| 1 | Taking down carefully sub main wiring of any type/size complete with MCB DBs MCB, isolators wooden batten, concealed/surface conduit/casing caping etc removing materials including accessories for taking credit and making good disturbed surface to match the existing complete all as specified and directed. |
| 2 | M&L for concealed sub main wiring using FRLS/FRLSH PVC insulated, unsheathed stranded copper conductor cable single core of size 2 x 4.0 Sqmm + 1 x 4 Sqmm earth wire voltage rating upto and including 1100 Volts drawn in and including rigid PVC concealed conduit of dia not less than 20mm dia medium grade with all fittings and accessories along with one run of PVC insulated unsheathed stranded copper conductor as earth continuity conductor complete all as specified and directed. Note : (i) Two runs of single core PVC cable with one run of earth conductor and conduit shall be measured as one length. (ii) The cost for cutting, chases required and making good the disturbed surface shall deemed to be included in the quoted unit rate. |
| 3 | Description same all as per item No 2 here-in-before but 2 x 6 Sqmm + 6 x Sqmm earth wire |
| 4 | Description same all as per item No 2 here-in-before but 2 x 10 Sqmm + 10 x Sqmm earth wire |
| 5 | Description same all as per item No 2 here-in-before but 4 x 10 Sqmm + 1 x 10 Sqmm earth wire |
| 6 | M&L for surface sub main wiring using FRLS/FRLSH PVC insulated, unsheathed stranded copper conductor cable single core of size 2 x 2.5 Sqmm + 1 x 2.5 Sqmm earth wire voltage rating upto and including 1100 Volts drawn in and including non metallic PVC rigid, medium grade not less than 20mm dia surface conduit/non metallic PVC casing and caping with all fittings and accessories alongwith one run of PVC insulated unsheathed stranded copper conductor as earth continuity conductor complete all as specified and directed. Note : (i) Two runs of single core PVC cable with one run of earth conductor and conduit shall be measured as one length. (ii) The cost for cutting, chases required shall deemed to be included in the quoted unit rate. |
| 7 | Description same all as per item No 6 here-in-before but 2 x 4.0 Sqmm + 1 x 4.0 Sqmm earth wire |
| 8 | Description same all as per item No 6 here-in-before but 2 x 6 Sqmm + 6 x Sqmm earth wire |
| 9 | Taking down carefully aluminium / copper point wiring any type for one light, fan, socket power point or buzzer controlled by one switch complete including fitting / fixtures such as switches, ceiling roses, holder, socket, light fitting etc for credit and making good disturbed surfaces of walls, ceilings etc complete all as specified and directed. |
| 10 | M&L for concealed point wiring with FRLS/FRLSH PVC insulated unsheathed stranded copper conductor cable 1.5 Sqmm (nominal area) 1100 Volts grade, alongwith one single run of same size and type of copper wire as continuous earth wire to common earth dolly drawn in and including non metallic PVC rigid, medium grade concealed conduit with all fixing accessories of 20mm dia, and including modular sunken box, cover plate / frame for any module as required at site with all accessories and including fixing with switch, socket, ceiling rose, fan regulator, holder, etc and making good to disturbed conceal surfaces for one light / fan / bell point controlled by one switch, complete all as specified and directed. Note :(a) Colour code of wire shall be strictly followed, Red for Phase, Black for neutral and green for earth wire. (b) The unit rate quoted is deemed to be inclusive of cost of cutting chases in wall for providing concealed conduit and making good to match with existing finish/surface. (c) Only 04 point shall be allowed is one circuit. |
| 11 | Description same all as per item No 10 here-in-before but one point for socket outlet 5 Amps on independent board |
| 12 | Description same all as per item No 10 here-in-before but one point for socket outlet 5 Amps on same board |
| 13 | Description same all as per item No 10 here-in-before but one light point controlled by two 2-way switches |
| 14 | Description same all as per item No 10 here-in-before but for one socket outlet 16 Amps on independent board with 4.0 Sqmm cable and 4.0 Sqmm earth wire |
