Tendering Authority Overseas Keralites Investment & Holding Ltd
Tender No RS-013(7)/TRANSFORMER
Tender ID 2026_OKIH_846087_2
Tender Brief Corrigendum : Tender For Boq For Supply, Installation, Testing And Commissioning Of Transformers And Allied Infrastructure (To Be Filled Only In Excel Sheet In E-Tender Portal To Protect Sanctity Of Rfp Process. No Hard Copy To Be Forwarded) Sl No: Description Of
City Kasaragod
State Kerala
Document Fees Refer document
EMD INR 25000.0 /-
Tender Value Refer document
Tender Type Tender
Bidding Type Open Tender
Competition Type Indian

Tender Details

Tender for Boq For Supply, Installation, Testing And Commissioning Of Transformers And Allied Infrastructure (To Be Filled Only In Excel Sheet In E-Tender Portal To Protect Sanctity Of Rfp Process. No Hard Copy To Be Forwarded) Sl No: Description Of Item Scope/Purpose Quantity Unit Rate , Transformner 02 Supply Of 400 Kva Outdoor Type Unitized Substation (Uss) Comprising Of Cast Resin Transformer With 630A, 4Pole On Lt. Side As Per Technical Details Furnished Below. Transformer Portion Consists Of 400Kva 11Kv/433V Outdoor Cast Resin Dry Type(An) Transformer (Copper Wound) Having A Continuous Rating For 11Kv/433V 3 Phase, Vector Dyn-11 With Off Load Tap Changing From +5% To -10% In Step Of 2.5. Transformer Should Have Cable End Box On Hv Side And Lv Side With All Accessories, Complete As Required As Per State Electricity Board And Ie Rules Specifications. The Class Of Winding Insulation Shall Be Correspond To Class F. The Transformer Shall Confirm To Is 2067/77, 11171/1985 With Latest Amendment Etc. Transformer Losses Shall Be As Per Ecbc 2017 (With Amendments Up To 2020). The Lt Portion Shall Be Provided With 1No 4Pole 630A 50Hz 36Ka Microprocessor Based Mccb With Inbuilt Earth Fault Release, Shunt/Uv Coil, Adjustable Setting Range Of 50-100%, Rotary Handle, And Spreader Links. A Low-Set Earth-Fault Relay Shall Be Provided Lt Side, And Ct Of Suitable Ratio With Accuracy Class 5P10 Shall Be Provided At The Neutral Earthing Point. All Inter Connection From Transformer To Lt Breaker Shall Be Given Using Electrolytic Copper Bus Bar Insulated With Heat Shrink And Tinned At The Point Of Contacts. All Internal Earth Connections Are To Be Given As Per Standards. Necessary Protection Shall Be Made For Giving Cable Connections On The Ht Side As Well As Lt Side. Phase Barriers And Shrouding As Per Rules Has To Be Given. The Enclosure Shall Comply To Ip Standards For Outdoor Installation And Shall Be Powder Coated Over Suitable Primer After Seven Tank Processing. , Transformner 03 Supply Of 315 Kva Outdoor Type Unitized Substation (Uss) Comprising Of Cast Resin Transformer With 500A, 4Pole On Lt. Side As Per Technical Details Furnished Below. Transformer Portion Consists Of 315Kva 11Kv/433V Outdoor Cast Resin Dry Type(An) Transformer (Copper Wound) Having A Continuous Rating For 11Kv/433V 3 Phase, Vector Dyn-11 With Off Load Tap Changing From +5% To -10% In Step Of 2.5. Transformer Should Have Cable End Box On Hv Side And Lv Side With All Accessories, Complete As Required As Per State Electricity Board And Ie Rules Specifications. The Class Of Winding Insulation Shall Be Correspond To Class F. The Transformer Shall Confirm To Is 2067/77, 11171/1985 With Latest Amendment Etc. Transformer Losses Shall Be As Per Ecbc 2017 (With Amendments Up To 2020). The Lt Portion Shall Be Provided With 1No 4Pole 500A 50Hz 36Ka Microprocessor Based Mccb With Inbuilt Earth Fault Release, Shunt/Uv Coil, Adjustable Setting Range Of 50-100%, Rotary Handle, And Spreader Links. A Low-Set Earth-Fault Relay Shall Be Provided Lt Side, And Ct Of Suitable Ratio With Accuracy