| 1 | Excavation in trenches n. exc 1.5 m wide and n.exc 1.5 m as in foundations or for laying of cables, fixing of poles, etc and getting out in any type of soil complete all as specified and as directed. |
| 2 | Excavation in trenches n. exc 1.5 m wide and exc 1.5 m but n exc 3.0m in depth for foundation or for fixing of poles, etc and getting out in any type of soil complete all as specified and as directed. |
| 3 | M&L for sand filling around the cable with approved quality coarse sand for sand cushioning of Under ground cable including spreading and punning down to desired thickness complete all as specified and as directed. NOTE: Punned thickness shall be measured for payment purpose. |
| 4 | Supply and laying burnt brick sub class 'B' locally available best quality laid in trenches for protections of under ground cable complete all as specified and as directed. |
| 5 | Returning, filling in trenches including spreading leveling, watering and well ramming in layers not exceeding 25 cm thick in any type of soil complete all as specified and as directed. |
| 6 | Removing excavated soil to a distance not exceeding 50 metre and depositing where directed at a level not exceeding 1.5 metre above the starting point complete all as specified and as directed. |
| 7 | Demoltion of PCC of any description and in any position including removal of debris outside MoD land complete all as specified and as directed. |
| 8 | Breaking of P.C.C coping of any description poles, taking out unserviceable cable junction box, unserviceable cables including removalof debries outside MoD land complete all as specified and as directed. |
| 9 | M&L for Cutting existing metal/bituminus road/PCC walk way/any type of tile works n.exc 0.45m width and n.exc 0.90 m in depth including all connected earth work and making good disturbed surfaces matching with the existing specification and finish including refixing of old tiles including removalof debries outside MoD land complete all as specified and as directed. |
| 10 | M&L for plain cement concrete (1:4:8) type D2 (using 40 mm graded stone aggregrates) as in foundations filling, coping for pole and mass concreate complete all as specified and as directed. |
| 11 | M&L for plain cement concrete (1:3:6) type C2 (using 40 mm gradeed stone aggregrates) as in foundations filling, coping for pole and mass concrete complete all as specified and as directed. |
| 12 | M&L for plain cement concrete type B1 (1:2:4) using 20mm graded stone aggregrates) as in coping, kneelers, columns posts and like etc including watering, slghtly rounded or chamfered angles and throating including necessary form work complete all as specified and as directed. |
| 13 | M&L for Brick work with subclass ‘B’ bricks, straight or curved on plan exc 6m mean radius built in cement mortar 1:4 complete all as specified and as directed. |
| 14 | M&L for 10 mm thick rendering on faces of brick works or concrete surface in cement morter (1:4) and finish surfaces even and smooth without using extra cement complete all as specified and as directed. |
| 15 | S&F GI pipe light grade 50mm tubes with all fitting and fixed complete to walls and ceilings or laid in floors complete all as specified and as directed |
| 16 | S&F GI pipe light grade 80 mm tubes with all fitting and fixed complete to walls and ceilings or laid in floors complete all as specified and as directed |
| 17 | Supply and erecting Steel tubular swaged poles with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-31, 9 metres long including 4 Nos nuts and bolts of suitable size and including painting two coats of aluminium paint over & including a coat of red oxide zinc chrome primer on external surface and black bitumen paint on internal surface including taking down old pole, any type & length complete all as specified and as directed. |
| 18 | S&F in replacement MS Pole Cap 150 mm long and sitable dia for steel tublar pole of length 8.5 to 9 mtr duly fabricated with MS pipe (medium grade) and MS Sheet (3mm) and two numbers 8 mm dia 32 mm long MS Bolt and nut duly welded with the pipe with & including applying two coats of aluminium paint over & including one coat of red oxide metal primer complete all as specified and as directed. |
