Indian Tenders

Tender Notice

TDR 55326411
Tendering Authority Uttar Pradesh Projects Corporation Limited
Tender No 14/UPPCL/GM-1/2026-27/E-TENDER Dated-18.04.2026
Tender ID 2026_UPPRC_1144910_1
Tender Brief Tender For Construction Work At The Primary Health Center, Negura District-Mirzapur To Provide A-50 Bed Facility, Comprising A 32-Bed Ward And R On The First Floor Of The Main Building, One Additional Unit On The First Floor For The Medical Officer A
City Mirzapur
State Uttar Pradesh
Document Fees INR 17700 /-
EMD INR 426000.0 /-
Tender Value INR 2.12 Crore /-
Tender Type Tender
Bidding Type Open Tender
Competition Type Indian

Tender Details

Tender for Construction Work At The Primary Health Center, Negura District-Mirzapur To Provide A-50 Bed Facility, Comprising A 32-Bed Ward And R On The First Floor Of The Main Building, One Additional Unit On The First Floor For The Medical Officer And Two Additional Residential Units On The First Floor For Class-2 Staff (Notice No. 14/Uppcl/Gm-1/2026-27/E-Tender Dated: 18.04-2026 )

Key Dates

Publish Date 04-05-2026
Last Date of Bid Submission 11-05-2026
Tender Opening Date 11-05-2026

Contact Information

Company Name Uttar Pradesh Projects Corporation Limited
Contact Person General Manager, Zone-1, Prayagraj
Address General Manager, Zone-1, U. P. Projects Corporation Ltd., 230/1A, Mehdaury, Teliyarganj, District-Prayagraj.

BOQ Items

Name of Work:- Construction work at the Primary Health Center, Negura District-Mirzapur to Provide A-50 Bed Facility, Comprising A 32-Bed Ward and R on the First Floor of the Main Building, One Additional Unit on the First Floor for the Medical Officer and Two Additional Residential Units on the First Floor for Class-2 Staff (Notice No. 14/UPPCL/GM-1/2026-27/E-TENDER Dated: 18.04-2026 )
Sl. No. Item Description
1Construction work at the Primary Health Center, Negura District-Mirzapur to Provide A-50 Bed Facility, Comprising A 32-Bed Ward and Ramp on the First Floor of the Main Building, One Additional Unit on the First Floor for the Medical Officer and Two Additional Residential Units on the First Floor for Class-2 Staff
2(Civil work)
3Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-in-charge.All kinds of soil
4Filling available excavated earth (excluding rock) in trenches, plinth,sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m.
5Excavating, supplying and filling of local earth (including royalty) by mechanical transport upto a lead of 5km also including ramming and watering of the earth in layers not exceeding 20 cm in trenches, plinth, sides of foundation etc. complete.
6Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :1:4:8 (1 Cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size)
7Supplying and filling in plinth with sand under floors, including watering, ramming, consolidating and dressing complete.
8Treatment of soil under existing floors using chemical emulsion @ one litre per hole, 300 mm apart including drilling 12 mm diameter holes and plugging with cement mortar 1:2 (1 cement:2 coarse sand) to match the existing floor.With Chlorpyriphos/ Linadane E.C. 20% with 1% concentration.
9Reinforced cement concrete work in beams, suspended floors, roofs having slope up to 15° landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral stair cases above plinth level up to floor five level, excluding the cost of centering, shuttering,finishing and reinforcement with 1:1.5:3 (1 cement : 1.5 coarse sand(zone-III) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources).
10As in item 6 above but in R.C.C. Raft foundation and footing with approved stone ballast. (Using 1:1.5:3 Mix concrete)
11Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. above plinth level up to floor five level, excluding cost of centering, shuttering, finishing and reinforcement :
12Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in:Cement mortar 1:6 (1 cement : 6 coarse sand)
13Painting on D.P.C. with two coats of airblown bitumen 85/50 or 85/25 @ 1.7 kg/sqm approx. including cost of fuel if any.
14Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in :Cement mortar 1:6 (1 cement : 6 coarse sand)
15Half brick masonry with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level.Cement mortar 1:4 (1 cement :4 coarse sand)
16Mild steel or iron in plain work such as reinforced concrete or reinforced, brick work (when not included in anover all rates ) wrought to required shape as necessary including bending for proper completion of the work and including supply of steel its wastage bend hooks and authorised over lapping shall be measured upto floor two level.
1715 mm cement plaster on rough side of single or half brick wall of mix:1:6 (1 cement: 6 coarse sand)
1812 mm cement plaster of mix :1:6 (1 cement: 6 coarse sand)
1915 mm cement plaster on rough side of single or half brick wall of mix : 1:4 (1 cement: 4 coarse sand).
20Add for plaster drip course/ groove in plastered surface or moulding to R.C.C. projections.
21Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS: 15622, of approved make, in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand), jointing with grey cement slurry @ 3.3 kg/ sqm including grouting the joints with white cement and matching pigments etc., complete.Size of Tile 600x600 mm
22Providing and laying Vitrified tiles in different sizes (thickness to be specified by manufacturer), with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make, in all colours & shade, in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 cement: 3 coarse sand), jointing with grey cement slurry @ 3.3 kg/ sqm including grouting the joint with white cement & matching pigments etc. complete.Size of Tile 600x600 mm
23Providing and fixing 18mm thick gang saw cut mirror polished premoulded and prepolished) machine cut for kitchen platforms, vanity counters, window sills , facias and similar locations of required size of approved shade, colour and texture laid over 20mm thick base cement mortar 1:4 (1 cement : 4 coarse sand) with joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels. Granite of any colour and shade. (FLOORING)
24Providing and fixing 18mm thick gang saw cut mirror polished premoulded and prepolished) machine cut for kitchen platforms, vanity counters, window sills , facias and similar locations of required size of approved shade, colour and texture laid over 20mm thick base cement mortar 1:4 (1 cement : 4 coarse sand) with joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels. Granite of any colour and shade. (skirting)
25Kota stone slab flooring over 20 mm (average) thick base laid over and jointed with grey cement slurry mixed with pigment to match the shade of the slab, including rubbing and polishing complete with base of cement mortar 1 : 4 (1 cement : 4 coarse sand) :25 mm thick
26Kota stone slabs 20 mm thick in risers of steps, skirting, dado and pillars laid on 12 mm (average) thick cement mortar 1:3 (1 cement: 3 coarse sand) and jointed with grey cement slurry mixed with pigment to match the shade of the slabs, including rubbing and polishing complete.
27Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm, including pointing in white cement mixed with pigment of matching shade complete.
28Providing and laying Ceramic glazed floor tiles of size 300x300 mm (thickness to be specified by the manufacturer) of 1st quality conforming to IS : 15622 of approved make in colours such as White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick cement mortar 1:4 (1 Cement : 4 Coarse sand), Jointing with grey cement slurry @ 3.3 kg/sqm including pointing the joints with white cement and matching pigment etc., complete. (FLOORING)
29Making plinth protection 50mm thick of cement concrete 1:3:6 (1 cement : 3 coarse sand (zone-III) derived from natural sources : 6 graded stone aggregate 20 mm nominal size derived from natural sources) over 75mm thick bed of dry brick ballast 40 mm nominal size, well rammed and consolidated and grouted with fine sand, including necessary excavation, levelling & dressing & finishing the top smooth
30Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) non-decorative type, core of block board construction with frame of 1st class hard wood and well matched commercial 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters: (Both side laminated)
31(a) 35 mm thick including ISI marked Stainless Steel butt hinges with necessary screws. Single leaf.
