| 1 | Item Rate BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: Executive Engineer Electric Division-Reasi,JPDCL Name of Work: Survey,Supply, Installation, Testing and Commissioning of Electrical Infrastructure which includes Shifting/Creation of HT/LT Lines,11 KV Isolation Points, Shifting/Creation of Distribution Substations from High Risk Disaster Zone to Geographically stable areas under SASCI in the jurisdiction of Executive Engineer ED-Reasi JPDCL. ( Complete Scope of the Work are incorporated in the SBD ) Contract No: e-Nit No 04 of 2026-27 Dated: 02-05-2026 Bidder Name : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # |
| 2 | Item Description |
| 3 | Survey,Supply,Installation,Testing and Commissioning of 11/0.415KV, 25 KVA, 3-phase Distribution Substation (Complete Job Inclusive of Material and Labour) |
| 4 | 11/0.433KV, 3-phase 25 KVA Distribution Transformer with Bimetallic Terminal Connectors Energy Level-2, (Aluminium wound) and with LV cable box having detachable Aluminium Gland plate ( As per IS1180 Part-I;2014 as per latest upto date amendment. |
| 5 | 9 mtr long Pole ST-410, SP33 |
| 6 | Gapless Surge Arrestor, 9kV, 10kA, LA with polymer housing, Station type |
| 7 | 11KV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, vertical type |
| 8 | 11KV Horn Gap Fuse set 3-phase, 200 Amp |
| 9 | 70 sqmm cable 1.1kv grade, PVC insulated stranded conductor FRLS type |
| 10 | 11kV Polymeric composite Disc Insulator 12kV,minfailing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm |
| 11 | 11kV Polymeric composite Pin Insulator 12kV, 5kN,Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm |
| 12 | GI Channel/Angle/Flat of different sizes including clamps ( Galvanized ) |
| 13 | Galvanised Nuts & Bolts |
| 14 | Earthing of substation - Excavation of earthing pit of dia 650mm & depth 3000mm, installation ofEarthing pipe of 40mm nominal bore & 4mm wall thickness & length 2.5 mtr long as per IS 1239. GI strip for neutral earthing of size 25mm x 3mm for connection of transformer body, GO set & lightening arrestor as per IS 2629/85, GI nuts & bolts, refilled with earth enhancement materials and earth chamber made of brick masonary with RCC slab cover. |
| 15 | 32/63 Amp TPN Switch disconnector fuse unit |
| 16 | Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete |
| 17 | LT Distribution Box for 25 KVA DTR with MCCB for Incomer & SFUs for outgoing Circuits including 32/63 Amp TPN Switch disconnector fuse unit and separate earthing of LT Box. LT box sahll be properly sealed with gaskets and cable entry shall be though double compression glands. |
| 18 | Painting of Poles with Red Oxide |
| 19 | Painting of Poles with Aluminium Paint |
| 20 | Cement bottoming 1:2:4 mix as per REC standards .5cum/Pole |
| 21 | The old dismantled/unserviceable material at site shall be returned/written back to Divisional Store, Reasi. Labour and mechanical carriage for transportation charges involved for the same are included. |
| 22 | Survey,Supply,Installation,Testing and Commissioning of 11/0.415KV, 63 KVA, 3-phase Distribution Substation (Complete Job Inclusive of Material and Labour) |
| 23 | 11/0.433KV, 3-phase 63 KVA Distribution Transformer with Bimetallic Terminal Connectors Energy Level-2 ( New), (Aluminium wound) of latest energy efficiency IS1180 Part-I;2014 as per latest upto date amendemnet with externally fitted MCCB with cable box and 4x4 Mtrs suitable capable of ratings. |
| 24 | 9 mtr long Pole ST-410, SP33 |
| 25 | Gapless Surge Arrestor, 9kV, 10kA, LA with polymer housing, Station type |
| 26 | 11KV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, vertical type |
| 27 | 11KV Horn Gap Fuse set 3-phase, 200 Amp |
| 28 | 70 sqmm cable 1.1KV grade, PVC insulated stranded conductor FRLS type |
| 29 | 11kV Polymeric composite Disc Insulator 12kV,minfailing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm |
| 30 | 11kV Polymeric composite Pin Insulator 12kV, 5kN,Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm |
| 31 | GI Channel/Angle/Flat of different sizes including clamps ( Galvanized ) |
| 32 | Galvanised Nuts & Bolts |
| 33 | Earthing of substation - Excavation of earthing pit of dia 650mm & depth 3000mm, installation of Earthing pipe of 40mm nominal bore & 4mm wall thickness & length 2.5 mtr long as per IS 1239. GI strip for neutral earthing of size 25mm x 3mm for connection of transformer body, GO set & lightening arrestor as per IS 2629/85, GI nuts & bolts, refilled with earth enhancement materials and earth chamber made of brick masonary with RCC slab cover. |
| 34 | Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete |
| 35 | Wedge Connectors / PG Clamps |
| 36 | Danger Plates with Clamps |