| 19 | S&F in repairs 1100 V grade FRLSH PVC insulated stranded copper cables of size 1.0 sqmm 3 core drawn through street light poles brackes/PVC conduits connecting from the junction box to street light fittings complete all as specified and as directed. |
| 20 | S&F in repairs LED street light with IP 66 (Minimum) protection and front toughen glass luminaries of capacity 30 watt with high power LED and ensure uniform light distribution complete all as specified and as directed. |
| 21 | S&F in repairs LED street light with IP 66 protection and front toughen glass luminaries of capacity 60 watt with high power LED and ensure uniform light distribution complete all as specified and as directed. |
| 22 | S&F in repairs LED security light with IP 66 protection and front toughen glass luminaries of capacity 70 watt with high power LED and ensure uniform light distribution complete all as specified and as directed. |
| 23 | S&F in repairs LED street light with IP 66 protection and front toughen glass luminaries of capacity 120 watt with high power LED and ensure uniform light distribution complete all as specified and as directed. |
| 24 | S&F in repairs (Cool/ Warm White) LED flood light of IP protection 66 with front toughen glass luminaries of capacity 30 watt with high power LED and ensure uniform light distribution complete all as specified and as directed. |
| 25 | S&F in repairs (Cool/ Warm White) LED flood light of IP protection 66 with front toughen glass luminaries of capacity 50 watt with high power LED and ensure uniform light distribution complete all as specified and as directed. |
| 26 | S&F in repairs (Cool/ Warm White) LED flood light of IP protection 66 with front toughen glass luminaries of capacity 70 watt with high power LED and ensure uniform light distribution complete all as specified and as directed. |
| 27 | S&F in repairs (Cool/ Warm White) LED flood light of IP protection 66 with front toughen glass luminaries of capacity 100 watt with high power LED and ensure uniform light distribution complete all as specified and as directed. |
| 28 | S&F in repairs (Cool/ Warm White) LED flood light of IP protection 66 with front toughen glass luminaries of capacity 120 watt with high power LED and ensure uniform light distribution complete all as specified and as directed. |
| 29 | S&F in repairs 20 watt LED post top lantrerns fittings made in cast aluminium spigot, housing with decorative clear acrylic diffuser and IP 65 protection with and including LED lamp and all necessory electric connection with from junction box to post top lantern complete all as specified and as directed. |
| 30 | S&F in repairs 40 watt LED post top lantrerns fittings made in cast aluminium spigot, housing with decorative clear acrylic diffuser and IP 65 protection with and including LED lamp and all necessory electric connection with from junction box to post top lantern after complete all as specified and as directed. |
| 31 | S&F MS Fabrication work consisting of wire mesh, MS Angle square pipe, flat, etc duly cut into shape and size to fabricate cage for post top lanterns mounted on boundary wall including grouting on wall, and including applying one coat of red oxide metal primar over & including two coats of synthetic enamel paint complete all as specified and as directed. |
| 32 | S&F Mild steel angle grade Fe 310-0 as in framing of duct cover including hinge and locking arrangement complete all as specified and directed. |
| 33 | S&F in repairs thermoplastic street light junction box, weather proof having ingress protection level IP-66 and dually fixed with Aluminium flat clamp and support made of 25mm x 3mm/Flush in existing wall, duly painted with 2 coats of aluminium paint over & including a coat of red oxide metal prmer including 1 no 5 way cable connector suitable to connect 16 Sqmm Aluminium cable 3 nos polymide cable gland having sealing range 17-25 mm with 1 no 19 mm PVC blend complete all as specified and as directed. |
| 34 | Disconnecting and taking up old unserviceable cable from trench/pipe cable tray etc and keeping aside for removal from site complete all as specified and as directed. |