| 15 | M&L for point wiring with FRLSH PVC insulated unsheathed stranded copper conductor cable 1.5 Sqmm (nominal area) 1100 Volts grade, along with one single run of same size and type of copper wire as continuous earth wire to common earth dolly drawn in and including non metallic PVC rigid, medium grade concealed conduit with all fixing accessories of 20 mm dia, using new pressed steel sunk terminal boxes of thickness not less 1.2 mm, new 3mm thick laminated sheet cover with brass screw and cup washers with all accessories including fixing with switch, socket, ceiling rose, fan regulator, holder, etc and making good to disturbed conceal surfaces for one light / fan / bell point controlled by one switch, complete all as specified and directed. Note : (a) Colour code of wire shall be strictly followed, Red for Phase, Black for neutral and green for earth wire. (b) The unit rate quoted is deemed to be inclusive of cost of cutting chases in wall for providing concealed conduit and making good to match with existing finish/surface. |
| 16 | Description same all as per item No 15 here-in-before but one point for socket outlet 5 Amps on independent board |
| 17 | Description same all as per item No 15 here-in-before but one point for socket outlet 5 Amps on same board |
| 18 | Description same all as per item No 15 here-in-before but one light point controlled by two 2-way switches |
| 19 | Description same all as per item No 15 here-in-before but for one socket outlet 16 Amps on independent board with 4.0 Sqmm cable and 4.0 Sqmm earth wire |
| 20 | M&L for point wiring with FRLSH PVC insulated unsheathed stranded copper conductor cable 1.5 Sqmm (nominal area) 1100 Volts grade, along with one single run of same size and type of copper wire as continuous earth wire to common earth dolly drawn in and including non metallic PVC casing and caping/PVC conduit of appropriate size on wall/roof surface with all fixing accessories including fixing with switch, socket, ceiling rose, fan regulator, holder, etc and polycarbonate modular/modular GI sunken boxs and modular sunken box, cover plate / frame for any module as required at site with all accessories and making good to disturbed conceal surfaces for one light / fan / bell point controlled by one switch, complete all as specified and directed. Note : Colour code of wire shall be strictly followed , Red for Phase , Black for neutral and green for earth wire. |
| 21 | Description same all as per item No 20 here-in-before but one point for socket outlet 5 Amps on independent board |
| 22 | Description same all as per item No 20 here-in-before but one point for socket outlet 5 Amps on same board |
| 23 | Description same all as per item No 20 here-in-before but for one socket outlet 16 Amps on independent board with 4.0 Sqmm cable and 4.0 Sqmm earth wire |
| 24 | Supply and fixing in replacement of AC Starter unit consisting of one 25 Amps capacity starter, one 240 Volts, 25 Amps, 10 KA SPN MCB, one 25 Amps socket and one 25 Amps plug top prewired complete as specified after taking out old unserviceable starter unit complete all as specified and directed. |
| 25 | Supply and fixing in replacement of Flexible LED strips with uniform light distribution and long lasting adhesive for perfect cove lighting solution Flexion Neo LED Strip 24 Watt 3000 K as approved by Engr-in-charge for ceiling applications complete all as specified and directed. |
| 26 | Receiving complaints from complaint cell, lodged by the occupants of electrification nature, rectification of the fault as per the complaint lodged by the user onward KWH meter in respect of main distribution board having switch fused, MCB distribution board in sheet metal enclosure, point wiring fixture for Light / Fan / Bell / Ceiling Fan, testing of Electronic meters or power socket complete repairs to the extent by removing connections from the system removing faults in wires, battens, conduit, sunken boxes, junction boxes, main switches, MCBs/DBs utility light fitting, lamp holders AC ceiling/exhaust fans and other connected fixtures of the internal electrification including providing of petty stores such as wires of appropriate size and conductor matching to existing one up to the length of 1 mtr including insulation tap, screws, nuts as required to rectified the fault with regard to the complaint lodged and refixing of fittings, fixture to their position as dismantled complete all as specified and directed at site to the entire satisfaction of Engineer-in-charge/user. Note - All spares required and accessories, required for repairing will be paid under relevant items of this schedule.Instructions (a) Attending complaint including taking down/refixing of LED light fittings and repair/replacement part (Labour) and minor repair shall be measured against under relevant of Schedule 'A' items .(b) Cost of material/labour for replacement of new items shall be measured & paid separately. (c) Panalty : Penalty for not attending complaints within stipulated time frame will be liable to Rs. 500.00 of per day for non attending the complaints multiple number of days of delay (d) Priority - 1 (to be done within 8 hours from time of lodging complaint): No light, repair/ replacement of switches, fan regulator, replacing burnt/damaged wiring, replacement of burnt MCBS and Main switch, voltage fluctuation, current leakage and replacement of tube lights. |
