Indian Tenders

Tender Notice

TDR 55595937
Tendering Authority Military Engineer Services
Tender No 8837 GE SOUTH PUNE
Tender ID 2026_MES_766569_1
Tender Brief Corrigendum : Tender For Repairs/Maint Of Lt Panels, Feeder Pillars, Cables, Protective System, Apfc Panel, Lt Distribution System And Other Connected Works In New Chsc Other Connected Area Under Age E/M-Ii At Ge (South) Pune.
City Pune
State Maharashtra
Document Fees INR 500 /-
EMD INR 98000.0 /-
Tender Value INR 49 Lakhs /-
Tender Type Tender
Bidding Type Open Tender
Competition Type Indian

Tender Details

Tender for Repairs/Maint Of Lt Panels, Feeder Pillars, Cables, Protective System, Apfc Panel, Lt Distribution System And Other Connected Works In New Chsc Other Connected Area Under Age E/M-Ii At Ge (South) Pune.

Corrigendum Details

Sr No CorrigendumDate Corrigendum CorrigendumType NewSubmissionDate
1 10-06-2026 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 17-06-2026

Key Dates

Publish Date 10-06-2026
Last Date of Bid Submission 17-06-2026
Tender Opening Date 24-06-2026

Contact Information

Company Name Military Engineer Services
Contact Person GE SOUTH PUNE
Address NO 1 GEN BHAGAT MARG PUNE 40