Class 5P10 Shall Be Provided At The Neutral Earthing Point. All Inter Connection From Transformer To Lt Breaker Shall Be Given Using Electrolytic Copper Bus Bar Insulated With Heat Shrink And Tinned At The Point Of Contacts. All Internal Earth Connections Are To Be Given As Per Standards. Necessary Protection Shall Be Made For Giving Cable Connections On The Ht Side As Well As Lt Side. Phase Barriers And Shrouding As Per Rules Has To Be Given. The Enclosure Shall Comply To Ip Standards For Outdoor Installation And Shall Be Powder Coated Over Suitable Primer After Seven Tank Processing. , Transformner 04 Supply Of 200 Kva Outdoor Type Unitized Substation (Uss) Comprising Of Cast Resin Transformer With 320A, 4Pole On Lt. Side As Per Technical Details Furnished Below. Transformer Portion Consists Of 200Kva 11Kv/433V Outdoor Cast Resin Dry Type(An) Transformer (Copper Wound) Having A Continuous Rating For 11Kv/433V 3 Phase, Vector Dyn-11 With Off Load Tap Changing From +5% To -10% In Step Of 2.5. Transformer Should Have Cable End Box On Hv Side And Lv Side With All Accessories, Complete As Required As Per State Electricity Board And Ie Rules Specifications. The Class Of Winding Insulation Shall Be Correspond To Class F. The Transformer Shall Confirm To Is 2067/77, 11171/1985 With Latest Amendment Etc. Transformer Losses Shall Be As Per Ecbc 2017 (With Amendments Up To 2020). The Lt Portion Shall Be Provided With 1No 4Pole 320A 50Hz 25Ka Microprocessor Based Mccb With Inbuilt Earth Fault Release, Adjustable Setting Range Of 50-100%, Rotary Handle, And Spreader Links. All Inter Connection From Transformer To Lt Breaker Shall Be Given Using Electrolytic Copper Bus Bar Insulated With Heat Shrink And Tinned At The Point Of Contacts. All Internal Earth Connections Are To Be Given As Per Standards. Necessary Protection Shall Be Made For Giving Cable Connections On The Ht Side As Well As Lt Side. Phase Barriers And Shrouding As Per Rules Has To Be Given. The Enclosure Shall Comply To Ip Standards For Outdoor Installation And Shall Be Powder Coated Over Suitable Primer After Seven Tank Processing. Total Amount 0.0 , Boq For Supply, Installation, Testing And Commissioning Of Transformers And Allied Infrastructure (To Be Filled Only In Excel Sheet In E-Tender Portal To Protect Sanctity Of Rfp Process. No Hard Copy To Be Forwarded) Sl No: Description Of Item Scope/Purpose Quantity Unit Rate , Transformner 02 Supply Of 400 Kva Outdoor Type Unitized Substation (Uss) Comprising Of Cast Resin Transformer With 630A, 4Pole On Lt. Side As Per Technical Details Furnished Below. Transformer Portion Consists Of 400Kva 11Kv/433V Outdoor Cast Resin Dry Type(An) Transformer (Copper Wound) Having A Continuous Rating For 11Kv/433V 3 Phase, Vector Dyn-11 With Off Load Tap Changing From +5% To -10% In Step Of 2.5. Transformer Should Have Cable End Box On Hv Side And Lv Side With All Accessories, Complete As Required As Per State Electricity Board And Ie Rules Specifications. The Class Of Winding Insulation Shall Be Correspond To Class F. The Transformer Shall Confirm To Is 2067/77, 11171/1985 With Latest Amendment Etc. Transformer Losses Shall Be As Per Ecbc 2017 (With Amendments Up To 2020). The Lt Portion Shall Be Provided With 1No 4Pole 630A 50Hz 36Ka Microprocessor Based Mccb With Inbuilt Earth Fault Release, Shunt/Uv Coil, Adjustable Setting Range Of 50-100%, Rotary Handle, And Spreader Links. A Low-Set Earth-Fault Relay Shall Be Provided Lt Side, And Ct Of Suitable Ratio With Accuracy Class 5P10 Shall Be Provided At The Neutral Earthing Point. All Inter Connection From Transformer To Lt Breaker Shall Be Given Using Electrolytic Copper Bus