32(b) Double leaf
33(a) 35 mm thick including ISI marked Stainless Steel butt hinges with necessary screws. Single leaf.
34Extra for providing lipping with 2nd class teak wood battens 25 mm minimum depth on all edges of flush door shutters (over all area of door shutter to be measured).
35French spirit polishing :Two or more coats on new works including a coat of wood filler
36Providing and fixing wooden moulded beading to door and window frames with iron screws, plugs and priming coat on unexposed surface etc. complete :2nd class teak wood 50 x 12 mm
37Mild steel or iron work Providing and fixing mild steel round holding down bolts with nuts and washer plates complete.
38Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required.In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works
39Providing and fixing M.S. Tubular frames for doors, windows, ventilators and cupboard with rectangular/ L-Type sections, made of 1.60 mm thick M.S. Sheet, joints mitred, welded and grinded finish, with profiles of required size, including fixing of necessary butt hinges and screws and applying a priming coat of approved steel primer.Fixing with 15x3 mm lugs 10 cm long embedded in cement concrete block 15x10x10 cm of C.C. 1:3:6 (1 Cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size)
40Providing and fixing wire gauge shutters using stainless steel grade 304 wire gauge with wire of dia 0.5 mm and average width of aperture 1.4 mm in both directions for doors, windows and clerestory windows with necessary screws : 35 mm thick shutters with ISI marked M.S. pressed butt hinges bright finished of required size. Second class teak wood
41Providing and fixing glazed shutters for doors, windows and clerestory windows using 4 mm thick float glass panes including ISI marked M.S. pressed butt hinges bright finished of required size with necessary screws. (a) 35mm thick Second class teak wood.
42Providing and fixing factory made uPVC white colour sliding glazed window upto 1.50 m in height dimension comprising of uPVC multi-chambered frame with in-built roller track and sash extruded profiles duly reinforced with 1.60 ± 0.2 mm thick galvanized mild steel section made from roll forming process of required length (shape & size according to uPVC profile), appropriate dimension of uPVC extruded glazing beads and uPVC extruded interlocks, EPDM gasket, wool pile, zinc alloy (white powder coated) touch locks with hook, zinc alloy body with single nylon rollers (weight bearing capacity to be 40 kg), G.I fasteners 100 x 8 mm size for fixing frame to finished wall and necessary stainless steel screws etc. Profile of frame & sash shall be mitred cut and fusion welded at all corners, including drilling of holes for fixing hardware's and drainage of water etc. After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealent over backer rod of required size and of approved quality, all complete as per approved drawing & direction of Engineer-in-Charge. (Single / double glass panes, wire mesh shall be paid separately). Variation in profile dimension in higher side shall be accepted but no extra payment on this account shall be made.
43Three track three panels sliding window with fly proof SS wire mesh (Two nos. glazed & one no. wire mesh panels) made of (small series) frame 92 x 44 mm & sash 32 x 60 mm both having wall thickness of 1.9 ± 0.2 mm and single glazing bead of appropriate dimension (Area of window upto 1.75 sqm).
44Providing and fixing factory made single extruded WPC (Wood Polymer Composite) solid door/window/Clerestory windows & other Frames/Chowkhat comprising of virgin PVC polymer of K value 58-60 (Suspension Grade), calcium carbonate and natural fibers (wood powder/ rice husk/wheat husk) and non toxic additives (maximum toxicity index of 12 for 100 gms) fabricated with miter joints after applying PVC solvent cement and screwed with full body threaded star headed SS screws having minimum frame density of 750 kg/cum, screw withdrawal strength of 2200 N (Face) & 1100 N (Edge), minimum compressive strength of 58 N/mm2, modulus of elasticity 900 N/mm2 and resistance to spread of flame of Class A category with property of being termite/borer proof, water/moisture proof and fire retardant and fixed in position with M.S hold fast/lugs/SS dash fasteners of required dia and length complete as per direction of Engineer-In- Charge. (M.S hold fast/lugs or SS dash fasteners shall be paid for separately).Note: For WPC solid door/window frames, minus 5mm tolerance in dimensions i.e depth and width of profile shall be acceptable. Variation in profile dimensions on plus side shall beacceptable but no extra payment on this account shall be made. Frame size 65 x 150 mm
45Distempering (Two coat) with oil bound distemper of approved brand and manufacture & of required shade on undecorated wall surface to give an even shade over & including a priming coat with cement primer of approved brand & manufacture such as Berger,J&N, Shalimar, Asian paints after thoroughly brushing the surface free from mortar droppings & other foreign matters & also including preparing the surface even with plaster of paris or approved synthetic material & sand papered smooth including cost ofall materials. (For Internal wall surface)
46Finishing walls with Premium Acrylic Smooth exterior paint with Silicone additives of required shade:New work (Two or more coats applied @ 1.43 ltr/10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/10 sqm)(Outer surface)
47Painting with silicon & acrylic emulsion based water thinnable sealer of approved brand and manufacture on wet or patchy portion of plastered surfaces :Two coats
48Distempering (Two coat) with oil bound distemper of approved brand and manufacture & of required shade on undecorated wall surface to give an even shade over & including a priming coat with cement primer of approved brand & manufacture such as Berger,J&N, Shalimar, Asian paints after thoroughly brushing the surface free from mortar droppings & other foreign matters & also including preparing the surface even with plaster of paris or approved synthetic material & sand papered smooth including cost ofall materials. (For ceiling surface)
49Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete.
50Providing and fixing 150 mm bright finished floor brass door stopper with rubber cushion, necessary brass screws etc. to suit shutter thickness complete.
51Providing and fixing Stainless steel 304 grade sliding door bolts, of 16mmx250mm solid rod with required nuts, screws, keeper, etc. all item to s.s. 304 grade only and supplied along with material test certificate. (OZ-ALD-01(16x250mm)
52Providing and fixing Stainless steel 304 grade tower bolts (barrel and plate type) with required nuts, screws, keeper, etc. all item to s.s. 304 grade only and supplied along with material test certificate.
53(a) 300 mm x 10mm -(OZ-TB-S-12\\" )
54(b) 250 mm x 10mm (OZ-TB-S-10\\" )
55Providing and fixing Stainless steel 304 grade handles with plate fixed with S.S. screws,etc. complete of size 10mm 125mm all item to s.s. 304 grade only and supplied along with material test certificate. (ODG-11-10x125)
56Providing and fixing aluminium sliding door bolts, ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868), transparent or dyed to required colour or shade, with nuts and screws etc. complete : (a) 250mm x 16mm.
