| 1 | B & R Division Items |
| 2 | Testing of earth Resistance of existing earth pit as and when required using earth resistance testing equipments as directed by the Engr-In- Charge and producing the test result for recording purpose all as directed by the Engr in Charge. Note: 1)The contractor shall be asked to carry out the Earth Test as and when required as a whole or as a part of the qty. 2) Testing of each earth pit shall be measured as one unit. 3)All test result to be entered in a register properly bound and covered and to be submitted to the Engr-In-Charge 4) For the purpose of testing contractor shall supply all equipments and apparatus/instruments at his own cost without any extra claim ] |
| 3 | Material and labour for repairs to Earth pit including replacement of broken RCC cover by new 50 mm thick pre cast RCC ( 1:2:4) type B-1 cover slab (reinforced with 8 mm dia deformed bar @ 15 cm C/C both ways and suitable handle of 10 mm dia round bar)and other allied works as directed by the Engr in Charge |
| 4 | Taking out of old air termination rod of any type and any size from building including dismantling and removing (except serviceable strips for re-fixing) materials from work site complete all as specified and directed. |
| 5 | Supply and fixing air termination single pointed, aluminium rod 12mm dia and 300mm long fixed on galvanised iron pipes with copper/ aluminium/ GI strip for earth conductivity to ground complete all as specified and directed. |
| 6 | Supply and fixing air termination single pointed, Copper rod 12mm dia and 300mm long fixed on galvanised iron pipes with copper/ aluminium/ GI strip for earth conductivity to ground complete all as specified and directed. |
| 7 | Re-fixing of old serviceable tilted air termination rod of any size and type after straightening & dressing with and including suitable nut, bolts and washers to earth strip complete all as specified and directed.(Note: Pipe/ PCC work shall be measured and paid seperately). |
| 8 | Taking down old Copper/ GI/ Aluminium Strip of any size and any type from building/hangar (roof/down conductor)/ pipe/ trench including dismantling and removing (except serviceable strips for re-fixing) materials from work site complete all as specified and directed. |
| 9 | Supply and fixing copper strip 20mm x 3.15 mm with fixing screws for conductors/ earth lead including brazing and nut bolts jointing at all joints for building/ equipment laid through pipe/ trench/ surface complete all as specified and directed. |
| 10 | Supply and fixing galvanised iron strip 32mm x 6mm with fixing screws for conductors/ earth lead including welding and nut bolts jointing at all joints for building/ equipment laid through pipe/ trench/ surface complete all as specified and directed. |
| 11 | Supply and fixing aluminium strip 25mm x 3mm Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc.complete all as specified and directed. |
| 12 | Re-fixing of old serviceable (serviceable strips as obtained from taking down) Aluminium Strip of any size and type after straightening & dressing with and including saddles/ insulators with srews for fixing and making good disturbed strip complete all as specified and directed. |
| 13 | Taking out of old unserviceable test point terminal block of any type and any size including dismantling and removing materials from work site complete all as specified and directed. |
| 14 | M&L complete for test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm, drilled and screwed including 3 nos. 8mmdia 25mm long hex, head screw all as specified and directed. |
| 15 | Supply and fixing in replacement of GI funnel with wire mesh for earting pits of existing size complete all as specified and directed. |
| 16 | Taking out old unserviceable earthing pit of any type complete with connected accessories including dismantling and removing materials from work site complete all as specified and directed. |
| 17 | M&L for earthing complete with galvanised steel earth plate 600mm x 600mm x 6mm thick electrode and 32mm x 6mm galvanised iron strip as earthing lead burried directly in ground vertically (earth pit not less than 2.25mtr deep below ground level) with top edge of the plate not less than 1.5mtr below normal ground level, the earth plate surrounded by adequate quantity of charcoal dust and common salt to a packed thickness of 15 cm on all sides connected to GI strip 32mm x 6mm as earth lead by means of bolts, nuts, check nuts and washers (including welding) of galvanised iron or steel and connected to main switch board / panel/ test point at the other including necessary earth work in any type of soil, returning filling in and removal of surplus soil, concrete pit in PCC (1:3:6) type C1, pre cast RCC 1:2:4 type B1 cover slab 54cm x 54cm x 5cm reinforce with 8mm dia bar TMT @150mm centre to centre both ways with one handle for lifting made out 8mm dia MS bar with wire mesh funnel, 20mm GI tubing medium grade for watering and 40mm GI tubing light grade for protection, test point, testing on completion all as shown in Electrical Plate No 3 of SSR Part-I complete all as specified and directed. Please Enable Macros to View BoQ information |
| 18 | M&L for earthing complete with galvanised steel earth plate 600mm x 600mm x 6mm thick electrode and 32mm x 6mm galvanised iron strip as earthing lead burried directly in ground vertically (earth pit not less than 2.25mtr deep below ground level) with top edge of the plate not less than 1.5mtr below normal ground level, the earth plate surrounded by adequate quantity of charcoal dust and common salt to a packed thickness of 15 cm on all sides connected to GI strip 32mm x 6mm as earth lead by means of bolts, nuts, check nuts and washers (including welding) of galvanised iron or steel and connected to main switch board / panel/ test point at the other including necessary earth work in any type of soil, returning filling in and removal of surplus soil, concrete pit in PCC (1:3:6) type C1, pre cast RCC 1:2:4 type B1 cover slab 54cm x 54cm x 5cm reinforce with 8mm dia bar TMT @150mm centre to centre both ways with one handle for lifting made out 8mm dia MS bar with wire mesh funnel, 20mm GI tubing medium grade for watering and 40mm GI tubing light grade for protection, test point, testing on completion all as shown in Electrical Plate No 3 of SSR Part-I complete all as specified and directed. Please Enable Macros to View BoQ information |