| 1 | Dismantelling of OLD OHT |
| 2 | Dismantling of old and defunct OHT of Allapur including all required formwork/shuttering, supply of all required labour, T&P etc complete and shifting of debris from campus to MRF or C&D waste center of Nagar Nigam Banswar as per direction of engineer in charge. Barricading of the entire campus by MS sheets supported on MS frame before start of the dismantelling work till the completion of work. Removing the barricading after the work is completed including cost of all material, labour, T&P etc complete. The material after dismantelling of barricading will belong to contractor |
| 3 | Supply of following sizes MS pipes for rising main conforming to latest/relevant I.S. Specifications with all jointing materials such as specials conforming to latest /relevant I.S. specifications, suitable for MS pipes, as per latest IS codes including F.O.R. destination and all taxes and insurance etc. |
| 4 | 100 MM DIA MS pipe |
| 5 | 150 MM DIA MS pipe |
| 6 | 200 MM DIA MS pipe |
| 7 | 250 MM DIA MS pipe |
| 8 | 300 MM DIA MS pipe |
| 9 | 350 MM DIA MS pipe |
| 10 | 400 MM DIA MS pipe |
| 11 | Carting from the site store upto (8 Km) the following size of MS pipe and special to the site work lowering them into trench and laying true to alignment and gradient including testing of pipeline but excluding cost of trenching and cutting of pipe etc. for making of length but including making joints. |
| 12 | 100 MM DIA MS pipe |
| 13 | 150 MM DIA MS pipe |
| 14 | 200 MM DIA MS pipe |
| 15 | 250 MM DIA MS pipe |
| 16 | 300 MM DIA MS pipe |
| 17 | 350 MM DIA MS pipe |
| 18 | 400 MM DIA MS pipe |
| 19 | Supply and carting up to site of work of the following dia DI butterfly/sluice valves, class I, working pressure 10 Kg/cm2 confirming to IS: 780/1969 or its latest amendments, including valve fittings & Dismantling Joints as per requirement F.O.R. destination, and lowering them into the already prepared trenches, fixing in position and jointing them with pipelines and testing etc. complete and also including supply of jointing materials etc. complete .including all taxes and insurance, as per instructions of Engineer -in -charge. |
| 20 | 100 MM DIA MS pipe |
| 21 | 150 MM DIA MS pipe |
| 22 | 200 MM DIA MS pipe |
| 23 | 250 MM DIA MS pipe |
| 24 | 300 MM DIA MS pipe |
| 25 | 350 MM DIA MS pipe |
| 26 | 400 MM DIA MS pipe |
| 27 | Excavation of earth in soil mixed with kankar for pipe line and rising main trenches including lift upto 1.50 m and lead upto 50 m and refilling watering, ramming of the excavated earth into the trench and also disposal of surplus earth upto 50m from the center of the trenches including supply of all material labour, T&P etc complete as per instructions of Engineer ‐in ‐charge. |
| 28 | Supply of all materials and construct following type sluice valve chambers complete as per type design. |
| 29 | Sluice valve - 100 mm dia |
| 30 | Sluice valve - 150 mm dia |
| 31 | Sluice valve - 200 mm dia |
| 32 | Sluice valve - 250 mm dia |
| 33 | Sluice valve - 300 mm dia |
| 34 | Sluice valve - 350 mm dia |
| 35 | Sluice valve - 400 mm dia |
| 36 | Construction of RCC thurst block including supply of all material Steel etc, labour and T&P |
| 37 | 100 MM DIA |
| 38 | 150 MM DIA |
| 39 | 200 MM DIA |
| 40 | 250 MM DIA |
| 41 | 300 MM DIA |
| 42 | 350 MM DIA |
| 43 | 400 MM DIA |
| 44 | Clear Water Reservoir 2000 KL |
| 45 | \\"Supply of all materials labour T&P etc. compete and construction of R.C.C. (M30 Grade) GLSR of 2000 KL capacity with main components, including cost of soil testing. \\" All the components of GLSR will be casted in M30 concrete with cement, coarse sand and approved stone grit as per I.S. 11682 and I.S.456 or its latest amendment Minimum depth of foundation below original ground level will be 5.5 M Seismic effects and wind load should be taken into consideration as I.S. 1893 latest amendment for earthquake resistance and I.S. 875 part-III for wind load on structure (this area is in seismic Zone IV and high damage risk zone for wind). Proper ventilator at top dome in circular shape of 15 m dia. along with an R.C.C. cover of minimum 1.50m dia and 7.5 cm thickness, pillar of ventilator should be minimum 50 cm dia.The space between top dome and R.C.C. cover should