| 1 | Supply, Installation,Testing and commisioning of 15 Passenger Lift with the following Specifications as per IS:-14665 (2000) along with AMC of 3 years.capacity passenger cum bed lift Machine room less (MRL) Bed lift with regenerative drive as per CPWD General Specification for Electrical Works (Part-III Lift & Escalator) 2003, BIS Codes, NBC 2016 as amended upto date having provision for barrier free access as per Harmonised Guidelines & Standards for Universal Accessibility in India - 2021 of MoHUA, serving different floors in the lift shaft as per detailed specifications enclosed and as under including all other equipment and accessories complete as required :- |
| 2 | Operating Voltage:- 415 Volts 3 PhaseHoistway size :- 1700mm X 2850 mmPit(mm) :- 1800Capacity (kgs) 1020 Kg, 15 personsRise (m ) :17- 22 m Appx. 75-100 m/sSTOPS: 4 Stops With (all opening on the same side) / Drive :Microprocessor Based V3F Drive.Machine : P M Gearless (Located in shaft on top of guide rails)Car Finish :Rear Mid Panel = SS Honey Comb Rear Corner Panels = SS Honey Comb Side Mid Panels = SS Honey Comb Side Corner Panels = SS Honey Comb Front Panels = SS Honey CombFalse Ceiling Finish: SS Mirror FinishHand Rail :Stainless Steel Hair Line Finish Handrails on rear car panelVentilation:Cross flow fanFlooring:Granite Flooring /anti skid /equivalentDoor Operator: DC Door Operator / Telescopic |
| 3 | Standard Features :(i) Speed-1.0- 1.5 MPS (ii)Floors-5(G+4) (iii) Travel-17 metres(approx) (iv) Stops & opening : 4 stops and 3 openings (v) Controller: A.C. variable voltage & variable frequency (vi) Automatic rescue device (ARD) complete with dry maintenance free batteries as required. (vii) Operation: Microprocessor based single automatic push button/simplex selective collective/ duplex collective selective with/without attendant (viii) Power-415 Volts+10%, 3 phase, 50 Hz, 4 wires system (ix) Car Enclosure: Stainless steel scratch proof (Moon Rock/Honeycomb/ Hairline Finish) on all sides and stainless steel decorative ceiling with fans (indirect throw) and LED fitting. (x) The car flooring should be smooth and antiskid as approved by engineer-in-charge. (xi) Type of doors:- (a) Car: Power operated, centre opening horizontal sliding stainless steel scratch proof (Moon Rock/Honeycomb/ Hairline Finish). (b) Landing doors: stainless steel scratch proof . (xii) A hand rail not less that 600mm long at 900mm above floor level to be fixed adjacent to control panel in the lift car. (xiii) Voice announcement system in the car to announce the position of the elevator in the hoist way as the car passes or stops at floor served by the elevator. (xiv) Closed loop Control System, protection against power fluctuation, self diagnostic control, Landing 112 DELHI SCHEDULE OF RATES (E&M)-2025 doors 2 hours Fire rated, Overload detection and protection, Overs peed Governer, Dot Matrix LED D & P Indicators In Car &Landings, BMS Compatibility, tamper proof infrared curtain covering almost the entire height of the lift car door, Alarm horn, Anti Nuisance Operation, CCTV camera system with 4 MP IP camera, suitable NVR and HDD for 30 days storage backup , Firemen switch, 2/3 way intercom, Emergency Stop Switch with battery backup for fan and light fitting for 1 hour, pit ladder. (xv) The lift doors shall have a vision panel to enable persons with hearing impairment to signal for help or assistance in the event of an emergency. (xvi)An appropriate technological support be provided (Through emergency messaging |services or alarms etc.) to respond to the emergency requirements of person with hearing impairment or deafness. (xvii) In case of failure of ARD or other electronic devices, a provision of manual rescue be provided. |
