| 1 | Wiring for light pointl fan polntl exhaust fan pointl call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, with piano type switch, phenolic laminated sheet, suitable size MS box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 2 | Group A |
| 3 | Group B |
| 4 | Group C |
| 5 | Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, 2 way piano type switch, phenolic laminated sheet, suitable size MS box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 6 | Wiring for light pointl fan pointl exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required |
| 7 | Group A |
| 8 | Group B |
| 9 | Group C |
| 10 | Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc .as required. |
| 11 | Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 12 | Wiring for light/ power plug with 4X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit alongwith 2 Nos. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 13 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surfacel recessed steel conduit as required. |
| 14 | 2 X 1.5 sq. mm +1 X1.5 sq. mm earth wire |
| 15 | 2 X 2.5 sq. mm +1 X 2.5 sq. mm earth wire |
| 16 | 2 X4 sq. mm + 1 X 4 sq. mm earth wire |
| 17 | 2 X 6 sq. mm + 1 X 6 sq. mm earth wire |
| 18 | 2 X 10 sq. mm + 1 X 6 sq. mm earth wire |
| 19 | 2 X 16 sq. mm + 1 X 6 sq. mm earth wire |
| 20 | 4 X 2.5 sq. mm + 2 X 2.5 sq. mm earth wire |
| 21 | 4 X4 sq. mm + 2 X4 sq. mm earth wire |
| 22 | 4 X 6 sq. mm + 2 X 6 sq. mm earth wire |
| 23 | 4 X 10 sq. mm + 2 X 6 sq. mm earth wire |
| 24 | 4 X 16 sq. mm + 2 X 6sq. mm earth wire |
| 25 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with piano type switch, phenolic laminated sheet, suitable size M.S. box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required. |
| 26 | Group A |
| 27 | Group B |
| 28 | Group C |
| 29 | Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2 way piano type switch, phenolic laminated sheet, suitable size MS box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required. |
| 30 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 31 | Group A |
| 32 | Group B |
| 33 | Group C |
| 34 | Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 35 | Wiring for lightl power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surfacel recessed medium class PVC conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 36 | Wiring for lightl power plug with 4X4 sq. mm FRLS PVC insulated copper conductor single core cable in surfacel recessed medium class PVC conduit alongwith 2 Nos. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 37 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surfacel recessed medium class PVC conduit as required. |
| 38 | 2 x 1.5 sq. mm +1 x1.5 sq. mm earth wire |
| 39 | 2 x 2.5 sq. mm +1 x 2.5 sq. mm earth wire |
| 40 | 2 x4 sq. mm + 1 x4 sq. mm earth wire |
| 41 | 2 x 6 sq. mm + 1 x 6 sq. mm earth wire |
| 42 | 2 x 10 sq. mm +1 x 6 sq. mm earth wire |
| 43 | 2 x 16 sq. mm +1 x 6 sq. mm earth wire |
| 44 | 4 x 2.5 sq. mm + 2 x 2.5 sq. mm earth wire |
| 45 | 4 x4 sq. mm + 2 x 4 sq. mm earth wire |
| 46 | 4 x 6 sq. mm + 2 x 6 sq. mm earth wire |
| 47 | 4 x 10 sq. mm + 2 x 6 sq. mm earth wire |
| 48 | 4 x 16 sq. mm + 2 x 6 sq. mm earth wire |
| 49 | Rewiring for light point fan point exhaust fan pointl call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS PVC insulated copper conductor single core cable as earth wire in existing surfacel recessed steel/PVC conduit including dismantling as required. |
| 50 | Group A |
| 51 | Group B |
| 52 | Group C |
| 53 | Rewiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS PVC insulated copper conductor single core cable as earth wire in existing surfacel recessed steel/PVC conduit including dismantling as required. |
| 54 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface! recessed steell PVC conduit as required. |
| 55 | 1x1.5sq. mm |
| 56 | 2x1.5sq. mm |
| 57 | 3x1.5sq. mm |
| 58 | 4x15sqmm |
| 59 | 5x15sqmm |
| 60 | 6x15sqmm |
| 61 | 7x15sqmm |
| 62 | 8x15sqmm |
| 63 | 9x15sqmm |
| 64 | 10 x 1.5 sq. mm |
| 65 | 2 x 2.5 sq. mm |
| 66 | 3 x 2.5 sq. mm |
| 67 | 4 x 2.5 sq. mm |
| 68 | 5 x 2.5 sq. mm |
| 69 | 6 x 2.5 sq. mm |
| 70 | 7 x 2.5 sq. mm |
| 71 | 8 x 2.5 sq. mm |
| 72 | 9 x 2.5 sq. mm |
| 73 | 10 x 2.5 sq. mm |
| 74 | 2 x 4 sq. mm |
| 75 | 3 x 4 sq. mm |
| 76 | 4 x 4 sq. mm |
| 77 | 5 x 4 sq. mm |
| 78 | 6 x 4 sq. mm |
| 79 | 7 x 4 sq. mm |
| 80 | 8 x 4 sq. mm |
| 81 | 9 x 4 sq. mm |
| 82 | 10x4sq.mm |
| 83 | 2 x 6 sq. mm |
| 84 | 3 x 6 sq. mm |
| 85 | 4 x 6 sq. mm |
| 86 | 5 x 6 sq. mm |
| 87 | 6 x 6 sq. mm |
| 88 | 7 x 6 sq. mm |
| 89 | 8 x 6 sq. mm |
| 90 | 9 x 6 sq. mm |
| 91 | 10 x 6 sq. mm |
| 92 | 1× 50 sq. mm |
| 93 | 1 × 70 sq. mm |
| 94 | 1 × 95 sq. mm |
| 95 | Supplying and drawing co-axial TV cable RG-6 grade, 0.7 mm solid copper conductor PE insulated, shielded with fine tinned copper braid and protected with PVC sheath in the existing surfacel |
| 96 | Supplying and drawing following pair 0.5 mm dia FRLS PVC insulated annealed copper conductor, unarmored telephone cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 97 | 1 Pair |
| 98 | 2 Pair |
| 99 | 4 Pair |
| 100 | Supplying and drawing co-axial TV cable RG-6 grade, 0.7 mm solid copper conductor PE insulated, shielded with fine tinned copper braid and protected with PVC sheath in the existing surface/ recessed steel/ PVC conduit as required |
| 101 | Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required. |
| 102 | 20 mm |
| 103 | 25 mm |
| 104 | 32 mm |
| 105 | 40 mm |
| 106 | 50 mm |
| 107 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 108 | 20 mm |
| 109 | 25 mm |
| 110 | 32 mm |
| 111 | 40 mm |
| 112 | 50 mm |
| 113 | Supplying and Fixing 25 mm Double Locked PVC Channel 2 mm thick |
| 114 | Supplying and Fixing DLP PVC Trunking compartment along with accessories divider, extra cover, end caps, internal angles external angles, flat angles etc.25 mm Double Locked PVC Channel 2 mm thick |
| 115 | 50 × 80 |
| 116 | 50 × 105 |
| 117 | 50 × 130 |
| 118 | 50 × 145 |
| 119 | 50 × 180 |
| 120 | Supplying and fixing metal box of following sizes (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including painting etc. as required. |
| 121 | 75 mm X 75 mm X 60 mm deep |
| 122 | 100 mm X 100 mm X 60 mm deep |
| 123 | 150 mm X 75 mm X 60 mm deep |
| 124 | 150 mm X 150 mm X 60 mm deep |
| 125 | 180 mm X 100 mm X 60 mm deep |
| 126 | 200 mm X 125 mm X 60 mm deep |
| 127 | 200 mm X 150 mm X 60 mm deep |
| 128 | 200 mm X 150 mm X 75 mm deep |
| 129 | 200 mm X 250 mm X 60 mm deep |
| 130 | 200 mm X 250 mm X 75 mm deep |
| 131 | 200 mm X 150 mm X 100 mm deep |
| 132 | 200 mm X 250 mm X 100 mm deep |
| 133 | 200 mm X 300 mm X 60 mm deep |
| 134 | 200 mm X 300 mm X 100 mm deep |
| 135 | 250 mm X 300 mm X 60 mm deep |
| 136 | 250 mm X 300 mm X 100 mm deep |
| 137 | Supplying and fixing following piano type switch/ socket on the existing switch box/ cover including connections etc. as required. |
| 138 | 5/6 amps switch |
| 139 | 2 way 5/6 A switch |
| 140 | 15/16 A switch |
| 141 | 3 pin 5/6 A socket outlet |
| 142 | 6 pin 15/16 A socket outlet |
| 143 | Telephone socket outlet |
| 144 | 5/6A 3 Pin TOP |
| 145 | 16 A TOP |
| 146 | 15 A switch Socket Combine with out box |
| 147 | 15 A switch socket combine with box |
| 148 | Fan Regulator Stepped type 1 Module |
| 149 | Fan Regulator Stepped type 2 Module |
| 150 | Supplying and Fixing PVC Gang Box 2 mm thick with srew fixing with concrete wall/brick walll / play wood |
| 151 | 2 way gang box pvc |
| 152 | 4 way gang box pvc |
| 153 | Bell push |
| 154 | Supplying and fixing an electronic AC/DC Bell, superior quality ISI make. |
| 155 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 156 | 5/6 A switch |
| 157 | 2 way 5/6 A switch |
| 158 | 15/16 A switch |
| 159 | 3 pin 5/6 A socket outlet |
| 160 | 6 pin 15/16 A socket outlet |
| 161 | Telephone socket outlet |
| 162 | TV antenna socket outlet |
| 163 | Bell push |
| 164 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 165 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 166 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 167 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 168 | Supplying and fixing following size modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required. |
| 169 | 1 or 2 Module (75mmX75mm) |
| 170 | 3 Module (100mmX75mm) |
| 171 | 4 Module (125mmX75mm) |
| 172 | 6 Module (200mmX75mm) |
| 173 | 8 Module (125mmX125mm) |
| 174 | 12 Module (200mmX150mm) |
| 175 | Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required. |
| 176 | 1 or 2 Module |
| 177 | 3 Module |
| 178 | 4 Module |
| 179 | 6 Module |
| 180 | 8 Module |
| 181 | 12 Module |
| 182 | Supply and laying of following sizes of PVC insulated, overall PVC sheathed, FRLS, 1.1 kV grade, unarmoured, Copper wire |
| 183 | a) 1.0 sq. mm, 2-Core |
| 184 | b) 1.5 sq. mm, 2-Core |
| 185 | b) 1.5 sq. mm, 3-Core |
| 186 | c) 2.5 sq. mm, 2-Core |
| 187 | c) 2.5 sq. mm, 3-Core |
| 188 | d) 4.0 sq. mm, 2-Core |
| 189 | d) 4.0 sq. mm, 3-Core |
| 190 | e) 1.0 sq. mm, 4-Core |
| 191 | f) 1.5 sq. mm, 4-Core |
| 192 | g) 2.5 sq. mm, 4-Core |
| 193 | h) 4.0 sq. mm, 4-Core |
| 194 | Supply and laying of the following sizes of glass-coated insulated, cotton-insulated heat-resistant overall sheathed, FRLS, 1.1 kV grade, unarmoured, Copper wire for water heater, |
| 195 | a) 1.0 sq. mm, |
| 196 | b) 1.5 sq. mm, |
| 197 | c) 2.5 sq. mm, |
| 198 | Supplying and fixing metal box of 150mm X 75mm X 60mm deep (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including providing and fixing 3 pin 5/6.A socket outlet and 5/6 A piano type switch, connections, painting etc. as required. |
| 199 | Supplying and fixing metal box of 180mm X 100mm X 60mm deep (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including providing and fixing 6 pin 5/6 & 15/16 A socket outlet and 15/16 A piano type switch, connections, painting etc. as required. |
| 200 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. |
| 201 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 202 | Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required. |
| 203 | Supplying and fixing brass batten/ angle holder including connection etc. as required. |
| 204 | Supplying and fixing PVC Square block on the existing, including fixing on the wall /ceiling, etc. As required. |
| 205 | Installation ,Testing, Commissioning of wall bracket /ceiling fittings of all sizes and shapes containing upto two GLS/CFL/LED lamps per fitting, complete with all accessories including connections etc. as required. |
