Indian Tenders

Tender Notice

TDR 55304197
Tendering Authority Madhyanchal Vidut Vitran Nigam Limited
Tender No NVS_01-04/EWC(G)/2026-27
Tender ID 2026_MVVNL_1144202_3
Tender Brief Corrigendum : Tender For Construction Of 33/11 Kv Sub-Station, Gondipur (2X5 Mva Capacity) Distt. Balr Ur, 33 Kv Overhead And Underground Line From Sectional Point Of Existing 33 Kv Line Naharbalaganj To Newly Proposed 33/11 Kv S/S Gondipur (Balr Ur) & 05 Nos. 11
City Gonda
State Uttar Pradesh
Document Fees INR 3540 /-
EMD INR 43060.0 /-
Tender Value INR 43.06 Lakhs /-
Tender Type Tender
Bidding Type Open Tender
Competition Type Indian

Tender Details

Tender for Construction Of 33/11 Kv Sub-Station, Gondipur (2X5 Mva Capacity) Distt. Balr Ur, 33 Kv Overhead And Underground Line From Sectional Point Of Existing 33 Kv Line Naharbalaganj To Newly Proposed 33/11 Kv S/S Gondipur (Balr Ur) & 05 Nos. 11 Kv Lines Overhead Newly Proposed 33/11 Kv S/S Gondipur To Existing Sectional Point For Bifurcation Of 11 Kv Load In The Concerning Distribution Area Under The Head Of B.Plan 2026-27 Under Electricity Works Division, Gonda. All The Following Works Will Be Executed As Per Resspo, Uppcl Drawing/Norms

Corrigendum Details

Sr No CorrigendumDate Corrigendum CorrigendumType NewSubmissionDate
1 04-05-2026 FEE, EMD AND TENDER VALUE Other 07-05-2026

Key Dates

Publish Date 04-05-2026
Last Date of Bid Submission 07-05-2026

Contact Information

Company Name Madhyanchal Vidut Vitran Nigam Limited
Contact Person SE EWC GONDA
Address EWC GONDA

BOQ Items

Name of Work:- Construction of 33/11 KV Sub-Station, Gondipur (2x5 MVA Capacity) Distt. Balr ur, 33 KV overhead and underground line from Sectional Point of Existing 33 KV line Naharbalaganj To Newly proposed 33/11 KV S/S Gondipur (Balr ur) & 05 Nos. 11 KV lines Overhead Newly Proposed 33/11 KV S/S Gondipur to Existing sectional point for bifurcation of 11 KV Load in the concerning distribution area under the head of B.Plan 2026-27 under Electricity Works Division, Gonda. ALL THE FOLLOWING WORKS WILL BE EXECUTED AS PER RESSPO, UPPCL DRAWING/NORMS
Sl. No. Item Description
1PART-(A) Construction of 33 kv line Carriage of Material-Safe Loading carriage including unloading & proper stacking of following store materials from from any store of MVVNL to site of work.
2PCC 11.0 Mtr. Long
3STP 13.0 Mtr. Long
433 KV Pin Insulattor(Polymeric)
533KV Disc insulator B& S Type (Polymeric)
6Disc Fitting 7000kg
7V Type channel X-arm for 33kv
8MS earthing rod of 20x2500mm & 6 SWG earth Wire
9M.S. TOP Channel 125x65x3200mm
10M.S. Angle Iron 65x65x6mm, 4300 mm long 8 no. Bracing, with 16 clamps (5.8 kg./m)
11Dropper Channel 100x50mm, 3200 mm long
12Cost of ACSR Dog conductor (including sag charges, cutting and wastage)
1333KV 3x300sq.mm XLP Cable
1433 KV cable jointing kit suitable for 3x300sq.mm XLP Cable (O/D Type)
1533KV Cable Jointing Kit for 3x300 mm sqr cable Straight Through
16Stay set complete with stay wire 7/8 S.W.G(10 kg for each stay).
17Errection of Single Pole Support-The excavation of foundation pit of size (750x450) mm and having depth of 1/6 of the full length of the support. Errection of support, complete with providing & Fixing of all clamps and other accessories as per respo drawing. The work includes carriage and handling support from sectional store to pit site as well as any fabrication work if required. (Necessary clamps with nut & bolts, F-Bracket, stone pad shall be provided by Contractor.)
18P.C.C Pole 11.0 Mtr. Long.
19S.T.P. 13.0 Mtr long
20Errection of Sectional Double Pole support-The excavation of foundation pit of size (750x450) mm and having depth of 1/6 of the full length of the support. Errection of support, complete with providing & Fixing of all clamps and other accesories as per respo drawing. The work includes carriage and handling of supports from sectional store to pit site, fixing of Top Channel and cross bracing sets as well as any fabrication work if required. (Nuts & Bolts of different sizes, Top channel clamps, Bracing angle Clamp, E-Bracket, Disc fitting, bolt and nuts, stone pad as per norms etc shall be provided by Contractor.)