| 35 | Supply and laying under ground heavy duty XLPE insulated, armoured, stranded aluminium conductor cable 1100 volts grade, cross-sectional area 10 sqmm, 2 core in trenches / through pipe in road crossing / plinth/ drain/ duct/ floor along pole / wall /ceillings etc complete all as specified and as directed.Note:- Earth work, bricks protection, sand cushioning shall be measured and paid seperately. |
| 36 | Supply and laying under ground heavy duty XLPE insulated, armoured , stranded aluminium conductor cable 1100 volts grade, cross-sectional area 10 sq. mm 4 core in trenches / through pipe in road crossing / plinth/ drain/ duct/ floor along pole / wall /ceillings etc complete all as specified and as directed.Note:- Earth work, bricks protection, sand cushioning shall be measured and paid seperately. |
| 37 | Supply and laying under ground heavy duty XLPE insulated, armoured, stranded aluminium conductor cable 1100 volts grade, cross-sectional area 16 sqmm 4 core in trenches / through pipe in road crossing / plinth/ drain/ duct/ floor along pole / wall /ceillings etc complete all as specified and as directed.Note:- Earth work, bricks protection, sand cushioning shall be measured and paid seperately. |
| 38 | Supply and laying under ground heavy duty XLPE insulated, armoured, stranded aluminium conductor cable 1100 volts grade, cross-sectional area 25sq. mm 4 core in trenches / through pipe in road crossing / plinth/ drain/ duct/ floor along pole / wall /ceillings etc complete all as specified and as directed. Note:- Earth work, bricks protection, sand cushioning shall be measured and paid seperately. |
| 39 | Supply and laying under ground heavy duty XLPE insulated, armoured, stranded aluminium conductor cable 1100 volts grade, cross-sectional area 35 sq. mm 3.5 core in trenches / through pipe in road crossing / plinth/ drain/ duct/ floor along pole / wall /ceillings etc complete all as specified and directed by the Engr- in- Charge. Note:- Earth work, bricks protection, sand cushioning shall be measured and paid seperately. |
| 40 | Supply and laying under ground heavy duty XLPE insulated, armoured, stranded aluminium conductor cable 1100 volts grade, cross-sectional area 70 sq. mm 3.5 core in trenches / through pipe in road crossing / plinth/ drain/ duct/ floor along pole / wall /ceillings etc complete all as specified and as directed.Note:- Earth work, bricks protection, sand cushioning shall be measured and paid seperately. |
| 41 | Supply and laying for under ground heavy duty XLPE insulated, armoured, stranded aluminium conductor cable 1100 volts grade, cross-sectional area 95 sq. mm 3.5 core in trenches / through pipe in road crossing / plinth/ drain/ duct/ floor along pole / wall /ceillings etc complete all as specified and as directed.Note:- Earth work, bricks protection, sand cushioning shall be measured and paid seperately. |
| 42 | Supply and laying under ground heavy duty XLPE insulated, armoured, stranded aluminium conductor cable 1100 volts grade, cross-sectional area 120 sq. mm 3.5 core in trenches / through pipe in road crossing / plinth/ drain/ duct/ floor along pole / wall /ceillings etc complete all as specified and directed.Note:- Earth work, bricks protection, sand cushioning shall be measured and paid seperately. |
| 43 | Supply and laying under ground heavy duty XLPE insulated, armoured, stranded aluminium conductor cable 1100 volts grade, cross-sectional area 150 sq. mm 3.5 core in trenches / through pipe in road crossing / plinth/ drain/ duct/ floor along pole / wall /ceillings etc complete all as specified and as directed.Note:- Earth work, bricks protection, sand cushioning shall be measured and paid seperately. |
| 44 | Supply and laying under ground heavy duty XLPE insulated, armoured, stranded aluminium conductor cable 1100 volts grade, cross-sectional area 185 sq. mm 3.5 core in trenches / through pipe in road crossing / plinth/ drain/ duct/ floor along pole / wall /ceillings etc complete all as specified and as directed.Note:- Earth work, bricks protection, sand cushioning shall be measured and paid seperately. |
