Indian Tenders

Tender Notice

TDR 55425158
Tendering Authority Military Engineer Services
Tender No GE MAINT EZHIMALA 8851
Tender ID 2026_MES_764372_1
Tender Brief Corrigendum : Tender For Repair/ Replacement Of Switch Gear, Indoor And Out Door Lt Panels, Sub Panels And Connected E/M Works In Substation And Electrical Installation At Nasa, Cera, And Ora Area At Ina Ezhimala.
City Kannur
State Kerala
Document Fees INR 500 /-
EMD INR 70000.0 /-
Tender Value INR 35 Lakhs /-
Tender Type Tender
Bidding Type Open Tender
Competition Type Indian

Tender Details

Tender for Repair/ Replacement Of Switch Gear, Indoor And Out Door Lt Panels, Sub Panels And Connected E/M Works In Substation And Electrical Installation At Nasa, Cera, And Ora Area At Ina Ezhimala.

Corrigendum Details

Sr No CorrigendumDate Corrigendum CorrigendumType NewSubmissionDate
1 30-05-2026 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 06-06-2026
2 13-05-2026 BoQ Corrigendum BOQ 30-05-2026

Key Dates

Publish Date 30-05-2026
Last Date of Bid Submission 06-06-2026
Tender Opening Date 12-06-2026

Contact Information

Company Name Military Engineer Services
Contact Person GE(MAINT)EZHIMALA
Address GARRISON ENGINEER (MAINT) MILITARY ENGINE SERVICES INDIAN NAVAL ACADEMY POST KANNUR DIST KERALA 670 310

BOQ Items

Name of Work:- Repair/ Replacement of switch gear, indoor and out door LT Panels, sub panels and connected E/M works in substation and electrical installation at NASA, CERA, and ORA area at INA Ezhimala.
Sl. No. Item Description
1Supply and fix in repairs LT Panel Outdoor type floor mounted free standing dust and vermin proof panel / DB with IP-55 protection, CPRI approved, frame fabricated out of 40mm x 40mm x 4mm angle iron, 3 mm thick CRCA sheet for entire outer panel with single door and locking arrangements & 1.6 mm for inner compartment with 40mmx4mm flat Iron, including Separate cubicle chamber with cable alley not less than 300mm width for installation/connecting switchgears with the main bus bar using aluminium bus link or copper conductor flexible wires suitable for switch rating and connecting outgoing terminals of the switchgear with terminal blocks of appropriate current rating using flexible copper wires duly terminated by cable lugs and thimbles, MS surfaces epoxy based powder coated, shade as approved over 2 coats of red oxide primer, surfaces pre-treated in seven tank process for de-greasing, de-rusting & Phosphated, panel having front and rear opening and provision for installation of separate cable alleys, all MCCBs must be have thermal magnetic relrase, busbar chamber and switchgear compartments, Provision in cable alleys for bottom cable entry for incoming & outgoing cables, affixing MV danger plate at suitable intervals / locations including erection, testing and commissioning complete all as specified and directed including the following Switchgears, fixtures and fitments mentioned below.
2Busbars:-TPN- Not less than 400 A, Aluminium bus bars E91 grade, 1100 volts grade duly covered with heat shrinkable sleeves colour coded duly fixed on moulded brackets and covered all around by insulating/CRCA sheet having no exposed portion. Bus bar chamber to be selected so that it provides gap between Bus bar and heat dissipation conforming to IS standard -1 set. Incoming:- (i) MCCB 250 A, 4 Pole, 36KA with thermomagnetic release- 01 No., (ii) CT's 200/5 -03 No., (iii)Multifuction meter -01 No. (iv) Phase Indicating lamps -03 (v) Control fuses / MCB -03 Nos
3Outgoing:-Separate cubical chamber with a cable alley not less than 300 mm width for installation/connecting the following switch gear with the main bus bar using aluminium bus link or copper conductor flexible wires suitable to the switch rating and connecting outgoing terminals of the switch gear with terminal blocks of appropriate current rating using flexible copper wires duly terminated by cable lugs and thimbles.(Contd....) Please Enable Macros to View BoQ information
4Outgoing:-Separate cubical chamber with a cable alley not less than 300 mm width for installation/connecting the following switch gear with the main bus bar using aluminium bus link or copper conductor flexible wires suitable to the switch rating and connecting outgoing terminals of the switch gear with terminal blocks of appropriate current rating using flexible copper wires duly terminated by cable lugs and thimbles.(Contd....) Please Enable Macros to View BoQ information

Other Detail

Information Source https://defproc.gov.in/nicgep/app
Download FileName File Description File Size
Download 43c319d3-704c-4587-b9ef-71709bdc1601.html Tender Documents 0 KB
Download BOQ_856134.xls Tender Documents 0 KB
Download Tender.pdf Tender Documents 0 KB
Download Tendernotice_1 (1).pdf Tender Documents 0 KB
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.