Indian Tenders

Tender Notice

TDR 55168825
Tendering Authority Road And Building Department
Tender No SE CTC (RandB)-01 of 2026-27
Tender ID 2026_EICCL_128295_1
Tender Brief Corrigendum : Tender For Supply Installation Testing and Commissioning of 500 Kva Transformer With Dp Structure & Other Accessories For Drug Ware House And Newly Constructed Fire Pump House, Scbmch, Cuttack
City Cuttack
State Odisha
Document Fees INR 6000 /-
EMD INR 27200.0 /-
Tender Value INR 27.18 Lakhs /-
Tender Type Tender
Bidding Type Open Tender
Competition Type Indian

Tender Details

Tender for Supply Installation Testing and Commissioning of 500 Kva Transformer With Dp Structure & Other Accessories For Drug Ware House And Newly Constructed Fire Pump House, Scbmch, Cuttack

Corrigendum Details

Sr No CorrigendumDate Corrigendum CorrigendumType NewSubmissionDate
1 02-05-2026 Corrigendum Date 11-05-2026

Key Dates

Publish Date 02-05-2026
Last Date of Bid Submission 11-05-2026
Tender Opening Date 12-05-2026

Contact Information

Company Name Road And Building Department
Contact Person SE Cuttack RandB Division No_I, Cuttack
Address O/O SE Cuttack RandB Division No_I, Cuttack