| 45 | Supply and laying under ground heavy duty XLPE insulated, armoured, stranded aluminium conductor cable 1100 volts grade, cross-sectional area 240 sq. mm 3.5 core in trenches / through pipe in road crossing / plinth/ drain/ duct/ floor along pole / wall /ceillings etc complete all as specified and directed by the Engr- in- Charge. Note:- Earth work, bricks protection, sand cushioning shall be measured and paid seperately. |
| 46 | Supply and laying under ground heavy duty XLPE insulated, armoured, stranded aluminium conductor cable 1100 volts grade, cross-sectional area 300 sq. mm 3.5 core in trenches / through pipe in road crossing / plinth/ drain/ duct/ floor along pole / wall /ceillings etc complete all as specified and as directed.Note:- Earth work, bricks protection, sand cushioning shall be measured and paid seperately. |
| 47 | Supply and laying under ground heavy duty XLPE insulated, armoured, stranded aluminium conductor cable 1100 volts grade, cross-sectional area 400 sq. mm 3.5 core in trenches / through pipe in road crossing / plinth/ drain/ duct/ floor along pole / wall /ceillings etc complete all as specified and as directed.Note:- Earth work, bricks protection, sand cushioning shall be measured and paid seperately. |
| 48 | M&L for end termination of LT Underground cables by providing single compression type chromium plated heavy duty brass cable glands including check nuts etc.and heavy duty aluminium cable lugs of size 2 Core10 sq mm including cutting holes in the gland plate and connection complete in the panel board by providing galvanised steel bolts,nuts, flat washers & spring washers complete all as specified and as directed.Make of cable gland & Lugs : DOWELL'S / UML / COSMOS or equivalent as approved by GE |
| 49 | M&L for end termination of LT Underground cables by providing single compression type chromium plated heavy duty brass cable glands including check nuts etc.and heavy duty aluminium cable lugs of size 2 Core16 sq mm including cutting holes in the gland plate and connection complete in the panel board by providing galvanised steel bolts,nuts, flat washers & spring washers complete all as specified and as directed.Make of cable gland & Lugs : DOWELL'S / UML / COSMOS or equivalent as approved by GE |
| 50 | M&L for end termination of LT Underground cables by providing single compression type chromium plated heavy duty brass cable glands including check nuts etc.and heavy duty aluminium cable lugs of size 4 Core 35 sq mm including cutting holes in the gland plate and connection complete in the panel board by providing galvanised steel bolts,nuts, flat washers & spring washers complete all as specified and as directed.Make of cable gland & Lugs : DOWELL'S / UML / COSMOS or equivalent as approved by GE |
| 51 | M&L for end termination of LT Underground cables by providing single compression type chromium plated heavy duty brass cable glands including check nuts etc.and heavy duty aluminium cable lugs of size 3.5 Core 35 sq mm including cutting holes in the gland plate and connection complete in the panel board by providing galvanised steel bolts,nuts, flat washers & spring washers complete all as specified and as directed.Make of cable gland & Lugs : DOWELL'S / UML / COSMOS or equivalent as approved by GE |
| 52 | M&L for end termination of LT Underground cables by providing single compression type chromium plated heavy duty brass cable glands including check nuts etc.and heavy duty aluminium cable lugs of size 3.5 Core 50 sq mm including cutting holes in the gland plate and connection complete in the panel board by providing galvanised steel bolts,nuts, flat washers & spring washers complete all as specified and as directed.Make of cable gland & Lugs : DOWELL'S / UML / COSMOS or equivalent as approved by GE |
| 53 | M&L for end termination of LT Underground cables by providing single compression type chromium plated heavy duty brass cable glands including check nuts etc.and heavy duty aluminium cable lugs of size 3.5 Core70 sq mm including cutting holes in the gland plate and connection complete in the panel board by providing galvanised steel bolts,nuts, flat washers & spring washers complete all as specified and as directed.Make of cable gland & Lugs : DOWELL'S / UML / COSMOS or equivalent as approved by GE |