| 4 | Anti-nuisance Car Call ProtectionControl System :- Simplex automatic operation Overload Device NudgingFloor Annoucement Syatem with Music Emergency Firemen’s Service Emergency Car Light UnitInfrared Curtain Door ProtectionFull Car Operating Panel 8 Press & Speak Phone Door Time ProtectionEmergency Alarm ButtonExtra Door Time of Lobby & Parking Door Open/Close ButtonAutomatic Rescue Device with Dry Maintenance Free Batteries Auto Fan Cut OffProvision of CCTV CameraFire Rating of Landing Doors for 2 Hours Floor Annuciator with MusicProvision of 3 way intercom with instrument. Indicators in Car and Landings |
| 5 | Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) |
| 6 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 7 | S/L of 4 X 16 sq. mm + 2 X 6 sq. mm earth wire and termination works etc in PVC conduit |
| 8 | S/I of MCBTPN 63A TPN with enclosure etc |
| 9 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 10 | Group B |
| 11 | S/I of LED bulk head 9 watt |
| 12 | Supplying and fixing following way, SPN DB on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 13 | 12 way Double door |
| 14 | Supplying and fixing 5 amps. to 32 amps.rating 240 volts 'C' series, miniature circuit breaker of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 15 | Single Pole |
| 16 | 63 Amps MCB DP |
| 17 | Fabrication, supply, installation, testing & commissioning of outdoor type compartmentalized feeder pillar having front area not less than 0.60 Sqmtr (900 mm x 900 mm) and depth 45 Cm (NS) made out of 2mm thick CRCA sheet with tappered roof having separate cable and bus bar alley, 1 door arrangement i/c locking arrangement, having 300 Amp four pole aluminium bus bar of full length with base frame made out of 50mmx50mmx6mm (thick) angle iron having 80cm legs for erection in ground with construction of cement concrete suitable foundation size complete with connections and interconnections with copper conductor PVC insulated cables/ insulated aluminium busbar strips of appropriate size and terminal blocks (on outgoing) including supplying & fixing following switchgears & accessories there in, powder coating, labelling, earthing etc. complete as required. Providing and fixing following accessories in existing cubical panel board i/c making connection etc. as reqd.INCOMER/OutgoingThermal Magnetic Based MCCB 100 Amps FP Icu=Ics=100% with Breaking Capacity 18-36 KA (01 Nos)S/I of Onload Changeover , Panel Mounted Standard Make 100 Amp SPN , RCCB 100A 100 mA , 1 phase Preventer , Voltage Monitoring Relay System DIgital Indicating Lamps RYB (1 Set)Voltmeter-0-500 Volts(1 Nos)Ammeter(0-150 A)(1 Nos)Selector Switch (2 Nos)Current Transformer 100/5 A 10 VA Burden, Class-1(1 sets)Aluminium Busbar 300 Amps FP E-91 E Grade Electrolytic AluminiumDP MCB 32 A(01Nos)Gland Plates to be 3.0 mm Thick. |
| 18 | EATON/APC/Legrand ABB make 20KVA/384V On-Line UPS model 93E Tower type with 3 phase input and 3 phase output , built in OVCD, 1.0 pf, VFI technology complete with 32 nos. EnerRocket make 12V/42AH SMF batteries to provide back up time of 30 minutes ,MS battery rack, battery interlinks and Built in ReGEN kit for lift operation. |
| 19 | 20KVA phase sequence corrector panel, wall mounted with indicating lamps, top/bottom cable entry, indoor type |
| 20 | Supply of advance maintenance free Chemical Gel Earthing of Dual Pipe Technology (GI) of 3 mtrs long 80 mm dia of outer shell (MS) with the 50 mm dia of inner shell (MS) of 80-100 microns galvanized CHEMRODE filled with highly conducting metallic compounds with the permenant sealings at both the ends with the lead terminal of 50x10mm size at the top. The electrode shall be duly tested and certified by CPRI (Central Power Research Institute), Govt of India for a peak short circuit withstanding capacity of 60 KA. including Supply/ fixing of environment friendly rust proof heavy duty weather proof polyplastic earth pit chamber. |