57Providing and fixing aluminium tower bolts, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868 ) transparent or dyed to required colour or shade, with necessary screws etc. complete :
58(a) 250 mm x 10mm
59(a) 200 mm x 10mm
60Providing and fixing aluminium handles, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade, with necessary screws etc. complete :
61(a) 125mm (For Doors)
62(b) 100mm (For Windows)
63(c) 100mm (For Cup board)
64Providing and fixing aluminium hanging floor door stopper, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour and shade, with necessary screws etc. complete. Twin rubber stopper
65Providing and laying integral cement based water proofing treatment including preparation of surface as required for treatment of roofs, balconies, terraces etc consisting of following operations: a) Applying a slurry coat of neat cement using 2.75 kg/sqm of cement admixed with water proofing compound conforming to IS. 2645 and approved by Engineer-in-charge over the RCC slab including adjoining walls upto 300 mm height including cleaning the surface before treatment. b) Laying brick bats with mortar using broken bricks/brick bats 25 mm to 115 mm size with 50% of cement mortar 1:5 (1 cement : 5 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge over 20 mm thick layer of cement mortar of mix 1:5 (1 cement :5 coarse sand ) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge to required slope and treating similarly the adjoining walls upto 300 mm height including rounding of junctions of walls and slabs c) After two days of proper curing applying a second coat of cement slurry using 2.75 kg/ sqm of cement admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge. d) Finishing the surface with 20 mm thick jointless cement mortar of mix 1:4 (1 cement :4 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge including laying glass fibre cloth of approved quality in top layer of plaster and finally finishing the surface with trowel with neat cement slurry and making pattern of 300x300 mm square 3 mm deep. e) The whole terrace so finished shall be flooded with water for a minimum period of two weeks for curing and for final test. All above operations to be done in order and as directed and specified by the Engineer-in-Charge : With average thickness of 120 mm and minimum thickness at khurra as 65 mm.
66P/F curtain rods of 1.25mm thick chromium plated brass plate, with two chromium plated brass brackets fixed with C.P. brass screws and wooden plugs etc. wherever necessary complete (a) 25 mm dia.
67Providing and fixing of wardrobe. (As per specification and details attached)
68Painting with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade.Two or more coats on new work over an under coat of suitable shade with ordinary paint of approved brand and manufacture : (M.S. works).
69Painting with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade.Two or more coats on new work over an under coat of suitable shade with ordinary paint of approved brand and manufacture : (Wood works).
70Providing & fixing glass panes with putty and glazing clips in steel doors, windows, clerestory windows, all complete with : 4 mm thick
71Providing and fixing stainless steel ( Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners , stainless steel bolts etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in-charge.
72Chequerred precast cement concrete tiles 22 mm thick in footpath & courtyard, jointed with neat cement slurry mixed with pigment to match the shade of tiles, including rubbing and cleaning etc. complete, on 20 mm thick bed of cement mortar 1:4 (1 cement: 4 coarse sand).Ordinary cement without any pigment
73Providing and fixing double scaffolding system (cup lock type) on the exterior side, up to seven story height made with 40 mm dia M.S. tube 1.5 m centre to centre, horizontal & vertical tubes joining with cup & lock system with M.S. tubes, M.S. tube challies, M.S. clamps and M.S. staircase system in the scaffolding for working platform etc. and maintaining it in a serviceable condition for the required duration as approved and removing it there after .
74The scaffolding system shall be stiffened with bracings, runners, connection with the building etc wherever required for inspection of work at required locations with essential safety features for the workmen etc. complete as per directions and approval of Engineerin- charge .The elevational area of the scaffolding shall be measured for payment purpose .The payment will be made once irrespective of duration of scaffolding.
75Providing & laying of light cinder filling under floor of toilets & other sunken roofs.
76Providing and laying water proofing treatment in sunken portion of WCs, bathroom etc., by applying cement slurry mixed with water proofing cement compound consisting of applying :(a) First layer of slurry of cement @ 0.488 kg/sqm mixed with water proofing cement compound @ 0.253 kg/ sqm. This layer will be allowed to air cure for 4 hours.(b) Second layer of slurry of cement @ 0.242 kg/sqm mixed with water proofing cement compound @ 0.126 kg/sqm. This layer will be allowed to air cure for 4 hours followed withwater curing for 48 hours. The rate includes preparation of surface, treatment and sealing of all joints, corners, junctions of pipes and masonry with polymer mixed slurry.
77Centering and shuttering including strutting, propping etc. and removal of form for :
78Foundations, footings, bases of columns, etc. for mass concrete
79Suspended floors, roofs, landings, balconies and access platform with water proof ply 12 mm thick
80Lintels, beams, plinth beams, girders, bressumers and cantilevers with water proof ply 12 mm thick
81Columns, Pillars, Piers, Abutments, Posts and Struts
82ELECTRICAL WORKS
83Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular type switch, modular plate, suitable size G.I. box and earthing the point with 1.5 sq.mm. FRLS/HFFR PVC insulated copper conductor single core cable etc as required.
84Group C
85Wiring for twin control light point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2 way modular type switch, modular plate, suitable G.I. box and earthing the point with 1.5 sq.mm. FRLS/HFFR PVC insulated copper conductor single core cable etc as required.
86Wiring for circuit/sub-main wiring along with earth wire with the following size of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.
872X1.5 sqmm + 1x1.5 sqmm earth wire
882X2.5 sqmm + 1x 2.5 sqmm earth wire
892X4.0 sqmm + 1x 4.0 sqmm earth wire
902X6.0 sqmm + 1x 6.0 sqmm earth wire
912X10.0 sqmm + 1x 6.0 sqmm earth wire
924X10 sqmm + 2x 6.0 sqmm earth wire
93Supplying and drawing co-axial TV cable RG-6 graded, 0.7 mm solid copper conductor PE insulated,shielded with fine tinned copper braid and protected with PVC sheath in the existing surface/ recessed steel/ PVC conduit as required.
94Supplying and drawing following pair 0.5 sqmm FRLS PVC insulated annealed copper conductor, unarmoured telephone cable in the existing surface/recessed steel/PVC conduit as required. 2 Pair
95Supply and fixing of following size of PVC conduit alongwith the accessories in recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required:25mm
96Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc as required.
97Telephone socket outlet
98Bell push
99Supply and fixing of two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
100Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required.
101Supplying and fixing following size/modules, GI box along with modular base & cover plate for modular switches in recess etc as required. 1 or 2 module(75mm X 75 mm )
102Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch,connection etc. as required.
103Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch,connection etc. as required.
104Supplying and fixing 3 pin 5 A ceiling rose on the existing junction box/wooden block including connectionetc. as required.
105Supplying and fixing brass batten/angle holder including connectionetc. as required.
106Supplying and fixing call bell/ buzzer suitable for single phase, 230 volts, complete as required.
107Installation of exhaust fan in the existing opening, including making good the damage, connections, testing, commissioning etc. as required.
108upto 450 mm sweep.
109Extra for fixing the louvers / shutters complete with frame fro exhaust fans of all sizes.
110Providing and fixing circular/Hexagonal cast iron or M.S. sheet box for ceiling fan clamp, of internal dia 140 mm, 73mm height, top lid of 1.5 mm thick M.S. sheet with its top surface hacked for proper bonding, top lid shall be screwed into the cast iron/M.S. sheet box by means of 3.3 mm dia round headed screwed, one loc at the conrners. Clamp shall be made of 12 mm dia M.S. bar bent to shape as per standard drawing.
111DISTRIBUTION BOARDS, MCB'S & ISOLATORS :
112Supplying and fixing following way, single pole and neutral sheet steel, MCB distribution board, 240 V on surface /recess complete with , tinned copper busbar, neutral busbar, earth bar, din bar, interconnections, powder painted including earthing etc. as required (But without MCB / RCCB / Isolators).