be covered with mosquito net of standard quality along with expanded metaled jali. Water level indicator fabricated with good quality minimum 45mm x 45mm x 6mm S.S.angle and 3mm thick 6mm flat S.S.sheet. The indicator board scale made of 3mm thick M.S. plate should have a clear width of minimum 25cm painted with good quality outdoor paint. It should also consists of 3mm brass wire rope minimum 4 smooth pulleys about 8 cm dia with guides,15cm dia copper ball float which shall be completely water tight suitable pointer of brass etc. Lightening conductor as per IS:2309 of its latest amendments of latest electricity rules. It should consist proper elevation rod with 5 or more fork points proper down conductors of prescribed metal of proper size prescribed by IS:2309 and manhole of min 60x60cm size made of M.S.channel section with adequate cover made of M.S. sheet of minimum 3mm thickness hinged with manhole with locking arrangement. This manhole should be fixed at top dome at proper place. Construction of bed blocks in 1:2:4 PCC with cement, coarse sand and approved stone grit under each duck foot bend to support the vertical pipes. These bed blocks should supported on the raft not on the soil . Painting of all concrete surface and steel pipe works with three coats of approved cement paint and anticorrosive paints. Supply & laying of 100 mm dia PVC pipe(SN-8) as per I.S.-15328 or as latest / relevant specification including all taxes and insurance etc.F.O.R. destination for disposal of water from overflow and washout chamber to suitable point outside the water works compound including excavation of trenches. Laying of pipe line etc. Foundation including pilling if required as per actual ground condition after soil testing and plinth protection around CWR. |
| 46 | Supply of all materials labour T&P etc. compete and construction of Pump House over CWR of 60 sqm x 5m height. at site of RCC CWR including all labour, material, T&P etc complete |
| 47 | Supply of all materials labour T&P etc. complete and construction of electric power sub-station room size 15 sqm x 5m height including all labour, material, T&P etc complete |
| 48 | Dismantling of Following type of surfaces including sorting out and stacking of serviceable materials and disposal of unserviceable materials upto a distance of 50m as per instructions of Engineer ‐in ‐charge. |
| 49 | Bituminous surface |
| 50 | C.C. Road |
| 51 | Reinstatement of the following type of road surface with old and new materials including supply of all materials, labour, T&P etc. required for proper completion of the work as per instructions of Engineer‐in-charge. |
| 52 | Bituminous surface |
| 53 | C.C. Road |
| 54 | BOUNDARY WALL AND GATE |
| 55 | Dismentaling of old damage boundary wall around OHT including stacking of dismantled material to a suitable place as per direction of Engineer-in-charge |
| 56 | Construction of boundary wall around OHT/WTP as per type design including supply of all Materials, Labour, Tools and Plants etc. complete. |
| 57 | Supply & fixing of 3.60 M wide MS Gate and 1.2 m wide wicket gate including fabrication and supply of steel and construction of boundary pillars all complete. |
| 58 | Construction of interlocking approach road including supply of all matrerial, labour, tools and plant etc.complete. |
| 59 | Providing surge tank in 350 mm dia distribution line including study of surge, freight, insurance, octroi, excise and all taxes, unloading and local carting etc complete with all necessary specials, 12 mm thick MS pipe line epoxy coated outside and PU coated inside, supply of all labour materials and also including construction of foundation of surge tank foundation of surge tank as per design.( 3 Cum) |
| 60 | Installation of surge tank including all labour, material T&P etc complete. |
| 61 | Interconnection in CWR & old existing pump house and pipe lines including supply of all required CI/DI bend, tailpiece & all other specials, material, labour, T&P etc complete. |
| 62 | 100 mm dia (100 mm x100 mm) |
| 63 | 150 mm dia (150 mm x150 mm) |
| 64 | 200 mm dia (200 mm x200 mm) |
| 65 | 250 mm dia (250 mm x250 mm) |
| 66 | 300 mm dia (300 mm x300 mm) |
| 67 | 350 mm dia (350 mm x350 mm) |
| 68 | 400 mm dia (400 mm x400 mm) |
| 69 | (150 mm x100 mm) |