Bar Insulated With Heat Shrink And Tinned At The Point Of Contacts. All Internal Earth Connections Are To Be Given As Per Standards. Necessary Protection Shall Be Made For Giving Cable Connections On The Ht Side As Well As Lt Side. Phase Barriers And Shrouding As Per Rules Has To Be Given. The Enclosure Shall Comply To Ip Standards For Outdoor Installation And Shall Be Powder Coated Over Suitable Primer After Seven Tank Processing. , Transformner 03 Supply Of 315 Kva Outdoor Type Unitized Substation (Uss) Comprising Of Cast Resin Transformer With 500A, 4Pole On Lt. Side As Per Technical Details Furnished Below. Transformer Portion Consists Of 315Kva 11Kv/433V Outdoor Cast Resin Dry Type(An) Transformer (Copper Wound) Having A Continuous Rating For 11Kv/433V 3 Phase, Vector Dyn-11 With Off Load Tap Changing From +5% To -10% In Step Of 2.5. Transformer Should Have Cable End Box On Hv Side And Lv Side With All Accessories, Complete As Required As Per State Electricity Board And Ie Rules Specifications. The Class Of Winding Insulation Shall Be Correspond To Class F. The Transformer Shall Confirm To Is 2067/77, 11171/1985 With Latest Amendment Etc. Transformer Losses Shall Be As Per Ecbc 2017 (With Amendments Up To 2020). The Lt Portion Shall Be Provided With 1No 4Pole 500A 50Hz 36Ka Microprocessor Based Mccb With Inbuilt Earth Fault Release, Shunt/Uv Coil, Adjustable Setting Range Of 50-100%, Rotary Handle, And Spreader Links. A Low-Set Earth-Fault Relay Shall Be Provided Lt Side, And Ct Of Suitable Ratio With Accuracy Class 5P10 Shall Be Provided At The Neutral Earthing Point. All Inter Connection From Transformer To Lt Breaker Shall Be Given Using Electrolytic Copper Bus Bar Insulated With Heat Shrink And Tinned At The Point Of Contacts. All Internal Earth Connections Are To Be Given As Per Standards. Necessary Protection Shall Be Made For Giving Cable Connections On The Ht Side As Well As Lt Side. Phase Barriers And Shrouding As Per Rules Has To Be Given. The Enclosure Shall Comply To Ip Standards For Outdoor Installation And Shall Be Powder Coated Over Suitable Primer After Seven Tank Processing. , Transformner 04 Supply Of 200 Kva Outdoor Type Unitized Substation (Uss) Comprising Of Cast Resin Transformer With 320A, 4Pole On Lt. Side As Per Technical Details Furnished Below. Transformer Portion Consists Of 200Kva 11Kv/433V Outdoor Cast Resin Dry Type(An) Transformer (Copper Wound) Having A Continuous Rating For 11Kv/433V 3 Phase, Vector Dyn-11 With Off Load Tap Changing From +5% To -10% In Step Of 2.5. Transformer Should Have Cable End Box On Hv Side And Lv Side With All Accessories, Complete As Required As Per State Electricity Board And Ie Rules Specifications. The Class Of Winding Insulation Shall Be Correspond To Class F. The Transformer Shall Confirm To Is 2067/77, 11171/1985 With Latest Amendment Etc. Transformer Losses Shall Be As Per Ecbc 2017 (With Amendments Up To 2020). The Lt Portion Shall Be Provided With 1No 4Pole 320A 50Hz 25Ka Microprocessor Based Mccb With Inbuilt Earth Fault Release, Adjustable Setting Range Of 50-100%, Rotary Handle, And Spreader Links. All Inter Connection From Transformer To Lt Breaker Shall Be Given Using Electrolytic Copper Bus Bar Insulated With Heat Shrink And Tinned At The Point Of Contacts. All Internal Earth Connections Are To Be Given As Per Standards. Necessary Protection Shall Be Made For Giving Cable Connections On The Ht Side As Well As Lt Side. Phase Barriers And Shrouding As Per Rules Has To Be Given. The Enclosure Shall Comply To Ip Standards For Outdoor Installation And Shall Be Powder Coated Over Suitable Primer After Seven Tank Processing. Total Amount 0.0