1138 way, Double door
114Supplying and fixing following way, Horizontal type three pole and neutral MCB distribution board, 415 volts on surface /recess complete with , tinned copper busbar, neutral busbar, earth bar, din bar, interconnections, powder painted including earthing etc. as required (But without MCB / RCCB / Isolators).
1156 way (4 + 18), Double door
116Supplying and fixing 5 amps. to 32 amps. rating, 240 volts `C' series, miniature circuit breaker (MCB) suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
117Single Pole
118Double Pole
119Supplying and fixing single pole, blanking plate in the existing MCB DB complete etc. as required.
120Supply and fixing 20 amp, 240 volts, SPN industrial Type, socket outlet ,With 2 pole and earth ,metal enclosed plug top along with 20 amp. `C` series SPMCB , in sheet steel encosure, on surface or in recess with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.
121Providing and fixing M.V. danger notice plate of 200 mmx150 mm, made of mild steel, at least 2 mm thick, and viterous enameled white on both sides, and with incription in single red colour on front side as required.
122Supplying and fixing Cable End Box(Loose Wire Box) suitable for following triple pole and neutral, sheet steel, MCB distribution borad, 415 Volts, on surface/recess, complete with testing and commissoning ect. as required.
123For 6 way, Double Door TPNMCBDB
124Supply and installing of following size of perforated pre-painted M.S. cable trays with perforation not more than 17.5%, in convenient sections, jointed with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.
125300mm width x 62.5mm depth x 2.0mm thickness
126Supplying and fixing Cable End Box(Loose Wire Box) suitable for following single pole and neutral, sheet steel, MCB distribution borad, 240 Volts, on surface/recess, complete with testing and commissoning ect. as required. For 8 way, Double Door SPNMCBDB
127Earthing with GI earth pipe, 600 mm X 600 mm X 6 mm thick including accessories and providing masonary enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc, with charcoal/cock and salt as required.
128Supplying and Laying of 25 mm X 3 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection / terminating with nut, bolt, spring, washer etc. as required.( jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)
129Providing & fixing 6 SWG dia G.I. on surface or in recess for loop earthing as required.
130LED Down lighter(SMD Type) (System lumen efficancy≥120<135 lm/Watt)
131Supplying, installation, Testing & Commissioning of LED Recessed/surface Down lighter (Round/ square/ Rectangular) SMD type of following body body material with PMMA and prismatic diffuser and construction as per IS: 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt,frequency 50/60 hz, Operating temp range-15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection, THD<10%, P.F. ≥0.95, IP20,CRI>80,UGR(Unified Glare Rating)<19,Flicker free(Flicker should be below 5%), life time(LED,Driver & electrical circuitary), of minimum 50000 Buring Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K/4000°K/5700°K/6000°K/6500°K(As per ANSI Bim.)SDCM(Standard Deviation Colour Matching)<3, Maximum power consumption should not more than the specified rating and Fixture shall be confirming to relevant BIS standards.
132Manufactures Word Mark/Name Engraved/Embossing/ Screen printing on housing Complete in all respect i/c connection with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable and earthing etc. as required with minimum 5 year OEM warranty. System lumen efficancy ≥120 and <135lm/watt output. LM79 & LM 80 test report from NABL lab for all testing required for LED fictures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in Charge as per requirement.(Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C).
133Powder coated die cast/Extruded aluminum Body including trim
13412-15 watt
135LED Batten light (System lumen efficancy ≥120<135 lm/Watt)
136Supplying,installation, Testing & Commissioning of Batten light of following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt,frequency 50/60 hz, Operating temp range-15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection, THD<10%, P.F. ≥0.95, IP20,CRI>80,UGR(Unified Glare Rating)<19,Flicker free(Flicker should be below 5%), life time(LED,Driver & electrical circuitary), of minimum 50000 Buring Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K/4000°K/5700°K/6000°K/6500°K(As per ANSI Bim.)SDCM(Standard Deviation Colour Matching)<3, Maximum power consumption should not more than the specified rating and Fixture shall be confirming to relevant BIS standards.
137Manufactures Word Mark/Name Engraved/Embossing/ Screen printing on housing. OEM must have its own in house NABL lab setup for testing facilities for LED fixtures. Complete in all respect i/c connection with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and earthing etc. as required with minimum 5 year OEM warranty. System lumen efficancy ≥120<135 lm/watt output. LM79 & LM 80 test report from NABL lab for all testing required for LED fictures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in Charge as per requirement.(Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C).
138Powder coated die cast/Extruded aluminum Body (Thickness ≥1.20mm)
13918-22 watt
140Brush Less Direct Current(BLDC) Motor with Remote
141Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current(BLDC) motor, class of insulation: B, 3 nos. metel(Aluminum alloy)blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/AI body Power Factor not less than 0.9, Service Value(CM/M/W) minimum as below,350 RPM(tolerance as per IS: 374-2019), THD(Toatl harmonic Distortion) less than 10%, remote(preferably mobile app based) for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C(max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Ceiling Fan complient to IS 374:2019 fan i/c external connections with 1.5 sq. mm FRLS/HFFR with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required.
142900 mm, service value ≥ 5.1 CM/Min/Watt, air delivery 130 Cm/Min(Minimum)
1431200 mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 Cm/Min(Minimum)
144Supplying & making end termination with brass compression gland and aluminium lugs for the following size of PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
1452 X 10 sqmm. (19mm)
1463.5 X 35 sqmm. (32mm)
1473.5 X 95 sqmm. (45mm)
1483.5 X 25 sqmm. (28 mm)
149L.T. PANEL
150Supply, Installation, Testing, Design, inspection,handling and Commissioning of cubical type L.T. Panel vermin & dust proof front operated floor mounting, M.S. Channel Base with bottom and Fabricated out of 2.0/1.6 mm thick CRCA sheet steel painted with powder coated paint of shade as per the direction of Engineer In charge after proper sheet treatment peocess of sheet steel with top/bottom removable gland plates, as required. The bus bar of panel shall be electrical grade high conductive alluminium alloy of appropriate cross section as per the rating. The main busbar shall be run throughout the panel of rating as main incomer rating. The Bus Bar shall be supported by non hygroscopic SMC/DMC Bus bar suports which shall be mounted on proper interval to ensure the bear the jerks of suport of short cuircuit of 50kA for panels having ACB as Incomer & 36 kA for panels having MCCB Incomers.
151Panel shall be constructed in fully Segregated Compartment Design for each Feeder as per 3b construction Format. The panel shall be completed in all respect as per IS 8623 Part 2 & 3. There shall be Seperated metering Component for Incomer metering and Outgoing metering. The Panel feeders shall be suitable for termination suitable nos. 3.5/4 core armoured aluminium cable as required.
152All Incomer Feeders shall be provided with Multifunctional metering along with phase Indicating lights and other associated components such as CT control MCB Terminal Blocks etc. and all outgoing Feeders 100 A & above shall be provided with 3 phase Ammeter along with phase Indicating lights and other associates components such as CT control MCB Terminal Blocks etc. The feeder above shall be provided ac accommodated all measuring instrument shall be digital type & all indicating lights shall be LED type. Small wiring shall be done from 1100V Grade PVC Insulated copper flexible wire(min. 2.5 sqmm). All ACB shall be electricaly operated Draw out Type with microprosser based O/L, S/C & E/F Release off Breking/withstand capacity(ICU/ICs/Icw) 50 kA or more. All MCCB shall be thermal magnetics/microprossor with O/L & S/C protection along with required Spreders Extended rotary handle with pad locking facility of bracking capacity(ICU/ICS) 36 kA or more.