| 206 | Supplying and fixing stiff pendent with 300 mm long, 20 mm dia X 1.6 mm thick steel conduit, aluminium cast back plate and brass holder complete, including wiring the down rod with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and painting etc. as required. |
| 207 | Supplying and fixing call bell/ buzzer suitable for single phase, 230 V, complete as required. |
| 208 | Providing and fixing plain 1610.20mm (0.50sqmm) twin flat flexible, FRLS PVC insulated, copper conductor cable, in PVC sleeve of suitable size on the floor/ wall, or side of the table/ door etc. as required. |
| 209 | Providing and fixing plain 1610.20mm (0.50sqmm) twin circular flexible FRLS PVC insulated, PVC sheathed copper conductor cable direct on the wall with PVC clips etc. as required. |
| 210 | Installation, testing and commissioning of pre-wired, fluorescent fitting / compact fluorescent fitting of all types, complete with all accessories and tube/lamp etc. directly on ceiling/ wall, including connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required. |
| 211 | Installation, testing and commissioning of pre-wired, fluorescent fitting / compact fluorescent fitting of all types, complete with all accessories and tube/lamp etc., including supplying and fixing ball and socket arrangement, 2 Nos. down rods of 20 mm dia X 1.6 mm thick steel conduit upto 30 cm length, painting and wiring the down rods and connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required. |
| 212 | Providing and fixing extra conduit down rod of 20 mm dia, 2 X 10 cm length, wiring with 2 X 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable including painting etc. as required.(Note: More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored) |
| 213 | Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc.as required. |
| 214 | Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable, including providing and fixing phenolic laminated sheet cover on the fan box etc. as required. |
| 215 | Supplying and fixing extra down rod of 10 cm length G.I. pipe , 15 mm dia, heavy gauge including painting etc. as required. (Note :More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored) |
| 216 | Supplying and fixing extra conduit down rod of 20 cm length G.I. pipe 15 mm dia, heavy gauge including painting etc. as required.(Note: More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored) |
| 217 | Numbering of ceiling fan/ exhaust fan/ fluorescent fittings as required. |
| 218 | Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required. |
| 219 | Upto 450 mm sweep |
| 220 | 510 mm sweep |
| 221 | Extra for fixing the lovers/ shutters complete with frame for a exhaust fan of all sizes. |
| 222 | Painting of ceiling fan in installed position with one or more coats of spray painting with synthetic enamel paint of approved brand and manufacture to give an even shade, including cleaning of surface with detergent etc. as required. |
| 223 | Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required. |
| 224 | 1 run of cable |
| 225 | 2 run of cable |
| 226 | 3 run of cable |
| 227 | Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent switch etc.) with 1.5 sq. mm |
| 228 | FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 229 | Group A Group B |
| 230 | Group C |
| 231 | Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point ( without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 232 | Group A |
| 233 | Group B |
| 234 | Group C |
| 235 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including proving and fixing 2 nos. 3 pin 5/6 A modular socket outlet and 2 nos. 5/6 A modular switch, connections etc. as required. (For light plugs to be used in non residential buildings). |
| 236 | Supplying & fixing suitable size Gl box wih modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, \\"C\\" curve including connections, painting etc. as required. |
| 237 | Supplying and fixing PVC batten/ angle holder including connections etc. as required. |
| 238 | Dismantling of ceiling fan and painting the same with with one or more coats of spray painting with synthetic enamel paint of approved brand and manufacture to give an even shade, including cleaning of surface with detergent and replacing the damaged rubber reel, nuts and bolts with washers and safety pins, reinstalling the same as required. |
| 239 | Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required. |
| 240 | 32 A TP&N |
| 241 | 63 A TP&N |
| 242 | 100 A TP&N |
| 243 | 125 A TP&N |
| 244 | 160 A TP&N |
| 245 | 200 A TP&N |
| 246 | 315 A TP&N |
| 247 | 400 A TP&N |
| 248 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. |
| 249 | 100 A. 16 KA.ТРМССВ |
| 250 | 125 A, 16 KA, ТРМССВ |
| 251 | 150 A, 16 КА, ТРМССВ |
| 252 | 200 A, 16 KA, ТРМССВ |
| 253 | 200 А. 25 КА.ТРМССВ |
| 254 | 250 A, 25 KA, ТРМССВ |
| 255 | 250 A. 35 KA. ТРМССВ |
| 256 | 315 A. 35 KA.ТРМССВ |
| 257 | 400 A, 35 KA, ТРМССВ |
| 258 | 500 A, 35 KA, ТРМССВ |
| 259 | 630 A, 50 KA, ТРМССВ |
| 260 | 800 A, 50 KA, ТРМССВ |
| 261 | 100 A, 30KA, FPMCCB |
| 262 | 125 A, 36KA,FPMCCB |
| 263 | 200 A,36KA,FPMCCB |
| 264 | 250 A,36KA,FPMCCB |
| 265 | 250 A,50KA, FPMCCB |
| 266 | 400 A,50KA,FPMCCB |
| 267 | 630 A,50KA,FPMCCB |
| 268 | 800 A,50KA,FPMCCB |
| 269 | 1000 A,50KA,FPMCCB |
| 270 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required.(But without MCB/RCCB/Isolator) |
| 271 | 6 way, Double door |
| 272 | 8 way, Double door |
| 273 | 12 way, Double door |
| 274 | 16 way, Double door |
| 275 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/lsolator) |
| 276 | 4 way (4 + 12), Double door |
| 277 | 6 way (4 + 18), Double door |
| 278 | 8 way (4 + 24), Double door |
| 279 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) |
| 280 | 4 way (4 + 12), Double door |
| 281 | 8 way (4 + 24), Double door |
| 282 | 12 way (4 + 36), Double door |
| 283 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioninq etc. as required. |
| 284 | Single pole |
| 285 | Single pole and neutral |
| 286 | Double pole |
| 287 | Triple pole |
| 288 | Triple pole and neutral |
| 289 | Supplying and fixing following rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 290 | a) 40A TPN |
| 291 | b) 63A TPN |
| 292 | c) 40A TP |
| 293 | d) 63A TP |
| 294 | e) 40A DP |
| 295 | f) 63A DP |
| 296 | Supplying and fixing following rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioninq etc. as required. |
| 297 | Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete connections, testing and commissioning etc. as required.with |
| 298 | Supplying and fixing following rating , residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DP complete with connections, testing and commissioning etc. as required. |
| 299 | Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioninq etc. as required. |
| 300 | Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required. |
| 301 | Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32 A 240 V \\"C\\" curve DP MCB complete with connections, testing and commissioning etc. as required. |
| 302 | Supplying and fixing TP sheet steel enclosure on surface/ recess each 848 along with 16/25/32 A 415 V \\"C\\" curve TP MCB complete with connections, testing and commissioning etc. as required |
| 303 | Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 20 A \\"C\\" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required |
| 304 | Supplying and fixing 20 A, 415 V, TPN Industrial type socket outlet, with 4 pole and earth, metal enclosed plug top alongwith 20 A \\"C\\" curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. |
| 305 | Supplying and fixing 30 A, 415 V, TPN Industrial type socket outlet, with 4 pole and earth, metal enclosed plug top alongwith 30 A \\"C\\" curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. |
| 306 | Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required. |
| 307 | Replacement/supply and fixing of following accessories |
| 308 | a) LED Lamp 9 watt with minimum lumens 900 |
| 309 | b) LED Lamp 12 watt with minimum lumens 1200 |
| 310 | Replacement/supply and fixing of following accessories |
| 311 | a) LED Lamp 9 watt with minimum lumens 900 |
| 312 | b) LED Lamp 12 watt with minimum lumens 1200 |
| 313 | Replacement/supply and fixing of following luminaries as specified below. |
| 314 | Surface type LED luminaries 12-16 Watt circular/square type slim decorative aluminium casted and separate electronic driver with system temperature 5500/6000/6500 K and robust construction in combination with flat diffuser with minium system Lumens 1000 with burning hours greater than 40000 Hourshaving system lumens =110 lm/watt, Industrial Type. |
| 315 | Surface type LED luminaries 15-20 Watt circular/square type slim decorative aluminium casted and separate electronic driver with system temperature 5500/6000/6500 K and robust construction in combination with flat diffuser with minium system Lumens 1200 with burning hours greater than 40000 Hours having system lumens =110 lm/watt, Industrial Type |
| 316 | Hanging light (fancy-type light) with min 8 Watts LED lamp |
| 317 | 10-12 Watt LED Bulkhead luminaire with burning hours >= 50000 Hours. |
| 318 | Recessed type LED luminaries 12-16 Watt circular/square type slim decorative aluminium casted and separate electronic driver with system temperature 5500/6000/6500 K and robust construction in combination with flat diffuser with minium system Lumens 1000 with burning hours >= 50000 Hours having system lumens =110 lm/watt, Industrial Type |
| 319 | Recessed type LED luminaries 15-20 Watt circular/square type slim decorative aluminium casted and separate electronic driver with system temperature 6000/6500 K and robust construction in combination with flat diffuser with minium system Lumens 1200 with burning hours >= 50000 Hours having system lumens =110 lm/watt, Industrial Type |
| 320 | 4 feet long LED batten 6000/6500k Light with anti-glare diffuser with energy efficient electronic driver CRI greater than 80 with minimum sytem lumens 4000 and maximum wattage24 including connection with multistrand copper conductor 3 core cable etc as required at site with burning hours >= 50000 Hours having system lumens 110 lm/watt, Industrial Type |
| 321 | 4 feet long batten 6000/6500k Light having extruded aluminium heat sink with anti-glare diffuser with energy efficient electronic driver CRI greater than 80 with minimum sytem lumens 2000 and maximum wattage 20 including connection with multistrand copper conductor 3 core cable etc as required at sitewith burning hours >= 50000 Hours having system lumens 110 lm/watt, Industrial Type |
| 322 | 2 feet long LED batten 6000/6500k Light having extruded aluminium heat sink with anti-glare diffuser with energy efficient electronic driver CRI greater than 80 with minimum sytem lumens 1000 and maximum wattage 15 including connection with multistrand copper conductor 3 core cable etc as required at site with burning hours >= 50000 Hours having system lumens 110 lm/watt, Industrial Type |
