Indian Tenders

Tender Notice

TDR 55150657
Tendering Authority Public Works Department
Tender No NIT No. 239-260 dated 08/04/2026
Tender ID 2026_PWD_134656_1
Tender Brief Corrigendum : Tender For Construction Of Rajiv Gandhi Govt. Model Day Boarding School At Amlehar, Tehsil Nadaun Distt. Hamirpur (Hp) (Sh:- Supply Installation Testing and Commissioning of 58.5 Kva Dg Set (Cpcb+4 Norms) Therein)
City Una
State Himachal Pradesh
Document Fees INR 500 /-
EMD INR 29300.0 /-
Tender Value INR 14.65 Lakhs /-
Tender Type Tender
Bidding Type Open Tender
Competition Type Indian

Tender Details

Tender for Construction Of Rajiv Gandhi Govt. Model Day Boarding School At Amlehar, Tehsil Nadaun Distt. Hamirpur (Hp) (Sh:- Supply Installation Testing and Commissioning of 58.5 Kva Dg Set (Cpcb+4 Norms) Therein)

Corrigendum Details

Sr No CorrigendumDate Corrigendum CorrigendumType NewSubmissionDate
1 27-04-2026 Extended of date Date 04-05-2026

Key Dates

Publish Date 27-04-2026
Last Date of Bid Submission 04-05-2026
Tender Opening Date 04-05-2026

Contact Information

Company Name Public Works Department
Contact Person Executive Engineer Electrical Division HPPWD. Una
Address Executive Engineer Electrical Division HPPWD. Una