153(To avoid heating necessary exhaust fans shall have to be provided along with top louvers. In L.T. Panel)
154The internal control wiring shall fuse less. All control wiring and metering protection by MCB's. shall be Thermal 10kA 'C'Curve .
155200 Amp. 4P MCCB - 1No
156Metering :
157One (1) No. (0-500V) 96 x 96 Sqmm voltmeter with control fuse & selector switch.
158One (1) No. (0-200) 96 x 96 Sqmm CT operated Ammeter with selector switch, CTs etc.
159One (1) Set of Phase Indication Lamp.
160Bus Bar :
161One (1) No.250 A, TPN aluminimum bus bar of suitable length.
162Outgoing :
163Phase indication lamps on each outgoing to be provided.
164125 Amp. 4P MCCB- 1 No.
16563 Amp. 4P MCB- 3 No.
166125 Amp. 4P MCCB- 1 No. -Spare
16763 Amp. 4P MCB- 1 No. -Spare
16840 Amp. 4P MCB- 1 No. -Spare
169OR outgoing as per site requirment(AS/SLD)
170EM-L.T. PANEL
171125 Amp. 4P MCCB - 2No
172Metering :
173One (1) No. (0-500V) 96 x 96 Sqmm voltmeter with control fuse & selector switch.
174One (1) No. (0-125) 96 x 96 Sqmm CT operated Ammeter with selector switch, CTs etc.
175One (1) Set of Phase Indication Lamp.
176Bus Bar :
177One (1) No.150 A, TPN aluminimum bus bar of suitable length.
178Outgoing :
179Phase indication lamps on each outgoing to be provided.
18063 Amp. 4P MCB- 2 No.
18140 Amp. 4P MCB- 2 No.
18232 Amp. DP MCB- 1 No.
18363 Amp. 4P MCB- 1 No. -Spare
18440 Amp. 4P MCB- 1 No. -Spare
185OR outgoing as per site requirment(AS/SLD)
186With AMF & ATS electrical & mechanical interlocking
187METER PANEL BOARD
188Supply, Installation, Testing, Design, inspection,handling and Commissioning of cubical type L.T. Panel vermin & dust proof front operated floor mounting, M.S. Channel Base with bottom and Fabricated out of 2.0/1.6 mm thick CRCA sheet steel painted with powder coated paint of shade as per the direction of Engineer In charge after proper sheet treatment peocess of sheet steel with top/bottom removable gland plates, as required. The bus bar of panel shall be electrical grade high conductive alluminium alloy of appropriate cross section as per the rating. The main busbar shall be run throughout the panel of rating as main incomer rating. The Bus Bar shall be supported by non hygroscopic SMC/DMC Bus bar suports which shall be mounted on proper interval to ensure the bear the jerks of suport of short cuircuit of 50kA for panels having ACB as Incomer & 36 kA for panels having MCCB Incomers.
189Panel shall be constructed in fully Segregated Compartment Design for each Feeder as per 3b construction Format. The panel shall be completed in all respect as per IS 8623 Part 2 & 3. There shall be Seperated metering Component for Incomer metering and Outgoing metering. The Panel feeders shall be suitable for termination suitable nos. 3.5/4 core armoured aluminium cable as required.
190All Incomer Feeders shall be provided with Multifunctional metering along with phase Indicating lights and other associated components such as CT control MCB Terminal Blocks etc. and all outgoing Feeders 100 A & above shall be provided with 3 phase Ammeter along with phase Indicating lights and other associates components such as CT control MCB Terminal Blocks etc. The feeder above shall be provided ac accommodated all measuring instrument shall be digital type & all indicating lights shall be LED type. Small wiring shall be done from 1100V Grade PVC Insulated copper flexible wire(min. 2.5 sqmm). All ACB shall be electricaly operated Draw out Type with microprosser based O/L, S/C & E/F Release off Breking/withstand capacity(ICU/ICs/Icw) 50 kA or more. All MCCB shall be thermal magnetics/microprossor with O/L & S/C protection along with required Spreders Extended rotary handle with pad locking facility of bracking capacity(ICU/ICS) 36 kA or more.
191(To avoid heating necessary exhaust fans shall have to be provided along with top louvers. In L.T. Panel)
192The internal control wiring shall fuse less. All control wiring and metering protection by MCB's. shall be Thermal 10kA 'C'Curve .
193100 Amp. 4P MCCB - 1No
194Metering :
195One (1) No. (0-500V) 96 x 96 Sqmm voltmeter with control fuse & selector switch.
196One (1) No. (0-100) 96 x 96 Sqmm CT operated Ammeter with selector switch, CTs etc.
197One (1) Set of Phase Indication Lamp.
198Bus Bar :
199One (1) No.125 A, TPN aluminimum bus bar of suitable length.
200Outgoing :
201Phase indication lamps on each outgoing to be provided.
20263 Amp. 4P MCB- 2 No.
20325 Amp. DP MCB- 1 No.
20463 Amp. 4P MCB- 2 No. -Spare
205With Provision of meter space
206OR outgoing as per site requirment(AS/SLD)
207METER PANEL BOARD
208Supply, Installation, Testing, Design, inspection,handling and Commissioning of cubical type L.T. Panel vermin & dust proof front operated floor mounting, M.S. Channel Base with bottom and Fabricated out of 2.0/1.6 mm thick CRCA sheet steel painted with powder coated paint of shade as per the direction of Engineer In charge after proper sheet treatment peocess of sheet steel with top/bottom removable gland plates, as required. The bus bar of panel shall be electrical grade high conductive alluminium alloy of appropriate cross section as per the rating. The main busbar shall be run throughout the panel of rating as main incomer rating. The Bus Bar shall be supported by non hygroscopic SMC/DMC Bus bar suports which shall be mounted on proper interval to ensure the bear the jerks of suport of short cuircuit of 50kA for panels having ACB as Incomer & 36 kA for panels having MCCB Incomers.
209Panel shall be constructed in fully Segregated Compartment Design for each Feeder as per 3b construction Format. The panel shall be completed in all respect as per IS 8623 Part 2 & 3. There shall be Seperated metering Component for Incomer metering and Outgoing metering. The Panel feeders shall be suitable for termination suitable nos. 3.5/4 core armoured aluminium cable as required.
210All Incomer Feeders shall be provided with Multifunctional metering along with phase Indicating lights and other associated components such as CT control MCB Terminal Blocks etc. and all outgoing Feeders 100 A & above shall be provided with 3 phase Ammeter along with phase Indicating lights and other associates components such as CT control MCB Terminal Blocks etc. The feeder above shall be provided ac accommodated all measuring instrument shall be digital type & all indicating lights shall be LED type. Small wiring shall be done from 1100V Grade PVC Insulated copper flexible wire(min. 2.5 sqmm). All ACB shall be electricaly operated Draw out Type with microprosser based O/L, S/C & E/F Release off Breking/withstand capacity(ICU/ICs/Icw) 50 kA or more. All MCCB shall be thermal magnetics/microprossor with O/L & S/C protection along with required Spreders Extended rotary handle with pad locking facility of bracking capacity(ICU/ICS) 36 kA or more.