| 70 | (200 mm x150 mm) |
| 71 | (250 mm x200 mm) |
| 72 | Campus development including levelling of the inside of campus including all labour, material, T&P etc complete |
| 73 | Rain water harvesting at campus including all, labour, material, T&P etc complete |
| 74 | Item No :-1 Clear Water PUMPS WITH MOTOR |
| 75 | SITC of 3800 LPM, 40M head HSC/Submerged centrifugal Pumps with Motor suitable to discharge & head as given below having Stainless Steel impeller, Stainless Steel Shaft, Upper & Lower casing, Shaft sleeves, Base frame, coupling & coupling guard etc..Casing & suction Bowl: CI IS 210 FG 260 with suitable coating inside casing of 500 DFT, suitable for protection against corroison, erosion and prevent oxidation.Impeller: CD4MCu (Chromium24.5% minimum, Carbon≤0.04%) as per ASTM A890 Gr1A ,Hardness 220-260 BHN Pump Shaft: Stainless Steel: AISI 410 All the Pumps shall be tested at manufacturers works as per scope of inspection in presence of Third party inspection agency approved by UPJN & Engineer Incharge or his representative.. |
| 76 | SITC of 1800 LPM, 55 M Head Pumping Plant and VFD Starter Arrangement for TW feeding arrangement Tubewells and other required work as per direction of EIC |
| 77 | SITC of 2000 LPM, 55 M Head Pumping Plant and VFD Starter Arrangement for TW feeding arrangement Tubewells and other required work as per direction of EIC |
| 78 | SITC of SLUICE VALVE WITH ACTUATOR , P.N.1.6 |
| 79 | Motor operated Actuators with DIDF Sluice Valves |
| 80 | a) 250 mm dia |
| 81 | b) 300 mm dia(for common header) |
| 82 | c)300 mm or suitable dia(For CWR inlet) |
| 83 | REFLUX VALVE, P.N. 1.6 |
| 84 | SITC of ISI mark CI D/F reflux valves (non-return valves ) of following dia including freight, inspection charges, unloading from railway wagon, loading into truck, transportation upto departmental stores, unloading, stacking excluding etc. complete. Reflux valves as per I.S.5312 Part I (1984) |
| 85 | a) 250 mm dia ( with bye pass arrangement ) |
| 86 | b) 300 mm dia ( with bye pass arrangement ) |
| 87 | SITC of DISMANTLING JOINT |
| 88 | Providing M.S. Dismantling Joint of size as given below as per detailed specification. |
| 89 | A) 250 mm dia |
| 90 | B) 300 mm dia |
| 91 | M.S. PIPES FOR MANIFOLD |
| 92 | SITC OF 300mm 7.1 mm thickness ERW/ SAW / fabricated M. S. pipes |
| 93 | SITC OF 250mm 7.1 mm thickness ERW/ SAW / fabricated M. S. pipes |
| 94 | FLANGE JOINT |
| 95 | Providing and making flanged joints to flanged M.S. pipes of all classes/specials etc. including cost of all jointing materials ( rubber packing, nut bolts, etc. ) labour, hydraulic testing, etc. complete. |
| 96 | a) 250 mm dia |
| 97 | b) 300 mm dia |
| 98 | E.O.T. CRANE, 3 Ton, 8 Mtr. Span |
| 99 | Supply , erecting and commissioning Single Girder Hand Operated Circular / Rectangular Travelling Crane with 10 m lift complete with chain pulley block ISI marked and travelling trolley both tested for 50 % overload including arrangement for longitudinal travel / circular travel and cross travel with wheel, hand chain, etc complete. The EOT Crane shall be tested at manufacturers works as per scope of inspection in presence of Third party inspection agency approved by UPJN & Engineer Incharge or his representative.. |
| 100 | L.T.PANEL BOARD |
| 101 | Providing,erecting and giving satisfactory test and trial of L.T.Panel (TTA Panel Confirming to EC61439 Cubicle Type ) comprising of specified Breakers 630A, 35KA FP incomer, MCCB with Thermal Magnetic Release Based (O\C,S\C) RELEASE - 3 Nos incoming feeder, 5 x 320A MCCB O/G Feeder, 3 x 250 A MCCB, 2 x 100 A MCCB 3 x 63 A MCCB O/G Feeder Smart Enery Meter , Bus bar, switches, indicating instruments etc as per detailed specification. |
| 102 | VFD STARTER WITH RS 485 PORT |
| 103 | SITC of Variable Frequency Drives with panel supplied by manufacturer conforming to applicable standards with logic inputs & outputs, relay outputs and analogue outputs, plug in I/O connections, display of electrical parameters, state of load & operating time, RS 485 serial link for connections to ModbusAll the Starters shall be tested at manufacturers works as per scope of inspection in presence of Third party inspection agency approved by UPJN & Engineer Incharge or his representative.. |