| 323 | 2'x2', 36-40W LED light fixture suitbale for ceiling recessed applications. The fixture has a power consumption of 36-40W and producing a system lumen output of minimum 3600 lumen. The fixture is designed for 50, 000 hrs of operational life Housing made of Metallic CRCA powder coated body Withstands 440Volt fast transit & Surge Protection 2KV. system Luminous efficieny 110 lm/ W, CRI> 80. The fixture has an operating voltage range 220-240V AC 50 Hz ,withstand 300Volt input for continuous operation & driver designed to withstand casing temperature of 85 degree C. |
| 324 | Providing and Fixing of 4x1 LED light panel with max 36-40 wattage 110 lm/watt, Industrial Type |
| 325 | Providing fixing well glass lights 30 Watt 6000/6500k having high pressure diecast aluminum housing with poly carbonate antiglare diffuser including connection complete as required at site. (Surface Type) |
| 326 | Providing & Fixing 20W Spot Light Al. Housing 110 lm/watt, Industrial Type Surface type |
| 327 | Dismantling and repair of led batten by way repairing/replacing led driver and refitting the same in position after cleaning. |
| 328 | P/f of Phenolic Laminated Sheet 3 mm thick. |
| 329 | P/f of fibers sheet of following thickness. |
| 330 | a) 6 mm |
| 331 | b) 8 mm |
| 332 | c) 12 mm |
| 333 | P/f of Acrylic milky sheets of following thickness. |
| 334 | a) 2 mm |
| 335 | b) 3 mm |
| 336 | Supply and Fixing including making of connections complete job of 3P Contactor AC1 160A, AC3 130A, 240/440Volt. |
| 337 | Supply and Fixing including making of connections complete job of Contactor AC1 165A, AC3 130A, 240/440Volt. |
| 338 | Providing and fixing following rating of Four pole onload front operated Changeover Switch in cubicle panel, making connections, Indoor Type etc. as required.. |
| 339 | 100 A |
| 340 | 160 A |
| 341 | 200 A |
| 342 | 250 A |
| 343 | 1000A |
| 344 | Providing and fixing following rating of Four pole onload front operated Changeover Switch in cubicle panel, making connections, Outdoor Type etc. IP-65, as required.. |
| 345 | 100 A |
| 346 | 160 A |
| 347 | 200 A |
| 348 | 250 A |
| 349 | 1000A |
| 350 | Providing and fixing of Spreader links for MCCB's |
| 351 | a) 4 links set for 125-200 A |
| 352 | c) 4 links set for 250A |
| 353 | d) 4 links set for 400A |
| 354 | d) 4 links set for 630A |
| 355 | P/F of MCB boxes (pvc) with strip |
| 356 | a) 2 way |
| 357 | b) 4 way |
| 358 | P/F of below mentioned Geyser accessories as per site requirements |
| 359 | a) P/f of connection pipes for Geysers of various sizes |
| 360 | b) Foundation nut bolts. |
| 361 | c) Geysers indicator. |
| 362 | c) Vocal copper tube. |
| 363 | d) Element copper glass. |
| 364 | e) Flange washer. |
| 365 | Replacement/Supplying and fixing of Geyser element 1500/2000 watts (power pack/prince/Theeta make) |
| 366 | a) Coil type (long) |
| 367 | b) Coil type (short) |
| 368 | c) Triangular type. |
| 369 | d) Round type. |
| 370 | e) Thermostat Geyser.(Long/short)(insertion type) |
| 371 | e) Thermostat Geyser.( Capillary type) |
| 372 | Replacement of Geyser element Coil type 2000 watts (for Venus Geysers) |
| 373 | Replacement of Geyser element Coil type 2000 watts (for Ferrolic geysers) |
| 374 | Replacement of Geyser element Coil type 2000 watts (for Havells geysers) |
| 375 | Replacement of Geyser element Coil type 3000 watts . |
| 376 | Replacement of Geyser element Coil type 6000 watts . |
| 377 | Servicing of Geyser by way of complete dismantling of all its accessories, removal of sludge / scale, thorough cleaning of all its parts, replacement of all worn-out/rusted/damaged Nuts/Bolts/Washers etc. and refixing of all parts of the geyser and making it operational. |
| 378 | i) without repair of Tank |
| 379 | ii) with repair of Tank |
| 380 | SITC of Electric Heater / Geyser of capacities as mentioned below with following parameters .1.Energy saving. 5 Star Certification by BEE 2. Provision of Temperature regulation by means of external Knob3. Power Rating:- 220/ 230V, 50 Hz, Single Phase. 4. Maximum Rated Pressure.= 8 bar 5. Installation Type Vertical / Horizontal mounted as per site requirement 6. Body Type:- Rust, water proof and Shock Proof outer body with attractive looks and corrosion resistant inner tank made of cold rolled steel ,resistant to hard water. 7. Element Type:- glass coated heating element to prevent from corrosion and hard water.8.Safety Valve maximum pressure =8 bar maximum9. Energy efficiency feature:- Should have high density PUF insulation for energy Saving10. Anti syphon system to prevent back flow of water. 11. Should have Indicating Lamps for ON & CUTT OFF.12. Conforming to :IS 2082:2018 , IS 302-1, IS 302-2-21 |
| 381 | a) 25 litre (2KW) |
| 382 | b) 35 litre (2KW) |
| 383 | c) 50 litre (2KW) |
| 384 | d) 100 litre (3KW) |
| 385 | a) Repairing of Blowers (heat Convectors) by way of changing internal wiring,screw, complete. |
| 386 | b) Wall mount Blowers Electronic Type by changing internal wiring and relays etc |
| 387 | i) P/f heating coil 3 way, 4 way, 5 way. |
| 388 | ii) P/f of motor complete |
| 389 | iii) P/f of thermostat blower |
| 390 | iv) P/f of knob |
| 391 | v) Blower Switch |
| 392 | vi) Blower Fan |
| 393 | Rewinding of fans |
| 394 | a) Wall mount fan 400 mm |
| 395 | b) Ceiling fan |
| 396 | i) 1200 mm |
| 397 | ii) 1400 mm |
| 398 | Rewinding of exhaust fans of various sizes. |
| 399 | a) 9” |
| 400 | b) 12” |
| 401 | c) 15” |
| 402 | d) 24” |
| 403 | Extra for fixing the louvers/ shutters complete with frame for a exhaust fan of all sizes. |
| 404 | Dismantling of ceiling fan and painting the same with with one or more coats of spray painting with synthetic enamel paint of approved brand and manufacture to give an even shade, including cleaning of surface with detergent and replacing the damaged rubber reel, nuts and bolts with washers and safety pins, reinstalling the same as required. |
| 405 | P/f of accessories for various types of fans. |
| 406 | a) Ball bearing set |
| 407 | b) Capacitor/condenser. |
| 408 | c) Top lead. |
| 409 | d) Rubber bush. |
| 410 | e) Resistance. |
| 411 | f) Blades for all types of fans. |
| 412 | g) Gear griller. |
| 413 | h) Switch plate of wall mount fan. |
| 414 | i) Nut bolts. |
| 415 | j) Ceiling fan rod. |
| 416 | k) Ceiling fan clip. |
| 417 | l) Wall mount fan cover net. |
| 418 | Supply and fixing of Round PVC / Plastic Plates for Ceiling Fans |
| 419 | i) 3\\" |
| 420 | ii) 6\\" |
| 421 | Supply installation testing and commissioning of following sizes of metallic type exhaust fans with Bird guard to protect fan in running condition, Double ball bearing with Heavy duty motor. |
| 422 | i) 9\\" |
| 423 | ii) 12\\" |
| 424 | iii) 15\\" |
| 425 | ii) 18\\" |
| 426 | iii) 24\\" |
| 427 | Supply installation testing and commissioning of following sizes of metallic type exhaust fans with Bird guard to protect fan in running condition, Double ball bearing with Heavy duty motor froce Turbo Industrial. |
| 428 | i) 9\\" |
| 429 | ii) 12\\" |
| 430 | iii) 15\\" |
| 431 | ii) 18\\" |
| 432 | iii) 24\\" |
| 433 | Supply installation testing and commissioning of following sizes of plastic body exhaust fans shutter type with Heavy duty motor Rated speed = 1400 RPM. Rate voltage -220 to 240 Volts . |
| 434 | i) 150 mm |
| 435 | ii) 200 mm |
| 436 | ii) 225 mm |
| 437 | iii) 250 mm |
| 438 | iv) 300 mm |
| 439 | Making of holes for installing of exhaust fans and P/F of wooden frames of play to play 8 mm various sizes. Complete with colour of wooden frame civil work in all respects. |
| 440 | i) 12” |
| 441 | ii) 15” |
| 442 | iii) 18” |
| 443 | iv) 24” |
| 444 | P/f of fan hooks of various types S type, U type, J type. |
| 445 | Supplying and making end termination with Aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required. |
| 446 | 6 sq. mm |
| 447 | 10 sq. mm |
| 448 | 16 sq. mm |
| 449 | 25 sq. mm |
| 450 | 35 sq. mm |
| 451 | 50 sq. mm |
| 452 | 70 sq. mm |
| 453 | 95 sq. mm |
| 454 | 120 sq. mm |
| 455 | 150 sq. mm |
| 456 | 185 sq. mm |
| 457 | 240 sq. mm |
| 458 | 300 sq. mm |
| 459 | 400 sq. mm |
| 460 | 500 sq. mm |
| 461 | 630 sq. mm |
| 462 | 800 sq. mm |
| 463 | 1000 sq. mm |
| 464 | Supplying and making end termination with Copper lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required. |
| 465 | 6 sq. mm |
| 466 | 10 sq. mm |
| 467 | 16 sq. mm |
| 468 | 25 sq. mm |
| 469 | 35 sq. mm |
| 470 | 50 sq. mm |
| 471 | 70 sq. mm |
| 472 | 95 sq. mm |
| 473 | 120 sq. mm |
| 474 | 150 sq. mm |
| 475 | 185 sq. mm |
| 476 | 240 sq. mm |
| 477 | 300 sq. mm |
| 478 | 400 sq. mm |
| 479 | 500 sq. mm |
| 480 | 630 sq. mm |
| 481 | 800 sq. mm |
| 482 | 1000 sq. mm |
| 483 | Providing / fixing of Box made out of Sheet Steel (26 SWG) of suitable size consisting of clamp for resting of the MCB with Pole Clamp; the box is to be fixed on Pole. |
| 484 | SITC of Wall mount fans 400 mm with Plastic Body as specified below: 1.Motor AC 2.Governing standard I.S.2997 (Latest) 3.Power Consumption: Approx. 100 Watts4.Power supply Single phase AC 230V, 50Hz 5.Speed: 1200 -1400 rpm with regulator 6.Sweep: 400mm 7.Air Flow: 72-80 m3/min. 8..motor protection through thermal9.overload protection device 10.It should have minimum 3 levels of speed control. Features:Suitable for mounting on walls with easy mounting system, Noise level shall be within limits adjustable upward and downward tilt mechanism |
| 485 | Supplying, Installation, Testing & Commissioning (SITC) of 450 mm sweep heavy-duty industrial wall fan, complete with the following specifications:Sweep: 450 mm (18 inch)Type: Heavy-duty industrial wall-mounted fanMotor: Single-phase, 230V, 50Hz, copper-wound motorSpeed: Minimum 1300 RPM (high air delivery type)Air Delivery: Not less than 100–120 CMMBody: Powder-coated metal body with aluminum bladesMounting: Heavy-duty wall bracket with clamp/bolt arrangementOscillation: Automatic oscillation with lock facilityRegulator: Electronic step/rotary regulator (5-step)Safety: Front & rear MS powder-coated guard. Features: Suitable for mounting on walls with an easy mounting system, Noise level shall be within limits, and an adjustable upward and downward tilt mechanism. |