2111 Mtr. PCC Pole.
22Errection of Four Pole Structure -The excavation of foundation pit of size (750x450) mm and having depth of 1/6 of the full length of the support. Errection of support, complete with providing & Fixing of all clamps and other accesories as per respo drawing. The work includes carriage and handling of supports from sectional store to pit site & fixing of Top Channel and Cross Bracing sets as well as any fabrication work if required. (Nuts & Bolts of different sizes, Top Channel clamp, Bracing clamp, E-Bracket, Disc fitting, stone pad as per norms etc shall be provided by Contractor.)
2311 Mtr. PCC Pole
24Concreting and plinthing of Poles-Grouting of supports in PCC 1:4:8 (cement, sand, & 20 mm size stone Grit). Grouting will be done in the block of size (450x450)mm x 1/6th of full length of support, upto ground level, 300mm plinth above the ground level with C.C 1:3:6 (Cement, Coarse sand and Stone grit of 20mm of size with muffing as per respo drawing).
2511 Mtr. P.C.C Pole
26S.T.P. 13.0 Mtr long
27Fixing of Stay rod (size 20x1800 mm)
28Fixing of Stay set complete (size 20x1800 mm) on different types of supports as per drawing. (8 Nos.on each sectional pole)
29Grouting of stay rods including all work of excavation, cement concrete in size (0.60x0.6x0.30)m in ratio 1:4:8 cement, sand, 400mm brick ballast as per drg. Including back filling of soil and proper ramming.
30Stringging and Sagging of Conductor-Laying, Spreading, lifting and final sagging of 3 phases of ACSR Dog conductor in accordance with Line chart including binding and fixing of all accessories in 03 Nos. Conductor in Parallel.
31Making jumpers on Section Points, by providing and fixing of P.G. Clamps of proper sizes, suitable for Dog Conductor
32Sectional Double Pole structure
33Secton Four Pole structure
34Laying of Cable
35Laying of 33 KV 3x300 Sq.mm XLPE Cable In Double circuit in normal soil by digging of trench 1050 mm deep, 750 mm wide including supply of required material as fine a sand, Ist class bricks, Inter axial spacing between the two cable should be in between 0.25 . to 0.40m, the two cables should be separated by a partition of single bricks along the cable and stone's slab/brick on top of the each cable, including back filling of soil and proper ramming.High voltage (HV) testing of 33 kV, 3C x 300 sq.mm UG cable after laying & termination, including IR test, application of test voltage, and reporting, complete.
36Laying of 33 KV 3x300 Sq.mm XLPE Cable by drill method in Double Circuit with the help of H.D.D. machine (Trenchless technology method by Deep Drilling System) with proper testing.High voltage (HV) testing of 33 kV, 3C x 300 sq.mm UG cable after laying & termination, including IR test, application of test voltage, and reporting, complete.
37Installation of Heat Shrinkable Type cable jointing kits 3x300 mm.sqr. Cable
38Straight through
39End termination kit
40Hoisting of 33 KV Cable
41Hoisting of 33 KV Cable on existing/erected support by MS Pipe 150 mm dia 3 mtr long suitable for 3x300 sq mm cable fixing of proper support and its clamping, jumpering properly as per RESSPO Norms. (MS pipe, supporting channel and clamps shall be provided by contractor).
42Miscellaneous Work
43Supply & fixing of danger board at each location.
44Earthing of support with M.S. Earth rod of (20x2500 mm) long including excavation of pit and driving M.S. rod 0.5 mtr. Below the ground level and connecting the electrode with help of G.I. wire No 8 SWG and earthing lug. (G.I. Wire, bolt and nut and lugs shall be provided by the contractor.)
45Chopping of branches of trees of eucalyptus, Neem, Keeker and other kind of trees along the route of the line and disposal of the same at suitable place.
46Cradle Guarding of 33KV line at road crossing, 11 line crossing, canal/telephone line crossing by fixing M.S. Angle 65x65x2600 mm at double pole and 65x65x2600 mm long at single pole by strining and sagging of 3 No. G.I. wire, tighting with mounting. (MS angle and GI wire, Nut & Bolts, I-Hook shall be provided by the controctor).
47Wraping of barbed wire on 33 KV SP-72/SP-55 ST Poles as anti climbing device for a length of 0.9 Mtr. Wire pitch /Gap 33 mm and fixing upper and lower end keeping lower end at a height of 2.75Mtr. From the ground complete with providing and fixing of lower end & upper end clamps made of M.S Flat 40x5mm complete with nuts&bolts. (All the material will be supplied by the contractor).