| 104 | a) For above Pumps (60 HP) |
| 105 | PVC INSULATING MAT |
| 106 | Supplying and fixing PVC synthetic elastomer electrically insulating mat with class A insulation CPRI tested having 12 mm thickness upto 3.3 kV |
| 107 | CABLE |
| 108 | Providing, lowering, laying, jointing, Commissioning & Giving test and trial of XLPE insulated , armoured cable, ISI Marked, with stranded or solid conductor as per detailed specification. |
| 109 | a) 1.1 KV, 3.5 Core, 185 sq mm Alluminium ( MSEDCL METER to LT Panel ) ( Double Run ) |
| 110 | b) 1.1 KV, 3.5 Core, 35 sq mm Cu ( Double Run ) ( Starter Panel to Motor of 60 HP ) |
| 111 | c) 1.1 KV, 3.5 Core, 16 sq mm Cu |
| 112 | d) 1.1 KV, 3.5 Core, 10 sq mm Cu |
| 113 | CABLE TRENCH |
| 114 | Making trench in soft soil having 0.75 m depth and minimum 0.3 m width for laying provided cables up to voltage level of 1.1kV complete |
| 115 | PLATE TYPE EARTHING |
| 116 | Providing earthing with galvanized iron earth plate size 60 x 60 x 0.6 cm Earthing Strip with funnel with a wire mesh for watering and brick masonry block C.l. cover complete with all materials, testing & recording the results as per specification no. EA-EP |
| 117 | IRON WORK |
| 118 | Providing, fabricating iron work of ISMB, ANGLES, CHEQUARED PLATE, MS FLAT for base frame, panel stand, square bar for crane,cable tray, supports of ventilation ducting and items related to crane with bars of crane & all other similar work including cutting, bending, welding and painting as per detailed specification. |
| 119 | ELECTRIFICATION |
| 120 | Providing & erecting intrnal and external Electrification for Substation as per specification. |
| 121 | VENTILATION |
| 122 | Providing & fixing Ventilation System, furniture, Tools of standard make as per dircion of EIC. |
| 123 | CONSTRUCTION OF SUBSTSTION |
| 124 | SITC of 11 KV floor mounting, single row type H.T. panel having 1 No. incoming (incoming 630 amp CTR 400/200/5 Amp) and 2 Nos. outgoing(outgoing 630 amp CTR 200/100/5 Amp) VCB panels complete with insulated bus bars, all necessary metering and safety equipments. including Cable Jointing Kit. |
| 125 | SITC of 11 KV / 0.415 KV, 250 KVA outdoor, step down transformers. |
| 126 | Supply and laying of 11 KV XLPE cable of 3x70 sqmm size Al. armoured HT cable |
| 127 | Double earthing of all sub-station equipments complete with salt, charcoal, G.I. earth electrode, C.I. earth boxes, G.I. watering pipe, G.I. earth strip of adequate capacity and labour. |
| 128 | Foundation, Fencing around outdoor Transformers |
| 129 | Pole mounted solar based LED light |
| 130 | CE/UL Certified Electromagnetic Flowmeter 300 mm dia |
| 131 | Pressure Transmitter for each pump |
| 132 | Level Transmitter for Sump |
| 133 | Auto Phase Reversl Unit for 400 Amp |
| 134 | Fire fighting equipments such as four nos. fire extinguisher ABC type, one set sand buckets(6 nos.) with stand and grouting at site and Alstrong plates and bolts etc. |
| 135 | CE & UL certified PLC/RTU in IP 54 encloser suitable to communicate with GSM based modem unit with CPU and power supply with analog and digital parameter & features as specified for each ZPS /OHT to store and transmit data on GSM backbone,RTU/PLC designed with logic to transfer data in multiple stations as specified in tender technical specifications |
| 136 | G.S.M./G.P.R.S. based wireless communication with 4G Modem for RTU/ PLC Capable to transfer and gather data from remote sites to control stations, all accessories included with signal enhancer antenna made for pumping plant internate charges as specified in tender technical specifications |
| 137 | CE / UL certified Surge protector for control panel |
| 138 | CE / UL certified 7\\" HMI touchscreen suitable to communicate with PLC/RTU, for local display & control of process parameters |
| 139 | Complete Cabling for CWR including all power & control cables of all equipment at pumphouse and OHT ( upto 3 Pumps ) |
| 140 | Control panel with IP 54 protection, industrial grade fro all equipments (separate for control (24V) and power equipments.( upto 3 Pumps ) |
| 141 | CE/UL certified 5 KVA UPS with batteries. |
| 142 | Automatic Chlorination System |
| 143 | Security Surveillance IP Camera with recorder Please Enable Macros to View BoQ information |