall
84Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge 32 mm dia 10 Kgf/cm2 - External work- Exposed on wall
85Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge 50 mm dia 10Kgf/cm2 - External work - Exposed/ Concealed on wall
86Providing and fixing C.P. brass angle valve for basin mixer and geyser points of approved quality conforming to IS:8931 :15mm nominal bore
87Providing and fixing white vitreous china pedestal type water closet (European type W.C. pan) with seat and lid, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever), conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required :W.C. pan with ISI marked white solid plastic seat and lid
88Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require: White Vitreous China Flat back wash basin size 550x 400 mm with single 15 mm C.P. brass pillar tap
89Providing and fixing Stainless Steel A ISI 304 (18/8) kitchen sink as per IS:13983 with C.I. brackets and stainless steel plug 40 mm, including painting of fittings and brackets, cutting and making good the walls wherever required : Kitchen sink with drain board 510x1040 mm bowl depth 200 mm
90Providing and fixing PTMT Waste Coupling for wash basin and sink, of approved quality and colour.
91Flexible (coil shaped) PVC waste pipe for sink and wash basin 40 mm dia with length not less than 700 mm i/c PVC waste fittings.
92Supplying and fixing CP Health Faucet superior quality ( Jagur or equvalent make ) including cost of materials and labour charges etc complete as per the direction of site Engineer-in-charge
93Providing and fixing ball valve (brass) of approved quality, High or low pressure, with plastic floats complete : 15 mm nominal bore
94Providing and fixing ball valve (brass) of approved quality, High or low pressure, with plastic floats complete : 15 mm nominal bore
95Providing and fixing C.P. brass bib cock of approved quality conforming to IS:8931 :15 mm nominal bore
96Providing and fixing C.P. brass long body bib cock of approved quality conforming to IS standards and weighing not less than 690gms. 15 mm nominal bore
97Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. Concealed work, including cutting chases and making good the walls etc. 20 mm nominal outer dia Pipes
98Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. Concealed work, including cutting chases and making good the walls etc. 32 mm nominal outer dia Pipes
99Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.50 mm nominal dia Pipes
100Constructing masonry chamber 30x30x50 cm inside, in brick work in cement mortar 1:4 (1 cement :4 coarse sand) for stop cock, with C.I. surface box 100x100x75 mm (inside) with hinged cover fixed in cement concrete slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), i/c necessary excavation, foundation concrete 1:5:10 ( 1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design: 18.32.1 With common burnt clay F.P.S. (non modular ) bricks of class designation 7.5
101Providing and placing on terrace (at all floor levels) polyethylene water storage tank, IS : 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank.
102Providing and fixing PTMT extension nipple for water tank pipe, fittings of approved quality and colour.20 mm nominal bore, weighing not less than 40 gms
103Providing and fixing PTMT grating of approved quality and colour. Circular type100 mm nominal dia
104Providing and fixing PVC pipes including fixing the pipe with clamps/ clips/ at 1.00 m spacing . This includes jointing of pipes with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge 110 mm dia 6 Kgf/cm2 - External work- Exposed on wall
105Providing and fixing PVC pipes includings jointing of pipes with one step PVC solvent cement, trenching, refilling & testing of Joints complete as per direction of engineer in charge.110 mm dia 6Kgf/cm2
106Providing and fixing C.P. brass angle valve for basin mixer and geyser points of approved quality conforming to IS:8931 15mm nominal bore
107Supplying and placing of 5000 Litre 1mm thick stainless steel water tank of 1750mm dia , 2600mm height, Stainless steel mounted stand around 180kg and grade of ASTM A240 gr.304/ SS316 BA/2B as per the direction of Engineer in-charge. The rate inclusive of all the transportation, Steel stand support, loading and unloading charges, fixing charges, Labour charges, etc. Nothing shall be additionally paid in this item.
108SIGNAGES
109Design, providing and fixing Digital Printed vinyl signage boards with transparent 3mm acrylic Sheet with 4 nos. SS Studs of Size 16\\" x 10\\". Complete as per the per the direction of Engineer in charge.
110Design, providing and fixing Acrylic LED Sign Board of 5cm Letter Thickness 20 - 30cm Letter Height. Complete as per the direction of Engineer in charge.
111Electrical Works
112Point wiring in PVC conduit with modular type switch.
113Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. Group B
114Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. Group C
115Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point ( without independent switch etc.) with 1.5 sq. mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required.. Group C
116Wiring for twin control light point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required.
117Wiring through PVC conduit
118Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire
119Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
120Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2 X 4 sq. mm + 1 X 4 sq. mm earth wire
121S/F PVC CONDUIT (CCTV)
122Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. 20 mm
123Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. 25 mm
124Modular boxes, bases & cover plate:
125Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required. 1 or 2 Module (75mmX75mm)
126Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required. 3 Module (100mmX75mm)
127Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required. 6 Module (200mmX75mm)
128Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required.
129Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required.
130Modular type switch/socket:
131Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 5/6 A switch
132Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 3 pin 5/6 A socket outlet
133Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 15/16 A switch
134Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 6 pin 15/16 A socket outlet
135Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )25A SP switch with indicator
136Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )25A 3pin Shuttered socket
137DB ACCESSORIES
138Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 8 way (4 + 24), Double door
139Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator). 6 way (4 + 18), Double door
140Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 8 way , Double door
141Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 A
142Supplying and fixing following rating, four pole, (three phase and neutral), 415 V, residual current breaker with overload (RCBO), having a sensitivity current 100 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required 25A, 4P, 100mA
143Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Double pole
144Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. 25 A
145Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Triple pole
146Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole
147Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
148PANEL
149MAIN PANEL: Fabrication, supply, erection, testing and commissioning of floor or wall mounting dust and vermin proof, cubicle type, front operated MV panel board as per IS 8623 - CPRI Certified made out of 16 SWG thick CRCA sheet (7 tank treatment) fully compartmentalized complete with hinged and earthed front doors with name plate, danger notice board, heavy duty rubber gaskets, removable gland plates made out of 3mm thick sheet steel including all components as shown in the schematic drawing. The panel shall be with Top/bottom entry to receive incoming & outgoing, all opening parts of the panel shall be sealable. This panel should include surge arrester Type 1+2 as per IEC 61643 (IP 20) complete with back up fuse for SPD protection as per manufacturer standard. Providing all connections and interconnections as required and providing all accessories as required for complete installation as instructed by engineer in charge/consultant and as shown in the schematic layout provided.Incomer - 160A 36kA FP Thermal Magnetic based MCCB having isolation duty with 3 O/C and 1 E/F release, isolation duty type 160A 433V, 36kA best conductivity extensible Al TPN bus bar with SMC supports, heat shrinkable sleeves etc. complete as required. Multifunction meter having multiline LED display with following parameters -Phase wise instantaneous and Average values Voltage, Current, Power Factor, Phase wise instantaneous and Average values,Active Power, Reactive Power lead & lag, Apparent Power, Import & Export Cumulative values Active Energy, Reactive Energy lead & lag, Apparent Energy, PF for 3 phases and average, Instantaneous Frequency, Total Harmonics Distortion, Phase wise Voltage and Phase wise Current - 1 Set RYB phase indicating LED lamps with control fuses and switches - 1 set. Class B & Class C/ Class 1 & Class 2 Surge arrestor device with Fuse set 1 no.Outgoings: 80A 25kA TP MCCB Thermal Magnetic based -4nos. 63A/40A 25kA FP MCCB Thermal Magnetic based - 3 nos, 63A TPN ISO - 1 no
150Metering Panel :-Supply, Installation, Testing and Commissioning of 415 V 50Hz OEM design verified LT Switch board complying to IEC 61439 Part 1 & 2. The Enclosure shall be self-supported, free standing powder coated compartmentalized cubicle type with CRCA sheet,Ingress Protection rating shall be IP42, Impact protection shall be IK10 & form of construction 3B or better. Cable entry facility shall be at top or bottom (as per site condition) with necessary cable alleys, switchgear compartments, meter chambers, C.T chambers, Aluminium bus bar with bus bar chamber etc. Control wiring shall be with 2.5 sq.mm copper cable of 1100 volts grad for C.T leads and 1.5 sq.mm for voltage leads and protection of control shall be with appropriately rated HRC fuses. Doors shall be earthed as per standards. The main earth bus shall be of suitable size copper and run through the switch board for earthing metallic parts of switch gears. All copper joints shall be tinned. Gland plates shall be 3mm thick and knock - outs of proper diameter shall be provided on gland plates. The height of the operating handle of any switch gear shall be minimum 300mm and maximum up to 1800mm from the finished floor level. Note: Relevant Test certificates from third party certification agencies: ASTA, ASEFA, DEKRA, KEMA, UL will be accepted as proof of compliance. OEM certification is also mandatory. Incomers - 100A TPN Isolator - 1No. 25 x 6 Al TPN bus bar with SMC supports, heat shrinkable sleeves etc complete as required. RYB phase indicating LED lamps with control fuses and switches - 1 set. Outgoing Consumer service unit consisting of 8 Nos. 32A FP MCB, 32 A fuse unit & eight numbers three phase energy meter and the meter shall be tested and approval shall be taken from utility including all accessories required for complete installation and its inter connections etc
151PUMP SET
152Supply & Installation of Open well water pump and control panel of approved make including cost of labour, and material required for completion of work, capacity 3 HP
153S & F Motor starters of the following ratings Three phase DOL starters for 0.25HP to 7.5 HP motor
154EARTHING
155Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc. with charcoal/ coke and salt as required.
156Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)
157Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
158Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required4.00 mm copper conductor ( 8 SWG)
159Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required4.00 mm copper conductor ( 10 SWG)
160Providing and fixing earth bus of 50 mm X 5 mm copper strip on surface for connections etc. as required.
161SUPPLY AND LAYING OF LT CABLES
162Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 185 sq mm
163Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 50 sq mm
164Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 16 sq mm with factory made clamp
165Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 10 sq mm with factory made clamp
166Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3 core 10 sq mm with factory made clamp
167Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3 core 4 sq mm with factory made clamp
168Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.2 core 10 sq mm with factory made clamp
169Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. Upto 35 sq. mm (clamped with 1mm thick saddle)
170LT CABLE TERMINATION
171Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3½ X 185 sq. mm (57mm)
172Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3½ X 50 sq. mm (35mm)
173Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 4 X 16 sq. mm (28mm)
174Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 4 X 10 sq. mm (25mm)
175Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. - 3 X 10 sq. mm (22mm)
176Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 2 X 10 sq. mm (19mm)
177CABLE TRAYS
178Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with two numbers GI Suspenders i/c base of suitable size GI angle, GI bolts & nuts, fastner etc as required. 100 mm width X 50 mm depth X 1.6 mm thickness
179Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \\"bends\\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with two numbers GI Suspenders i/c base of suitable size GI angle, GI bolts & nuts, fastner etc as required. 100 mm width X 50 mm depth X 1.6 mm thickness
180LIGHT FITTINGS & FANS
181LED Batten light (System lumen efficacy ≥105 <120 lm/Watt). Supplying, Installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85%, Operating voltage AC 140- 270 Volt, frequency 50/60 hz, Operating temp range -5 °C to 40 °C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10%, P. F.≥0.95, IP20, CRI >80, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till lifeends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation 45 DELHI SCHEDULE OF RATES (E&M)-2025 Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in- Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm) Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm) 18- 22 Watt
182SITC of 2 feet surface/suspended mounted LED batten type luminaire with a power consumption not more than 10 W, luminaire lumen output of 1100 lumens, luminaire efficacy > 110 lm/W with an operating voltage range from 140 V - 270 V. The luminaire shall have a sleek design with extruded aluminum section, white CRCA housing with optically efficient poly carbonate diffuser to provide uniform illumination and wider light distribution. The luminaire shall have a CCT of 4000K /6500 K, CRI > 80, power factor >0.95, SDCM < 5, THD <10%. The luminaire shall be EMI/ EMC compliant and shall have an internal surge protection of 3 kV with 50,000 burning hours as per L70B50 criteria. The luminaire and driver shall be BIS approved and test certificates of LM79 and LM80 reports from NABL accredited labs. The luminaire shall have flicker content <5% and shall have high and low cut off with auto restart feature, including all accessories necessary as required to complete installation.