| 486 | Supply, Installation, Testing and Commissioning of 1200 mm sweep,BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC)Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2nos. canopies, shackle kit, safety rope, copper winding, Power Factornot less than 0.9, Service Value (CM/M/\N) minimum 6.00,Air deliveryminimum 210 Cum/Min , 350 RPM (tolerance as per IS : 374-2019),THD less than 10%, remote or electronic regulator unit for speedcontrol and all remaining accessories including safety pin, nut bolts,washers, temperature rise=75 degree C (ma><.), insulation resistancemore than 2 mega ohm, suitable for 230 V, 50 Hz, single phase ACSupply, earthing etc. complete as required, including Fan Dimmer 150W |
| 487 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, Ceiling fan, Induction Type, Class of insulation: B, 3 Nos. Blades, 30 cm long down rod, 2 Nos. Canopies, Shackle kit, Safety rope, Copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 230 CMM, > 270 RPM (tolerance as per IS : 374-2019), THD less than 10% and all remaining accessories including safety pin, Nuts / Bolts, Washers, Temperature rise = 75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, Single Phase AC Supply, Earthing etc. complete as required. The Job includes providing, fixing and commissioning of the associated Fan Regulator. The Ceiling fans are to be provided with a 3 years' Warranty on Motor and 2 years' Warranty on other parts. |
| 488 | Installation testing & commissioning of fans copper wound heavy duty. |
| 489 | a) Wall mount fans 400/300 mm |
| 490 | b) Ceiling fans 1200 mm |
| 491 | c) Exhaust fans double ball bearing |
| 492 | i) 9” |
| 493 | ii) 12” |
| 494 | iii) 15” |
| 495 | iv) 18” |
| 496 | v) 24” |
| 497 | Supplying & fabrication of timber KD/Fir or Equivalent |
| 498 | Wireman |
| 499 | Cable jointer |
| 500 | Lineman |
| 501 | Fitter, Grade 1 |
| 502 | Fitter, Grade 2 |
| 503 | Painter |
| 504 | Khallasi |
| 505 | Carpenter, Grade 1 |
| 506 | Blacksmith, Grade 2 |
| 507 | Mason, Grade 2 |
| 508 | Stone Chiseler |
| 509 | Beldar/ coolie |
| 510 | Bhisti |
| 511 | Excavator |
| 512 | Stone Breaker |
| 513 | Engineer |
| 514 | Highly Skilled |
| 515 | Electrician |
| 516 | Electronic Technician |
| 517 | Technician |
| 518 | Software Engineer |
| 519 | Hire charges for 5 ton truck |
| 520 | Hire charges for compressor and spray gun |
| 521 | Drilling of 46 Nos 12 mm dia holes on G.I. pipe |
| 522 | Drilling holes |
| 523 | Solder jointing |
| 524 | Welding charges |
| 525 | Welder |
| 526 | Hire Charges for the Crane upto 20 Ton |
| 527 | Hire Charges for the Crane Above 20 Ton |
| 528 | Hire Charges for the Concrete Demolisher |
| 529 | Supply, installation, testing and commissioning of 12V, 40-45Ah Sealed Lead Acid Battery |
| 530 | Supply, installation, testing and commissioning of 12V, 70-75Ah Sealed Lead Acid Battery |
| 531 | Supply, installation, testing and commissioning of 12V, 100Ah Sealed Lead Acid Battery |
| 532 | Supply, installation, testing and commissioning of 12V, 120-130Ah Sealed Lead Acid Battery |
| 533 | Supply, installation, testing and commissioning of 12V, 150-170Ah Sealed Lead Acid Battery |
| 534 | Supply, installation, testing and commissioning of 12V, 180Ah Sealed Lead Acid Battery |
| 535 | Supply, installation, testing and commissioning of 12V, 200Ah Sealed Lead Acid Battery |
| 536 | Supply, installation, testing and commissioning of pure sine-wave, 1kVA, Inverter |
| 537 | Supply, installation, testing and commissioning of pure sine-wave, 2kVA, Inverter |
| 538 | Supply, fixing, testing and commissioning of Multistrand, Flexible, PVC-insulated, 1.1kV Copper Conductor, Heat-resistant, Flame-retardant, Cable of following sizes: |
| 539 | a) 25 sq. mm |
| 540 | a) 35 sq. mm |
| 541 | a) 50 sq. mm |
| 542 | b) 70 sq. mm |
| 543 | c) 95 sq. mm |
| 544 | d) 120 sq. mm |
| 545 | e) 150 sq. mm |
| 546 | f) 185 sq. mm |
| 547 | Supply, installation, testing and commissioning of Extension Cord fabricated out of wooden frame and Hylum Sheet of minimum thickness 2mm, consisting of 3 Nos 16A Switches, 2 Nos 15A/16A 3-Pin Sockets, 2 Nos 5A/6A 3-Pin Sockets Indication, Surge Protector. The Extension cord is to be provided with 2 Metres of 3 × 4 sq. mm wire (P + N + E) and fitted with a 16A-20A TOP. The Extension cord is to be approved from the site Engineer. |
| 548 | Supply, installation, testing and commissioning of Extension Cord fabricated out of wooden frame and Hylum Sheet of minimum thickness 2mm, consisting of 2 Nos 16A Switches, 1 No. 15A/16A 3-Pin Socket, 3 Nos 5A/6A 3-Pin Sockets, Indication, Surge Protector. The Extension cord is to be provided with 2 Metres of 3 × 2.5 sq. mm wire (P + N + E) and fitted with a 16A TOP. The Extension cord is to be approved from the site Engineer. |
| 549 | Supply, installation, testing and commissioning of Extension Cord fabricated out of wooden frame and Hylum Sheet of minimum thickness 2mm, consisting of 1 No. 16A Switch, 3 Nos 5A/6A 3-Pin Sockets, Indication, Surge Protector. The Extension cord is to be provided with 2 Metres of 3 × 2.5 sq. mm wire (P + N + E) and fitted with a 5A/6A TOP. The Extension cord is to be approved from the site Engineer. |
| 550 | Supply of 8 inch, Combination Pliers, Double Color Sleeve, Anti-Rust Protected, Jaws and cutting Edge are Induction Hardened and Tempered- Black-Phosphate Finish, Material: C45, Full Body Hardened. The same is to be approved from the site Engineer. |
| 551 | Supply of 5 in. Miniature Basic Bent Nose Pliers, Double dip handles for comfort, Nickel chromed for durability, Small sized for precision work. The same is to be approved from the site Engineer. |
| 552 | Supply of 6\\"-8\\" Wire Stripper(Cutter). The same is to be approved from the site Engineer. |
| 553 | Supply of Rechargeable LED Light, 15W-30W, Multi-Functional Long Range Handheld Light with Powerful Beam and Emergency Mode, Durable Body, providing a backup time of min 4 Hours, charging time of 5-7 Hours, with Inbuilt Battery. The same is to be approved from the site Engineer. |
| 554 | Supply of Flat Head 8 mm Screwdriver having Rod length 8 inches. The same is to be approved from the site Engineer. |
| 555 | Supply of 100-500V Spark Detecting Tester Screwdriver having Insulating plastic handle for complete safety, Sheathed chrome vanadium steel blade for safety and long product life. The same is to be approved from the site Engineer. |
| 556 | Supply of 12-Piece Combination Spanner Set with 6mm to 22mm, Chrome-Vanadium Steel, Anti-Slip Design on Open End, Anti-Rust, Matt Finish, Silver. The same is to be approved from the site Engineer. |
| 557 | Supply of Digital Multifunction Clamp Meter, 3¾ digits AC/DC Clamp meter with a backlight and an LCD display. The jaw opening shall be 60mm approx and should be able to measure AC/DC up to 1000A. It should also be able to measure DC voltage up to 1000V, AC voltage up to 700V, resistance up to 40 MΩ, frequency up to 10 MHz with Duty cycle, continuity & diode measurements, Auto power off for battery life saving. The same is to be approved from the site Engineer. |
| 558 | Supply of Insulation Resistance Meter having Ultra-large LCD display, featuring digitalized insulation test with an analog bar graph, Preset test voltage: 250 V, 500 V, 1000 V, 2500 V; having Adjustable testing voltage: 250 V to 2500 V with step of 100 V Polarity index (PI), Dielectric absorption ratio (DAR), Automatic power-off for battery life saving, Breakdown voltage indicator, USB interface used to download measurement data, should be able to automatically calculate Dielectric Discharge (DD). The same is to be approved from the site Engineer. |
| 559 | Supply of 13 mm Hammer Drill, 700-1200 Watt powerful motor for higher working efficiency and longer durability, High performance motor delivering 0-2,900 rpm & impact rate 0-49,300; Adjustable variable speed dial control with forward and reverse mode to suit different materials, with a durable metal gear housing for a long life. The same is to be approved from the site Engineer. |
| 560 | Supply of Hydraulic Hose Crimping Tool, 30-40 Ton Pressure, Hexagonal Crimping Tool With CP-700 Manual Hydraulic Pump, with 50, 70, 95, 120, 150, 185, 240, 300, 400, 500, 630 mm Dies for Crimping Copper & Aluminium Terminal Cable Lugs, Equipped with an oil-seal mechanism for enhanced durability and smooth operation under high pressure, Manual Heavy Duty HYdraulic Crimping Tool, designed for industrial use. The same is to be approved from the site Engineer. |
| 561 | Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32 A 240 V \\"C\\" curve DP MCB complete with connections, testinq and commissioninq etc. as required. |
| 562 | Supplying and fixing TP sheet steel enclosure on surface/ recess along with 16/25/32 A 415 V \\"C\\" curve TP MCB complete with connections, testing and commissioning etc. as required. |
| 563 | Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet,with 2 pole and earth, metal enclosed plug top alongwith 20 A \\"C\\"curve, SP, MCB, in sheet steel enclosure, on surface or in recess,with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. |
| 564 | Supplying and fixing 20 A, 415 V, TPN Industrial type socket outlet,with 4 pole and earth, metal enclosed plug top alongwith 20 A \\"C\\" curve, TPMCB, in sheet steel enclosure, on surface or in recess,with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. |
| 565 | Supplying and fixing 30 A, 415 V, TPN Industrial type socket outlet,with 4 pole and earth, metal enclosed plug top alongwith 30 A \\"C\\"curve, TPMCB, in sheet steel enclosure, on surface or in recess,with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. |
| 566 | Providing and fixing M.V. danger notice plate of 200 mm X 150 mm,made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required. |
| 567 | Providing and fixing H.T. danger notice plate of 250 mm X 200 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required. |
| 568 | Supplying and fixing Cable End Box (Loose Wire Box) suitable for following single pole and neutral, sheet steel, MCB distribution board, 240 Volts, on surface/ recess, complete with testing and commissioning |
| 569 | Supplying and fixing Cable End Box (Loose Wire Box) suitable for triple pole and neutral, sheet steel, Vertical MCB distribution board, 415 Volts, on surface/ recess, complete with testing and commissioning etc. as required. |
| 570 | For 6 way, Double door SPN MCBDB For 8 way, Double door SPN MCBDB For 10 way, Double door SPN MCBDB For 14 way, Double door SPN MCBDB |
| 571 | Supplying and fixing Cable End Box (Loose Wire Box) suitable for following triple pole and neutral, sheet steel, MCB distribution board, |
| 572 | 415 Volts, on surface/ recess, complete with testing and commissioning etc.as required. |
| 573 | For 4 way, Double door TPN MCBDB |
| 574 | For 6 way, Double door TPN MCBDB |
| 575 | For 8 way, Double door TPN MCBDB |