BOQ Items

Name of Work:- SITC of 500 KVA Transformer with DP structure & other accessories for Drug ware House and newly constructed Fire Pump House, SCBMCH, Cuttack
Sl. No. Item Description
1PART-A :- Construction of 11 KV O/H line of 0.08 CKM using 55 Sq.mm. XLPE AAAC Covered Conductor along with cutpoint arrangementNo. of Cut Point with 180 Degree Angle(Ref. Drawing No.- TPCODL-MVD-0004)WPB (GI) Pole 160x152 (11Mtr. Long, 30.44KG/Mtr.)
2Straight Cross Arm 100X50X6mm, 9.56 KG/Mtr., each Channel(GI) length 1.2 mtr., 2 no's Channel(GI) required =( 2x9.56x1.2)
3Fish Plate(GI) 50x6 mm., 2.36 kg/Mtr., each 0.280 mtr. length, 8 no's required = (8x2.36x0.280)
4Straight Cross Arm 100X50X6mm, 9.56 KG/Mtr., each Channel(GI) length 0.306 mtr., 2 no'sChannel(GI) required =(2x9.56x0.306)
5Danger Plate, 1 no's.
6Back Clamp for danger Plate 25X3 mm. Flat(GI), 0.59Kg/Mtr. Flat(GI) of 0.510mtr length 1 no's = (1x0.59x0.510)
7GI barbed wire anticlimbing device 3 Kg. Per support
8Back Clamp for anticlimbing device 25X3 mm. Flat(GI), 0.59Kg/Mtr. Flat(GI) of 0.510mtr length 4 no's= (4x0.59x0.510)
911 KV pin insulator polymer
10H W fitting(B&S) 70KN, 3Bolt
11Disc insulator (B&S) 70 KN polymer
12Earthing of Support ( Coil Type )
13No-8 GI wire (Dia 4.6mm) 0.131 KG/ Mtr.- 2 Mtr. For connecting pole with Coil earthing
14NON METALLIC TIES -11KV 55SQMM CVRD AAAC
15IPC for 55 sq.mm AAA conductor (For covered conductor)-11kV
16GI Nut , Bolt & Washer of different sizes (3.55 Kg each Cut Pole)
17Black Paint(GIS Numbering & Zebra Stripping)
18Yellow Colour Paint(GIS Numbering & Zebra Stripping) for Background
19Civil & ServicesConcreting ratio 1:1.5:3(M-20 Grade) (500mmX500mmX1800mm) = 0.45Cu.mtr(Per Pole)
20Couping ratio 1:1.5:3(M-20 Grade) with dimension (500X500X450)= 0.1125 Cu mtr(Per Pole)
21No. of Cut Point with 90 Degree Angle(Ref. Drawing No.- TPCODL-MVD-0005)WPB (GI) Pole 160x152 (11Mtr. Long, 30.44KG/Mtr.)
22Straight Cross Arm 100X50X6mm, 9.56 KG/Mtr., each Channel(GI) length 1.2 mtr., 4 no's Channel(GI) required =( 4x9.56x1.2)
23Fish Plate(GI) 50x6 mm., 2.36 kg/Mtr., each 0.280 mtr. length, 16 no's required = (16x2.36x0.280)
24Straight Cross Arm 100X50X6mm, 9.56 KG/Mtr., each Channel(GI) length 0.306 mtr., 4 no'sChannel(GI) required =( 4x9.56x0.306)
25Danger Plate, 1 no's.
26Back Clamp for danger Plate 25X3 mm. Flat(GI), 0.59Kg/Mtr. Flat(GI) of 0.510mtr length 1 no's = (1x0.59x0.510)
27GI barbed wire anticlimbing device 3 Kg. Per support
28Back Clamp for anticlimbing device 25X3 mm. Flat(GI), 0.59Kg/Mtr. Flat(GI) of 0.510mtr length 4 no's= (4x0.59x0.510)
2911 KV pin insulator polymer
30H W fitting(B&S) 70KN, 3Bolt
31Disc insulator (B&S) 70 KN polymer
32Earthing of Support ( Coil Type )
33No-8 GI wire (Dia 4.6mm) 0.131 KG/ Mtr.- 2 Mtr. For connecting pole with Coil earthing
34NON METALLIC TIES -11KV 55SQMM CVRD AAAC
35IPC for 55 sq.mm AAA conductor (For covered conductor)-11kV
36WEDGE CONNECTOR FOR 80 SQMM.CONDUCTOR
37H.T. Stay clamp, 50x8 mm. Flat(GI), 3.14Kg/Mtr., 0.551 Mtr. Length, 2 no's qty. required ( 1 Pair)
38H.T. Stay set (Complete )
39H.T. Stay Insulator Type-C
407/10 SWG Stay Wire 15kg /stay
41GI Nut , Bolt & Washer of different sizes (7.433 Kg each Cut Pole)
42Black Paint(GIS Numbering & Zebra Stripping)
43Yellow Colour Paint(GIS Numbering & Zebra Stripping) for Background