| 54 | M&L for end termination of LT Underground cables by providing single compression type chromium plated heavy duty brass cable glands including check nuts etc.and heavy duty aluminium cable lugs of size 3.5 Core 95 sq mm including cutting holes in the gland plate and connection complete in the panel board by providing galvanised steel bolts,nuts, flat washers & spring washers complete all as specified and as directed.Make of cable gland & Lugs : DOWELL'S / UML / COSMOS or equivalent as approved by GE |
| 55 | M&L for end termination of LT Underground cables by providing single compression type chromium plated heavy duty brass cable glands including check nuts etc.and heavy duty aluminium cable lugs of size 3.5 Core 120 sq mm including cutting holes in the gland plate and connection complete in the panel board by providing galvanised steel bolts,nuts, flat washers & spring washers complete all as specified and as directed.Make of cable gland & Lugs : DOWELL'S / UML / COSMOS or equivalent as approved by GE |
| 56 | M&L for end termination of LT Underground cables by providing single compression type chromium plated heavy duty brass cable glands including check nuts etc.and heavy duty aluminium cable lugs of size 3.5 Core 150-300 sq mm including cutting holes in the gland plate and connection complete in the panel board by providing galvanised steel bolts,nuts, flat washers & spring washers complete all as specified and as directed.Make of cable gland & Lugs : DOWELL'S / UML / COSMOS or equivalent as approved by GE |
| 57 | S&F Heat Shrink type straight through cable jointing kit for 1.1 KV grade Under Ground XLPE insulated Aluminium Cable complete with Jointing material and other connected accessories suitable for 3.5 / 4 core 10 to 16 sqmm complete all as specified and as directed. |
| 58 | S&F Heat Shrink type straight through cable jointing kit for 1.1 KV grade Under Ground XLPE insulated Aluminium Cable complete with Jointing material and other connected accessories suitable for 3.5 / 4 core 25 to 50 sqmm complete all as specified and as directed. |
| 59 | S&F Heat Shrink type straight through cable jointing kit for 1.1 KV grade Under Ground XLPE insulated Aluminium Cable complete with Jointing material and other connected accessories suitable for 3.5 / 4 core 70 to 120 sqmm complete all as specified and as directed. |
| 60 | S&F Heat Shrink type straight through cable jointing kit for 1.1 KV grade Under Ground XLPE insulated Aluminium Cable complete with Jointing material and other connected accessories suitable for 3.5 / 4 core 150 to 240 sqmm complete all as specified and as directed. |
| 61 | M&L for painting external surfaces of steel tubular poles and brackets of height upto 9m above ground level after preparation of old painted and rusted surfaces with two coats of aluminium paint over a coat of red oxide primer and writing pole No. with black colour on round yellow background or pasting of sticker 100 mm dia (yellow colour) with black lettering 50mm complete all as specified and as directed. |
| 62 | S&F in repairs Astronomical Street light Panel three phase for output rating of 6 KW with in-built short circuit protection and complete internal wiring etc complete all as specified and as directed. |
| 63 | M&L for making of 20mm hole in steel tublar pole, by using drill/electric arc welding etc at a level 0.9 mtr above ground level and 100mm below the bottom connecting cable complete all as specified and directed. |
| 64 | S&F in repairs GI bracket on street light pole/ boundary wall for post top lantern made of 40 mm dia light grade GI pipe including fixing clamps, nuts and bolts,/cement work and painting with two coats of aluminium paint over a coat of red oxide metal primer complete for maximum length of 1.20 mtr complete all as specified and directed. |
| 65 | S&F in repairs low density poly ethylene (LDPE) pipe, flexible type of pressure rating 6.0 kg/sqm laid through the coping of the poles for passing of pipes for bore of pipe 50mm complete all as specified and directed. |