| 576 | Supplying, installing on wall, testing and commissioning of following capacity rising mains made of 1.6mm thick IP 42 sheet steel enclosure duly painted with powder coating, wall straps, fully PVC insulated 4 Nos aluminium bus bars having current density of 130 A/ sq cm at nominal current rating in convenient sections and suitable for 415 V, 3 phase, 4 wire, 50 Hz, A.C. supply with extension joints, fire proof barriers, expansion joints, thrust pads including jointing and earthing with 2 runs of galvanised iron strips etc. as required. (Rising mains confirming to IS8623. TEC 439) |
| 577 | 200 A (S.C. rating for 1 sec - 15 kA) |
| 578 | 300 A (S.C. rating for 1 sec - 20 kA) |
| 579 | 400 A (S.C. rating for 1 sec - 25 kA) |
| 580 | 600 A (S.C. rating for 1 sec - 45 kA) |
| 581 | 800 A (S.C. rating for 1 sec - 50 kA) |
| 582 | Supplying, installing, testing and commissioning of following capacity TPN tap off box made of 1.6mm thick sheet steel enclosure duly painted with powder coating on existing rising mains complete with TP disconnector FSU and HRC fuses, connections, earthing etc. as required. |
| 583 | 16 A TPN |
| 584 | 32 A TPN |
| 585 | 63 A TPN |
| 586 | 100 A TPN |
| 587 | 200A TPN |
| 588 | 315 A TPN |
| 589 | 400 A TPN |
| 590 | Supplying, installing, testing and commissioning of following capacity TP distribution tap off box made of 1.6mm thick sheet steel enclosure duly painted with powder coating on existing rising mains complete with HRC fuses, interconnections, earthing etc. as required. |
| 591 | 16 A TPN, 2 way |
| 592 | 16 A TPN, 4 way |
| 593 | 16 A TPN, 6 way |
| 594 | 16 A TPN, 8 way |
| 595 | 32 A TPN, 2 way |
| 596 | 32 A TPN, 4 way |
| 597 | 32 A TPN, 6 way |
| 598 | 32 A TPN, 8 way |
| 599 | 63 A TPN, 2 way |
| 600 | 63 A TPN, 4 way |
| 601 | 63 A TPN, 6 way |
| 602 | 63 A TPN, 8 way |
| 603 | Supplying, installing, testing and commissioning of following capacity End Feed Unit made of 1.6mm thick sheet steel enclosure duly painted with powder coating to existing rising mains complete with TPN disconnector FSU and HR fuses, mounting stands, cable end box, brass compression gland, connections, earthing etc. as required. |
| 604 | 200 A TPN |
| 605 | 300 A TPN |
| 606 | 400 A TPN |
| 607 | 600 A TPN |
| 608 | 800 A TPN |
| 609 | Supplying, installation, including suspension, testing and commissioning of following capacity bus trunking with aluminium bus bars having current density of 130 A/ sq cm at nominal current rating in 1.6mm thick IP 42 sheet steel enclosure in convenient sections for use on, 3 phase, 4 wire, 415 V, 50 Hz, A.C. supply including jointing of sections, flexible joints, expansion joints, bends and earthing with 2 runs of galvanised iron strips, suspenders, angle iron bracket, steel fasteners, connecting to earthing system etc. as required. |
| 610 | 800 A |
| 611 | 1000 A |
| 612 | 1250 A |
| 613 | 1400 A |
| 614 | 1600 A |
| 615 | Supplying, installation, testing and commissioning of following capacity overhead distribution bus trunking with aluminium bus bars having current density of 130 A/ sq cm at nominal current rating in 1.6mm thick IP 42 sheet steel enclosure in convenient sections with provision of tapping points for use on, 3 phase, 4 wire, 415 volts, 50 Hz, A.C. supply including jointing of sections, bends, earthing with 2 runs of galvanised iron strips, all installation accessories etc. as required. |
| 616 | 200 A |
| 617 | 400 A |
| 618 | Supplying, installing, testing and commissioning of following capacity TP tap off box / plug-in box made of 1.6mm thick sheet steel enclosure duly painted with powder coating on existing overhead bus bar system complete with TP disconnector FSU and HRC fuses, connections, earthing etc. as required. |
| 619 | 100 A |
| 620 | Supplying, installing on wall, testing and commissioning of following capacity Air Insulated Compact Type Rising Mains for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply with enclosure having IP-54 rating after fixing the tap off boxes and all accessories, made of 1.6mm thick steel sheet duly powder coated in convenient sections complete with 4 Nos aluminium bus bars having current density of 130 A/ sq cm at nominal current rating, necessary joints & expansion joints, fire barrier at each floor, provision of tapping at every metre, continuous earthing with 2 Nos aluminium strip of suitable size (one on each side) including, G.I. clamping brackets, angle iron bracket, steel fasteners, connecting to earthing system etc. as required. |
| 621 | 200 A. Isc = 15kA for 1 second |
| 622 | 315 A, Isc = 25kA for 1 second |
| 623 | 400 A, Isc = 30kA for 1 second |
| 624 | 500 A, Is = 35kA for 1 second |
| 625 | 630 A, Is = 50kA for 1 second |
| 626 | 800 A. Isc = 50kA for 1 second |
| 627 | 1000 A, Isc = 50kA for 1 second |
| 628 | 1250 A, Is = 50kA for 1 second |
| 629 | Supplying, installing on wall or suspension on ceiling, testing and commissioning of following capacity Air Insulated Compact Type Bus Trunking for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply with metal clad enclosure having IP-54 rating after fixing the tap off boxes and all accessories, made of 1.6mm thick steel sheet duly powder coated in convenient sections complete with 4 Nos aluminium bus bars having current density of 130 A/ sq cm at nominal current rating, necessary joints, elbow joints & expansion joints, fire barrier at each floor, continuous earthing with 2 Nos aluminium strip of suitable size (one on each side) including, G.I. clamping brackets, suspenders, angle iron bracket, steel fasteners, connecting to earthing system etc.as required. |
| 630 | 200 A, Isc = 15kA for 1 second |
| 631 | 315 A, Isc = 25kA for 1 second |
| 632 | 400 A, Is = 30kA for 1 second |
| 633 | 500 A, Is = 35kA for 1 second |
| 634 | 630 A, Is = 50kA for 1 second |
| 635 | 800 A, Is = 50kA for 1 second |
| 636 | 1000 A, Is = 50kA for 1 second |
| 637 | 1250 A, Is = 50kA for 1 second |
| 638 | Supplying, installation, testing & commisioning of following capacity End Feed Unit for the existing Air Insulated Compact Type bus trunking/ rising mains for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply made with 1.6mm thick steel sheet enclosure (IP54) duly powder coated with provision of MCCB/ACB (but without MCCB/ACB) complete with necessary joints including clamping brackets, angle iron bracket, steel fasteners, connecting to earthing system etc. as required |
| 639 | 200 A, lsc= 15kA for 1 sec |
| 640 | 315 A, lsc= 25kA for 1 sec |
| 641 | 400 A, lsc= 30kA for 1 sec |
| 642 | 500 A, lsc= 35kA for 1 sec |
| 643 | 630 A, lsc= 50kA for 1 sec |
| 644 | 800 A, lsc= 50kA for 1 sec |
| 645 | 1000 A, lsc= 50kA for 1 sec |
| 646 | 1250 A, lsc= 50kA for 1 sec |
| 647 | Supplying, installation, testing & commisioning of following capacity Plug lnl tap off box on the existing Air Insulated Compact Type bus trunkingl rising mains for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply made with 1.6mm thick sheet steel enclosure (IP54) duly powder coated with provision of MCCB/ACB (but without MCCB/ACB) complete etc. as required |
| 648 | 125 A, lsc= 15kA for 1 sec |
| 649 | 200 A, lsc= 25kA for 1 sec |
| 650 | 250 A, lsc= 30kA for 1 sec |
| 651 | 400 A, lsc= 35kA for 1 sec |
| 652 | 500 A, lsc= 50kA for 1 sec |
| 653 | 630 A, lsc= 50kA for 1 sec |
| 654 | Supplying, installing by suspension on ceiling, testing and commissioning of following capacity Sandwich Type Rising Mains for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply with metal clad enclosure having IP-54 rating after fixing the tap off boxes and all accessories, made of 1.6mm thick steel sheet duly powder coated in convenient sections complete with 4 Nos aluminium bus bars having current density of 130 Al sq cm at nominal current rating, necessary joints, elbow joints & expansion joints and bends, fire barrier at each floor, provision of tapping at every metre, adopter box and copper flexible for joints, continuous earthing with 2 Nos aluminium strip of suitable size (one on each side) including, G.l. clamping brackets, suspenders, angle iron bracket, steel fasteners, connecting to earthing system etc. as required |
| 655 | 400 A, lsc= 25kA for 1 sec |
| 656 | 500 A, lsc= 30kA for 1 sec |
| 657 | 630 A, lsc= 50kA for 1 sec |
| 658 | 800 A, lsc= 50kA for 1 sec |
| 659 | 1000 A, lsc= 50kA for 1 sec |
| 660 | 1250 A, lsc= 50kA for 1 sec |
| 661 | 1600 A, lsc= 50kA for 1 sec |
| 662 | 2000 A, lsc= 50kA for 1 sec |
| 663 | 2500 A, lsc= 50kA for 1 sec |
| 664 | 3200 A, lsc= 50kA for 1 sec |
| 665 | 4000 A, lsc= 50kA for 1 sec |
| 666 | Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. |
| 667 | 100 mm width X 50 mm depth X 1.6 mm thickness |
| 668 | 150 mm width X 50 mm depth X 1.6 mm thickness |
| 669 | 200 mm width X 50 mm depth X 1.6 mm thickness |
| 670 | 300 mm width X 50 mm depth X 1.6 mm thickness |
| 671 | 375 mm width X 50 mm depth X 2.0 mm thickness |
| 672 | 450 mm width X 50 mm depth X 2.0 mm thickness |
| 673 | 600 mm width X 50 mm depth X 2.0 mm thickness |
| 674 | 300 mm width X 62.5 mm depth X 2.0 mm thickness |
| 675 | 375 mm width X 62.5 mm depth X 2.0 mm thickness |
| 676 | 450 mm width X 62.5 mm depth X 2.0 mm thickness |
| 677 | 600 mm width X 62.5 mm depth X 2.0 mm thickness |
| 678 | 750 mm width X 62.5 mm depth X 2.0 mm thickness |
| 679 | 900 mm width X 62.5 mm depth X 2.0 mm thickness |
| 680 | 600 mm width X 75 mm depth X 2.0 mm thickness |
| 681 | 750 mm width X 75 mm depth X 2.0 mm thickness |
| 682 | 900 mm width X 75 mm depth X 2.0 mm thickness |
| 683 | Supplying and installing following size of perforated painted with powder coating M.S. cable trays bends with perforation not more than 17.5%,, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. |
| 684 | 100 mm width X 50 mm depth X 1.6 mm thickness |
| 685 | 150 mm width X 50 mm depth X 1.6 mm thickness |
| 686 | 200 mm width X 50 mm depth X 1.6 mm thickness |
| 687 | 300 mm width X 50 mm depth X 1.6 mm thickness |
| 688 | 375 mm width X 50 mm depth X 2.0 mm thickness |
| 689 | 450 mm width X 50 mm depth X 2.0 mm thickness |
| 690 | 600 mm width X 50 mm depth X 2.0 mm thickness |
| 691 | 300 mm width X 62.5 mm depth X 2.0 mm thickness |
| 692 | 375 mm width X 62.5 mm depth X 2.0 mm thickness |
| 693 | 450 mm width X 62.5 mm depth X 2.0 mm thickness |
| 694 | 600 mm width X 62.5 mm depth X 2.0 mm thickness |
| 695 | 750 mm width X 62.5 mm depth X 2.0 mm thickness |
| 696 | 900 mm width X 62.5 mm depth X 2.0 mm thickness |
| 697 | 600 mm width X 75 mm depth X 2.0 mm thickness |
| 698 | 750 mm width X 75 mm depth X 2.0 mm thickness |
| 699 | 900 mm width X 75 mm depth X 2.0 mm thickness |