BOQ Items

Name of Work:- Construction of Rajiv Gandhi Govt. Model Day Boarding School at Amlehar, Tehsil Nadaun Distt. Hamirpur (HP) (SH:- SITC of 58.5 KVA DG set (CPCB+4 NORMS) therein)
Sl. No. Item Description
1Supplying, Installation, Testing & Commissioning of ‘Silent Type Diesel Generating set as per CPCB IV + or better norms along with having Prime Power Rating of 58.5 KVA as below, 415 volts at 1500 RPM, 0.8 lagging power factor at 415 V suitable for 50 Hz, 3 phase system & for 0.85 Load Factor, including testing at factory and site with fuel, load for test and other necessary arrangements Complete as per CPWD specifications, should have QR code which should contain drawing, test report OEM manual,Geo- Tag of manufacturing location, rating plate as per relevant IS Code etc. and consisting of the followings. The DG Set canopy should be DG Set OEM Maufactured only.
2Diesel Engine:
3Turbocharged Diesel engine 4 stroke water cooled, multi cylinder, dynamically balanced fly wheel, electric start of suitable BHP at 1500 RPM suitable for above output of alternator at 40 0C, 50% RH & at 1000 Meter MSL , capable of taking 10% over loading for one hour after 12 hours of continuous operation. The engine will be with Electronic governor, Dry type Air filter with service indicator, first filling of engine fuel (after commissioning) lubricating Oil, Coolant and other consumables complete with all the required accessories, the Electronic governor shall be as per ISO 8528.The engine shall comply to the latest CPCB norms (CPCB IV + or better) and Conforming to BS 5514, BS 649, IS 10000, IS 10002, IS 13018 and as per CPWD specifications.:- Kirloskar /Cummins/ Caterpillar/Volvo Penta/ Perkins/Mitsubishi/ Ashok Leyland make only..
4Engine mounted Instrument Panel fitted with and having digital display for following:
5(i) Start-stop switch with key
6(ii) Water temperature indication
7(iii) Lubrication oil pressure indication
8(iv) Lubrication oil temperature indication
9(v) Battery charging indication
10(vi) RPM indication
11(vii) Over speed indication
12(viii) Low lub. Oil trip indication
13(ix) Engine Hours indication
14(X) Turbo charger
15Alternator :
16Synchronous alternator rated of appropriate 58.5 KVA, 415 volts at 1500 RPM, 3 phase 50 Hz, AC supply with 0.8 lagging power factor at 40 0C, 50% RH & at 1000 Meter MSL. The alternator shall be having Screen Protected Drip Proof (SPDP) enclosure IP23, brushless, continuous duty, dynamically balanced rotor, capable of taking 10% over loading for one hour after 12 hours of continuous operation, self cooled,self-excited and self-regulated through AVR conforming to IS13364(Part 2)/IS: 4722/BS 2613 suitable for tropical conditions and with class- H insulation.The alternator should be of Stamford/ Kirloskar/ Leroysomer/ Mitsubishi/ Caterpillar make only).
17Acoustic Encloure Base Frame & Foundation:
18Both the engine and alternator shall be mounted on suitable base frame made of MS channel with necessary reinforcement which shall be installed on suitable cement concrete foundation and vibration isolation arrangement as per recommendations of manufacturer.
19Fuel Tank:
20Daily service fuel tank of suitable liters capacity as per CPWD Specifications, fabricated out of 3 mm thick M.S. sheet complete with all standard accessories and fuel piping between fuel tank and diesel engine with MS class ‘C’ pipes of suitable dia. Complete with valves, level indications & accessories as required as per specifications.
21Exhaust System:
22Dry exhaust mainfold with hospital exhaust silencer and catalytic convertor.
2312V/DC starting system comprising of starter motors: voltage regulator and arrangement for initial excitation complete with suitable 1 no of battery (25 plates, 120 Amp. Hour capacity lead acid type) including 50 sqmm copper cable .The battery should be accommodate in battery rack as required as per specifications.
24Accoustic and weather proof enclosure with arrangement for fresh air intake for cooling of the engine & alternator, extraction, discharging hot air in to the atmosphere.There should be 2 nos 10 watt LED tubes provided inside the enclosure controlled by a 5 amp switch for adequate lighting during service.The power supply to this luminaire should be load side of the AMF panel. as per specifications.
25AMF PANEL
26Fabricating, Installing, Testing & Commissioning of automatic mains failure control including auto by-pass panel, suitable for 58.5 KVA silent type DG set complete with relays, timers, set of CTs for metering & protection and energy analyser to indicate currents, Signal cable appropriate size, phase and line voltages, frequency, power factor, KWH, KVARH & provision for overload, short circuit, restricted earth fault, under frequency, control cabling from AMF panel to diesel engine and elsewhere if required, all complete and inter locking including the following:
272 Nos.4 pole MCCB 100 AMP for D.G and main Contactor
282 nos. Mains and DG Contactor 100 amp
29Auto/Manual/Test/Off selector switch
302 Nos. over voltage relay, 2 Nos. reverse power relay and 2 Nos. under voltage relay.
313 Sets of current transformers 5 P 10 accuracy for protection and 15 VA class-I for metering
32Energy analyser unit to indicate current voltage frequency power factor and KWH
33Digital ammeter voltmeter
34Indicating lamps for load on mains and load on set
35Fuse for instruments