48Painting of following supports/structures with 2 coats of synthetic enamel Aluminium Paint after one coat of ready mix primer including cost of all material, as well as rubbing/cleaning of surface as required for proper completion of work.
49S.T.P. 13.0 Mtr long (Single Support)
50Supply & installation of cable route marker with engraving, including excavation, PCC foundation, fixing, backfilling, and all materials, labor & consumables, complete.
51Safe Loading carriage including unloading & proper stacking of following store materials from from any store of MVVNL to site of work.
5233 KV VCB 800A, 750 MVA
5333KV Control Panel For Double Transformer
54C.T. O/D 33 KV CTR 200/100/1-1A
55C.T. O/D 33 KV CTR 400/200/1-1A
5611 KV Incoming switch gear 600/300/5A, 350MVA, 24 Volt
57Outgoing 11KV switch gear 200/100/5A 350MVA
5811KV 3 Core cable 3x300mm XLPE
5911 KV 3x185 sq.mm XLPE Cable
6063KVA 11/0.4KV T/F
6111MTR. PCC
62STP 9 Mtr. long for street Light
6333KV Line Isolator
6433KV Bus Isolator
6533KV Post Insulator
6633KV Lightening Arrestor
6790lbs rail Pcs for T/F (44.64Kg/m)
68ACSR Panther Conductor
6933 KV Disc Insulator B&S Type 70KN (Polymeric)
7033 KV Disc Insulator fitting
7133 KV Pin Insulator (Polymeric)
7211 KV Pin insulator (Polymeric)
7311 KV DISC INSULATOR(POLYMERIC)
7411 KV DISC FITTING
7511KV cable jointing kit indoor 3x300sq.mm XLPE
7611KV cable jointing kit outdoor 3x300sq.mm XLPE
7711KV cable jointing kit indoor 3x185sq.mm
7811KV cable jointing kit outdoor 3x185sq.mm
79Steel Sections(M.S Channel, M.S. Angle, 32 mm Round Bar etc)
8033 KV Control Pannel for single Feeder
81M.S. Top Channal for 11 KV line
82Bracing Angel for 11 KV Line
83Stay Set for 11 kV line
84Earthing of pole by MS Rod Complete
8533 KV Fuseset
8633 KV P.T. (Outdoor)(33 KV / 110 Volt)
87Construction of retaining wall arround the 33 KV switch yard insize (25+30) mtrx2 using first class bricks, Local rivers, sand and brick ballast which includes the following works (Including cost of 1st class brick, brick ballast sand/core sand cement etc.)
88Excavation of earth in-foundation
89Cement concrete in foundation in 1:5:10 ratio
90First Class brick work in 1:6 ratio
91Plaster Work 1:6 ratio
92CC 1:2:4 ratio for grouting mid angles post for fencing
93Fabrication of Switchyard fencing by welded mesh with gate in size 25x30 Mtr by 10 S.W.G. wire mess, MS Angle 50x50x6, MS flate 25x5 mm and 40x5 mm, its fitting tightening with nuts and bolt on the studs. Supported by drilling the required Pole along with febrication of 1 No. Gate m/o MS angle.
94Earth Mat- Laying of earth mat in the Switchyard by laying of MS round bar of 32 mm Dia in 750 mm deep trenches and grounding of earth mat with MS Round bar 32 mm Dia 3 Mtr. Long earth electrode as per respo drawing. The work includes welding/ bolting of MS round bar, G.S. strip and connecting all steel structure in the switchyard with the earth mat by means of G.S. strips of size 50x6mm as per item below.
95Digging of trench of size 500x750mm for laying of 32mm Dia MS round bar including refilling of earth and ramming the same after laying of MS round bar/G.S. strip
96Laying and welding of lap joints of MS round bar of 32mm Dia with minimum 150mm overlaping. The MS round shall be welded on both side so as to fill the wedges completely using high quality Arc welding and good work Manship. The Joint shall be covered with black Bitumen Paint.
97Fabrication of 32mm Dia MS round bar 3 Mtr long earth electrodes and driving them into ground so that tip of the electrodes remains atleast 750mm below the ground level and Jointing of earth electrodes 32mm Dia with the earth mat using high quality Arc welding and good workmanship.
98Jointing of MS round bar 32mm Dia in earth mat at cross joints using high quality Arc welding. A 75mm piece of 32mm Dia MS round bar shall also be welded to make the joint strong for carrying fault current. The joints shall be covered with black Bitumen Paint.
99Providing and laying of G.S. strip of size 50x6mm for connecting the earth mat with the super structure, Security fencing post, Including digging of trench 500x500,, bending, cutting, straightening and welding of the earth strip with the earth mat and various street structure using high quality Arc welding. The work include proper overlapping of the strip and jointing by welding .
100Plinth of 5 MVA, for 33/11 KV T/Fs - Construction of Plinth of size 3.46x3.46 Mtr suitable for 5 MVA to 10 MVA T/F Plinth decided by E/I. The work includes Excavation of foundation, base concreting in C.C. 1:6:12 ratio (cement, coarse sand and brick ballast) Ist Class bricks work in cement mortar of ratio 1:4 foundation, C.C.in 1:4:8 ratio (cement, coarse sand and brick ballast) and RCC working ratio 1:2:4 (cement, coarse sand and stone grit of 20 mm gauge) using MS Bars of 10 mm Dia (Tor) in reinforcement including its cutting, bending and binding in required shape. The work also includes laying of 2 Nos. 3.46 mts long each rail pieces complete with cutting, welding and proper fitting etc. The Plinth will be made as per Drawing and shall be plastered/ finished on Top and Side of the Plinth.
101Fabrication, Erection & Grouting of Sub Station Structure -
102Terminal Gantry - Digging two No. pits of size 2.2 Mtrx .4MtrxD.75 Mtr providing stone pad at the bottom of trench and grouting of the two legs of the Terminal Gantry In CC ( cement, coarse sand and stone grit of 20 mm gauge) in the ratio 1:3:6 including supply of all T&P shutrering etc. In a block of size, 2.2mtx 1.4 mtx 0.75 mtr. The work consist of dragging, shifting up to 40 mtr raising and erecting the Two pre fabricated legs of terminal gantry in proper alignment, level and plumb. Both the plinth of the Terminal Gantry shall be properly finished with champering of edges.
103Bus Bar Gantry - Digging of 2 Nos Pits of size 2.2mtr x1.4mtr x 0.75 mtr providing stone pad at the bottom of the trench and grouting of the two legs of the Bus Bar Gantry in CC ( cement, coarse sand and stone grit of 20mm gauge) in the ratio 1:3:6 including supply of all T&P shuttering etc. in a block of size 2.2 mtr x1.4 mtr x O.75 mtr. The work consists of dragging, shifting up to 40 mtr raising and erecting the two pre fabricated legs of Bus Gantry in proper allingment level and plumb. Both the plinths of the Termainal Gantry shall be properly finished with champering of edges.
104Bus Isolator, Line Isolator Structure & 33 KV fuse set Structure - Fabrication of isolator structures 3.5mtr in height as per drawing No. RES 39 Digging of two Nos. Pits of size 1.075 x0.9 xO.3 Mtr providing stone pad at the bottom of the pit and grouting pad at the bottom of the pit and grouting of two legs of the isolator structure in CC (cement, coarse sand and stone grit of 20 mm gauge) of ratio 1:4:8 in block of 1.075 mtx 0.3 Mtr including supply of all T&P complete in all respect. The work includes dragging, shifting upto 40 Mtr., Raising and erecting the two legs with runner of Isolator in proper allingment level and plumb. Both Plinths of the Isolator structure shall be properly finished with champering of edges.
105Lightening Arrestor Structure - Fabrication of Lightening Arrestor per respo drawing No. RES 39 Digging of two Nos. Pits of size 1.075 x 0.3 xO.3 Mtr providing stone pad at the bottom of the pit and grouting of two legs of the above structure in CC (cement, coarse sand and stone grit of 20 mm gauge) of ratio 1:4:8 in block of 1.075 Mtr x 0.3 Mtr x 0.3 Mtr including supply of all T&P complete in all respect. The work includes dragging, shifting upto 40 Mtr. Raising and erecting the two legs with Top frame above structure's in proper allignment level and plumb. Both Plinths of the structure shall be properly finished with champering of edges etc.
106Post Insulator, C.T. Structure & 33 KV P.T. Structure - Fabrication of Post Insulator per respo drawing No. RES 39 Digging of two Nos. Pits of size 1.075 x 0.3 x O.3 Mtr providing stone pad at the bottom of the pit and grouting of two legs of the above structure in CC (cement, coarse sand and stone grit of 20 mm gauge) of ratio 1:4:8 in block of 1.075 Mtr x 0.3 Mtr x 0.3 Mtr including supply of all T&P complete in all respect. The work includes dragging, Shifting upto 40 Mtr. Raising and erecting the two legs with Top frame above structure's in proper allingment level and plumb. Both Plinths of the structure shall be properly finished with champering of edges etc.
107Plinth for 33 KV VCB - Construction of Plinth of 2.0X1.5X0.9(mtr) suitable for erection of super structure 33 KV VCB including grouting of Anchor boards in proper alligntment and level. Scope of work incluldes exvacation of foundation base concreting base CC 1:6:12(cement, Coarse sand and brick ballast) first class brick work in cement mortar of ratio 1:4 CC in ratio 1:4:8 and RCC work in ration 1:2:4(Cement, coarse sand and stone grid of 20 mm gaze) as per drawing.
108Hiring of 3 phase diesel generator Set 02 nos. including Carriage,Loading, unloading operating charges (with fuel) at 33/11 KV Substation Under Construction in case L.T. Supply is not available near S/s within prescribed accessible limit. 63 KVA, There phase D/G Set for fabrication and other work .
109Erection and Installation Of 33/11 KV 5 MVA Transformer
110Fabrication and grouting of M.S. Angle 65x65x6 mm in L shape & in proper size and allignment to provide support for the two separate earthing strips for Power Transformer Neutral including supply & fixing of two Nos Flexible Copper bonds for neutral earthing.
111Fabrication and erection of cable support made of two pieces of M.S. Strip 50x50x6 mm, 3.0 Mtr long joined to each other by means of 5 Nos M.S. Flat 5Ox6mm pieces of size 150 mm long each by welding at equal intervals as per drawing and grouting in a block of size 300 x 300 x 700 mm complete with one coat of ready mixed primer and two coats of Alluminum Paint. This includes providing of four Nos. M.S.clamp made of M.S. flat for holding the Cable including nuts and Bolts and fixing of XLPE cable.
112Special Delta Earthing by way of boring and lowering of \\"B\\" class G.I. pipe 50mm Dia, 20Mtr long from ground upto the water level.The G.S. strip size 50X6mm will be welded to the G.I. Pipe. The work also includes Cap & Clamps for pouring water, the cost of all material with all labour & T&P etc.Providing and constructing earth pit with GI pipe electrode, brick masonry chamber, RCC/CI cover, and watering arrangement, complete as per standard specifications. Complete in all respect.
113Body earthing of 5 MVA T/F
114Neutral of Transformer
11511 KV I/G & O/G Panel
11633KV Control Panel
117Lightening Arrestor
118C.T. O/D 33 KV CTR 200/100/1-1A
119Earth filling in the Switchyard of size 15x30 mtr including cost of earth handling and cartage upto Switcyard from outside with its unloading and laying in the yard, Leveling, Watering and Ramming till its Compactness.
120Installation of Isolators - Assembling and installation of line/Bus isolator on the Isolator structure, adjusting of opening mechanism in proper alignment so as to ensure smooth operation of the same. In case of line Isolator proper operation of earth links shall also be ensured. The work includes fabrication for proper fixing if required.
121Installation of 33 KV Fuse set- Assembling & installation of 33 KV Fuse set on the fuse set structure. The work in cludes fabrication for proper fixing if required.
122Installation of lightning Arrestors - Assembling and installation/ mounting of three Nos. Lightening Arrestors on the L.A. structure/ complete with making earth connection (Separate) and line connections. The work includes fabrication for proper fixing if required.
123Installation of Post Insulator - Installation of 3 Nos Post Insulators on the post insulators. The work includes fabrication for proper fixing if required
124Installation of CT's - Installation of 3 no. CT's of ratio 200/100/1 amp. On the Ct's structure. The work includes fabrication for proper fixing if required.
125Installation of 33 KV PT (O/D) Type- Installation of 03 Nos. P.T.'s (33 KV/ 110 Volt) O/D Type on the P.T.'s structure. The work includes fabrication for proper fixing if required.
126Installation of VCB - Installation of 33 kv VCB 800 amp capacity complete in all respect including commissioning.
127Installation of 11 KV Switchgears & 11 KV Buscoupler in Control Room
128Shifting, carefully and safely 11 KV Switchgear & 11 KV Bus Coupler from out side of the , switch gear room, Including grouting the two Nos. 100x50x6mm channels pieces (each 800mm long including cutting to size) and, foundation Bolts in 1:2:4 CC (Including cutting of CC of the floor and finishing of Floor) as per direction of Engineer Incharge, Placing and fixing of switchgear on foundation providing nuts & bolt of proper size in proper position in the alignment and filling of oil in tank after cleaning and checking, complete work with mounting of P.T. on incoming S/G.
129Fixing and making Bus Bar connection in between all switchgears after cleaning and tapping with H.T. tape, Empire tape and PVC tape properly Providing and fixing of 6mm thick bakelite seperators and plugging of all opening and holes with plastic compound. complete work including cost of all material (Except Copper Bus Bars) Strictly to the satisfaction of site incharge
130Shifting carefully and installation of 33 KV VCB Double transformer pannel & 33 KV Cantrol Panel For Single Feeder in control room including grouting of above and its proper connection.
131Providing and fixing of protection board made of teak wood with white sunmica top of size 600mmx450mm duly fitted with good quality ISI mark, 3 Nos Bells, 3 Nos ON-OFF Switches, 3 Nos Indication lamps with holders, 3 Nos. Test Button Switches on wall of switchgear room duly wired with 3/20 SWG PVC copper wire, Complete Job with cost of all materials.
132Earthing of 11 KV & 33 KV Switchgear
133Laying of earth mat for earthing of indoor equipments by means of M.S. Strip 50x6mm Connecting to 4 Nos. earthing electrodes of 32 mm (lncluding fabrication of eartring electrodes) 3 Mtr long on each side (as per RESPO Drawing RES-40).This work includes driving of each electrodes deep down into the earth so that its TOP remains 500 mm below ground level. The work include laying, bending, welding of M.S. earth strips 50 x 6 mm in the control room and connecting to both side squares.
134Earthing of all indoor equipment by providing and laying G.S. strip 50 x 6 mm including cutting, welding, bending etc.
135Supply & Installation of 24 Volt 150 AH Battery and Battery Charger with cabinet including its commisioning.
136H.T. Cable Laying
137Laying & dressing of 11 KV, 3x300 Sq.mm XLPE Cable underground from 5 MVAT/F to 11 KV incoming switchgear in the trench 450mm wide, 900mm deep, providing 150mm fine sand cushion bench and 150mm fine sand cushion above the cable. The cable shall be duly protected by 1st class bricks two either side and third on top of the cables. The cable shall be duly protected by 1st class bricks two either side and third on top of the cables, laid in series one after the other, the work includes supplying of fine sand and bricks, refilling and ramming of the left out soil, closing the trench and leveling. Spare cable shall be left and buried in the trench in the safe of rings at both ends. Cable laying work includes unrolling, cutting, meggering and sealing both end of the cable.Supply & fixing of double compression brass cable gland with all accessories including earthing tag, shroud, complete termination, testing & commissioning as per IS/IEC standards.
138Laying & dressing of 11 KV, 3x120 Sq.mm ground cable in the trench 450mm wide, 900mm deep, providing 150mm fine sand cushion bench and 150mm fine sand cushion above the cable. The cable shall be duly protected by1st class bricks two either side and third on top of the cables, laid in series one after the other, the work includes supplying of fine sand and bricks, refilling and ramming of the left out soil, closing the trench and leveling. Spare cable shall be left and buried in the trench in the safe of rings at both ends. For the protection of the cable 100mm Dia G.I.pipe has to be provided on the Cable where the cable is to be laid across PUCCA/Main Road/ Nallah. Cable laying work includes supply of G.I.Pipe, unrolling, cutting, meggring & sealing both ends of the cable.Supply & fixing of double compression brass cable gland with all accessories including earthing tag, shroud, complete termination, testing & commissioning as per IS/IEC standards.
139Hoisting of 11 KV cable, cable box, fixing with clamp nut & bolt with proper clamping with provision of G.I. pipe 3 mtr long of 150 mm dia.(All material will be supplied by the contractor)
140Supply ,Fixing and fabrication and erection of cable jointings kits suitable for following sizes of 11 KV XLPE cable of 11 KV cables. With housing of 3.5Mtr long 100 sq.mm. Dia G.I.pipe with feeder cable at feeder D/P.
14111 KV 3x300 sq.mm. indoor jointing kit
14211 KV 3x300 sq.mm.outdoor jointing kit
14311 KV 3x120 sq.mm. indoor jointing kit
14411 KV 3x120 sq.mm. outdoor jointing kit
14533KV Bus Bar & Stringing - Stringing of 33KV Bus Bar by using and laying of ACSR Panther Conductor including fixing of Disc Insulator. Strings and tension fitting complete with sagging of Bus Bar etc. and making Vertical/Horizontal jumper connection through PG clamps and connecting all the equipments with each other through connecting clamps.
146Construction of 11/0.4 KV Double Pole Mounted Sub- Station
147Erection & Grouting of 2 Nos 11Mtr STP support for making D/P structure Including fabrication, Fixing of MS Channel, M.S. angle, Disc Insulators/ Pin Insulators etc. The work Includes supply and fixing of necessary clamp with nut, bolts and washers. The work also includes grouting of double pole supports in CC 1:4:8 in block of size 0.45Mtr into 0.45Mtr into 2.0Mtr earthing of Double pole with M.S. earthing rod, complete in all respect. Painting of one Coat of Red Oxide Primer and Two Coats of Aluminum paint of good quality.
148Erection & installation of 63KVA, 11/0.4 KVT/F on double pole including shifting of the same upto double pole and making of 11KV connections to the Transformer. The work includes supply of material required such as clamps, nut & bolts etc. for mounting of T/F.11 kV TPMO & DO Fuse set will be provided by the contractor.
149Station/Switchyard lighting
150Erection of STP 9 Mtr long support after excavation of earth and grouting of cc in ratio 1:4:8 (Cement, Coarse sand and Brick ballast) as per RESPO drawing with plinth. Painting of one Coat of Red Oxide Primer and Two Coats of Aluminum paint of good Quality. For making cable LT line for colony and switchyard lighting.
151Providing and fixingLED Light-100W, with prefabricated G.I. Pipe, mounting of bracket on 9.0 Mtr STP support by using M.S. Clamp, made of 50x6mm. M.S. Flat with Bolt,Nut and washers, making the connectin with L.T. Line.
152Laying and spreading of 3½ core 25 sq.mm. PVC LT cable (70 mtr Approx.) from 11/0.04 KV, 63KVA T/F to LT distribution board in switchgear room after digging the trench, Laying cable and refilling of trench including connections at both ends after providing and crimpling of Lugs of proper size complete work. The work includes cost of all the material.
153Providing, Fixing and Grouting By 4 Nos rag bolts distribution Box of size 75x60 cms of bakelite sheet 8mm thick and 2\\"x0.5\\" bedding all round providing and fixing of ISI Mark ICTP 100Amp/440V main switch-1 No, ICDP switch 32 amp.240/415V- 3Nos, Pilot lamps with holders-3Nos including wiring and making connections with 3/20 copper wire. The work includes cost of all the material.
154Providing and laying of 2 core 2.5 sqmm LT AL.cable from S/G room to street light supports after digging of trench, Laying of cable providing a brick on TOP of cable, Refilling of trench making connection at poles with street light fittings complete with all respects. The work includes cost of all the material.
155Construction of control cable Trunch (Pacca) in size 450 mm Deep & 300 mm wide with cover by first class bricks, coares sand & cament etc. as per respo norms (All the materials shall be proposed by Contracter) including Supply & fixing of MS rest angles in cable trench for supporting control cables, including painting, fastening, and all materials, labor & consumables, complete.
156Laying of 2x2.5 sq.mm./ 4x2.5 sq.mm. armoured control cable in Control cable trench and interlinking through proper connection Protection Board / Bucholz Relay/ 33/11KV T/F junction Box/VCB/CTs to 33 kv control pannel as per site conditions including Supply & fixing of double compression brass cable gland with all accessories including earthing tag, shroud, complete termination, testing & commissioning as per IS/IEC standards.Control cables shall be properly terminated using suitable size lugs and ferrules, ensuring correct identification, tight connections, and reliable operation as per standard practices.The work includes cost of all the material.
157Laying and Fixing of lnterlocking Bricks in the Switchyard 1.5 Mtr wide. Making approach path after Proper leveling and finishing etc. The work includes cost of all the material.
158Painting of Structure Painting of following structure with one coat of ready mixed primer and 2 coats of AL.Paint of good quality including cost of material, Labour and T&P complete in all respect. The work includes cost of all the material.
159Bus Gantry ( Complete set)
160Terminal Gantry
161Bus/Line Isolator Structure & Fuse set Structure
162Lightening Arrestor
163Post Insulator Structure
164Cable Stand
165Neutral Stand
166CT Structure & P.T. Structure
167Scraping, Rubbing, cleaning of wiremesh fencing and its Gate of both side with one coat of Red Oxide Paint as primer then painting with superior quality of Bus Grean Colour in two coats including cost of paint & other allied material.
168Supply, fixing and mounting of following equipments/ items in the control room
169Fire Extinguisher Mounted Type
170Fire Bucket (4 No) with stand Complete
171Rubber matting one side chequered and other side plane size 1800x900x12mm
172Rubber hand gloves
173Office Table (Size 1220 mm X 915 mm) & 3 No Chair and 1 No. Bench
174Wall Clock
175Sign Board, Single Line Diagramm Board, Notice Board, Max/Min Load Board with complete fittings.
176Commissioning of 01 No. 5MVA T/F and its eqipments installed in switchyards and 11 KV Incoming and Outgoing Pannels complete in all respect upto energising.
177Supply and filling of river sand in Cable Trench in this Switch gear room
178Maintenance & Repairing of 5MVA T/F
179If The B.D.V. of Oil is Low then the centrifusing of Transformer Oil is Necesarry On the Basis for requirement of Centrifusing of Transformer Oil,All the Equipment and Machinary Needed For Centrifusing of Oil shall be provided By Contractor.
180Supply and Installation of Silica Gel With Cabinet.
181Supply and Installation of OTI&WTI
182Painting of 5 MVA T/F
183Replacement of Damage oil seal/Packing
184Part-(C ) Construction of 11 KV LineSafe Loading carriage including unloading & proper stacking of following store materials from from any store of MVVNL to site of work.
185PCC 8.5 Mtr. Long
186STP 11.0 Mtr. Long
18711 KV Pin Insulattor polymeric
18811 KV Disc insulator polymeric
18911 kv Disc insulator Fitting
190V Type channel X-arm for 11 KV
191M.S. Earthing Rod with GI wire
192M.S. TOP Channel For 11 KV Line
193MS. Bracing Angle
19411 KV stay Set Complete for 11 KV line
1953x120mm2 XLPE 11KV
19611KV Cable Jointing Kit for 3x120 mm sqr cable O/D type
197Cost of ACSR Weasel Conductor
198T- off chennel.
199Errection of Single Pole Support-The excavation of foundation pit of size (750x450) mm and having depth of 1/6 of the full length of the support. Errection of support, complete with providing & Fixing of all clamps and other accessories as per respo drawing. The work includes carriage and handling support from sectional store to pit site as well as any fabrication work if required. (Necessary clamps, F-Bracket, stone pad shall be provided by Contractor.)
200P.C.C Pole 8.5 Mtr. Long.
201STP,SP 55 Round Pole 11 Mtr. Long
202Errection of Sectional Double Pole support-The excavation of foundation pit of size (750x450) mm and having depth of 1/6 of the full length of the support. Errection of support, complete with providing & Fixing of all clamps and other accesories as per respo drawing. The work includes carriage and handling of supports from sectional store to pit site, fixing of Top Channel and cross bracing sets as well as any fabrication work if required. (Top channel clamps, Bracing angle Clamp, E-Bracket, Disc fitting, bolt and nuts, stone pad as per norms etc shall be provided by Contractor.)
2038.5 Mtr. PCC Pole.
204Concreting and plinthing of Poles-Grouting of supports in PCC 1:4:8 (cement, sand, & 20 mm size stone Grit). Grouting will be done in the block of size (450x450)mm x 1/6th of full length of support, upto ground level, 300mm plinth above the ground level with C.C 1:3:6 (Cement, Coarse sand and Stone grit of 20mm of size with muffing as per drawing).
2058.5 Mtr. P.C.C Pole
206STP,SP 55 Round Pole 11 Mtr. Long
207Fixing of Stay rod (size 16x1800 mm)
208Fixing of Stay set complete (size 16x1800 mm) on different types of supports as per drawing.
209Grouting of Stay rods including all work of excavation, cement concrete in size (0.60x0.6x0.30)m in ratio 1:4:8 cement, sand, 400mm brick ballast as per drg. Including back filling of soil and proper ramming.
210Stringging and Sagging of Conductor
211Laying, Spreading, lifting and final sagging of 3 phases of ACSR Weasel conductor in accordance with Line chart including binding and fixing of all accessories in 03 Nos. Conductor in Parallel.
212Making jumpers on Section Points, by providing and fixing of P.G. Clamps of proper sizes, suitable for Dog Conductor
213Sectional Double Pole structure
214Supply & fixing of danger board at each location as per specification of drawing.
215Earthing of support with M.S. Earth rod of (20x2500 mm) long including excavation of pit and driving M.S. rod 0.5 mtr. Below the ground level and connecting the electrode with help of G.I. wire No 8 SWG and earthing lug. (G.I. Wire, bolt and nut and lugs shall be provided by the contractor.)
216Chopping of branches of trees of eucalyptus, Neem, Keeker and other kind of trees along the route of the line and disposal of the same at suitable place.
217Cradle Guarding of 33KV line at road crossing, 11 line crossing, canal/telephone line crossing by fixing M.S. Angle by strining and sagging of 3 No. G.I. wire, tighting with mounting. (MS angle, I-Hook, Nut & Bolts, Clamps and GI wire shall be provided by the controctor).
218Wraping of barbed wire on 33 KV SP-72/SP-55 ST Poles as anti climbing device for a length of 0.9 Mtr. Wire pitch /Gap 33 mm and fixing upper and lower end keeping lower end at a height of 2.75Mtr. From the ground complete with providing and fixing of lower end & upper end clamps made of M.S Flat 40x5mm complete with nuts&bolts. (All the material will be supplied by the controctor).
21911 kv Disc insulator Fitting
220Painting of following supports/structures with 2 coats of synthetic enamel Aluminium Paint after one coat of ready mix primer including cost of all material, as well as rubbing/cleaning of surface as required for proper completion of work.
221Single Pole STP 11 mtr. Long.
222Errection of T-Off Channel on supports properly complete Job in all respect Please Enable Macros to View BoQ information

Other Detail

Information Source https://etender.up.nic.in
Download FileName File Description File Size
Download 3.pdf Tender Documents 0 KB
Download b808798c-a636-460e-b29d-1717f436aed3.html Tender Documents 0 KB
Download BOQ_2137627.xls Tender Documents 0 KB
Download Tendernotice_1 (15).pdf Tender Documents 0 KB
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.