183SITC of 10W LED BULKHEAD LIGHT fixture , System efficacy>=100 lm/W and system lumen output not less than 1000 lm. , driver with minimum 2.50 KV internal surge protection with electronic drive system, power factor >0.95, THD<10%, rated life of 50,000 hours at L70 with a CRI > 80, SDCM<5 and CCT in between 4000K to 5700K. ANSI rated LEDs from reputed makes should be provided and including connection with 1.5 sq.mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. all necessary accessories as required for the light fixture.LM79, LM80, type test certificate & BIS certificate shall be submitted, Luminaire/Drive shall be BIS approved of same make
184Supply Conveyance, installation, testing and commissioning of 36/40W LED street light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)
185Supplying and fixing of required length 32 mm dia G.I. Pipe (light class) including painting etc. as required.
186Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal(Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body. Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, remote (preferably mobile app based) for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required. 1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum)
187SITC of 250mm sweep Exhaust Fan, 900rpm light duty exhaust fan shutter type white colour, 9\\" or 10\\" star rated as per BEE, with its all accessories including mounting as required for complete installation.
188Supplying Installation Testing and Commissioning of 2MP IP IR Dome Camera having followingspecifications, type of lens and features etc :-1) Signal System: PAL/NTSC, Signal to Noise Ratio:>50 dB, Camera should display Camera title, Date &Time in live & recorded video2)Image Sensor: 1/2.8\\" or better progressive ScanCMOS to get color image even at night condition(Minimum Illumination: 0.006 Lux@ F1.4, AGC ON, 0 lux with IR or better) True Day & Night High Performance Mechanical IR cut filter with auto switch, Integrated IR Source (Auto, Manual)- Inbuilt IR LED's with effective distance upto 50 meter or better and 30 meter for colour view in night, Imaging: 1/3s to 1/30000s electronic shutter support, Auto Gain Control , White Balance- Auto, Back Light Compensation, Multi zone Privacy Masking, HLC, Digital Watermarking. 3) Compression (Minimum):-Video:- H.265 or better,H.264H, H.264, Audio:- G.711U/A, G.711Mu, G.726, AAC, G.723 4) Wide Dynamic Range:- WDR (120db or more)5) Digital Noise Reduction:- DNR (3D) On/Off6) Video Streaming & Frame Rates :- Triple streaming, configurable (Main stream: 2MP (1920×1080)@25/30 fps,Sub streams minimum:720P@25/30 fps).7) Image Setting: Rotate Mode, saturation, brightness,contrast, sharpness adjustable through client softwareor web browser, Edge Analytics: Tripwire, Intrusion,Motion Detection8) Cyber Security: AES 256-bit Encryption,Configuration encryption, trusted execution, Digest,security logs, account lockout, syslog, videoencryption, IP/MAC filtering, HTTPS, trusted upgrade,trusted boot.9) Onboard Storage: Camera should support built-inMicro SD/SDHC/SDXC Card slot upto 512 GB. Itshould be supplied with minimum 128GB memoryCard.280 10) Recording Management: Format SD, overwrite, storage management, video to NAS device 11) Alarm Trigger : Motion/tampering detection; audio detection; network disconnection detection; IP conflict detection; memory card state detection; memory space detection 12)Network Protocol: SFTP, IPv6, IPv4, DNS,RTCP, NTP, RTP, HTTP, HTTPS, SNMP TCP/IP, PPPoE,NFS, UDP, ICMP, SSL, DHCP, SMTP, RTSPS,unicast13) System Capability: ONVIF, Camera shall supportopen source VMS14) Ethernet: 1 RJ 45 10/100 Ethernet port15) Audio : It should support 1 x Built-In