36Battery charger, complete with transformer/ rectifier, D.C. voltmeter and ammeter, selector switch for trickle, off and boost and current adjustment.
37Main supply failure monitor
38Supply failure timer
39Restoration timer
40Control unit with three impulse automatic engine start/stop and failure to start lockout.
41Impulse counter with locking and reset facility.
42ON/OFF/Control circuit switch with indicator
43Audio/Video annunciation for
44(i) High water temperature
45(ii) Low lubricating oil pressure
46(iii) Engine over speed
47(iv) Engine fails to start
48(v) Full load/maximum load warning
49vi Signal cable appropriate size
50Supplying and fixing exhaust gas piping of 3 inch dia. welded black MS, B Class pipe conforming to IS:3589 cut to required lengths and installed with necessary bends, supports and clamps, anti-vibration mountings, insulation of exhaust system with mineral wool/ Rockwool,50 mm thick wiremesh & aluminum cladding etc., as required as per specifications.
51Supplying and fixing true power make advanced earthing system having copper pipe 3 meter long 50 mm dia with terminal size 50x6 mm ,internal strip size 25x3 with 50 Kg compound including exvation of pit and refiling the same and making earthing pit cover 12 inch dia as required complete in all respect. make :- True power /Earth plus/Ashloka as per best satisfaction of Engineer-in -charge.
52Supplying and laying 20 mm X 3 mm copper strip on surface as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm)
53Supplying and Laying of 4 core 2.5 sq mm multistranded copper conuctor, FRLS PVC insulated and FRLS PVC Sheathed cable as required. Make:- Polycab/Finolex/ Plaza as approved by Engineer-In-Charge
54Supplying and fixing of following sizes of Heavy class FRLS PVC conduit with wall thickness minimum 2.00mm along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.Diplast/BEC/Polyfit. as approved by Engineer-In-Charge
5525 mm
5650 mm
57Providing, laying and fixing of one No. aluminium conductor, PVC insulated and PVC sheathed, armoured/XLPE power cable, working voltage 1100 volts grade on surface etc. of the required size:-Make:- Plaza/ Polycab/ Finolex/ Havell's as approved by Engineer-in-charge.
58Armoured cable 25 sq. mm (3.5 core)
59Providing & Laying of one number aluminium conductor, PVC insulated and PVC sheathed armoured/ XLPE power cable, 1.1 KV grade of following sizes direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering etc. of the rquired size. Make:- Plaza/ Polycab/ Finolex/ Havell's as approved by Engineer-in-charge.
60Armoured cable 25 sq. mm (3.5 core)
61Excavation in foundation, trenches etc. in earth work, lift upto 1.50 Metres stacking the excavated soil not more than 3 Metres clear from the edge of the excavation and then returning the stacked soild in 15cm layers, when required into plinths sides of foundations etc. consolidating each deposited layer by ramming and watering and then disposing of all surplus excavated earth as directed within in a lead of 20 metres, in pick jumper work.
62Providing and laying P.C.C. cement concrete 1:4:8 (1cement:4sand:8 graded stone aggregate 20mm nominal size) and curing complete excluding cost of form work in Foundation and plinth.
63Providing form work with steel plates 3.15 mm thick welded with angle iron in frame 30x30x5mm, so as to give a fair finish including centring, shuttering strutting and propping etc. with wooden batten and ballies, height of propping and centring below sipporting floor to ceiling not exceeding 4 mtr. and removal of the same for insitu-reinforced concrete & plain concrete wotk in: vertical surfaces such as walls (any thickness) partition and the like including attached plasters buttresses, plinth and string courses and the like.
64Providing and Laying Reinforcement binding TOR in position 3.7cum @ 190Kg/cum=703Kg.
65Providing and laying R.C.C. cement concrete 1:1.5:3 (1cement:1.5sand:3 graded stone aggregate 20mm nominal size) and curing complete excluding cost of form work in :Foundation and plinth.
66Providing and fixing M.S. round holding down or anchor bolts with nuts and washer plates complete.
67Provding and refilling of high speed diesel for 58.5 KVA DG SET complete in all respect.
68Annual maintenance contract of 58.5 KVA DG SET for five years consisting of monthly visit to check the general condition of generator. Check and set operation parameters as specified by company. Service of engine will be carried out strictiy as per company norms.Engine oil volume 20 ltr capacity, filter, coolant, air filter ,fan belt, etc complete one service in a year will be carried out strictly as per company norms.check and monitor the performs during each visit.To check & ensure optimum performance of sub assembles of machine, fuel timming, tappet clearance etc, for engines and reset the same as require. To check & set all the fasteners, operation of warning devices, operational parameters of breakdown of engines.if any breakdown occure in dg set ,the breakdown should be check & rectify within 24 hour by service engineer. Please Enable Macros to View BoQ information

Other Detail

Information Source https://hptenders.gov.in
Download FileName File Description File Size
Download undertaking.pdf Tender Documents 0 KB
Download BOQ_199274.xls Tender Documents 0 KB
Download SBD.pdf Tender Documents 0 KB
Download 240b1c08-419a-48ec-aa3f-b333a87456ba.html Tender Documents 0 KB
Download Tendernotice_1.pdf Tender Documents 0 KB
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.