Corrigendum Details

Sr No CorrigendumDate Corrigendum CorrigendumType NewSubmissionDate
1 18-05-2026 Date Extension Date 08-06-2026

Key Dates

Publish Date 18-05-2026
Last Date of Bid Submission 08-06-2026
Tender Opening Date 10-06-2026

Contact Information

Company Name Overseas Keralites Investment & Holding Ltd
Contact Person Managing Director
Address Managing Director, OKIH Ltd., 6th Floor, NORKA Centre, Thycaud, Thiruvananthapuram

BOQ Items

Name of Work:-
Sl. No. Item Description
1BOQ FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF TRANSFORMERS AND ALLIED INFRASTRUCTURE (To be filled only in Excel Sheet in e-Tender Portal to protect sanctity of RFP process. No hard copy to be forwarded) Sl No: Description of Item Scope/Purpose Quantity Unit Rate
2Transformner 02Supply of 400 KVA outdoor type unitized substation (USS) comprising of cast resin Transformer with 630A, 4pole on LT. side as per technical details furnished below.Transformer portion consists of 400kVA 11kV/433V outdoor cast resin dry type(AN) transformer (copper wound) having a continuous rating for 11kV/433V 3 phase, vector DYN-11 with off load tap changing from +5% to -10% in step of 2.5. Transformer should have cable end box on HV side and LV side with all accessories, complete as required as per State electricity board and IE rules specifications. The class of winding insulation shall be correspond to class F. The transformer shall confirm to IS 2067/77, 11171/1985 with latest amendment etc. Transformer losses shall be as per ECBC 2017 (with amendments up to 2020).The LT portion shall be provided with 1No 4Pole 630A 50Hz 36kA microprocessor based MCCB with inbuilt earth fault release, shunt/UV coil, adjustable setting range of 50–100%, rotary handle, and spreader links. A low-set earth-fault relay shall be provided LT side, and CT of suitable ratio with accuracy class 5P10 shall be provided at the neutral earthing point.All inter connection from transformer to LT breaker shall be given using electrolytic copper bus bar insulated with heat shrink and tinned at the point of contacts. All internal earth connections are to be given as per standards. Necessary protection shall be made for giving cable connections on the HT side as well as LT side. Phase barriers and shrouding as per rules has to be given. The enclosure shall comply to IP standards for outdoor installation and shall be powder coated over suitable primer after seven tank processing.
3Transformner 03Supply of 315 KVA outdoor type unitized substation (USS) comprising of cast resin Transformer with 500A, 4pole on LT. side as per technical details furnished below.Transformer portion consists of 315kVA 11kV/433V outdoor cast resin dry type(AN) transformer (copper wound) having a continuous rating for 11kV/433V 3 phase, vector DYN-11 with off load tap changing from +5% to -10% in step of 2.5. Transformer should have cable end box on HV side and LV side with all accessories, complete as required as per State electricity board and IE rules specifications. The class of winding insulation shall be correspond to class F. The transformer shall confirm to IS 2067/77, 11171/1985 with latest amendment etc. Transformer losses shall be as per ECBC 2017 (with amendments up to 2020).The LT portion shall be provided with 1No 4Pole 500A 50Hz 36kA microprocessor based MCCB with inbuilt earth fault release, shunt/UV coil, adjustable setting range of 50–100%, rotary handle, and spreader links. A low-set earth-fault relay shall be provided LT side, and CT of suitable ratio with accuracy class 5P10 shall be provided at the neutral earthing point.All inter connection from transformer to LT breaker shall be given using electrolytic copper bus bar insulated with heat shrink and tinned at the point of contacts. All internal earth connections are to be given as per standards. Necessary protection shall be made for giving cable connections on the HT side as well as LT side. Phase barriers and shrouding as per rules has to be given. The enclosure shall comply to IP standards for outdoor installation and shall be powder coated over suitable primer after seven tank processing.
4Transformner 04Supply of 200 KVA outdoor type unitized substation (USS) comprising of cast resin Transformer with 320A, 4pole on LT. side as per technical details furnished below.Transformer portion consists of 200kVA 11kV/433V outdoor cast resin dry type(AN) transformer (copper wound) having a continuous rating for 11kV/433V 3 phase, vector DYN-11 with off load tap changing from +5% to -10% in step of 2.5. Transformer should have cable end box on HV side and LV side with all accessories, complete as required as per State electricity board and IE rules specifications. The class of winding insulation shall be correspond to class F. The transformer shall confirm to IS 2067/77, 11171/1985 with latest amendment etc. Transformer losses shall be as per ECBC 2017 (with amendments up to 2020).The LT portion shall be provided with 1No 4Pole 320A 50Hz 25kA microprocessor based MCCB with inbuilt earth fault release, adjustable setting range of 50–100%, rotary handle, and spreader links.All inter connection from transformer to LT breaker shall be given using electrolytic copper bus bar insulated with heat shrink and tinned at the point of contacts. All internal earth connections are to be given as per standards. Necessary protection shall be made for giving cable connections on the HT side as well as LT side. Phase barriers and shrouding as per rules has to be given. The enclosure shall comply to IP standards for outdoor installation and shall be powder coated over suitable primer after seven tank processing. Total Amount 0.0

Other Detail

Information Source https://etenders.kerala.gov.in
Download FileName File Description File Size
Download 15a7f3aa-4281-4f8c-891b-64c4a56d63a6.html Tender Documents 0 KB
Download BoQtrans.xls Tender Documents 0 KB
Download Tendernotice_1.pdf Tender Documents 0 KB
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.