Mic and 1/1Alarm In/ Out for External Mic. and Speakers as persite requirement.16) Power Input: The camera should supportsimultaneous dual power input—12 VDC (via poweradapter) and PoE (802.3af)—to ensure continuousoperation in the event of a failure in one power source.17) Power Requirement: 12VDC/24 VAC/PoE(802.3af)/ePoE18) Housing/ Enclosure:- IP67 weather proof, IK10, Metallic body 19) Operating Condition:- Ambient Temperature:- (- )05°C to 50°C, humidity 95% (max) (non-condensing) 20) IR life: 40000 hours or higher 21) Video Bit rate: 32 KBPS - 8 MBPS or better22) Standards: BIS with ER, STQC Certified, CE, FCC and RoHS 2MP (@ 25/30fps@1080P (1920×1080)) IP IR Dome Camera with 2.8/ 3.6mm fixed lens
189Supplying Installation Testing and Commissioning of 2MP Fixed Lens IP IR Outdoor Bullet Camera havingfollowing specifications and features etc :-1) Signal System: PAL/NTSC, Signal to Noise Ratio: >50 dB,Camera should display Camera title, Date &Time in live & recorded video 2)Image Sensor: 1/2.8\\" or better progressive Scan CMOS to get color image even at nightcondition(Minimum Illumination: 0.006 Lux@ F1.4,AGC ON, 0 lux with IR or better) True Day & NightHigh Performance Mechanical IR cut filter with autoswitch, Integrated IR Source (Auto, Manual)- InbuiltSmart IR LED's with effective distance upto 50 meteror better and 30 meter for colour view in night,Imaging: 1/3s to 1/30000s electronic shutter support,Auto Gain Control , White Balance- Auto, Back LightCompensation, Multi zone Privacy Masking, HLC,Digital Watermarking.3) Compression (Minimum):-Video:- H.265 or better,H.264H, H.264, Audio:- G.711U/A, G.711Mu, G.726,AAC, G.7234) Wide Dynamic Range:- WDR (120db or more)5) Digital Noise Reduction:- DNR (3D) On/Off6) Video Streaming & Frame Rates :- Triple streaming, configurable(Main stream: 2MP (1920 ×1080)@25/30 fps Sub streams minimum:720P@25/30 fps).7) Image Setting: Rotate Mode, saturation, brightness,contrast, sharpness adjustable through client softwareor web browser, Edge Analytics: Tripwire, Intrusion,Motion Detection8) Cyber Security: AES 256-bit Encryption,Configuration encryption, trusted execution, Digest,security logs, account lockout, syslog, videoencryption, IP/MAC filtering, HTTPS, trusted upgrade,trusted boot.9) Onboard Storage: Camera should support built-inMicro SD/SDHC/SDXC Card slot upto 512 GB. Itshould be supplied with minimum 128GB memoryCard.10) Recording Management: Format SD, overwrite,storage management, video to NAS device,11) Alarm Trigger : Motion/tampering detection; audiodetection; network disconnection detection; IP conflictdetection; memory card state detection; memoryspace detection12)Network Protocol: SFTP, IPv6, IPv4, DNS,RTCP,NTP, RTP, HTTP, HTTPS, SNMP TCP/IP, PPPoE,NFS, UDP, ICMP, SSL, DHCP, SMTP, RTSPS,unicast,13) System Capability: ONVIF, Camera shall supportopen source VMS 2MP @ 25/30fps@1080P (1920×1080) Outdoor Bullet Camera with 2.8/ 3.6mm fixed lens
19016 Channel Network Video Recorder (NVR) having display split :- Main screen: 1/4/8/9/16, 2nd screen: 1/4/8/9/16
191Supplying, Installation, Testing and Commissioning following capacity Serveillance grade Hard Disk with upto 256MB/s Transfer Rate, 256 MB Cache, 7200 RPM Disk Speed, 3.5 inch form factor, SATA Interface, BSMI, ICES-003/NNB-003, CE, FCC, KC, Maghreb, RCM, UKCA, VCCI, CB-Scheme, TUV, UL Certifications.
192SITC Of 16 Channel Power Supply with Input of 200-240VAC 50-60Hz, 3.5A Max and Output Voltage 12VDC 20A with metal Housing Desktop/Wall Hanging
193SITC OF 4U Rack with PDU unit with Suitable for all type of DVR Box & Double DVR / Network Switch / Server Rack with 4 Power Socket & Cable , Tray (1No) - 1 Cooling Fan Lock & Key.