| 700 | Supplying and installing following size of perforated painted with powder coating M.S. cable trays Tee with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S.suspenders including bolts & nuts, painting suspenders reauired.etc as |
| 701 | 100 mm width X 50 mm depth X 1.6 mm thickness |
| 702 | 150 mm width X 50 mm depth X 1.6 mm thickness |
| 703 | 225 mm width X 50 mm depth X 1.6 mm thickness |
| 704 | 300 mm width X 50 mm depth X 1.6 mm thickness |
| 705 | 375 mm width X 50 mm depth X 2.0 mm thickness |
| 706 | 450 mm width X 50 mm depth X 2.0 mm thickness |
| 707 | 600 mm width X 50 mm depth X 2.0 mm thickness |
| 708 | 300 mm width X 62.5 mm depth X 2.0 mm thickness |
| 709 | 375 mm width X 62.5 mm depth X 2.0 mm thickness |
| 710 | 450 mm width X 62.5 mm depth X 2.0 mm thickness |
| 711 | 600 mm width X 62.5 mm depth X 2.0 mm thickness |
| 712 | 750 mm width X 62.5 mm depth X 2.0 mm thickness |
| 713 | 900 mm width X 62.5 mm depth X 2.0 mm thickness |
| 714 | 600 mm width X 75 mm depth X 2.0 mm thickness |
| 715 | 750 mm width X 75 mm depth X 2.0 mm thickness |
| 716 | 900 mm width X 75 mm depth X 2.0 mm thickness |
| 717 | Supplying and installing following size of perforated painted with powder coating M.S. cable trays Cross Member with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & suspenders etc as required.nuts,painting |
| 718 | 100 mm width X 50 mm depth X 1.6 mm thickness |
| 719 | 150 mm width X 50 mm depth X 1.6 mm thickness |
| 720 | 225 mm width X 50 mm depth X 1.6 mm thickness |
| 721 | 300 mm width X 50 mm depth X 1.6 mm thickness |
| 722 | 375 mm width X 50 mm depth X 2.0 mm thickness |
| 723 | 450 mm width X 50 mm depth X 2.0 mm thickness |
| 724 | 600 mm width X 50 mm depth X 2.0 mm thickness |
| 725 | 300 mm width X 62.5 mm depth X 2.0 mm thickness |
| 726 | 375 mm width X 62.5 mm depth X 2.0 mm thickness |
| 727 | 450 mm width X 62.5 mm depth X 2.0 mm thickness |
| 728 | 600 mm width X 62.5 mm depth X 2.0 mm thickness |
| 729 | 750 mm width X 62.5 mm depth X 2.0 mm thickness |
| 730 | 900 mm width X 62.5 mm depth X 2.0 mm thickness |
| 731 | 600 mm width X 75 mm depth X 2.0 mm thickness |
| 732 | 750 mm width X 75 mm depth X 2.0 mm thickness |
| 733 | 900 mm width X 75 mm depth X 2.0 mm thickness |
| 734 | Supplying and installing following size of perforated painted with powder coating M.S. cable trays Tee with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. |
| 735 | 100 mm width X 50 mm depth X 1.6 mm thickness |
| 736 | 150 mm width X 50 mm depth X 1.6 mm thickness |
| 737 | 225 mm width X 50 mm depth X 1.6 mm thickness |
| 738 | 300 mm width X 50 mm depth X 1.6 mm thickness |
| 739 | 375 mm width X 50 mm depth X 2.0 mm thickness |
| 740 | 450 mm width X 50 mm depth X 2.0 mm thickness |
| 741 | 600 mm width X 50 mm depth X 2.0 mm thickness |
| 742 | 300 mm width X 62.5 mm depth X 2.0 mm thickness |
| 743 | 375 mm width X 62.5 mm depth X 2.0 mm thickness |
| 744 | 450 mm width X 62.5 mm depth X 2.0 mm thickness |
| 745 | 600 mm width X 62.5 mm depth X 2.0 mm thickness |
| 746 | 750 mm width X 62.5 mm depth X 2.0 mm thickness |
| 747 | 900 mm width X 62.5 mm depth X 2.0 mm thickness |
| 748 | 600 mm width X 75 mm depth X 2.0 mm thickness |
| 749 | 750 mm width X 75 mm depth X 2.0 mm thickness |
| 750 | 900 mm width X 75 mm depth X 2.0 mm thickness |
| 751 | Supplying and installing following size of perforated painted with powder coating M.S. cable trays Cross Member with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. |
| 752 | 100 mm width X 50 mm depth X 1.6 mm thickness |
| 753 | 150 mm width X 50 mm depth X 1.6 mm thickness |
| 754 | 225 mm width X 50 mm depth X 1.6 mm thickness |
| 755 | 300 mm width X 50 mm depth X 1.6 mm thickness |
| 756 | 375 mm width X 50 mm depth X 2.0 mm thickness |
| 757 | 450 mm width X 50 mm depth X 2.0 mm thickness |
| 758 | 600 mm width X 50 mm depth X 2.0 mm thickness |
| 759 | 300 mm width X 62.5 mm depth X 2.0 mm thickness |
| 760 | 375 mm width X 62.5 mm depth X 2.0 mm thickness |
| 761 | 450 mm width X 62.5 mm depth X 2.0 mm thickness |
| 762 | 600 mm width X 62.5 mm depth X 2.0 mm thickness |
| 763 | 750 mm width X 62.5 mm depth X 2.0 mm thickness |
| 764 | 900 mm width X 62.5 mm depth X 2.0 mm thickness |
| 765 | 600 mm width X 75 mm depth X 2.0 mm thickness |
| 766 | 750 mm width X 75 mm depth X 2.0 mm thickness |
| 767 | 900 mm width X 75 mm depth X 2.0 mm thickness |
| 768 | Supplying and installing following size of perforated painted with powder coating M.S. cable trays Reducer with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. |
| 769 | 100 mm width X 50 mm depth X 1.6 mm thickness |
| 770 | 150 mm width X 50 mm depth X 1.6 mm thickness |
| 771 | 225 mm width X 50 mm depth X 1.6 mm thickness |
| 772 | 300 mm width X 50 mm depth X 1.6 mm thickness |
| 773 | 375 mm width X 50 mm depth X 2.0 mm thickness |
| 774 | 450 mm width X 50 mm depth X 2.0 mm thickness |
| 775 | 600 mm width X 50 mm depth X 2.0 mm thickness |
| 776 | 300 mm width X 62.5 mm depth X 2.0 mm thickness |
| 777 | 375 mm width X 62.5 mm depth X 2.0 mm thickness |
| 778 | 450 mm width X 62.5 mm depth X 2.0 mm thickness |
| 779 | 600 mm width X 62.5 mm depth X 2.0 mm thickness |
| 780 | 750 mm width X 62.5 mm depth X 2.0 mm thickness |
| 781 | 900 mm width X 62.5 mm depth X 2.0 mm thickness |
| 782 | 600 mm width X 75 mm depth X 2.0 mm thickness |
| 783 | 750 mm width X 75 mm depth X 2.0 mm thickness |
| 784 | 900 mm width X 75 mm depth X 2.0 mm thickness |
| 785 | Hot Dipped Galvanized Iron Cable Tray |
| 786 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.l. suspenders including G.l. bolts&nuts, etc. as required. |
| 787 | 100 mm width X 50 mm depth X 1.6 mm thickness |
| 788 | 150 mm width X 50 mm depth X 1.6 mm thickness |
| 789 | 225 mm width X 50 mm depth X 1.6 mm thickness |
| 790 | 300 mm width X 50 mm depth X 1.6 mm thickness |
| 791 | 375 mm width X 50 mm depth X 2.0 mm thickness |
| 792 | 450 mm width X 50 mm depth X 2.0 mm thickness |
| 793 | 600 mm width X 50 mm depth X 2.0 mm thickness |
| 794 | 300 mm width X 62.5 mm depth X 2.0 mm thickness |
| 795 | 375 mm width X 62.5 mm depth X 2.0 mm thickness |
| 796 | 450 mm width X 62.5 mm depth X 2.0 mm thickness |
| 797 | 600 mm width X 62.5 mm depth X 2.0 mm thickness |
| 798 | 750 mm width X 62.5 mm depth X 2.0 mm thickness |
| 799 | 900 mm width X 62.5 mm depth X 2.0 mm thickness |
| 800 | 600 mm width X 75 mm depth X 2.0 mm thickness |
| 801 | 750 mm width X 75 mm depth X 2.0 mm thickness |
| 802 | 900 mm width X 75 mm depth X 2.0 mm thickness |
| 803 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray bends (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.l. suspenders including G.l. bolts&nuts, etc. as required. |
| 804 | 100 mm width X 50 mm depth X 1.6 mm thickness |
| 805 | 150 mm width X 50 mm depth X 1.6 mm thickness |
| 806 | 225 mm width X 50 mm depth X 1.6 mm thickness |
| 807 | 300 mm width X 50 mm depth X 1.6 mm thickness |
| 808 | 375 mm width X 50 mm depth X 2.0 mm thickness |
| 809 | 450 mm width X 50 mm depth X 2.0 mm thickness |
| 810 | 600 mm width X 50 mm depth X 2.0 mm thickness |
| 811 | 300 mm width X 62.5 mm depth X 2.0 mm thickness |
| 812 | 375 mm width X 62.5 mm depth X 2.0 mm thickness |
| 813 | 450 mm width X 62.5 mm depth X 2.0 mm thickness |
| 814 | 600 mm width X 62.5 mm depth X 2.0 mm thickness |
| 815 | 750 mm width X 62.5 mm depth X 2.0 mm thickness |
| 816 | 900 mm width X 62.5 mm depth X 2.0 mm thickness |
| 817 | 600 mm width X 75 mm depth X 2.0 mm thickness |
| 818 | 750 mm width X 75 mm depth X 2.0 mm thickness |
| 819 | 900 mm width X 75 mm depth X 2.0 mm thickness |
| 820 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \\"Tee\\" (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.l. suspenders including G.l. bolts&nuts, etc. as required. |
| 821 | 100 mm width X 50 mm depth X 1.6 mm thickness |
| 822 | 150 mm width X 50 mm depth X 1.6 mm thickness |
| 823 | 225 mm width X 50 mm depth X 1.6 mm thickness |
| 824 | 300 mm width X 50 mm depth X 1.6 mm thickness |
| 825 | 375 mm width X 50 mm depth X 2.0 mm thickness |
| 826 | 450 mm width X 50 mm depth X 2.0 mm thickness |
| 827 | 600 mm width X 50 mm depth X 2.0 mm thickness |
| 828 | 300 mm width X 62.5 mm depth X 2.0 mm thickness |
| 829 | 375 mm width X 62.5 mm depth X 2.0 mm thickness |
| 830 | 450 mm width X 62.5 mm depth X 2.0 mm thickness |
| 831 | 600 mm width X 62.5 mm depth X 2.0 mm thickness |
| 832 | 750 mm width X 62.5 mm depth X 2.0 mm thickness |
| 833 | 900 mm width X 62.5 mm depth X 2.0 mm thickness |
| 834 | 600 mm width X 75 mm depth X 2.0 mm thickness |
| 835 | 750 mm width X 75 mm depth X 2.0 mm thickness |
| 836 | 900 mm width X 75 mm depth X 2.0 mm thickness |
| 837 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \\"Cross member\\" (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.l. suspenders including G.l. bolts&nuts, etc. as required. |
| 838 | 100 mm width X 50 mm depth X 1.6 mm thickness |
| 839 | 150 mm width X 50 mm depth X 1.6 mm thickness |
| 840 | 225 mm width X 50 mm depth X 1.6 mm thickness |
| 841 | 300 mm width X 50 mm depth X 1.6 mm thickness |
| 842 | 375 mm width X 50 mm depth X 2.0 mm thickness |
| 843 | 450 mm width X 50 mm depth X 2.0 mm thickness |
| 844 | 600 mm width X 50 mm depth X 2.0 mm thickness |
| 845 | 300 mm width X 62.5 mm depth X 2.0 mm thickness |
| 846 | 375 mm width X 62.5 mm depth X 2.0 mm thickness |
| 847 | 450 mm width X 62.5 mm depth X 2.0 mm thickness |
| 848 | 600 mm width X 62.5 mm depth X 2.0 mm thickness |
| 849 | 750 mm width X 62.5 mm depth X 2.0 mm thickness |
| 850 | 900 mm width X 62.5 mm depth X 2.0 mm thickness |
| 851 | 600 mm width X 75 mm depth X 2.0 mm thickness |
| 852 | 750 mm width X 75 mm depth X 2.0 mm thickness |
| 853 | 900 mm width X 75 mm depth X 2.0 mm thickness |
| 854 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \\"Reducer\\" (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.l. suspenders including G.l. bolts&nuts, etc. as required. |
| 855 | 100 mm width X 50 mm depth X 1.6 mm thickness |
| 856 | 150 mm width X 50 mm depth X 1.6 mm thickness |
| 857 | 225 mm width X 50 mm depth X 1.6 mm thickness |
| 858 | 300 mm width X 50 mm depth X 1.6 mm thickness |
| 859 | 375 mm width X 50 mm depth X 2.0 mm thickness |
| 860 | 450 mm width X 50 mm depth X 2.0 mm thickness |
| 861 | 600 mm width X 50 mm depth X 2.0 mm thickness |
| 862 | 300 mm width X 62.5 mm depth X 2.0 mm thickness |
| 863 | 375 mm width X 62.5 mm depth X 2.0 mm thickness |
| 864 | 450 mm width X 62.5 mm depth X 2.0 mm thickness |
| 865 | 600 mm width X 62.5 mm depth X 2.0 mm thickness |
| 866 | 750 mm width X 62.5 mm depth X 2.0 mm thickness |
| 867 | 900 mm width X 62.5 mm depth X 2.0 mm thickness |