| 27 | Supply only in repalacement of modular switch 1 way, 6 Amps, 230 Volts AC, one way complete all as specified and directed. |
| 28 | Supply only in repalacement of modular socket outlet 2-in-1, 3 pin, 6 Amps flush type 2 module complete all as specified and directed. |
| 29 | Supply only in repalacement of modular switch flush type 16 Amps, 230 Volts AC single pole one way complete all as specified and directed. |
| 30 | Supply only in repalacement of modular socket outlet 2-in-1, 3 pin, 5 & 16 Amps flush type 2 module complete all as specified and directed. |
| 31 | Supply only in repalacement of modular switch 2 way, 6 Amps, 230 Volts AC, one way complete all as specified and directed. |
| 32 | Supply only in repalacement of modular bell push flush type 6 Amps, 1 module SP, 230 Volts AC complete all as specified and directed. |
| 33 | Supply only in repalacement of modular fan regulator, 5 stepped, electronic type, single phase, 120 Watt, socket size including connection complete all as specified and directed. |
| 34 | Supply only in repalacement of switch piano flush button single pole one way 6 Amps complete all as specified and directed. |
| 35 | Supply only in repalacement of switch 2 way, 6 Amps, 230 Volts AC, one way complete all as specified and directed. |
| 36 | Supply only in repalacement of socket outlet 5 pin 6 Amps flush type complete all as specified and directed. |
| 37 | Supply only in repalacement of socket outlet multipurpose 3 pin 16 Amps and one 3 pin 6 Amps controlled by one switch complete all as specified and directed. |
| 38 | Supply only in repalacement of switch piano flush button single pole one way 16 Amps complete all as specified and directed. |
| 39 | Supply only in repalacement of switch & socket out let combination multipurpose 3 pin 16 Amps and one 3 pin 6 Amps controlled by one switch complete all as specified and directed. |
| 40 | Supply only in repalacement of ceiling fan regulator step type 240 Volts AC complete all as specified and directed. |
| 41 | Supply only in repalacement of PVC insulation tape of width 18mm in length of 25 mtrs ISI marked for proper insulation of joints in wire where as required or directed, complete all as specified and directed. |
| 42 | Supply only in repalacement of condenser of 2.5 Mfd , 240 Volts, AC confirming to IS -1709 suitable for fans complete all as specified and directed. |
| 43 | Supply only in repalacement of condenser of 3.15 Mfd, 240 Volts, AC confirming to IS -1709 suitable for fans complete all as specified and directed. |
| 44 | Supply only in repalacement of ceiling rose surface backelite three terminals, Make : Anchor / Havells / Legrand, complete all as specified and directed. |
| 45 | Supply only in replacement of MCB 63 to 100 Amps TPN 10 KA, C Curve, 415 Volts complete all as specified and directed. |
| 46 | Supply only in replacement of MCB SPN 63 Amps, 10 KA, C Curve, 240 Volts complete all as specified and directed. |
| 47 | Supply only in replacement of MCB SPN 40 Amps, 10 KA, C Curve, 240 Volts complete all as specified and directed. |
| 48 | Supply only in replacement of MCB Single Pole 6 to 32 Amps, 240 Volts, 'C' series, 10 KA breaking capacity & making connection complete all as specified and directed. |
| 49 | Supply only in replacement of MCB Single Pole 63 Amps, 240 Volts, 'C' series, 10 KA breaking capacity & making connection complete all as specified and directed. |
| 50 | Supply only in replacement of MCB Single Pole 40 Amps, 240 Volts, 'C' series, 10 KA breaking capacity & making connection complete all as specified and directed. |
| 51 | Supply only in replacement of MCCB 100 Amps, 4 pole, 25 KA at 415 Volts fixed type complete all as specified and directed. |
| 52 | Supply only in repalacement of Call Bell Ding Dong type AC 230 Volts single pole, complete all as specified and directed. |
| 53 | Supply only in repalacement of bell push flush type 6 Amps, 230 Volts AC complete all as specified and directed. |
| 54 | Supply only in replacement of Modular metal flush box of 12 module complete all as specified and directed. |
| 55 | Supply only in replacement of Modular metal flush box of 8 module complete all as specified and directed. |
| 56 | Supply only in replacement of Modular metal flush box of 6 module complete all as specified and directed. |