| 37 | GI Barbed Wire for Anti Climbing |
| 38 | Painting of Poles with Red Oxide |
| 39 | Painting of Poles with Aluminium Paint |
| 40 | LT Distribution Box for 63 KVA DTR with MCCB for Incomer & SFUs for outgoing Circuits including 32/63 Amp TPN Switch disconnector fuse unit and separate earthing of LT Box. LT box sahll be properly sealed with gaskets and cable entry shall be though double compression glands. |
| 41 | Painting of Poles with Red Oxide |
| 42 | Painting of Poles with Aluminium Paint |
| 43 | Cement bottoming 1:2:4 mix as per REC standards .5cum/Pole |
| 44 | The old dismantled/unserviceable material at site shall be returned/written back to Divisional Store, Reasi. Labour and mechanical carriage for transportation charges involved for the same are included. |
| 45 | Survey,Supply ,Erection ,Testing and Commissioning of 11KV HT line with ACSR Weasel Conductor on 9 Mtrs Steel Tubular poles (Complete Job Inclusive of Material and Labour) |
| 46 | 9 mtr long Pole ST-410SP-33 |
| 47 | GI V cross-arm with top Bracket including clamp |
| 48 | GI Channel Iron, GI Cross arms, GI Angle Iron Cross Braces etc duly fabricated including all necessary GI Nut & Bolts & Washers etc. for support of DP structure including GI clamps and braces |
| 49 | 11KV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, vertical type |
| 50 | ACSR Weasel Conductor (30 Sq.mm) |
| 51 | PG Clamps for ACSR Weasel Conductor |
| 52 | 11kV Polymeric composite Pin Insulator 12kV, 5kN,Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm |
| 53 | 11kV Polymeric composite Disc Insulator with GI fittings 12kV,minfailing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm |
| 54 | Galvanized Nuts and Bolts |
| 55 | Danger Plates with Clamps |
| 56 | Anti-Climbing Device with Clamps |
| 57 | Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip (25x3) mm. |
| 58 | Painting of Poles with Red Oxide |
| 59 | Painting of Poles with Aluminium Paint |
| 60 | Cement bottoming 1:2:4 mix as per REC standards .5cum /pole |
| 61 | Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete |
| 62 | The old dismantled/unserviceable material at site shall be returned/written back to Divisional Store, Reasi. Labour and mechanical carriage for transportation charges involved for the same are included. |
| 63 | Survey,Supply, Erection ,Testing and Commissioning of LT Line on 8.0 Mtr ST Poles with ACSR Squirrel Conductor 20mm2 (Complete Job Inclusive of Material and Labour) |
| 64 | 8 mtr long Pole ST-410, SP15 |
| 65 | GI M Clamp for shackle Insulator |
| 66 | ACSR Squirrel Conductor 20mm2 |
| 67 | 16 KN Polymer Shackle Insulators |
| 68 | Galvanised Nuts & Bolts |
| 69 | Danger Plates with clamps |
| 70 | Painting of Poles with Red Oxide |
| 71 | Painting of Poles with Aluminium Paint |
| 72 | Earthing Complete by GI Pipe 40mm or GI Rod 20 mm 2.5 Meter long through GI Strip |
| 73 | Anti-Climbing Device with Clamps |
| 74 | LT line Spacer |
| 75 | Cement bottoming 1:2:4 mix as per REC standards .5cum /pole |
| 76 | Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete. |
| 77 | The old dismantled/unserviceable material at site shall be returned/written back to Divisional Store, Reasi. Labour and mechanical carriage for transportation charges involved for the same are included. |
| 78 | Survey,Supply ,Erection ,Testing and Commissioning of 11 KV Isolation Points ( Complete Job Inclusive of Material and Labour) |
| 79 | ST Pole 9 mtr ( ST 410 SP-33) |
| 80 | GI V cross-arm with top Bracket including clamp and GI Channel X-arm including clamps and braces |
| 81 | 11KV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, vertical type |
| 82 | ACSR Weasel Conductor (30 Sq.mm) |
| 83 | 11kV Polymeric composite Pin Insulator 12kV, 5kN,Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm |
| 84 | 11kV Polymeric composite Disc Insulator with GI fitting 12kV,minfailing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm. |
| 85 | Galvinized Nuts and Bolts |
| 86 | Danger Plates with Clamps |
| 87 | Anti-Climbing Device with Clamps |
| 88 | Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip (25X3) mm. |
| 89 | Painting of Poles with Red Oxide |
| 90 | Painting of Poles with Aluminium Paint |
| 91 | Cement bottoming 1:2:4 mix as per REC standards .5cum /pole |
| 92 | Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete. |
| 93 | The old dismantled/unserviceable material at site shall be returned/written back to Divisional Store, Reasi. Labour and mechanical carriage for transportation charges involved for the same are included. Total in Figures 0.0 0.0 INR Zero Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 No Quoted Rate in Figures Select, Excess (+), Less (-) 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |