Indian Tenders

Tender Notice

TDR 55304920
Tendering Authority Sher-E-Kashmir University Of Agricultural Sciences & Technology
Tender No AU/Estates/2026-27/03 dated 22-04-2026
Tender ID 2026_SKUST_309179_5
Tender Brief Tender For Providing Electric Repair Work By Way Of Replacing Damaged Panel. Copper Wire, Pvc Power Cable And Other Allied Work At Fvsc & Ah R S Pura (Group No. 5)
City Jammu
State Jammu And Kashmir
Document Fees INR 500 /-
EMD INR 19980.0 /-
Tender Value INR 9.99 Lakhs /-
Tender Type Tender
Bidding Type Open Tender
Competition Type Indian

Tender Details

Tender for Providing Electric Repair Work By Way Of Replacing Damaged Panel. Copper Wire, Pvc Power Cable And Other Allied Work At Fvsc & Ah R S Pura (Group No. 5)

Key Dates

Publish Date 30-04-2026
Last Date of Bid Submission 07-05-2026
Tender Opening Date 08-05-2026

Contact Information

Company Name Sher-E-Kashmir University Of Agricultural Sciences & Technology
Contact Person Estates Officer, SKUAST-Jammu
Address Estates Division, SKUAST-J, Chatha

BOQ Items

Name of Work:- Providing electric repair work by way of replacing damaged panel. Copper wire, PVC power cable and other allied work at FVSc & AH R S Pura (Group No. 5)
Sl. No. Item Description
1Wiring for sub main wiring with following sizes of PVC/ insulated copper conductor wires in the surface/ recessed PVC / MS conduit along with PVC insulated copper conductor earth wire as required complete with connections, testing and commissioning etc. as per specifications and drawings.
24x6 sq. mm with 2 x 6.0sq. mm earth wire
34x10 sq. mm with 2 x 6.0sq. mm earth wire
44x16 sq. mm with 2 x 6.0sq. mm earth wire
5Supply, installation, designing testing at works, installation and commissioning of outdoor type cubical panel box suitable for 3 phase 4 wire 415 volts 50 Hz supply system CRCA sheet steel enclousre panel with febricated with 14/16 SWG CRCA sheet steel and duly powder coated with simns grey and chemical treattment for with front and rear openable provided with suitable gaskit to make dust/vermin proof for ip 54 as per IS 13947 degree of protection, fault rating 50 KA/1 sec including angle iron base frame of size 50x50x6 mm for mounting the panel board at the hieght of 600 mm from FFL etc ( L&T, Legarnd and schineder) including dismentaling of existing LT panel etc as Directed by eng-in- charge.
6Moulded case circuit Breakers shall be thermal magnetic trip type. Fault level for all MCCB and bus bar shall be 50 KA. ICU shall be equal to ICS=100%
7Note :
8All metering current transformers shall be Class 1, 15 VA.
9MDB-1 (Indoor Type)
10Incomer
11160 A 4P 36K MCCB – 1No.
12R,Y,B phase indicating lights with control fuses - 1 set
13Bus Bar
14250 A 415V, 50Hz, 3ph, 4 wire Aluminium Bus bar
15Outgoing
16TPN 63 amp 8 no
17TPN 40 amp 8 no
18SPN 40 amp 6 no
19SPN 63 amp 6 no
20Moulded case circuit Breakers shall be thermal magnetic trip type. Fault level for all MCCB and bus bar shall be 50 KA. ICU shall be equal to ICS=100%
21Note :
22All metering current transformers shall be Class 1, 15 VA.
23MDB-1 (Indoor Type)
24Incomer
25250 A 4P 36K MCCB – 1No.
26R,Y,B phase indicating lights with control fuses - 1 set
27Bus Bar
28400 A 415V, 50Hz, 3ph, 4 wire Aluminium Bus bar
29Outgoing
30TPN 63 amp 8 no
31TPN 40 amp 8 no
32SPN 40 amp 6 no
33SPN 63 amp 6 no
34Moulded case circuit Breakers shall be thermal magnetic trip type. Fault level for all MCCB and bus bar shall be 50 KA. ICU shall be equal to ICS=100%
35Note :
36All metering current transformers shall be Class 1, 15 VA.
37MDB-1 (Indoor Type)
38Incomer
39125 A 4P 36K MCCB – 1No.
40R,Y,B phase indicating lights with control fuses - 1 set
41Bus Bar
42250 A 415V, 50Hz, 3ph, 4 wire Aluminium Bus bar
43Outgoing
44TPN 63 amp 6 no
45TPN 40 amp 6 no
46SPN 40 amp 4no
47SPN 63 amp 4no
48Supply and laying of PVC Power cable 1.1 KV Grade armoured aluminium XLPE cables including earth work, cost of end termination, thimbles and saddles etc. as required.
493.5 C X 120 SQ MM
503.5 C X 240 SQ MM
51Earthing withGI earth plate 600mm x 600 mm x 6mm thick including accessories and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. (with charcoal or coke and salt) complete as required for earthing and lightning protection
52Providing and fixing 25 mm x 6 mm GI strip from earth electrode as required(10 Meter) each approx
53Repairing of 150 KVA oil cooled servo voltage stablizer 3 phase by way of replacing of Dimmer/veriable (3nos) and complete rewinding of copper coil (3nos) including cost of old material and replacing of synchronizing motor 10KG(3nos) motor network,bacalite plate,microsoft switch(3nos),wiring for auto control micro procerror card(3nos), bearing variable socket (3nos), volt meter 96 mm 300 volt(3nos),front plate, push button(6nos) togal switch (6nos) and indicator 12 nos complete job
54Repairing of 5 HP motor( mono block pump set ) by way of complete rewinding etc as requried
55Providing and fixing of following rating and breaking capacity and Pole MCCB with thermal magnetic trip type and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel making connections, etc. as requried ( L&T, Legarnd and schineder)
56250 ampre MCCB 4 pole 36 ka thermal magnetic trip type with spreader link
57200 ampre MCCB 4 pole 36 ka thermal magnetic trip type with spreader link
58400 ampre MCCB 4 pole 36 ka thermal magnetic trip type with spreader link Please Enable Macros to View BoQ information

Other Detail

Information Source https://jktenders.gov.in
Download FileName File Description File Size
Download 0e8010ad-4cbd-4398-8606-54b61b91cf45.html Tender Documents 0 KB
Download BOQ_1001054.xls Tender Documents 0 KB
Download Tendernotice_1.pdf Tender Documents 0 KB
Download Termsandconditions.pdf Tender Documents 0 KB
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.