| 868 | 600 mm width X 75 mm depth X 2.0 mm thickness |
| 869 | 750 mm width X 75 mm depth X 2.0 mm thickness |
| 870 | 900 mm width X 75 mm depth X 2.0 mm thickness |
| 871 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. |
| 872 | Upto 35 sq. mm |
| 873 | Above 35 sq. mm and upto 95 sq. mm |
| 874 | Above 95 sq. mm and upto 185 sq. mm |
| 875 | Above 185 sq. mm and upto 400 sq. mm |
| 876 | Above 401 sq. mm and above |
| 877 | Laying of one number additional PVC insulated and PVC sheathed IXLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc as required. |
| 878 | Upto 35 sq. mm |
| 879 | Above 35 sq. mm and upto 95 sq. mm |
| 880 | Above 95 sq. mm and upto 185 sq. mm |
| 881 | Above 185 sq. mm and upto 400 sq. mm |
| 882 | Above 401 sq. mm and above |
| 883 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering. |
| 884 | Upto 35 sq. mm |
| 885 | Above 35 sq. mm and upto 95 sq. mm |
| 886 | Above 95 sq. mm and upto185 sq. mm |
| 887 | Above 185 sq. mm and upto 400 sq. mm |
| 888 | Above 401 sq. mm and above |
| 889 | Laying of one number additional PVC insulated and PVC sheathed IXLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering. |
| 890 | Upto 35 sq. mm |
| 891 | Above 35 sq. mm and upto 95 sq. mm |
| 892 | Above 95 sq. mm and upto185 sq. mm |
| 893 | Above 185 sq. mm and upto 400 sq. mm |
| 894 | Above 401 sq. mm and above |
| 895 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/HUME/ METAL pipe as required. |
| 896 | Upto 35 sq. mm |
| 897 | Above 35 sq. mm and upto 95 sq. mm |
| 898 | Above 95 sq. mm and upto 185 sq. mm |
| 899 | Above 185 sq. mm and upto 400 sq. mm |
| 900 | Above 401 sq. mm and above |
| 901 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required. |
| 902 | Upto 35 sq. mm |
| 903 | Above 35 sq. mm and upto 95 sq. mm |
| 904 | Above 95 sq. mm and upto 185 sq. mm |
| 905 | Above 185 sq. mm and upto 400 sq. mm |
| 906 | Above 401 sq. mm and above |
| 907 | Laying and fixing of one number PVC insulated and PVC sheathed /XLPE power cable of 1.1 KV grade of following size on wall surface as required. |
| 908 | Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 909 | Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp) |
| 910 | Above 95 sq. mm and upto 185 sq. mm (clamped with 25/4Ox3mm MS flat clamp) |
| 911 | Above 185 sq. mm and upto 400 sq. mm (clamped with 4Ox3mm MS flat clamp) |
| 912 | Above 401 sq. mm and above |
| 913 | Laying and fixing of one number PVC insulated and PVC sheathed I XLPE power cable of 1.1 KV grade of following size on cable tray as required. |
| 914 | Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 915 | Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp) |
| 916 | Above 95 sq. mm and upto 185 sq. mm (clamped with 25/4Ox3mm MS flat clamp) |
| 917 | Above 185 sq. mm and upto 400 sq. mm (clamped with 4Ox3mm MS flat clamp) |
| 918 | Above 401 sq. mm and above |
| 919 | Disconnecting and extraction of following sizes existing LT 3.5 core cables PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade from existing masonry open duct, cable tray /cable hungers as required. segregation on site transportion to site /location within skims premises including cost of roll and cable staking at designated place, complete job. |
| 920 | a) Upto 35 sq. mm |
| 921 | b) Above 35 sq. mm and upto 95 sq. mm |
| 922 | c) Above 95 sq. mm and upto 185 sq. mm |
| 923 | d) Above 185 sq. mm and upto 400 sq. mm |
| 924 | d) Above 400 sq. mm and upto 800 sq. mm |
| 925 | Excavation of existing 3.5 core and single cable trench for locating of cable fault by way of excavation , extraction removing of cable from cable trench .the job includes cost of refilling the trench after rectifiying the cable fault. and segregation on site transportion to site / location with in Skims premises including cost of roll and cable staking at designated place, complete job. |
| 926 | a) Upto 35 sq. mm |
| 927 | b) Above 35 sq. mm and upto 95 sq. mm |
| 928 | c) Above 95 sq. mm and upto 185 sq. mm |
| 929 | d) Above 185 sq. mm and upto 400 sq. mm |
| 930 | d) Above 400sq. mm and upto 630 sq. mm, |
| 931 | Disconnecting and extraction of following sizes existing LT 1 core core cables PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade from existing masonry open duct, cable tray /cable hungers as required. segregation on site transportion to site /location within skims premises including cost of roll and cable staking at designated place, complete job. |
| 932 | a) Upto 35 sq. mm |
| 933 | b) Above 35 sq. mm and upto 95 sq. mm |
| 934 | c) Above 95 sq. mm and upto 185 sq. mm |
| 935 | d) Above 185 sq. mm and upto 400 sq. mm |
| 936 | d) Above 400 sq. mm and upto 1000 sq. mm |
| 937 | Excavation of existing 1 core and single cable trench for locating of cable fault by way of excavation , extraction removing of cable from cable trench .the job includes cost of refilling the trench after rectifiying the cable fault. and segregation on site transportion to site / location with in Skims premises including cost of rolland cable staking at designated place, complete job. |
| 938 | a) Upto 35 sq. mm |
| 939 | b) Above 35 sq. mm and upto 95 sq. mm |
| 940 | c) Above 95 sq. mm and upto 185 sq. mm |
| 941 | d) Above 185 sq. mm and upto 400 sq. mm |
| 942 | d) Above 400 sq. mm and upto 1000 sq. mm |
| 943 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 944 | 2x6sq mm(19mm) |
| 945 | 2x10sq mm(19mm) |
| 946 | 2 x 16sq.mm(22mm) |
| 947 | 2x25sq mm(22mm) |
| 948 | 2x35sq mm(25mm) |
| 949 | 2x50sq mm(28 mm) |
| 950 | 3x10sq.mm(22 mm) |
| 951 | 3x16sq mm(25 mm) |
| 952 | 3x25sq mm(25 mm) |
| 953 | 3x35sq mm(28 mm) |
| 954 | 3x50sq mm(32mm) |
| 955 | 3x70sq mm (35mm) |
| 956 | 3x95sq mm(38mm) |
| 957 | 3x120sq mm(45mm) |
| 958 | 3x150 sq mm(50 mm) |
| 959 | 3x185 sq.mm(57 mm) |
| 960 | 3x225sq.mm(62 mm) |
| 961 | 3 x 240 sq.mm(62 mm) |
| 962 | 3 x 300 sq.mm (70 mm) |
| 963 | 3 1/2 x 25 sq.mm (28 mm) |
| 964 | 3 1/2 x 35 sq.mm(32 mm) |
| 965 | 3 1/2 x 50 sq.mm(35 mm) |
| 966 | 3 1/2 x 70 sq.mm(38 mm) |
| 967 | 3 1/2 x 95 sq.mm(45 mm) |
| 968 | 3 1/2 x 120 sq.mm(45 mm) |
| 969 | 3 1/2 x 150 sq.mm(50 mm) |
| 970 | 3 1/2 x 185 sq.mm(57 mm) |
| 971 | 3 1/2 x 225 sq.mm(62 mm) |
| 972 | 3 1/2 x 240 sq.mm(62 mm) |
| 973 | 3 1/2 x 300 sq.mm(70 mm) |
| 974 | 3 1/2 x 400 sq.mm(82 mm) |
| 975 | 4x10 sq.mm(25 mm) |
| 976 | 4x16 sq.mm(28 mm) |
| 977 | 4x25 sq.mm(28 mm) |
| 978 | 4x35 sq.mm(32 mm) |
| 979 | 4x50 sq.mm(35 mm) |
| 980 | Supplying and making outdoor end termination with cast resin compound including aluminium lugs and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE |
| 981 | 2x16 sq.mm |
| 982 | 2x25sq.mm |
| 983 | 2x35sq mm(25mm) |
| 984 | 2x50sq mm(28 mm) |
| 985 | 3x16sq mm(25 mm) |
| 986 | 3x25sq mm(25 mm) |
| 987 | 3x35sq mm(28 mm) |
| 988 | 3x50sq mm(32mm) |
| 989 | 3x70sq mm (35mm) |
| 990 | 3x95sq mm(38mm) |
| 991 | 3x120sq mm(45mm) |
| 992 | 3x150 sq mm(50 mm) |
| 993 | 3x185 sq.mm(57 mm) |
| 994 | 3x225sq.mm(62 mm) |
| 995 | 3 x 240 sq.mm(62 mm) |
| 996 | 3 x 300 sq.mm (70 mm) |
| 997 | 3 1/2 x 25 sq.mm (28 mm) |
| 998 | 3 1/2 x 35 sq.mm(32 mm) |
| 999 | 3 1/2 x 50 sq.mm(35 mm) |
| 1000 | 3 1/2 x 70 sq.mm(38 mm) |
| 1001 | 3 1/2 x 95 sq.mm(45 mm) |
| 1002 | 3 1/2 x 120 sq.mm(45 mm) |
| 1003 | 3 1/2 x 150 sq.mm(50 mm) |
| 1004 | 3 1/2 x 185 sq.mm(57 mm) |
| 1005 | 3 1/2 x 225 sq.mm(62 mm) |
| 1006 | 3 1/2 x 240 sq.mm(62 mm) |
| 1007 | 3 1/2 x 300 sq.mm(70 mm) |
| 1008 | 3 1/2 x 400 sq.mm(82 mm) |
| 1009 | 4x16 sq.mm(28 mm) |
| 1010 | 4x25 sq.mm(28 mm) |
| 1011 | 4x35 sq.mm(32 mm) |
| 1012 | 4X50 sq.mm(35 mm) |
| 1013 | Supplying and making straight through joint with cast resin compound including ferrules and other jointing materials for following size of PVC insulated and PVC sheathed XLPE aluminium conductor cable of 1.1 KV grade as required |
| 1014 | 2x16 sq.mm |
| 1015 | 2x25sq.mm |
| 1016 | 2x35sq mm(25mm) |
| 1017 | 2x50sq mm(28 mm) |
| 1018 | 3x16sq mm(25 mm) |
| 1019 | 3x25sq mm(25 mm) |
| 1020 | 3x35sq mm(28 mm) |
| 1021 | 3x50sq mm(32mm) |
| 1022 | 3x70sq mm (35mm) |
| 1023 | 3x95sq mm(38mm) |
| 1024 | 3x120sq mm(45mm) |
| 1025 | 3x150 sq mm(50 mm) |
| 1026 | 3x185 sq.mm(57 mm) |
| 1027 | 3x225sq.mm(62 mm) |
| 1028 | 3 x 240 sq.mm(62 mm) |
| 1029 | 3 x 300 sq.mm (70 mm) |
| 1030 | 3 1/2 x 25 sq.mm (28 mm) |
| 1031 | 3 1/2 x 35 sq.mm(32 mm) |
| 1032 | 3 1/2 x 50 sq.mm(35 mm) |
| 1033 | 3 1/2 x 70 sq.mm(38 mm) |
| 1034 | 3 1/2 x 95 sq.mm(45 mm) |
| 1035 | 3 1/2 x 120 sq.mm(45 mm) |
| 1036 | 3 1/2 x 150 sq.mm(50 mm) |
| 1037 | 3 1/2 x 185 sq.mm(57 mm) |
| 1038 | 3 1/2 x 225 sq.mm(62 mm) |
| 1039 | 3 1/2 x 240 sq.mm(62 mm) |
| 1040 | 3 1/2 x 300 sq.mm(70 mm) |
| 1041 | 3 1/2 x 400 sq.mm(82 mm) |
| 1042 | 4x16 sq.mm(28 mm) |
| 1043 | 4x25 sq.mm(28 mm) |
| 1044 | 4x35 sq.mm(32 mm) |
| 1045 | 4x50 sq.mm(35 mm) |
| 1046 | Supplying and making straight through joint with heat shrinkable kit including ferrules and other jointing materials for following size of PVC mswawd and and PVC sheathed XLPE aluminium conductor cable of 1.1 KV grade as required |
| 1047 | 2x16 sq.mm |
| 1048 | 2x25sq.mm |
| 1049 | 2x35sq mm(25mm) |
| 1050 | 2x50sq mm(28 mm) |
| 1051 | 3x16sq mm(25 mm) |
| 1052 | 3x25sq mm(25 mm) |
| 1053 | 3x35sq mm(28 mm) |
| 1054 | 3x50sq mm(32mm) |
| 1055 | 3x70sq mm (35mm) |
| 1056 | 3x95sq mm(38mm) |
| 1057 | 3x120sq mm(45mm) |
| 1058 | 3x150 sq mm(50 mm) |
| 1059 | 3x185 sq.mm(57 mm) |
| 1060 | 3x225sq.mm(62 mm) |
| 1061 | 3 x 240 sq.mm(62 mm) |
| 1062 | 3 x 300 sq.mm (70 mm) |
| 1063 | 3 1/2 x 25 sq.mm (28 mm) |
| 1064 | 3 1/2 x 35 sq.mm(32 mm) |
| 1065 | 3 1/2 x 50 sq.mm(35 mm) |
| 1066 | 3 1/2 x 70 sq.mm(38 mm) |
| 1067 | 3 1/2 x 95 sq.mm(45 mm) |
| 1068 | 3 1/2 x 120 sq.mm(45 mm) |
| 1069 | 3 1/2 x 150 sq.mm(50 mm) |
| 1070 | 3 1/2 x 185 sq.mm(57 mm) |
| 1071 | 3 1/2 x 225 sq.mm(62 mm) |
| 1072 | 3 1/2 x 240 sq.mm(62 mm) |
| 1073 | 3 1/2 x 300 sq.mm(70 mm) |
| 1074 | 3 1/2 x 400 sq.mm(82 mm) |
| 1075 | 4x16 sq.mm(28 mm) |
| 1076 | 4x25 sq.mm(28 mm) |
| 1077 | 4x35 sq.mm(32 mm) |
| 1078 | 4x50 sq.mm(35 mm) |
| 1079 | Supplying and making cable route marker with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size ) of size 60 cm X 60 cm at the bottom and 50 cm X 50 cm at the top with a thickness of 10cm including inscription duly enqraved as required. |
| 1080 | Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.|. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required. |
| 1081 | Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead upto 50 m and lift upto 1.5 m. |
