Indian Tenders

Tender Notice

TDR 55585148
Tendering Authority Military Engineer Services
Tender No 81274
Tender ID 2026_MES_766639_1
Tender Brief Corrigendum : Tender For Repair/Maintenance Of Distribution Transformers And Protective Relays And Connected Works At installation Dronacharya And Sma Rameshwaram Under Ge Fort Kochi.
City Ernakulam
State Kerala
Document Fees INR 500 /-
EMD INR 29980.0 /-
Tender Value INR 14.99 Lakhs /-
Tender Type Tender
Bidding Type Open Tender
Competition Type Indian

Tender Details

Tender for Repair/Maintenance Of Distribution Transformers And Protective Relays And Connected Works At installation Dronacharya And Sma Rameshwaram Under Ge Fort Kochi.

Corrigendum Details

Sr No CorrigendumDate Corrigendum CorrigendumType NewSubmissionDate
1 11-06-2026 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 18-06-2026

Key Dates

Publish Date 11-06-2026
Last Date of Bid Submission 18-06-2026
Tender Opening Date 22-06-2026

Contact Information

Company Name Military Engineer Services
Contact Person Shri Abu Amir IDSE CWE NB KOCHI
Address Commander Works Engineer NB Kochi Kataribagh Naval Base PO Kochi 682 004