211(To avoid heating necessary exhaust fans shall have to be provided along with top louvers. In L.T. Panel)
212The internal control wiring shall fuse less. All control wiring and metering protection by MCB's. shall be Thermal 10kA 'C'Curve .
213100 Amp. 4P MCCB - 1No
214Metering :
215One (1) No. (0-500V) 96 x 96 Sqmm voltmeter with control fuse & selector switch.
216One (1) No. (0-100) 96 x 96 Sqmm CT operated Ammeter with selector switch, CTs etc.
217One (1) Set of Phase Indication Lamp.
218Bus Bar :
219One (1) No.125 A, TPN aluminimum bus bar of suitable length.
220Outgoing :
221Phase indication lamps on each outgoing to be provided.
22232 Amp. DP MCB- 4 No.
22316 Amp. DP MCB- 1 No.
22432 Amp. DP MCB- 2 No. -Spare
225With Provision of meter space
226OR outgoing as per site requirment(AS/SLD)
227Supplying and laying of aluminium conductor PVC insulated armoured served sheathed cable 1100 volts grade at the depth of 750 mm bellow ground level over a cushion of 75 mm thick sand all around and protected with burnt bricks on side and on top as directed by Engineer-Incharge ,complete in all respect including excavation and refilling. The armouring of the cable shall be properly connected with the earth conductor by clamps etc.
22810 sqmm 2 core
22935 sqmm 3.5 core
23095 sqmm 3.5 core
23125 sqmm 3.5 core
232Supply & Fixing of 1X17 W mirror light complete in all respects. Make-Philips or Eq
233Supply & Fixing 12 W LED BULB complete in all respect. Make-Philips or Eq
234Supply of AC 230/250 Volts, 50 Hz 55w 1400 rpm exhaust fans including providing nuts, bolts, mounting frame and other accessories including connections etc. complete as required.Make: Havells-STANDARD -Refresh Air-SPS
235300mm sweep.
236Supply and fixing following rateing four pole, 415 V, MCB in the existing MCB DB complete with connections, testing and commissioning etc. as required.
23740 A,4P MCB-Bracking Capacity-10 kA, C-Curve-Make-Havells
23863 A,4P MCB-Bracking Capacity-10 kA, C-Curve-Make-Havells
239PLUMBING WORKS
240Providing and fixing water closet squatting pan (Indian type W.C. pan ) with 100 mm sand cast Iron P or S trap, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever) conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required
241White Vitreous china Orissa pattern W.C. pan of size 580x440 mm with integral type foot rests
242Providing and fixing white vitreous china pedestal type water closet (European type W.C. pan) with seat lid, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever) conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required
243W.C. pan with ISI marked white plastic seat and lid
244Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require:White Vitreous China Flat back wash basin size 550x 400 mm with single 15 mm C.P. brass pillar tap.
245Providing and fixing wash basin with C.I. brackets, 15 mm dia C.P. brass Single Hole Basin Mixture approved quality and make ,including painting of fittings and brackets, cutting and making good the walls wherever require.a) White Vitreous China wash basin size 550x 400 mm with 15 mm dia C.P. brass Single Hole Basin Mixture.
246Providing and fixing Stainless Steel A ISI 304 (18/8) kitchen sink as per IS : 13983 with C.I. brackets and stainless steel plug 40 mm, including painting of fittings and brackets, cutting and making good the walls wherever required Kitchen sink with drain board 510x1040x200mm
247Providing and fixing Stainless Steel A ISI 304 (18/8) kitchen sink as per IS : 13983 with C.I. brackets and stainless steel plug 40 mm, including painting of fittings and brackets, cutting and making good the walls wherever required Kitchen sink without drain board 610x460 mm bowl depth 200mm
248Providing and fixing white vitreous china laboratory sink with C.I. brackets, C.P. brass chain with rubber plug, 40 mm C.P brass waste and 40mm C.P. brass trap with necessary C.P. brass unions complete,including painting of fittings and brackets, cutting and making good the wall wherever required : Size 600x450x200 mm
249Providing and fixing flexible P.V.C. waste pipe for sink or wash basin including PVC waste fittings complete.Semi rigid pipe
250a) 32mm dia
251b) 40mm dia
252Providing and fixing 600x450 mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete.
253Providing and fixing 8 mm dia C.P./S.S. Jet with flexible tube upto 1 meter long with S.S. triangular plate for Eureopean type W.C. of quality and make as approved by engineer-in-charge. 15mm nominal bore
254Providing and fixing Toilet paper holder
255Providing and fixing CP Brass 32 mm size Bottal Trap of approved quality & make and as per thedirection of Enginer-in-charge.
256Providing and fixing CP Brass Single lever lelephonic wall mixture of quality & make and as per thedirection of Enginer-in-charge.a) 15mm dia nominal dia.
257Providing and fixing C.P. brass shower rose with 15 or 20 mm inlet a) 100 mm diameter
258Providing and fixing PTMT Liquid soap container 109 mm wide ,125 mm high and 112 mm distance from wall of standerd shape with bracket of the same material with snap fittings of approved quality and colour weighing not less than 105 gms.
259Providing & fixing PTMT towl rail complete with brackets fixed to wooden cleats with cp brass screws with concealed fitting arrangement of approved quality and colour. 600 mm. long towl rail length of 645 mm. width 78 mm. and effective height of 88 mm, weighing not less than 190 gms.
260Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A including jointing with seal ring conforming to IS : 5382 leaving 10 mm gap for thermal expansion . (i) Single socketed pipes. 110mm diameter
261Providing and fixing on wall face unplasticised PVC moulded fittings/accessories for unplasticised Rigid PVC rain water pipes conforming to IS:13592 Type A including jointing with seal ring conforming to IS:5382 leaving 10mm gap for thermal expansion.
262Bend 87.5 degree 110 mm Bend
263Shoe (Plain) 110 mm Shoe
264Providing and fixing unplasticised -PVC pipe clips of approved design to unplasticised - PVC rain water pipes by means of 50x50x50mm hard wood plugs, screwed with M.S. screws of required length including cutting brick work and fixing in cement mortar 1:4 (1 cement : 4 coarse sand) and making good the wall etc. complete. 110mm
265Providing and laying cement concrete 1:5:10(1 cement : 5 coarse sand : 10 graded stone aggregate 40mm nominal size) around P.V.C /C.I. Soil and waste pipe including bed concrete as per standard design(embedded in the flooring / ground) 110/75 mm diameter
266Providing & fixing G.I. pipes complete with G.I. fittings & clamps including cutting & making good the walls etc.(internal work)Exposed on wall 32mm dia nominal bore
267Painting G.I. pipes and fittings with two coats of anti corrosive bitumastic paint of approved quality.32mm dia nominal bore.
268Providing & fixing G.I. pipes complete with G.I. fittings & clamps including cutting & making good the walls etc. (internal work) Exposed on wall 25mm dia nominal bore
269Painting G.I. pipes and fittings with two coats of anti corrosive bitumastic paint of approved quality. 25mm dia nominal bore.
270Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings including fixing the pipe with clamps at 1.00m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.
271internal work -Exposed on wall
27220mm dia nominal outer dia pipes
27325mm dia nominal outer dia pipes
27432mm dia nominal outer dia pipes
275Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testiang of joints complete as per direction of Engineer in Charge.
276Concealed work including cutting chases and making good the walls etc.