194DC Connector Screw Type
195SITC Of Finolex co-axial 3+1 Copper CCTV Cable with more than 100% conductivity,with low signal loss, sharp picture & clear sound. In-House formulated & manufactured special grade FR PVC compound. (Brand Finolex)
196DOCUMENTATION AND APPROVAL
197DOCUMENTATION AND APPROVAL \\"Charges for Preparation of all drawings submitting and getting approval from Electrical Inspectorate and Fire Department, submitting of Completion certificates and arranging inspection, getting sanction and energization certificates, obtaining power allocation & power connection from Electrical Inspectorate & EB, Initial & Final NOC from Fire Department etc. including feasibility study. for commissioning of the whole installation. All statutory payments will be reimbursed on production of the original receipts. (for modification works)
198FIRE FIGHTING SYSTEM ESTIMATE FOR TYPE 4 BUILDING - AIIMS MANGALAGIRI
199TERRACE PUMP AND AIR VESSEL
200Supplying, installation, testing and commissioning of electric driven terrace pump conforming to IS 12469: 2019 suitable for automatic operation and consisting of following, complete in all respects, as required: (Terrace Pump)(b) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal as required.(c) Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase, 50 Hz, AC supply with IP55 class of protection for enclosure, horiziontal foot mounted type with Class-'F' insulation, conforming to IS-12615: 2018.(d) M.S.fabricated common base plate, coupling, coupling guard, foundation bolts etc.as required. (e) Suitable cement concrete foundation dulyplastered and with anti vibration pads.900 lpm at 35m Head
201supplying and fixing air vessel made of 250 mm dia 8 mm thick MS sheet , 1200 mm in height with Air release valve on top and flanged connection to riser , drain arrangement with 25 mm dia Gun metal wheel valve with required accessories , pressure guage and painting with synthetic enamel paint of approved shade as required.
202Power Control Panel- Supply, Installation, testing and commissioning of combined type automatic motor control panel with necessary star delta starters, indication lamps etc. for terrace fire pumps
203PIPE AND ACCESSORIES
204Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required.a) 20 mm nominal Internal dia water hose thermoplastic(Textile reinforced) type-2 as per IS:12585b) 20 mm nominal internal dia gun metal globe valve &nozzlec) Drum and brackets for fixing the equipments on wall.d) Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket.30 m
205Providing, laying, testing and commissioning of C class heavy duty M S Pipe conforming to IS 3589,IS 1239 i/c welding ,fittings, like elbows, tees, flanges, tapers, nuts ,bolts ,gaskets etc., and fixing the pipe on the wall , ceiling with suitable clamp or support frame and painting with two or more coats of synthetic enamel paints of required shades complete as required:50 mm dia
206Providing, laying, testing and commissioning of C class heavy duty M S Pipe conforming to IS 3589,IS 1239 i/c welding ,fittings, like elbows, tees, flanges, tapers, nuts ,bolts ,gaskets etc., and fixing the pipe on the wall , ceiling with suitable clamp or support frame and painting with two or more coats of synthetic enamel paints of required shades complete as required:100mm dia
207VALVES ,SWITCHES AND GAUGES
208Supplying, fixing, testing and commissioning of Butterfly Valve of PN 1.6 rating with bronze or gun metal seat duly ISI marked complete with nuts, bolts ,washers,gaskets conforming to IS 13095 of following sizes as required:100 mm dia
209Providing,installation,testing and commissioning of non-return valve of following sizes conforming to IS :5312 complete with rubber gasket, GI bolts , nuts, washers etc as required.100 mm dia
210Providing and fixing in position the industrial type pressure gauges with gun metal / brass valves complete as required
211Providing, installation ,testing and commissioning of stainless steel Y-strainer fabricated out of 1.6 mm thick stainless steel , Grade 304,sheet with3 mm dia holes with stainless steel flange.100 mm dia
212Providing and fixing of pressure switch in MS pipeline including connection etc as required:
213Providing and fixing of flow switch in MS pipe including connection etc as required:100 mm dia
214FIRE EXTINGUISHERS
215Supplying, installing and commissioning Portable Fire extinguishers of following type & capacity.Co2 type Fire Extinguisher, made from brand new seamless Steel cylinder, as per IS: 7285 and CCE approval, fitted with Discharge hose and horn and Wheel type valve with initial Charge and mounted on Rubber Wheels / wall mounted brackets as per IS: 16018 specification, bearing ISI Mark. 4.5 Kgs
216Supply and installation of ABC Stored pressure type Fire Extinguisher 6 Kgs Capacity Mono Ammonium Phosphate based Dry Chemical Powder as per IS 14609 with ISI Mark for Fighting ABC Class of Fire, stored Pressure type of Mild steel body pressurized by Nitrogen Gas. The Extinguisher shall have pressure gauge for indicating inside pressure with opening and closing lever of squeeze grip type with tamper proof seal, complete with wall bracket. The Extinguisher should be manufactured strictly as per IS: 15683:2006 with ISI mark
217SIGNAGES
218SITC of self glowing \\"FIRE EXTINGUISHER\\" sign boards of size (150 X 150 mm) in triangular shape fixed on the wall and shall be as per IS code 9457:2005, IS 12349, IS 12407.
