| 1 | Cat (A) -Items to be supply and fixing |
| 2 | Taking down existing point wiring carefully and making good disturbed surface of wall & floors etc. all as per the direction of Engineer In-charge. |
| 3 | S & F, One light point or one fan point with- a) 2.5 sq. mm. stranded Cu. Conductor PVC sheathed cables as per IS-694-1990 (make:-Jonson/Supercab/Finolex/Polycab or equivalent to mention make). (b) Stove enamelled steel conduit of size 20/25 mm. Dia. and 1.5 to 2.0 mm thick as per IS-9537 (P-2) 1981 and accessories, joint boxes, m. s. box type terminal boards with laminated top for fixing switches, sockets & fan regulators etc.(c) Continuous G.I. earth wire of 18 SWG. Complete, all as per the direction of Engineer-In-charge. |
| 4 | S & F, One 3 pin 5 Amp. socket outlet independent point with- a) 2.5 sq. mm. Stranded Cu. Conductor PVC sheathed cables as per IS-694-1990. (make – Jonson/Supercab/Finolex/polycab or equivalent to mention make). b) Stove enamelled steel conduit of size 20/25 mm. Dia. and 1.5 to 2.0 mm thick as per IS -9537 (P-2) 1981 and accessories, joint boxes, m. s. box type terminal boards with laminated top for fixing switches, sockets & fan regulators etc.(c)Continuous G.I. earth wire of 18 SWG. Complete, all as per the direction of Engineer-In-charge. |
| 5 | S & F, One 3 pin 5 Amp. socket outlet point on same board with 2.5 sq. mm. Stranded Cu. Conductor PVC sheathed cables as per IS-694-1990 (make – Jonson/Supercab/Finolex/polycab or equivalent to mention make). all as per the direction of Engineer-In-charge. |
| 6 | S & F, One 3 pin 15 Amp. Socket outlet point with- (a) 4 sq. mm. stranded, Copper. Conductor PVC sheathed cables as per IS-694-1990 make: - Jonson/Supercab/Finolex/Polycab). (b) Stove enamelled steel conduit of size 20/25 mm. Dia. and 1.5 to 2.0 mm thick as per IS-9537 (P-2) 1981 and accessories, joint boxes, m. s. box type terminal boards with laminated top for fixing switches, sockets & fan regulators etc.(c) Continuous G.I. earth wire of 18 SWG. complete, all as per the direction of Engineer-In-charge. |
| 7 | S & F, piyano Switch flush type 5 Amp. Single pole one way white colour as per IS- 3854/1997 (make:-Anchor/Cona or equivalent to mentioned make) all as per the direction of Engineer-In-charge. |
| 8 | Supply & Fixing Socket outlet 2 in 1 3 pin, 5 Amp. Flush type as per IS- 1293/1988 (make:-Anchor/Cona/or equivalent to mentioned make), all as per the direction of Engineer-In-charge. |
| 9 | Supply & Fixing Lamp holder, PVC/polycarbonate type with back plate for batten/Angle fitting as per IS-1258/1987 (make:-Anchor/or equivalent to mentioned make), all as per the direction of Engineer-In-charge. |
| 10 | S & F, Ceiling rose, surface bakelite 2/3 terminals as per IS- 371/1979 (make :- Anchor/Cona or equivalent to mentioned make) all as per the direction of Engineer-In-charge. |
| 11 | S & F, Switch socket combination 2 in1, 3 pin, 5 & 15 Amp, flush type. As per IS- 4615/1968 (make:- Anchor/Cona or equivalent to mentioned make) all as per the direction of Engineer-In-charge. |
| 12 | Supply & Fixing of stepped type, socket shape, Electronic five step fan speed regulator (make:-Anchor/Cona/or equivalent to mentioned make ), all as per the direction of Engineer-In-charge. |
| 13 | Supply and fixing LED light fitting 1X18 Watt, 220 volt AC, decorative box type with driver, holder including LED tube light (T8) connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete including base insulator/wooden round block. (make:-Bajaj/Phillips/Crompton/ or equivalent to mentioned make) all as per the direction of Engineer-In-charge. |
| 14 | Supply & Fixing sheet metal enclosure for single pole & neutral, with socket, plug top 2 pin & earth, and MCB of 20amp capacity (make – MDS/Havells/or equivalent to mentioned make), all as per the direction of Engineer-In-charge. |
| 15 | S & F, MCB isolator 3pole, 100 Amp, AC-22 category confirming to IS- 13947-3 (make – MDS/HPL/Havells/Standard or equivalent to mentioned make) all as per the direction of Engineer-In-charge. |
| 16 | S & F Exhaust fan steel body AC single phase 230V of size 300 mm sweep, with blade, frame and louvers (make:-Bajaj/Phillips/ Crompton/or equivalent to mentioned make), all as per the direction of Engineer-In-charge. |
| 17 | S & F, sheet metal enclosure for MCB. DB. Single pole & Neutral, 2 way without bus bar, 230 volt, Surface mounting type with including dummy packing. (make – MDS/HPL/Havells/Standard or equivalent to mentioned make) all as per the direction of Engineer-In-charge. |