BOQ Items

Name of Work:- REPAIRS/MAINT OF LT PANELS, FEEDER PILLARS, CABLES, PROTECTIVE SYSTEM, APFC PANEL, LT DISTRIBUTION SYSTEM AND OTHER CONNECTED WORKS IN NEW CHSC OTHER CONNECTED AREA UNDER AGE E/M-II AT GE (SOUTH) PUNE.
Sl. No. Item Description
1M&L for LT UG Cable fault finding/testing from Panel to fault location including taking shut down and opening the cable from both side of Bus Bar Panel/LT Panel/MCCB/ACB/Transformer etc and re-terminating the same cable in the same Bus Bar Panel/LT Panel/MCCB/ACB etc according to existing system after completion of fault finding/testing work complete all as specified and directed for any size of cable.Note:- Job will be measured after fault detection of any type regarding this decision of Engineer-in-charge shall be final & binding.
2M&L in replacement for heat shrinkable Straight through jointing kit for LT 1.1 KV XLPE cables 240 to 400 Sqmm 3.5 core including all accessories required. [Make :- Denson/M Seal/3M]
3M&L in replacement for heat shrinkable Straight through jointing kit for LT 1.1 KV XLPE cables 150 to 185 Sqmm 3.5 core including all accessories required. [Make :- Denson/M Seal/3M]
4M&L in replacement for heat shrinkable Straight through jointing kit for LT 1.1 KV XLPE cables 70 to 120 Sqmm 3.5 core including all accessories required. [Make :- Denson/M Seal/3M]
5M&L in replacement for heat shrinkable Straight through jointing kit for LT 1.1 KV XLPE cables 16 to 50 Sqmm 3.5 core including all accessories required. [Make :- Denson/M Seal/3M]
6Supply, laying, testing and commissionnig of LT cables 1100 volts grade, XLPE insulated and PVC sheathed, armoured, with multi stranded aluminum conductor, heavy duty conforming to IS - 1554 part-I, including cable glands, crimpimg type cable lugs in LT panel / MCCB in bldg etc to suit the cable laid in trenches/fixed to poles/drawn through pipes including taking down the existing cable complete of sizes:- 400 Sqmm 3.5 core.
7Ditto all as per item No 6 above but 300 sq mm 3.5 core
8Ditto all as per item No 6 above but 240 sq mm 3.5 core
9Ditto all as per item No 6 above but 185 sq mm 3.5 core
10Ditto all as per item No 6 above but 150 sq mm 3.5 core
11Ditto all as per item No 6 above but 120 sq mm 3.5 core
12Ditto all as per item No 6 above but 95 sq mm 3.5 core
13Ditto all as per item No 6 above but 70 sq mm 3.5 core
14Ditto all as per item No 6 above but 50 sq mm 3.5 core
15Ditto all as per item No 6 above but 35 sq mm 3.5 core
16Ditto all as per item No 6 above but 25 sq mm 3.5 core
17Ditto all as per item No 6 above but 16 sq mm 4 core
18Ditto all as per item No 6 above but 10 sq mm 2 core
19Ditto all as per item No 6 above but 10 sq mm 4 core
20Ditto all as per item No 6 above but 6 sq mm 2 core
21Ditto all as per item No 6 above but 6 sq mm 4 core
22Excavation in trenches in hard/dense soil n exc 1.5m wide and n.exc 1.5m in depth and getting out complete all as specified and directed by Engr-in-charge
23Excavation in trenches in soft/dis integrated rock n exc 1.5m wide and n.exc 1.5m in depth and getting out complete all as specified and directed by Engr-in-charge.
24Returning filling in including spreading leveling watering and well ramming in layers n.exc 25 cm complete all as specified and directed by Engr-in-charge.
25Removing excavated surplus soil / Soft disintegrated rock to a distance n exc 50 m and depositing where directed at a level n exc 1.5 mtr above starting point all as specified and directed by Engr-in-charge.
26Supply and laying 40 mm outer dia, double walled corrugated (DWC) HDPE duct pipe conforming to IS-14930 Pt-II with antirodent and non flame propogating properties of approved colour complete with fittings for cable protection complete all as specified and as directed.
27Supply and laying 90 mm outer dia, double walled corrugated (DWC) HDPE duct pipe conforming to IS-14930 Pt-II with antirodent and non flame propogating properties of approved colour complete with fittings for cable protection complete all as specified and as directed.
28Supply and laying 80mm bore light grade GI pipe fixed to walls / poles or laid in trenches, road crossing etc, for protection of under ground cable including sealing ends with hessian cloth impregnated with bituminous compound in ground and with suitable clamps, bolt/nuts etc for fixing on walls, poles etc. complete all as specified and directed.
29Ditto all as per item No 28 above but 50 mm bore complete all as directed
30Material and labour for cutting of existing road/ hard standing by providing suitable T&P to make suitable size bore for fixing 80/50/40 mm dia pipe in road crossing etc. including the cost of making good the disturbed surface and matching with existing (Chequered tiles/Road/PCC) complete all as specified and directed by Engr-In-Charge
31Supply, fix, test and commissioning of aluminium enclosure of 3200 Amps ratings, TPN, aluminium sandwich busduct, in repair of IP54, IEC 61439-6, copper contact, insulation class F suitable for indoor installation including connection with terminal with all accessores as required complete, copper laminated flexible connections, phase crossover, bends, adopter box, busbar supports, insulating materials all mounting accessories as per site requirement. All busbar joints shall have double headed bolt on connection plate, busbar joints shall have colour coded thermal indicator to indicate any excessive temperature rise at joints and other insulating material as per OEM specifiactions including taking down the existing one complete all as specified and as directed by Engr-in-Charge.
32Supply, fix, test and commissioning of aluminium enclosure of 3200 Amps ratings, TPN, aluminium sandwich busduct, in repair of IP66, IEC 61439-6, copper contact, class F insulation suitable for outdoor installation including connection with terminal with all accessores as required complete, copper laminated flexible connections, phase crossover, bends, adopter box, busbar supports, insulating materials all mounting accessories as per site requirement complete. All busbar joints shall have double headed bolt on connection plate, busbar joints shall have colour coded thermal indicator to indicate any excessive temperature rise at joints and other insulating material as per OEM specifiactions including taking down the existing one complete all as specified and as directed by Engr-in-Charge.
33Supply, fix, test and commissioning of aluminium enclosure of 2500 Amps ratings, TPN, aluminium sandwich busduct, in repair of IP54, IEC 61439-6, copper contact, class F insulation suitable for indoor installation including connection with terminal with all accessores as required complete, copper laminated flexible connections, phase crossover, bends, adopter box, busbar supports, insulating materials all mounting accessories as per site requirement complete. All busbar joints shall have double headed bolt on connection plate, busbar joints shall have colour coded thermal indicator to indicate any excessive temperature rise at joints and other insulating material as per OEM specifiactions including taking down the existing one complete all as specified and as directed by Engr-in-Charge. Please Enable Macros to View BoQ information
34Supply, fix, test and commissioning of aluminium enclosure of 2500 Amps ratings, TPN, aluminium sandwich busduct, in repair of IP54, IEC 61439-6, copper contact, class F insulation suitable for indoor installation including connection with terminal with all accessores as required complete, copper laminated flexible connections, phase crossover, bends, adopter box, busbar supports, insulating materials all mounting accessories as per site requirement complete. All busbar joints shall have double headed bolt on connection plate, busbar joints shall have colour coded thermal indicator to indicate any excessive temperature rise at joints and other insulating material as per OEM specifiactions including taking down the existing one complete all as specified and as directed by Engr-in-Charge. Please Enable Macros to View BoQ information

Other Detail

Information Source https://defproc.gov.in/nicgep/app
Download FileName File Description File Size
Download 7c1b03a7-1447-41fa-ba4f-aefa1e4bf72f.html Tender Documents 0 KB
Download 8837TD.pdf Tender Documents 0 KB
Download BOQ_858504.xls Tender Documents 0 KB
Download Tendernotice_1.pdf Tender Documents 0 KB
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.