44Civil & ServicesFixing of complete 11KV line Complete stay set includes1) Turn Buckle Assembly2) Stay Rod & Stay plate3) Stay Insulator4) Stay Wire.5)Stay clamps with Nuts & bolts BA will do the excvation including excvation, supply of 0.5Cum cement concrete foundation 1:2:4 size ( 500mmx500mmx800mm) using 20mm BHG metal with all labour and material as per TPCODL Drawing & Standard.
45Concreting ratio 1:1.5:3(M-20 Grade) (500mmX500mmX1800mm) = 0.45Cu.mtr(Per Pole)
46Couping ratio 1:1.5:3(M-20 Grade) with dimension ( 500X500X450)= 0.1125 Cu mtr(Per Pole)
4711 Kv Line Length In KM with 40 Mtr. Span(Ref. Drawing No.- TPCODL-MVD-0003)WPB (GI) Pole 160x152 (11Mtr. Long, 30.44KG/Mtr.)
4811 KV V cross Arm(GI) (10.2 K.g. each )
49Top bracket 100x50X6 mm GI Channel(GI) (2kg each)
50Danger Plate, 1 no's. for each pole
51Back Clamp for danger Plate 25X3 mm. Flat(GI), 0.59Kg/Mtr. Flat(GI) of 0.510mtr length 1 no's = (1x0.59x0.510)
52GI barbed wire anticlimbing device 3 Kg. Per support
53Back Clamp for anticlimbing device 25X3 mm. Flat(GI), 0.59Kg/Mtr. Flat(GI) of 0.510mtr length 4 no's= (4x0.59x0.510)
5411 KV pin insulator polymer, 3 Nos. required for each support
55Earthing of Support ( Coil Type )
56No-8 GI wire (Dia 4.6mm) 0.131 KG/ Mtr.- 2 Mtr. For connecting pole with Coil earthing
57GI Nut , Bolt & Washer of different sizes (1.45 Kg/ Pin Point)
5855 SQ.MM. AAAC XLPE Covered Conductor
59Black Paint(GIS Numbering & Zebra Stripping)
60Yellow Colour Paint(GIS Numbering & Zebra Stripping) for Background
61NON METALLIC TIES -11KV 55SQMM CVRD AAAC
62Civil & ServicesConcreting ratio 1:1.5:3(M-20 Grade) (500mmX500mmX1800mm) = 0.45Cu.mtr(Per Pole)
63Couping ratio 1:1.5:3(M-20 Grade) with dimension (500X500X450)= 0.1125 Cu mtr(Per Pole)
64Part-B :- Construction of 11KV Line Guarding from pole to pole for road crossingGuarding Channel(GI) 75x40x4.8 mm, 7.14 KG/Mtr., each Channel(GI)length 2.2 mtr., 4 no's Channel(GI) required =( 4x7.14x2.2) ( For Single Pole)
65No-6 GI wire (0.192 kg/mtr.) for Main String
66No-8 GI wire (0.131 kg/mtr.) for lacing
67Eye Bolt (236mm, 16mm dia, 1.577kg/mtr.)
68Gi Pipe Earthing 40mm. 3 Mtr. Long
6950x6mm Flat(GI) for earthing, 2.36kg/mtr., (10.7 mtr For raising)=10.7x2.36
70Civil & ServicesConstruction Earthing chamber including installation of earthing pipe.Making earthing chamber including excavation , soil treatment with bentonide powder , calculation of earth resistance, including Installation of 3Mtr GI Pipe 40mm/50mm including welding of Flat(GI)around pipe .
71Part C :- Installation of One No. of 11KV DP with AB Switch and LA for HT metering unit WPB(GI) 160x152 (11Mtr. Long, 30.44KG/Mtr.) -DP
72Top Channel(GI) 100X50X6mm, 9.56 KG/Mtr., each Channel(GI) length 3 mtr., 2 no's Channel(GI) required =( 2x9.56x3)
73Fish Plate(GI) 50x6 mm., 2.36 kg/Mtr., each 0.280 mtr. length, 6 no's required = (6x2.36x0.280)
74AB switch Mounting Channel(GI) 75X40X4.8mm, 7.14KG/Mtr, each Channel(GI) length 3Mtr., 2 no's Channel(GI) required =( 7.14x3x2)
75HT MU Mounting Channel(GI) 100X50X6mm, 9.56KG/Mtr, each Channel(GI) length 3 Mtr.,2 no's Channel(GI) required =( 9.56x3x2)
76Cantilever Support Channel(GI) 75x40x4.8 mm GI Channel(GI) (810 mm long,2No's.) (7.14Kg./Mtr., 2 No's.) (Each 2x0.81x7.14)
77Angle(GI) for Cantilever arrrangement for HT MU 50 x 50 x 6 - 1282 mm.each 2nos.(4.5 K.g. per mtr.)