| 18 | S & F, sheet metal enclosure for MCB. DB. Triple pole & Neutral, 4 way (for Each phase), 415 volt, double door Surface mounting type, comp. with copper bus bar and neutral link etc. (make – MDS/HPL/Havells/Standard or equivalent to mentioned make) all as per the direction of Engineer-In-charge. |
| 19 | Supply & Fixing single, Sheet metal enclosure (MCB DB), Surface mounting type, single pole & neutral, 12 way, consisting of 40 Amp. DP isolator-01 no, single pole MCB 240 V, 10 KA, B curve 10 & 20 Amp. capacity - 10 no. (make–MDS/Havells/or equivalent to mentioned make ) along with wooden fixing board, all as per the direction of Engineer-In-charge. |
| 20 | Excavation n.exc.1.5 meter wide and 2.4 meter depth in soft loose soil and getting out etc. for earth pit of power system complete as per the direction of Engineer-In-charge. |
| 21 | Returning, filling in including spreading, levelling and well ramming in layers of excavated soft loose soil in earth pit & trenches and making good disturbed surface, complete as per the direction of Engineer-In-charge. |
| 22 | Supply and Fixing of Earthing complete with G.I. earth plate electrode 600 X 600 X 6 mm thick buried directly in the ground vertically to a depth not less than 2.25 meter below normal ground level with top edge of the earth plate at a depth not less than 1.5 meter below ground level, connected to galvanised earth strip 25X4 mm as earthing lead up to test point, all as specified and shown in electrical plate no. 3 of SSR part 1 and testing on completion, all as per the direction of Engineer-In-charge. |
| 23 | Supply and fixing 6 mm diameter G I wire for earthing connection, all as per the direction of Engineer-In-charge. |
| 24 | S&F, of GI steel tubes of medium grade of 40 mm bore for protection of G I strip complete as per the direction of Engineer-In-charge. |
| 25 | S & F, of GI steel tubes of medium grade of 20 mm bore, 1.8 meter long with funnels for provision of water pipe as per the direction of Engineer In-charge. |
| 26 | M&L for provision of cement concrete of type- B1 1:2:4, 20 mm graded aggregate in foundation for earth pit , complete as per the direction of Engineer-In-charge. |
| 27 | Material &Labour for providing and fixing of 13 nos. precast cement concrete earth pit chamber of size 0.5X0.5X0.5 meter having 10 cm wall thick made from cement concrete of type- B1, 1:2:4, 20 mm graded aggregate, etc. all as per the direction of Engineer-In-charge. |
| 28 | M & L for provision of mild steel TMT bars of 8 mm dia. Including m. s. binding wire for reinforcement in PCC covers etc. all as per the direction of Engineer In-charge. Each cover require 10 pc of 0.5 meter ( 8 for mesh & 2 for handle). |
| 29 | S & F sub main wiring a) 2x6.0 sq. mm +1x4.0 sq. mm earth wire with stranded copper conductor PVC insulated ,1100 Volts grade cable (Red, Yellow Blue and Black colour) confirming to IS-694-1990 (Make- Jonson/Supercab/Finolex/Polycab or equivalent to mention make) b) Stove enamelled steel conduit of size 20/25 mm. Dia. and 1.5 to 2.0 mm thick as per IS-9537 (P-2) 1981 and accessories, joint boxes etc. (c) Continuous G.I. earth wire of 18 SWG. Complete, all as per the direction of Engineer-In-charge. |
| 30 | Supply and fixing 240V, 10 KA 'B' curve miniature circuit breaker (MCB) of single poles and current carrying capacity 6-20 AMP, in the MCB DB Complete with connection testing and commissioning. (make – MDS/Havells/ or equivalent to mentioned make), all as per the direction of Engineer In-charge. For 6 amp-168 & 10 amp-612. |
| 31 | Supply and fixing 240V, 10 KA 'C' curve miniature circuit breaker (MCB) of single poles with neutral (SPN and current carrying capacity 32 AMP, in the MCB DB Complete with connection testing and commissioning. (make – MDS/Havells/ or equivalent to mentioned make ), all as per the direction of Engineer-In-charge. |
| 32 | S & F Main switch 100 amp SDF (Switch Disconnect or Fuse Unit) in CRCA Sheet Enclosure, 100 Amp, 3 Pole with Neutral 415 Volt with extension box for suitable termination of cable & also include the glands lugs and dismantling of Existing main switch Confirming to Is/IEC 60947-3, Make: SIEMEN, L&T, ABB or Equivalent. all as per the direction of Engineer-In-charge. |
| 33 | Cat (B) - Buy Back Items |
| 34 | Credit to contractor for old removed point wiring material which consists of old ms conduit ,main switch, Al. conductor single core wires, old switches, sockets etc, all as per the direction of Engineer-In-charge. Please Enable Macros to View BoQ information |