219Supply, installation, testing and commissioning of Fire Exit Light, Laser type, with High Glow LED, size:300x 178 x 32 mm. or 390 x190 x 60mm, Ceiling Mounting type with hanging clamps, on/off switch, Red /Green Colour option with minimum of 25 Mtr. viewing distance, power consumption: 5.0 Watt per face (maximum) Double Side Display and shall be as per IS code 9457:2005, IS 12349, IS 12407.
220Supply, installation, testing and commissioning of Fire Exit Light, Laser type, with High Glow LED, size:300x 178 x 32 mm. or 390 x190 x 60mm, Ceiling Mounting type with hanging clamps, on/off switch, Red /Green Colour option with minimum of 25 Mtr. viewing distance, power consumption: 5.0 Watt per face (maximum), with Single Side Display and shall be as per IS code 9457:2005, IS 12349, IS 12407.
221Providing and fixing in position the signage \\" FIRE ORDER\\" on 3mm thick \\"Opaque\\" PVC foam board of computerized cut, PVC non- reflective self adhesive vinyl painted foam board of 2' x 3' and shall be as per IS code 9457:2005, IS 12349, IS 12407
222Providing and fixing of Floor Identification Signage (MAIN STAIRCASE, FIRE STAIRCASE, FIRE ASSEMBLY POINT, PUMP ROOM, FIRE CONTROL ROOM, ELECTRICAL ROOM, FIRE LIFT, PASSENGER LIFT Etc.) on every floor,lettering size shall be 5 Cm. with contrasting colour from background. Size shall be 15cm x 30cm and shall be as per IS code 9457:2005, IS 12349, IS 1240
223Providing and fixing of Floor identification signage (e.g., GROUND FLOOR, FIRST FLOOR, etc.) will be placed at each stair enclosure on every floor, displaying the floor number in words. The letter size will be 5 cm, with a contrasting color to the background. The dimensions of the signage will be 15 cm x 30 cm, and it will comply IS Code 9457:2005, IS 12349, and IS 12407.
224Providing and fixing of signage : \\"IN CASE OF FIRE, USE STAIRS UNLESS INSTRUCTED OTHERWISE\\" with red letters, each 1.25 cm in height, on a white background. The board dimensions will be 25 cm x 30 cm and will be mounted at a height of 2 meters from the finished floor, positioned near manual call points. The signage will comply with IS Code 9457:2005, IS 12349, and IS 1240 standards.
225FIRE BRIGADE
226FIRE BRIGADE INLET : Supply, installation, testing and commissioning of 3 way tank filling Inlet connection of 63 mm dia. valves instantaneous coupling type arrangement to be connected to wet riser main.
227FIRE ALARM SYSTEM
228FIRE DETECTION AND ALARM SYSTEM (CONVENTIONAL)Supplying,installation, testing & commissioning of manual call boxes of MS Construction in surface/recess with stainless steel chain & hammer assembly Complete with glass and push button etc. as required.
229FIRE DETECTION AND ALARM SYSTEM (CONVENTIONAL)Supplying,installation, testing & commissioning fire alarm sounder with facility to make announcement, mounted in M.S. box (16 SWG) with hinged cover plate & suitable for operation with amplifier i/c line matching transformer etc. complete as required.
230Supplying, installation, testing & commissioning sector panel suitable for following zones, complete with visual indications for short circuit fault, open circuit fault, fire condition and all other standard facilities as per IS:2189 with mimic diagram for all area/zone covered, complete with all connections, interconnections as required.4 Zone
231CABLING & WIRINGSupplying & laying of 2x1.5 sq mm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required. Please Enable Macros to View BoQ information

Other Detail

Information Source https://etenders.gov.in/eprocure/app
Download FileName File Description File Size
Download 59cce6bb-9585-4460-a5d7-10570d0fe6a9.html Tender Documents 0 KB
Download BOQ_325151.xls Tender Documents 0 KB
Download TEDOTYPEIV.pdf Tender Documents 0 KB
Download Tendernotice_1.pdf Tender Documents 0 KB