27715mm dia nominal outer dia pipes
27820mm dia nominal outer dia pipes
27925mm dia nominal outer dia pipes
280Providing and fixing 45 cm long unplasticised PVC connection pipe with brass unions. 15mm nominal bore
281Providing & fixing CP brass bib cock of approved quality conforming to IS 8931 15mm nominal bore
282Providing & fixing C.P. brass long body bib cock of approved quality conforming to IS standards and weighing not less than 690 gms. 15mm nominal bore
283Providing & fixing C.P. brass angle valve for basin mixer and gyser points of approved quality conforming to IS 8931 15mm nominal bore
284Providing & fixing C.P. Brass extension nipple (size 15mmx50mm) of approved make and quality as per direction of Engineer-in-charge.
285Providing and fixing gun metal gate valve with wheel of approved quality.
28625mm dia nominal bore
28720 mm dia nominal bore
28832mm dia nominal bore
289Providing and fixing ball valve (brass) of approved quality, High or low pressure, with plastic floats complete
29025 mm nominal bore
29120 mm nominal bore
292Providing and fixing high density ploythylene water storage loft tank with cover, confirming to IS:12701, colour of opaque white or as approved by Engineer-in-charge. The rate includes making necessary holes for inlet, outlet and overflow pipes. The base support i/c fittings & fixtures for tank shall be paid separately.
293Excavating trenches in all kind of soil of required width for pipes, cables etc. including excavation for sockets and dressing of sides, ramming of bottoms, depth upto 1.5 m. including getting out the excavated soil & then returning the soil as required, in layers not exceeding 20cm in depth including consolidating each deposited layer by ramming, watering, etc & disposig of surplus excavated soil as directed within a lead of 50m.Pipes, cables etc. exceeding 80mm dia. But not exceeding 300 mm dia.
294Providing, laying and joining glazed stone ware pipes class SP-1 with stiff mixture of cement mortar in the proportion of 1:1 (1 cement : 1 fine sand) including testing of joints etc. complete.
295100mm diameter
296150mm diameter
297Providing & laying cement concrete 1:5:10 (1 cement :5 coarse sand :10 graded stone aggregate 40mm nominal size) alround S.W. Pipes including bed concrete as per standard design.
298100mm diameter S.W. Pipe
299150mm diameter S.W. Pipe
300Providing and fixing square mouth S.W. Gully trap class SP-1 complete with C.I. grating brick masonry chamber with water tight C.I. cover with frame of 300x300 mm size (inside) the weight of cover to be not less than 4.50 Kg and frame to be not less than 2.70 Kg as per standard design:150 x 100 mm. size P type With Sewer bricks conforming to IS : 4885
301Constructing brick masonry manhole in cement mortar 1:4 (1 cement :4 coarse sand) RCC top slab with 1:2:4 mix (1 cement :2 coarse sand :4 graded stone aggregate 20mm nominal size), foundation concrete 1:4:8 mix (1 cement :4 coarse sand :8 graded stone aggregate 40mm nominal size) inside plastering 12mm thick with cement mortar 1:3 (1 cement :3 coarse sand) finished with floating coat fo neat cement and making channels in cement concrete 1:2:4 (1 cement :2 coarse sand :4 graded stone aggregate 20mm nminal size) finished with a floating coat of neat cement complete as per standard design
302Inside size 90x80cms and 45cms deep including CI cover with frame (light duty) 455x610mm internal diamensions total weight of cover and frame to be not less than 38 kg (weight of cover 23 kg and weight of frame 15kg).
303With FPS bricks of class designation 75
304(i) For Sewer Line
305Extra for depth of man hole size 90x80 cm
306Providing M.S. foot rests including fixing in manholes with 20x20x10 cm cement concrete blocks 1:3:6 (1 cement:3 coarse sand :6graded stone aggregate 20 mm nominal size) as per standard design With 20x20 mm square bar
307Supply and fixing of UPVC S.W.R. pipe type-B confirming to IS-13592 including jointing the pipes with rubber ring,lubricant and UPVC SWR cupler confirming to IS-14735. Also including excavation of treanches cutting of walls and holes and repairing the walls,floors and refilling the trenches as before with supply and cost of other fIttlings such as elbow,bend,tee and y-tee,Cowel including supply of all marerial labour and T&P. Required for proper completion of work.
30875 mm O.D.
309110 mm O.D.
310Supply and fixing of UPVC S.W.R. pipe nahni trap size 100x75,110/90 mm confirming to IS-14735 self cleaning design fixed in PCC 1:2:4 and supply and fixing of 125 mm dia heavy duty CP brass jali.
311Supply and fixing of UPVC S.W.R. Cowel confirming to IS-14735.
312Size 75/90 mm
313Size 110 mm
314FIRE FIGHTING WORK
315Providing, laying, testing & Commissioning of 'C' class heavy duty MS pipe confirming to IS 3589/IS1239 inculding welding, fittings like elbows,tees, langes,tapers,nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of syntetic enamel paint of required shade complete as required:
31625 mm dia
317100 mm dia
318Supplying & fixing single headed internal yard hydrant valve with instantaneous Gunmetal/Stainless Steel coupling of 63 mm dia with cast iron wheel, ISI marked, confirming to IS 5290(type A) with blank Gunmetal/Stainless Steel cap and chain as required:Single headed Gunmetal
319Supplying & fixing orifice plate made out of 6 mm thick stainless steel(grade 304) with orifice of required size to be fitted between flange & landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as required:
320Supplying & fixing 63 mm dia, 15m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. confirming to IS 636(type-A) as required:Gun Metal
321Supplying & fixing First-aid hose Reel with MS construction spray painted in post office red,conforming to IS 884 complete with the following as required. 20 mm nominal internal dia water hose thermoplastic(Textile reinforced) type-2 20 mm nominal internal dia gun metal globe valve & nozzle.Drum and brackets for fixing the equipments on wall.Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket 30 m
322Providing & fixing of pressure switch in M.S. pipe line including connection etc as required.
323Supplying, installation, testing & commissioning of Manual call Boxes of MS constuction in surface/recess with stainless steel chain & hammer assembly complete with glass and push button etc. as required.
324Supplying, installation, testing & commissioning fire alarm sounder with facility to make announcement, mounted in M.S. box(16 SWG) with hinged cover plate & suitable for operation with amplifier i/c line matching trasformer etc. complete as required.
325Supplying, installation, testing & commissioning talk back slave station in surface/recess suitable for operation on simplex mode complete with P.T.T. knob & speaker/microphone cenclosed in a M.S. box(16 SWG)/ABS box with break glass in front etc. complete as required.
326Supplying & laying of 2X1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS/HFFR outer sheath complete as required.
327Supplying & laying 25 mm dia MS flexible pipe with PVC coating along with all ancillaries and accessories like coupler etc. as required.
328Supply and fixing of following sizes of medium class PVC conduit alongwith the accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required: 25mm
329Supply & fixing of fire extinguisher, ABC Type 6.00 kg. capacity(ISI Marked IS:15683 & TAC approved) comlete with initial charge and wall bracket, along with supply of all materials and labour for proper completion of work.
330Supply & fixing of CO2 type fire extinguisher, 4.5 kg. capacity(ISI Marked IS:2878 & TAC approved) comlete with initial charge and wall bracket, along with supply of all materials and labour for proper completion of work.