78MU and AB Switch Side Support Channel(GI) 100X50X6mm,9.56 KG/Mtr., eachChannel(GI) length 0.35 mtr., 4 no's Channel(GI) required =( 9.56x4x0.35)
79Channel(GI) Support for down Pipe 75X40X 4.8mm., 7.14KG/Mtr., each Channel(GI) length 0.8 Mtr., 1 no's Channel(GI) required =( 7.14x0.8x1)
80Double Pole Belting Channel(GI) 75X40X 4.8mm., 7.14KG/Mtr., each Channel(GI) length 3 Mtr., 2 no's Channel(GI) required =( 7.14x3x2)
8150x50x6mm.GI Bracing Angle(GI), 4.5Kg./mtr., each Angle(GI) length 3.512 mtr., 2 nos Angle(GI) required = (4.5x3.512x2)
82Danger Plate, 2 no's.
83Back Clamp for danger Plate 25X3 mm. Flat(GI), 0.59Kg/Mtr. Flat(GI) of 0.510mtr length 2no's = (2x0.59x0.510)
8455mm2 ACSR - PVC Insulated for Jumpering
85H.T. Stay clamp, 50x8 mm. Flat(GI), 3.14Kg/Mtr., 0.551 Mtr. Length, 2 no's qty. required (1 Pair)
86H.T. Stay set (Complete )
87H.T. Stay Insulator Type-C
887/10 SWG Stay Wire 15kg /stay
89Gi Pipe Earthing 40mm. 3 Mtr. Long
9050x6mm Flat(GI) for earthing, 2.36kg/mtr., (12.5 Mtr. For L.A, 3 Mtr for AB Switch Body,2.5 mtr. For mesh formation and 2.5 mtr. For raising)= 20.5x2.36
91GI barbed wire anticlimbing device 3 Kg. Per support, 2 no's qty. required =(2x3kg)
92Back Clamp for anticlimbing device 25X3 mm. Flat(GI), 0.59Kg/Mtr. Flat(GI) of 0.510mtr length 8 no's = (8x0.59x0.510)
93Lightning Arrester(12KV,10KA) (Station Class,class-2)
94AB Switch (11KV,200A.3pole,50Hz)
9511 KV pin insulator polymer
96H W fitting(B&S) 70KN, 3Bolt
97Disc insulator (B&S) 70 KN polymer
98WEDGE CONNECTOR FOR 55 SQMM.CONDUCTOR
99GI Nut , Bolt & Washer of different sizes (13.718 Kg each DP with AB Switch)
100POLYCARBONATE BIRD GUARD
101Black Paint(GIS Numbering & Zebra Stripping)
102Yellow Colour Paint(GIS Numbering & Zebra Stripping) for Background
103Civil & ServicesFixing of complete 11KV line Complete stay set includes1) Turn Buckle Assembly2) Stay Rod & Stay plate3) Stay Insulator4) Stay Wire.5)Stay clamps with Nuts & bolts BA will do the excvation including excvation, supply of 0.5Cum cement concrete foundation 1:2:4 size ( 500mmx500mmx800mm) using 20mm BHG metal with all labour and material as per TPCODL Drawing & Standard.
104Concreting ratio 1:1.5:3(M-20 Grade) (500mmX500mmX1800mm) =0.45Cu.mtr(Per Pole)
105Couping ratio 1:1.5:3(M-20 Grade) with dimension ( 500X500X450)= 0.1125 Cumtr(Per Pole)
106Construction Earthing chamber including installation of earthing pipe.Making earthing chamber including excavation , soil treatment with bentonide powder , calculation of earthresistance, including Installation of 3Mtr GI Pipe 40mm/50mm including welding of Flat(GI) around pipe .
107Supply and Erection of GI Fencing with Gate
108Part D :- Dismentling of MaterialsDismantling of 9/8 Mtr. PCC/Joist Pole
109Part- E Supply & Installation of 11/0.4 KV 500 KVA DSSWPB 160x152 (11Mtr. Long, 30.44KG/Mtr.)
110Top Channel GI 100 X 50 X 6 MM (3000 mm long) (9.56Kg./Mtr, 2 No's.) (Each 2x3.000x9.56= 57.36 Kg)
111Fish Plate 50x6 mm., 2.36 kg/Mtr., each 0.280 mtr. length, 6 no's required = (6x2.36x0.280)
112Double Pole Belting Channel 75X40X 4.8mm., 7.14KG/Mtr., each channel length 3.0 Mtr., 2 no's channel required =( 7.14x3x2)
11350x50x6mm.GI Bracing Angle, 4.5Kg./mtr., each angle length 3.512 mtr., 2 nos angle required = (4.5x3.512x2)
114AB Switch Mounting Channel 75x40x4.8 mm GI Channel (3000 mm long)(7.14Kg./Mtr., 2 No's.) (Each 2x3.000x7.14= 42.84 Kg)