BOQ Items

Name of Work:- REPAIR/MAINTENANCE OF DISTRIBUTION TRANSFORMERS AND PROTECTIVE RELAYS AND CONNECTED WORKS AT INS DRONACHARYA AND SMA RAMESHWARAM UNDER GE FORT KOCHI.
Sl. No. Item Description
1GENERAL NOTE:- The contractor shall visit the site before quoting the tender and get acquaint himself regarding the make/ type of transformer etc, inorder to get a clear knowledge of site and quote accordingly. Nothing extra shall be admissible on this account please.
2Material and Labour for repair of Transformers 11 KV/433 Volts on site of any make installed at various location of Sub Stations, including disconnecting the HT/LT Cables, earth strips etc. from the transformer, draining the complete oil for removing sludge from the tank refilling and removing the top cover, conservator, explosion vent,etc, for detecting the faults and repairing by welding/bracing. Replacing all the gaskets & neoprene washers for leakage arresting. Reassembling the transformer and testing etc complete upto 400 KVA capacity complete all as specified and directed by the Engineer-in-charge.Note :- Supply only new transformer oil and oil filtration shall be measured and paid under the schedule of relevant items.
3Material and Labour for repair of Transformers 11 KV/433 Volts on site of any make installed at various location of Sub Stations, including disconnecting the HT/LT Cables, earth strips etc. from the transformer, draining the complete oil for removing sludge from the tank refilling and removing the top cover, conservator, explosion vent, etc, for detecting the faults and repairing by welding. Replacing all the gaskets & neoprene washers for leakage arresting. Reassembling the transformer and testing etc complete from 500 to 800 KVA capacity complete all as specified and directed by the Engineer-in-charge.Note :- Supply only new transformer oil and oil filtration shall be measured and paid under the schedule of relevant items.
4Supply and fix in repairs 11000V Bushing as per site requirements with superior quality brass rods complete with and including necessary Rubber `O' ring/oil seals and gaskets for distribution transformers of capacity up to 800 KVA complete all as specified and directed by the Engineer-in-charge.
5Supply and fix in repairs 415 V Bushing porcelain with superior quality brass rods complete with and including necessary Rubber `O' ring/oil seals and gaskets for distribution transformers of capacity up to 800 KVA complete all as specified and directed by the Engineer-in-charge.
6Material and Labour for repair of Transformers 11 KV 433 Volts on workshop transportation loading /unloading any make installed at various location of Sub Stations, including disconnecting the HT/LT Cables, earth strips etc. from the transformer, draining the complete oil for removing sludge from the tank refilling and removing the top cover, conservator, explosion vent, etc, for detecting the faults and repairing by hevy works. Replacing all the gaskets & neoprene washers for leakage arresting. Reassembling the transformer heating at chamber, transportaion back to site and commissioning etc complete upto 800 KVA capacity complete all as specified and directed by the Engineer-in-charge.Note :- Supply only new transformer oil and oil filtration shall be measured and paid under the schedule of relevant items.
7Dehydration and online filtration of transformer oil at site by centrifugal filtration method using mobile filtration plant on transformers so as to achieve appropriate di-electric strength (not less than 55KV) and testing of the same before and after filtration to entire satisfaction of Engr-in-Charge in various locations for transformers of various capacities and submitting of test results in triplicate all as specified and as per availability of shut down before and after monsoons or whenever as directed complete all as specified and directed by the Engineer-in-charge.
8Supply only new insulating transformer oil of superior quality low viscosity having di-electric strength not less than 55 KV bought at site in sealed containers and confirming to IS 335 complete all as specified and directed by the Engineer-in-charge.
9Material and Labour for preparation of old painted iron surfaces of the Transformer of capacity 100 KVA to 400 KVA, by cleaning completely after that applying two coats of synthetic enameled paint on the transformer as per MES colour complete all as specified and directed by the Engineer-in-charge. Note:- Painting shall be carried out with Spray Gun using compressor.
10Material and Labour for preparation of old painted iron surfaces of the Transformer of capacity 500 KVA to 800 KVA, by cleaning completely after that applying two coats of synthetic enameled paint on the transformer as per MES colour complete all as specified and directed by the Engineer-in-charge. Note:- Painting shall be carried out with Spray Gun using compressor.
11Supply and replace unserviceable transformer temperature gauge having 100 mm dia dial, 0 to 1200C, brass sensor, 6\\" length with 1/2\\" BSP thread adjustable brass connection and maximum reading pointer and re-setting device complete all as specified and directed by the Engineer-in-charge.
12Supply and fix in repair Gunmetal Gate valves 50 mm dia as per IS 778 ISI marked complete all as specified and directed by the Engineer-in-charge.
13Supply and fix in repair Gunmetal Gate valves 25 mm dia as per IS 778 ISI marked complete all as specified and directed by the Engineer-in-charge.
14Material and Labour for replacement of defective silica gel breather with silica gel transparent type complete set for 500-800 KVA capacity transformer complete all as specified and directed by the Engineer-in-charge.
15Material and Labour for replacement of defective silica gel breather with silica gel transparent type complete set for 100-400 KVA capacity transformer complete all as specified and directed by the Engineer-in-charge.
16Supply and fill the silica gel for breather of various transformers including taking out old gel complete all as specified and directed by the Engineer-in-charge.
17M & L for copper winding super enameled with insulation, varnish, heating etc after taking out from transformer core with same guage of existing for HT side complete all as specified and directed by the Engineer-in-charge.
18M & L for copper winding super enameled with insulation,varnish, heating etc after taking out from transformer core with same guage of existing for LT side complete all as specified and directed by the Engineer-in-charge.
19M & L for attending transformer 11 KV /433 V fault at any capacity by disconnections electrical connections and meggering for health check up, dismantling cable connections recommendation checking after heavy works complete all as specified and directed by the Engineer-in-charge.
20Supply and laying cable XLPE insulated screened PVC bedded, galvanised steel strip of wire armoured, electric power cables (Heavy duty) 11000 Volts grade with stranded aluminimum conductor of size 185 sqmm, 3.0 core including taking down old unserviceable cable, etc complete from trenches/poles/surface complete all as specified and directed by Engr-in-Charge.Note: Excavation, returning filling and removal of soil shall be measured and paid separately.
21Supply and laying cable XLPE insulated screened PVC bedded, galvanised steel strip of wire armoured, electric power cables (Heavy duty) 11000 Volts grade with stranded aluminimum conductor of size 240 sqmm, 3.0 core including taking down old unserviceable cable, etc complete from trenches/poles/surface complete all as specified and directed by Engr-in-Charge.Note: Excavation, returning filling and removal of soil shall be measured and paid separately.
22Material and labour for replacement of cable jointing kit for 11 KV (earthed) grade cable for straight through heat shrinkable type joint complete with jointing materials and all accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm complete all as specified and directed by Engr-in-Charge.
23Material and labour for replacement of cable jointing kit for 11 KV (earthed) grade cable for straight through heat shrinkable type joint complete with jointing materials and all accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 240 sqmm to 400 sqmm complete all as specified and directed by Engr-in-Charge.
24Material and labour for replacement of XLPE cable jointing kit end termination heat shrinkable indoor type suitable for UG cable 120 sqmm to 185 sqmm 3 core 11000 volt grade complete all as specified and directed by Engr-in-Charge.
25Material and labour for replacement of XLPE cable jointing kit end termination heat shrinkable indoor type suitable for UG cable 240 sqmm to 300 sqmm 3 core 11000 volt grade complete all as specified and directed by Engr-in-Charge.
26M&L for sand cushioning riddle earth in trenches/ducts for protection of UG Cables (below, above and around the UG cable laid) of 23 CM spread thickness (8 CM in depth before laying the cable and 15 CM in depth after laying the cable) and above sand shall be obtained through digging at site 500 mtrs distance and transporting to site for punned use to sand cushioning upto 18 CM thickness complete all as specified and as directed.Note: For the purpose of payment punned thickness of sand cusioning only will be measured.
27Supply and lay sub class \\"B\\" burnt bricks of size 23x11.5x7.5 cm as in cable protection, laid length of brick perpendicular to length of cable complete all as specified and directed.
28Excavation in trenches n exc 1.5m wide and n exc 1.5m deep for laying /removing of cable/ erection of poles in soft loose soil/floor and making good the disturbed surfaces complete all as specified and directed by Engr- in- charge.
29Returning filling in, including spreading, levelling, watering and well ramming in layers n exc 25mm thick in soil complete all as specified
30Removing excavated material (Soil) to a distance not exceeding 50 m and depositing where directed at a level n exc. 1.5 m above starting point complete all as specified and directed.
31Supply and fixing/laying GI tubing 100 mm dia light grade as cable protection in road cutting, etc complete all as specified and directed by Engr- in- charge. Please Enable Macros to View BoQ information
32Supply and fixing/laying GI tubing 100 mm dia light grade as cable protection in road cutting, etc complete all as specified and directed by Engr- in- charge. Please Enable Macros to View BoQ information

Other Detail

Information Source https://defproc.gov.in/nicgep/app
Download FileName File Description File Size
Download 81274TENDER.pdf Tender Documents 0 KB
Download BOQ_858578.xls Tender Documents 0 KB
Download c23920f9-03a6-41a5-9fd2-b34c09c1d9cd.html Tender Documents 0 KB
Download Tendernotice_1.pdf Tender Documents 0 KB
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.