| 66 | S&F in repairs MCCB 40 Amps, 16 KA 4-Pole type, with fixed magnetic & adjustable (80% - 100%) thermal release including all arrnagement for mounting and testing, operating on 415V, 50Hz , AC supply complete all as specified and directed. |
| 67 | S&F in repairs MCCB 63 Amps, 16 KA 4-Pole type, with fixed magnetic & adjustable (80%-100%) thermal release including all arrnagement for mounting and testing, operating on 415V, 50Hz, AC supply complete all as specified and directed. |
| 68 | S&F in repairs MCCB 100 Amps, 16 KA 4-Pole type, with fixed magnetic & adjustable (80% - 100%) thermal release including all arrnagement for mounting and testing, operating on 415V, 50Hz , AC supply complete all as specified and directed. |
| 69 | S&F in repairs MCCB 125 Amps, 25 KA 4-Pole type,with fixed magnetic & adjustable (80% - 100%) thermal release including all arrnagement for mounting and testing, operating on 415V, 50Hz , AC supply complete all as specified and directed. |
| 70 | S&F in repairs MCCB 160 Amps, 25 KA 4-Pole type, with fixed magnetic & adjustable (80% - 100%) thermal release including all arrnagement for mounting and testing, operating on 415V, 50Hz , AC supply complete all as specified and directed. |
| 71 | S&F in repairs MCCB, 200 Amps capacity, 4 pole, 25 KA with fixed magnetic & adjustable (80% - 100%) thermal release complete all as specified and directed. |
| 72 | S&F in repairs MCCB 250 Amps capacity 4 pole 25KA breaking capacity with fixed magnetic & adjustable (80% - 100%) thermal release complete all as specified and directed. |
| 73 | S&F in repairs on load change over switch 63 Amps 415 Volt 4 pole complete all as specified and directed. |
| 74 | S&F in repairs On load change over switch 100 Amps 415 Volt 4 pole complete all as specified and directed. |
| 75 | S&F in repairs On load change over switch 125 Amps 415 Volt 4 pole complete all as specified and directed. |
| 76 | S&F in repairs On load change over switch 160 Amps 415 Volt 4 pole complete all as specified and directed. |
| 77 | S&F in repairs On load change over switch 200 Amps 415 Volt 4 pole complete all as specified and directed. |
| 78 | S&F in repairs On load change over switch 250 Amps 415 Volt 4 pole complete all as specified and directed. |
| 79 | S&F in repairs On load change over switch 320 Amps 415 Volt 4 pole complete all as specified and directed. |
| 80 | S&F in repairs On load change over switch 400 Amps 415 Volt 4 pole complete all as specified and directed. |
| 81 | S&F in repairs outdoor type floor mounted Bus Bar Chamber made 3.0 mm thick M.S. sheet duly painted with powder coated paint (RAL7032 Siemens Grey) having 4 Nos of insulated Aluminium Bus Bar of 200 A rating and size 450mm(w) x 450mm(H) x 150mm(D) complete with hinged Single Door in both front and rear side (with locking arrangement), 4 side sloped roof and 600mm long MS Angle (50 x 50 x 6mm) leg, earthing termination bolt etc. complete all as specified and as directed. |
| 82 | M&L for Painting (in situ) feeder pillars (external surfaces only) with two coats of synthetic enamel paint after cleaning of existing surface and removing of all loose dirt and greasy spots and filling of cavities by providing putty complete all as specified and directed.Note : Painting to be done either by using Spray Painting Machine or by using Roller. Brush shall not be used. |
| 83 | S&F Mild Steel Frame work made of structural steel / Mild Steel pipe (Square / Round Medium Grade) duly cut into pieces, bent to shape, drilled, welded, rivetted etc. complete with one coat of Red Oxide Metal Primar and two coats of synthetic enamel paint of approved shade complete all as specified and as directed |
| 84 | M&L for taking out LT Panel/Feeder pillar Box from its foundation by taking shut down, braking PCC foundation, opening the existing cable from the LT Panel board and removing the panel complete all as specified and directed. Please Enable Macros to View BoQ information |
| 85 | M&L for taking out LT Panel/Feeder pillar Box from its foundation by taking shut down, braking PCC foundation, opening the existing cable from the LT Panel board and removing the panel complete all as specified and directed. Please Enable Macros to View BoQ information |