| 1082 | Earth work in excavation by manual means in trenches for foundations, drains, pipes, cables etc. (not exceeding 1.5 m in width) and for shafts, wells, cesspits and the like not exceeding 10 sqm on plan, including dressing of sides and ramming of bottoms lift upto 1.5 m, including getting out excavated earth and disposal of surplus excavated earth as directed All kinds of soil, Rate for a lead upto 50 meter beyond 1 m from cutting edge |
| 1083 | Deduct for not consolidation by ramming and watering while re-filling with sand and or good soil in cable pipe laying. |
| 1084 | Earth work in excavation by manual means in trenches for foundations, drains, pipes, cables etc. (not exceeding 1.5 m in width) and for shafts, wells, cesspits and the like not exceeding 10 sqm on plan, including dressing of sides and ramming of bottoms lift upto 1.5 m, including getting out excavated earth and disposal of surplus excavated earth as directed Ordinary Rock |
| 1085 | Providing and laying in position cement concrete of specified grade excluding cost of centering and shuttering (All works up to plinth level) 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) |
| 1086 | Providing and laying in position cement concrete of specified grade excluding cost of centering and shuttering (All works up to plinth level) 1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size) |
| 1087 | Providing and laying in position cement concrete of specified grade excluding cost of centering and shuttering (All works up to plinth level)1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) |
| 1088 | Providing and laying in position specified grade of reinforced cement concrete including curing but excluding the cost of centering, shuttering, finishing and reinforcement. All works upto plinth level 1:1½:3 (1 cement : 1½ coarse sand : 3 graded stone aggregate 20 mm nominal size) |
| 1089 | Brick work with common burnt clay (non-modular) bricks of class designation 7.5 in foundation and plinth including curing in : Cement mortar 1:4 ( 1 cement : 4 coarse sand) |
| 1090 | 15mm Cement plaster on the rough side of single or half brick wall of mix: 1 : 4 ( 1 cement : 4 fine sand) |
| 1091 | Providing and fixing G.I. pipes (Medium class) complete with G.I. fittings excluding trenching and refilling etc. (external work) |
| 1092 | 50 mm dia |
| 1093 | 80 mm dia |
| 1094 | 100 mm dia |
| 1095 | 150 mm dia |
| 1096 | Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement: 2 fine sand) including testing of joints etc. complete |
| 1097 | 100 mm dia |
| 1098 | 150 mm dia |
| 1099 | 250 mm dia |
| 1100 | 300 mm dia |
| 1101 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part ll complete with fitting and cutting, jointing etc. in the existing trench, complete as required. |
| 1102 | 63 mm dia (OD-63 mm & ID-51 mm nominal) |
| 1103 | 90 mm dia (OD-90 mm & ID-76 mm nominal) |
| 1104 | 120 mm dia (OD-120 mm & ID-103 mm nominal) |
| 1105 | 160 mm dia (OD-160 mm & ID-135 mm nominal) |
| 1106 | 200 mm dia (OD-200 mm & ID-175 mm nominal) |
| 1107 | 300mm dia (OD-315 mm & ID-290 mm nominal, Thickness min. 12mm) |
| 1108 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part ll complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc.,complete as required |
| 1109 | 63 mm dia (OD-63 mm & ID-51 mm nominal) |
| 1110 | 90 mm dia (OD-90 mm & ID-76 mm nominal) |
| 1111 | 120 mm dia (OD-120 mm & ID-103 mm nominal) |
| 1112 | ADDITIONAL CIVIL ITEMS INTRODUCED |
| 1113 | There are few items which are contained in Civil DSR which are required to be used in exclusive electrical works. Field units should use these items for such purposes. |
| 1114 | Providing and fixing M.S. fan clamp of 16mm dia M.S. bar, bent to shape with hooked ends in R.C.C, slabs or beams during laying, including painting the exposed portion of loop, all as per standard design complete. |
| 1115 | Providing and fixing circular/hexagonal cast iron box for ceiling fan clamp, of internal dia 140 mm, 73mm height, top lid of 1.5mm thick M.S. sheet with its top surface hacked for proper bonding, top lid shall be screwed into the cast iron/M.S. sheet box by means of 3.3mm dia. round headed screws, one lock at the corners. Clamps shall be made of 12mm dia M.S. bar bent to shape as per standard drawing. |
| 1116 | iii) Making hole for installation of exhuast fan Cutting holes of required size in brick masonry wall for fixing of exhaust fan of size upto 450mm sweep and making good the same etc. complete as per direction of Engineer-in-charge. |
| 1117 | Painting with synthetic enamel paint of approved brand and manufacture to give an even shade. Two or more coats on new work |
| 1118 | Painting with aluminum paint of approved brand and manufacture to give an even shade. Two or more coats on new work |
| 1119 | Painting with black anti-corrosive bitumastic paint of approved brand and manufacture to give an even shade on new work Two or more coat |
| 1120 | Supply of Installation testing commission Façade lighting is used to enhance the exterior appearance of buildings, improve visibility, and provide architectural highlighting during night hours. The system includes LED-based luminaires of different wattages installed strategically to highlight structural elements such as walls, columns, edges, and elevations. Wide area illumination, building front washMounting: Wall. Technical SpecificationsVoltage: 220–240V ACFrequency: 50 HzProtection: IP65 / IP66 (weatherproof)Material: Die-cast aluminum housingLife Span: 50,000 hours (LED)Power Factor: >0.95 Additional Features (Optional)RGB colour-changing system with controller Smart control (mobile / timer based) Dimming system DMX control for dynamic effects |
| 1121 | LED Flood Light min. 100W |
| 1122 | LED Wall Washer min. 36W |
| 1123 | LED Strip Light (per meter) min. 12W |
| 1124 | LED Spot Light min. 20W |
| 1125 | Onground Uplight min. 20W |
| 1126 | Installation and fixing for LED decorative string lighting, as per requirement, on rental basis per day, including, Loading, Transport to Site & Return to and fro at site, installation, Removal, Providing of skilled Manpower for the Operation, complete job |
| 1127 | LED String Light (50–60 ft per string, IP65 outdoor) |
| 1128 | Power Cable /PVC flexible wire |
| 1129 | Distribution Board with MCB & protection |
| 1130 | supply of 5pc screwdriver set THT60572-88 |
| 1131 | supply of Machinist Hammer WHM1303WADFOW |
| 1132 | supply of 12PC DOUBLE END OPEN JAW SPANNER 70 |
| 1133 | supply of 5m tape without lock STHT36519-812 |
| 1134 | Centre Punch 0-58-120 |
| 1135 | Classic 99 Retraceable knife 10-099 |
| 1136 | supply of 100MMX1.2MM CUTOFF WHEEL DWA8060 |
| 1137 | supply of 110mm Angle Grinder Dw801-In01 |
| 1138 | supply of 12'' open mouth Bag STST512114 |
| 1139 | supply of 20 pc pear head Ratchet set stmt 45504 |
| 1140 | supply of 22'' cainsaw Rover 54cc rcs stmt 5-5522 |
| 1141 | supply of CIWLI2085-20 1MP WRENCH 850NM |
| 1142 | supply of Digital Caliper 1112-150 |
| 1143 | supply of Digital Detection Screwdriver 66-137 |
| 1144 | supply of fixed Blade olding Knife STHT10424-0 |
| 1145 | supply of Long nose Plier |
| 1146 | supply of Mini Hacksaw 0-20-807 |
| 1147 | supply of Ring End Spanner Set 70-395E |
| 1148 | supply of Safety Helmet white Heavy |
| 1149 | supply of Variable speed blower STPT600 |
| 1150 | supply of water pump plier 71-669 |
| 1151 | High Quality HT (33KV Level) Gloves pair |
| 1152 | High Quality Working Gloves Gloves pair |
| 1153 | Design & Fabrication of 2mm MS Sheet Plates/Doors with hings/Locks, with 2 coats of Red oxide and 2 coats of Color Paint, to cover the openings/Distribution Boxes, including its fixing as per site requirement, complete job. |
| 1154 | Providing and RCC LT cable trench of internal size 1.0 m width and 1.2 m depth with PCC 1:4:8 bed 100 mm thick, RCC M20 side walls 150 mm thick including reinforcement, centering, curing, excavation and backfilling complete. Trench shall be provided with ISMC 75×40 mm bottom cable tray supports fixed 150 mm above PCC level and ISMC 75×40 mm staggered brackets anchored into RCC walls at 1.0 m c/c for second tier cable arrangement. Top shall be covered with 4 mm thick chequered steel plates (removable) including ISA 40*40*5 mm steel frame seating, lifting arrangement and including painting approved Synthetic enamel painting over steel priming coat , complete with all leads and lifts as per directions of Engineer-in-charge. |
| 1155 | Earth Ground Clamp, Stakeless earth ground loop and AC leakage current clamp for fast, safe indoor/outdoor earth ground resistance and ac Leakage Current Tester, Maximum voltage to earth ground: 1000 V, Battery type: 4 x 1.5 V AA alkaline IEC/EN LR6, Battery life More than 15 hours, Frequency range 40 Hz to 1 kHz, Ingress protection IEC/EN 60529: IP30 with jaw closed, LCD Digital reading 9999 counts, Refresh rate 4/s, Temperature: Operating -10 °C to +50 °C (14 °F to +122 °F), Storage -20 °C to +60 °C (-4 °F to +140 °F), Operating humidity: Non condensing (< 50 °F), ≤90 % RH (at 10 °C to 30 °C [50 °F to 86 °F]), ≤75 % RH (at 30 °C to 40 °C [86 °F to 104 °F]), ≤45 % RH (at 40 °C to 50 °C [104 °F to 122 °F]), (Non condensing), Altitude: Operating 2000 m (6561 ft), Temperature coefficient: 0.15 % X (specified accuracy)/ °C (28 °C ([82.4 °F]), Overload indication: OL, Data logging capacity Minimum of 30,000 measurements, Data logging interval 1 second to 59 minutes and 59 seconds, Safety: General IEC/EN 61010-1: Pollution Degree 2 IEC/EN 61557-1, Measurement IEC/EN 61010-2-032: CAT IV 600 V / CAT III 1000 V, Current clamp for leakage current measurements: IEC/EN 61557-13: Class 2, ≤30 A/m, Resistance to Earth: IEC/EN 61557-5, Effectiveness of the protective measures: IEC/EN 61557-16: cutoff frequency 20 kHz (-3 dB), Electromagnetic compatibility (EMC) International IEC/EN 61326-1: Portable Electromagnetic Environment CISPR 11: Group 1, Class B, IEC/EN 61326-2-2, Warranty; Min 2 years, Earth ground leakage current mA Autorange 50/60 Hz, True rms, crest factor CF ≤3 Range Resolution Accuracy [1] 0.200 mA to 3.999 mA 1 μA ±2.0 % rdg ±0.05 mA 4.00 mA to 39.99 mA 10 μA ±2.0 % rdg ±0.03 mA 40.0 mA to 399.9 mA 100 μA ±2.0 % rdg ±0.3 mA 0.400 A to 3.999 A 1 mA ±2.0 % rdg ±0.003 A 4.00 A to 39.99 A 10 mA ±2.0 % rdg ±0.030 AContd... |
| 1156 | Display Reading Specification with Loop Resistance Standard Input (Ω) Minimum Maximum 0.474 0.417 0.531 0.5 0.443 0.558 10 9.55 10.45 100 96 104.0 Earth ground loop resistance Range Accuracy [1] (± % of reading + Ω) 0.025 Ω to 0.249 Ω 1.5% + 0.02 Ω 0.250 Ω to 0.999 Ω 1.5% + 0.05 Ω 1.000 Ω to 9.999 Ω 1.5% + 0.10 Ω 10.00 Ω to 49.99 Ω 1.5% + 0.30 Ω 50.00 Ω to 99.99 Ω 1.5% + 0.50 Ω 100.0 Ω to 199.9 Ω 3.0% + 1.0 Ω 200.0 Ω to 399.9 Ω 5.0% + 5.0 Ω 400 Ω to 599 Ω 10.0% + 10 Ω 600 Ω to 1500 Ω 20.00% Please Enable Macros to View BoQ information |