| 57 | Supply only in replacement of Modular metal flush box of 4 module complete all as specified and directed. |
| 58 | Supply only in replacement of Modular metal flush box of 3 module complete all as specified and directed. |
| 59 | Supply only in replacement of Modular metal flush box of 2 module complete all as specified and directed. |
| 60 | Supply only in replacement of Modular white plate cover with frame of 12 module complete all as specified and directed. |
| 61 | Supply only in replacement of Modular white plate cover with frame of 8 module complete all as specified and directed. |
| 62 | Supply only in replacement of Modular white plate cover with frame of 6 module complete all as specified and directed. |
| 63 | Supply only in replacement of Modular white plate cover with frame of 4 module complete all as specified and directed. |
| 64 | Supply only in replacement of Modular white plate cover with frame of 3 module complete all as specified and directed. |
| 65 | Supply only in replacement of Modular white plate cover with frame of 1/2 module complete all as specified and directed. |
| 66 | Supply and fixing Angle/Batten type Lamp holder, PVC/Polycarbonate type with back plate suitable for light fittings complete all as specified and directed. |
| 67 | Supply & fixing in replacement single pole and neutral enclosure with a two pin earth plug and socket complete with one single pole MCB 20 Amps 'B' Curve complete all as specified and directed. |
| 68 | Taking down main switches fuse unit, MCB/Kit kat distribution board any type/size/capacity with steel enclosure along with MCB’s/Kit kat fuse of any Amps/ways including wooden board or from steel board and making good disturbed surfaces complete all as specified and directed. Note : Any disturbed surfaces of wall will be matched properly as the existing colour surfaces. |
| 69 | Supply and fixing in replacement of factory made epoxy polyester powder coated distribution board SP & N 4 way fabricated from recommended thick CRCA sheet with metal double door (IP-43 protection) fixed flush to wall and suitable for universal mounting & including aluminium alloy bus bar, Neutral bar, standard DIN rail, eath bar and cable ties for cable management, top and bottom removable gland plates with knockouts and suitable for one DP MCB as incomer and 2 SP MCBs as outgoings complete all as specified and conforming to IS: 8623 alongwith cable end box for above DB, Make : Legrand / GE Power / Schnieder or equivalent as approved by GE, complete all as specified and directed. Note : (a) MCBs shall be measured and paid separately.(b) All cables terminating into MCBs shall be connected by using suitable copper lugs / thimbles/sleeves and its cost shall be deemed to be included under respective item of Sch.(c) Making good and finishing of disturbed surfaces matching with the exisitng surfaces plastering, wood box work, painting if reqd any type including ecessary fixing arrangements complete deemed to be included under respective item of Schedule. (d) Make of MCBs /MCCBs and MCB DBs shall be same makes. |
| 70 | Description same all as per item No 69 here-in-before but SP & N 8 way |
| 71 | Description same all as per item No 69 here-in-before but SP & N 12 way |
| 72 | Description same all as per item No 69 here-in-before but TP & N 4 way |
| 73 | Description same all as per item No 69 here-in-before but TP & N 4 way (VTPN MCCB DB) DPX 125 4 pole MCCB as incommer and 40-63 SP MCBs outgoings |
| 74 | S&F MCB 63-100 Amps TPN 10 KA C curve 415 Volts complete all as specified and directed. |
| 75 | S&F MCB SPN 40-63 Amps KA C Curve 240 Volts complete all as specified and directed. |
| 76 | S&F MCB SPN 32 Amps 10 KA C Curve 240 Volts complete all as specified and directed. |
| 77 | S&F MCB Single Pole 6 to 32 Amps, 240 Volts, 'C' Series, 10 KA breaking capacity complete all as specified and directed. |
| 78 | S&F in repair MCB Single pole 40-63 Amps, 240 Volts, 'C' Series, 10 KA breaking capacity & making connection complete all as specified and directed. |
| 79 | Supply and fixing in replacement of MCCB 125 Amps 4 pole 25 KA at 415 Volts fixed type complete all as specified and directed. |
| 80 | Supply and fixing in replacement of MCCB 100 Amps 4 pole 25 KA at 415 Volts fixed type complete all as specified and directed. |
| 81 | Supply and fixing in replacement of MCCB 160 Amps 4 pole 36 KA at 415 Volts fixed type with sheet metal enclosure compatible to mount it including all lugs, separator etc complete all as specified and directed. |