| 21 | Providing and fixing of Heating points for lift using 4 sq.mmPVC insulated copper wire through 1” 2mm PVC conduit/1” PVC casing capping and providing and fixing of 6/16 Amp. of Modular Switch/socket recessed in wall covered with modular sheet/ MS box of required size including providing and fixing of 4mm² PVC insulated copper wire t as earth wire, point taken up to D.B. duly tested and commissioned, complete point in all as pects |
| 22 | Wiring for circuit (lift)/ submain wiring along with earth wire with the following sizes of FR PVC insulated copper conductor, single core cable in surface/ recessed in class heavy duty PVC conduit as required )Note :Rates of Suitable PVC conduit included in above description for the follwing items of make4 X 10 sq. mm + 1 X 10 sq. mm earth wire |
| 23 | Supply, laying, fixing of ISI marked aluminium conductor XLPE insulated cable as per IS 7098, un armoured, served, sheathed 1100 volts grade.i/c end terminations, clamping as required35sq mm 3.5 C |
| 24 | Supplying, fixing, testing and commissioning of following Amperes of MCCBs with spreader links 125 Amp 36KA 4 pole |
| 25 | Supplying, fixing of MCCB MS door type Enclosure suitable for 125 Amp 4 P MCCB |
| 26 | Providing, fixing, testing and Commissioning of TPN 63A/ 63A Automatic ChangeOver 415 Volts of reputed make as per requirement |
| 27 | Brick work with common burnt clay (non-modular) bricks of class designation 7.5 in foundation and plinth including curing in : 6.1.1 Cement lime mortar 1:1:6 ( 1 cement : 1 lime putty : 6fine sand) |
| 28 | CEMENT PLASTER IN TWO COATS (SSR 13.12)18mm Cement plaster in two coats under layer 12mm thick cement plaster 1 : 5 (1 cement : 5 coarse sand) finished with a top layer 6mm thick cement plaster 1 : 6 (1 cement : 6 fine sand) |
| 29 | Reinforced cement concrete work in beams, suspended floors, roofs having slope upto 15°,landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral stair cases upto five level including curing but excluding the cost of centring, shuttering,finishing and reinforcement with 1:1½:3 (1 cement : 1½ coarse sand : 3 graded stone aggregate 20 mm nominal size) |
| 30 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete above plinth level (5.22A.6) Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 31 | Wall Painting with acrylic emulsion paint of approved brand and manufacture to give an even shade. Two or more coats on new work |
| 32 | Marble work gang saw cut (polished and machine cut) of thickness 16 mm for wall lining (veneer work), backing filled with a grout of 12 mm thick average in cement mortar 1:3 (1ce ment: 3 coarse sand), including pointing with white cement mortar 1:2 (1 white cement: 2 marble dust) with an admixture of pigment to match the marble shade (To be secured to the backing by means of cramps, which shall be paid for separately). (Area of slab over 0.5 sqm) |
| 33 | C.G.I. SHEETS ROOFINGProviding corrugated G. S. sheet roofing including vertical/curved surface fixed with polymer coated J or L hooks, bolts and nuts 8mm diameter with bitumen and G.I limpet washers or with G.I. limpet washers filled with white lead, including a coat of approved steel primer and two coats of approved paint on overlapping of sheets complete (upto any pitch in horizontal/vertical or curved surface)excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required.(SSR12.1.1) 1.60 mm thick with zinc coating not less than 350 gram/m2 |
| 34 | Steel work welded in built up sections/framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required.In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works. |
| 35 | Providing, fixing and Cladding with 3 mm thick matt finish Aluminium composite panel with all fixing arrangements on lift wall with hinges/catchers etc as per sie requirement. |
| 36 | Note:-1. The rates quoted are inclusive of all carriages of materials (Mechanical/Manual) from source to site work and all extra charges including dewatering if any during the execution of work till complete in all respects. Please Enable Macros to View BoQ information |