115AB Switch Side Support Channel 100X50X6mm,9.56 KG/Mtr., each channel length 0.35 mtr., 2 no's channel required =( 9.56x2x0.35)
116Channel Support for down Pipe 75X40X 4.8mm., 7.14KG/Mtr., each channel length 0.8 Mtr., 1 no's channel required =( 7.14x0.8x1)
117HG/ DO Fuse Mounting Channel 75x40x4.8 mm GI Channel (3000 mm long)(7.14Kg./Mtr., 2 No's.) (Each 2x3.000x7.14= 39.98 Kg)
118Cantilever Support Channel 75x40x4.8 mm GI Channel (810 mm long,2 No's.) (7.14Kg./Mtr., 2 No's.) (Each 2x0.810x7.14= 11.57 Kg)
119Cantilever Support Angle 50 X 50 X 6MM GI (1282 mm long) (4.5Kg./Mtr, 2 No's.) (Each 2x1.282x4.5= 11.54Kg)
12050x6mm GI Flat for earthing, 2.36kg/mtr., (2.5x7 mtr. For mesh formation, 12 Mtr. For LA and 2.5 mtr. For raising, 11 mtr for AB switch, 2.8 mtr for HG Fuse, 5x2 mtr. for DTR Nutral, (1.3+4.5) mtr. For DTR Body, 0.500 mtr for LTDB & AB Switch operating handle, 3 mtr. for Fencing) ( Each 65.6x 2.36= 154.81 Kg)
121500 KVA , 11/ 0.4 KV (Cu) Transformer with Motorisied OLTC & RTCC Panel BIS Energy level II
122LT Distribution Box with MCCB, Aluminium Busbar for 3 Bay with kit kat fuse for 500 KVA S/S
12355mm2 All Alloy Aluminum Conductor (AAAC) - PVC Insulated (50 Mtr. Each Dtr.)
1241 Cx 400 mm2 LT XLPE Cable(Un-Armoured)
125AB Switch(11KV,200A.3pole,50Hz)
126H.G.Fuse( 11KV.200A.3Pole)
127PG Clamp for 55 sq.mm AAA conductor
128Disc insulator (B&S)70 KN polymer
129H W fitting (B&S)70KN(3bolted)
130Lightning Arrester(12KV,10KA) Station Class 2
13111KV pin insulator polymer
132HT stay set complete
133HT stay Clamp (1.9Kg/pair)
134HT stay insulator TYPE-C
1357/10 SWG GI stay wire, Grade -2 (15Kg./ Set)
13640 mm Nominal bore GI pipe (medium gauge) earthing device with 3 mtr .Long
137GI Nuts & Bolts of Assorted size (25 Kg/ DSS DP)
138GI Barbed wire/Anticlimbing device (3Kg /Pole)
139Back Clamp for danger Plate 25X3 mm. flat, 0.59Kg/Mtr. Flat of 0.510mtr length 8 no's (Each 8x0.59x0.510)
140Danger plate 11kv
141Back Clamp for danger Plate 25X3 mm. flat, 0.59Kg/Mtr. Flat of 0.510mtr length 2 no's (Each 2x0.59x0.510)
142Name plate
143Yellow Colour Paint for Background
144Black Colour Paint for numbering
145Civil and Services Works-Concreting ratio 1:1.5:3 (500mmX500mmX1800mm) = 0.450Cu.mtr
146Fixing of stay set with 0.5Cum cement concrete foundation 1:3:6 size ( 900mmx600mmx900mm) using 40mm BHG metal with all labor and material except stay set , stay wire , stay insulator .
147Couping ratio 1:1.5:3 (500mmX500mmX450mm) = 0.113Cu.mtr
148Construction Earthing chamber including installation of earthing pipe making earthing chamber including excavation, soil treatment with bentonide powder, calculation of earth resistance, including, installation of 3 Mtr GI pipe 40/50 mm including welding of GI flat around pipe.
149LTDB Plinth
150DTR Plinth Up to 1000 KVA
151Laying of 1.1 KV Cable upto 185 to 400 Sq mm
152Supply and Erection of GI Fencing with Gate Please Enable Macros to View BoQ information

Other Detail

Information Source http://tendersodisha.gov.in/nicgep/app
Download FileName File Description File Size
Download bde74a90-ce3a-4ac9-a5e7-e4cf04aefbf0.html Tender Documents 0 KB
Download BOQ_588261.xls Tender Documents 0 KB
Download Tendernotice_1.pdf Tender Documents 0 KB
Download Tendernotice_2 (2).pdf Tender Documents 0 KB
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.