| 82 | M&L for cutting/boring of PCC/Hard Standing at a depth not more than 15cm deep and 15cm in breadth for passing earthing conductor and making good the disturbed surfaces with PCC (1:2:4) type B-0 or cement mortar (1:3) complete all as specified and directed. |
| 83 | Supply and fixing in replacement of Non Metallic Rigid PVC casing caping/conduit pipe of size 20mm dia, ISI Marked, conforming to IS 9537 Part III, medium grade including all fittings like bends, elbow reducer, junction boxes, tee bell mouth all fixing accessories such as coupler lock, nuts, saddles pipe hooks etc complete all as specified and directed. |
| 84 | Description same all as per item No 83 here-in-before but of size 25 mm dia |
| 85 | Supply & fixing in replacement of worn out/rusted sunken box of size 100mm x 100mm with pressed MS/GI steel terminal boxes of depth not less than 50mm, flush type of thickness lot less than 1.22 mm along with new 3.0 mm thick plastic laminated sheet cover of suitable size including cutting/drilling hole and fixing switches, sockets, fan regulator etc as removed from old sheet and fitted with cadmium plated screw washer and making good to disturbed surface with cement mortar complete in all respect as specified and directed. |
| 86 | Description same all as per item No 85 here-in-before but of size 175mm x 100mm |
| 87 | Description same all as per item No 85 here-in-before but of size 200mm x 150mm |
| 88 | Description same all as per item No 85 here-in-before but of size 250mm x 200mm |
| 89 | Supply and fixing in replacement of Decorative, wall mounting, fixture with plastic body (City type -1) as per sample approved by Engineer-in-charge including 9 Watt LED lamp B22 complete all as specified and directed. |
| 90 | Supply & fixing in replacement Three pin metalic socket outlet suitable for sheet metal enclosure, Make : Bentac/C&S/HPL or equialent as approved by GE, complete all as specified and directed. |
| 91 | Supply & Fixing in replacement Three pin metallic plug top suitable for sheet metal enclsoure, Make : Bentac/C&S/HPL or equialent as approved by GE, complete all as specified and directed. |
| 92 | M&L for Dismantling of Ceiling Fans AC, Single Phase 230 Volts of sizes 1200mm/1400mm of any make / model, dismantled its stator, rotor, cutting out burnt copper winding and providing new winding with super enamelled copper winding wire existing size including cleaning of slots providing oil impregnated insulation paper or minimax, fibre, insulation in slots and well wraping, with cotton tape, bind with cotton thread and varnishing over all with winding varnish with bearing & paiting of complete as approved by Engineer-in-Charge and cleaning of bearing housing and shaft, replacing spares such as condenser, split pins, blade screws etc as required and deposited to MES store after testing complete all as specified and directed. Note - (i) Fans to be collected by the contractor at their own arrangement from AGE E/M store for repair/rewinding and to be deposited at same place after making serviceable duly tested. (ii) Additional spare parts as required to make the serviceable of same will be measured and paid separately as supply only. |
| 93 | Description same all as per item No 92 here-in-before but for Exhaust Fan of Sweep Size 300 / 380mm, AC, Single Phase 230/240 Volts. |
| 94 | Description same all as per item No 92 here-in-before but for Exhaust Fan of Sweep Size 230 / 250mm, AC, Single Phase 230/240 Volts. |
| 95 | Description same all as per item No 92 here-in-before but for Exhaust Fan of Sweep Size 450mm, AC, Single Phase 230/240 Volts. |
| 96 | Description same all as per item No 92 here-in-before but for Wall Mounted / Cabin / Padestral Fan of Sweep Size 400/450mm, AC, Single Phase 230/240 Volts. |
| 97 | Description same all as per item No 92 here-in-before but for Industrial Wall Mounted/ Padestral Fan of Sweep Size 480/600mm, AC, Single Phase 230/240 Volts. |
| 98 | Supply and fixing in replacement of ventilation fans PVC body of size 250 mm sweep including taking down the old unserviceable one and depositing the same in MES yard for further disposal as per existing procedure complete all as specified and directed. |
| 99 | Supply and fixing in replacement of 36 Watt LED 2' x 2' (Warm White) Panel Ultra slim recess mounted LED module with 120 Lumen / Watt high brightness LED package and unique pattern de-glaring PP diffuser and PS LGP de-glaring diffuser sheet for glare free uniform light distribution suitable for armstrong / grid ceiling applications complete all as specified and directed. |
| 100 | Supply and fixing in replacement of 40 Watt LED 2' x 2' Panel Ultra slim recess mounted LED module 120 Lumen/watt with high brightness LED package and unique pattern de-glaring PP diffuser and PS LGP de-glaring diffuser sheet for glare free uniform light distribution suitable for armstrong/grid ceiling applications complete all as specified and directed. |
| 101 | Supply and fixing of a deep recessed down light for comfort on eye suitable for versetile application such as offices retail 6 Watt LED including driver fixing arrangements & connecting with three core copper cable including taking down old worn out light complete all as specified and directed. |
| 102 | Description same all as per item No 101 here-in-before but 12 Watt LED |
| 103 | Description same all as per item No 101 here-in-before but 15 Watt LED |
| 104 | Supply & Fixing in replacement of LED Light fitting 1 x 9 Watt / 10 Watt bulk head luminaires including LED Light driver holder connecting up with three core flexible copper conductor cable of suitable size complete all as specified and directed. |
| 105 | Supply and fixing LED light fitting mirror type with high out put diffuser 2 feet, 10 Watt 220 Volts AC decorative type with driver holder and LED lamp including connecting up with three core flexible copper conductor cable of suitable size complete all as specified and directed. |
| 106 | M&L in replacement of energy saver LED battan fitting 20 Watt, 120 Lumen/Watt, 230 Volts, single tube mounting including with electronic driver LED Printed board, end cover, connector box etc and accessories, prewired, LED including required fixing arrangements and electrical connection two core copper cable from ceiling rose to led light fitting complete all as specified and directed. |
| 107 | M&L in replacement of bracket for building security light made out of 40mm bore GI pipe medium grade not less than 1.2 mtr length bent at 120 degree to shape fixed on pole/wall with and including 50 x 6mm FI clamps = 02 Nos with nut bolts, washers including painting of clamps with two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed. |
| 108 | Supply and fixing in replacement of LED street light fitting 35 Watt 120 Lumen/Watt, 230 Volts AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete all as specified and directed. |
| 109 | M&L in replacement of earthing complete with M.S galvanized earth plate electrode 600mm x 600mm x 6 mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below normal GL) with top edge of the earth plate not less than 1.5 mtr below normal GL, connected to galvanized earth lead wire 4 mm dia by means of bolts, nuts, check nuts & washers of GI or steel incl excavation, PCC (1:3:6) type C-1 chamber with RCC cover (1:2:4) type B0, 40mm thick reinforced with 8 mm dia bar, 3 Nos both way, 15mm dia light grade GI protection pipe, funnel with wire mesh, watering pipe of size 20 mm dia med. grade, lugs, main Earthing lead upto 7.5 mtr including Charcoal dust, salt etc, all as shown in electrical Plate No. 3 of SSR Part-I, 2009 specification, complete all as specified and directed. |
| 110 | M&L in replacement of provn of Earthing complete with M.S galvanized earth plate electrode 600mm x 600mm x 6mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below normal GL) with top edge of the plate not less than 1.5 mtr below normal GL, connected to Galvanized earth strip 32mm x 6mm upto 7.5 mtr with protection pipe by means of bolts, nuts, check nuts & washers of GI or steel incl excavation, PCC (1:3:6) type C-1 chamber with RCC cover (1:2:4) type B0, 40mm thick reinforced with 6mm dia bar, 3 Nos both way, 40mm dia light grade GI protection pipe, funnel with wire mesh, watering pipe of size 20mm dia med. grade, lugs, main Earthing lead upto 7.5 mtr including Charcoal dust, salt etc all as shown in electrical plate No. 5 of SSR Pt-I 2009 specification. |
| 111 | Supply and fixing of GI pipe light grade of size 40 mm bore for laying in trenches/floors or walls including all fittings for fixing complete all as specified and directed. |
| 112 | Supply and fixing of GI pipe light grade of size 15 mm bore for laying in trenches/floors or walls including all fittings for fixing complete all as specified and directed. |
| 113 | M&L for earth continuity conductor or main earthing lead 4mm dia GI or steel wire fixed to wall on batten or recessed or buried in ground or drawn in conduit/pipe complete all as specified and directed. |
| 114 | Schedule of Credit (MINUS) Rs. 1,44,944.00 B/F from Serial Page No. ____ [Note : Details of items for schedule of credit is given on Srl Page No. _____] This amount shall be automatically deducted to arrive at tendered sum Please Enable Macros to View BoQ information |