331Providing/Fixing of Fire Hose cabinet box made out of 18 gauge MS sheet including two coats of post office red paint over one coat of primer with 4 mm, thick glass door in front painted “FIRE” in red luminous paint. The size of the box should be 750 mm X 600 mm X 250 mm size capable of accommodating a pair of hose with coupling and nozzle. The box should be floor mounted type with railway coach lock arrangement and lever for opening the door after breaking the glass complete. Make : Standard/Lifeguard or EQ.
332Supplying and fixing of Self Glow Exit signage for stairs and exits made out from not less than 4 mm of transparent acrylic sheet of 300 x 150 mm size with self illuminated plastic words of 100 mm height suspended from ceiling by means of M.S. chain or fixed of the walls as required and as directed at site..(MAKE : Agni Suraksha (ASES) / Securiton-aka /System Sensor)
333Supplying and fixing of Fire man axe. Make :- Agni Suraksha (ASES) or EQ
334EXTERNAL ELECTRICAL WORK
335Providing and fixing M.V. danger notice plate of 200 mmx150 mm, made of mild steel, at least 2 mm thick, and viterous enameled white on both sides, and with incription in single red colour on front side as required.
336Earthing with GI earth pipe, 600 mm X 600 mm X 6 mm thick including accessories and providing masonary enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc, with charcoal/cock and salt as required.
337Supplying and Laying of 25 mm X 3 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection / terminating with nut, bolt, spring, washer etc. as required.( jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)
338Providing & fixing 6 SWG dia G.I. on surface or in recess for loop earthing as required.
339Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required.
340Supplying & making end termination with brass compression gland and aluminium lugs for the following size of PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
3414 X 16 sqmm. (28mm)
3423.5 X 25 sqmm. (28mm)
3433.5 X 50 sqmm. (35mm)
3443.5 X 95 sqmm. (45mm)
3453.5 X 185 sqmm. (57mm)
346Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep) and refilling etc as required.
347100 mm Dia
348150 mm Dia
349L.T. FEEDER PILLER-01(NEAR GATE)
350Incoming :
3511No. Of 400 Amps 4P FP MCCB of 36 KA service breaking capacity and 400 Amp trip setting.
352Metering : Voltmeter, Ammeter, Indication
353Bus Bar :
3541 Set of 500 Amps TPN Aluminium Bus Bars of suitable length and of cross section . Bus bar shall be insulated by heat shrinkable sleaves & clip on shrouds for joints. Bus bar shall be designed to with stand a fault level of 36 KA at 415 volts.
3553Nos. Phase indicating lamp each lamp shall have one toggle switch .
356Outgoing :
357Phase indication lamps on each outgoing to be provided.
358250Amp 4P MCCB (35kA) - 1 Nos.
359160Amp 4P MCCB (35kA) - 1 Nos.
36063Amp 4P MCB (10kA) - 1 Nos.
36132 Amp DP MCB (10kA) - 1 Nos.
36225 Amp DP MCB (10kA) - 2 Nos.
363L.T. FEEDER PILLER-02(NEAR PUMP HOUSE)
364Incoming :
3651No. Of 160 Amps 4P FP MCCB of 36 KA service breaking capacity and 160 Amp trip setting.
366Metering : Voltmeter, Ammeter, Indication
367Bus Bar :
3681 Set of 200 Amps TPN Aluminium Bus Bars of suitable length and of cross section . Bus bar shall be insulated by heat shrinkable sleaves & clip on shrouds for joints. Bus bar shall be designed to with stand a fault level of 36 KA at 415 volts.
3693Nos. Phase indicating lamp each lamp shall have one toggle switch .
370Outgoing :
371Phase indication lamps on each outgoing to be provided.
372100Amp 4P MCCB (35kA) - 2 Nos.
37363Amp 4P MCB (10kA) - 1 Nos.
37425 Amp DP MCB (10kA) - 2 Nos.
375Supplying and laying of aluminium conductor PVC insulated armoured served sheathed cable 1100 volts grade at the depth of 750 mm bellow ground level over a cushion of 75 mm thick sand all around and protected with burnt bricks on side and on top as directed by Engineer-Incharge ,complete in all respect including excavation and refilling. The armouring of the cable shall be properly connected with the earth conductor by clamps etc.
37616 sqmm 4 core
37725 sqmm 3.5 core
37850 sqmm 3.5 core
379185 sqmm 3.5 core
38010 KL O.H.T. OF 15.00 M STAGING
381Earth work in exacavation in ordinary soil ( loan clay orsand) including lift upto 1.5 m and leadup to 30m.&including filling watering& ramming of excavated earth in to trenches or in to the space between the building & the sides of foundation trenches or in to the plinth and removal & disposal of surplus excavated earth as directed by the Engineer i/c upto a distance of 30 m from the foundation trenches.
382Providing and laying in cement concrete 1:4:8 (1 cement :4 coarse sand :8 graded stone ballest 40 mm nominal size) and curing complete,including cost of form-work,in foundation and floors.
383R.c.c. work with cement approved coarse sand and 2 cm. (3/4\\") guage approved stone ballast in the proportion 1:6,(1 cement :6 aggregate) in lintels of doors and windows excluding supply of reinforcement and its fixing and binding the same with 24 B WG binding wire and including necessary centering and of all materials, labour and tools and plants etc, required for proper completion of the works. strength of the concrete shall not beless than M-200 for slabs , beams ,columns
384As in item 4 above but in R.C.C. Raft foundation and footing with approved stone ballast.
385Mild steel or iron in plain work such as reinforced concrete or reinforced, brick work (when not included in anover all rates ) wrought to required shape as necessary including bending for proper completion of the work and including supply of steel its wastage bend hooks and authorised over lapping shall be measured upto floor two level.
386M.S.Work in railing
387Painting Ist coat over priming coat (but excluding cost of priming coat) on steel and other metal surfaces up to 10 cm. width or girth or small articles not exceeding 0.10sqm in area white superior synthetic enamel such as LUXOL3,Hi-gloss apcolite superlac, DULUX specified brushing to give an even shade and including cleaning the surface of all dirt,dust and other foreign matter sand papering and stoping including cost of all materials, labour tools and plants etc. required for proper completion of the work.
388Centering and shuttering including strutting, propping etc. and removal of form for :
389Foundations, footings, bases of columns, etc. for mass concrete
390Suspended floors, roofs, landings, balconies and access platform with water proof ply 12 mm thick
391Lintels, beams, plinth beams, girders, bressumers and cantilevers with water proof ply 12 mm thick
392Columns, Pillars, Piers, Abutments, Posts and Struts
393Cost for inlet outlet washout overflow
394meter gauge etc.M.R.
395Cost for Distributioin system M.R.
396Cost of Tubewell
397COST OF C.C. ROAD
398COST OF INTERLOCKING
399COST OF BARBED WIRE ON BOUNDARY WALL
400GST Extra as applicable Please Enable Macros to View BoQ information

Other Detail

Information Source https://etender.up.nic.in
Download FileName File Description File Size
Download 0bb0f80b-cc58-4741-ae71-ce893b1147e7.html Tender Documents 0 KB
Download BIDDOC14.pdf Tender Documents 0 KB
Download BOQ_2139710.xls Tender Documents 0 KB
Download Tendernotice_1 (15).pdf Tender Documents 0 KB
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.