Indian Tenders

Tender Notice

TDR 55095760
Tendering Authority Military Engineer Services
Tender No 8947/2026-27/E8
Tender ID 2026_MES_760401_1
Tender Brief Corrigendum : Tender For Repair/Replacement Of Area Lighting, Garden Light, Junction Box, Cable, Decorative Pole, Earthing Infrastructure, Apfc/Svrs/Ups/Eot/Hot & Connected Work At Zone B Under Ge (U) Bathinda Mil Stn
City Bathinda
State Punjab
Document Fees INR 500 /-
EMD INR 99000.0 /-
Tender Value INR 49.50 Lakhs /-
Tender Type Tender
Bidding Type Open Tender
Competition Type Indian

Tender Details

Tender for Repair/Replacement Of Area Lighting, Garden Light, Junction Box, Cable, Decorative Pole, Earthing Infrastructure, Apfc/Svrs/Ups/Eot/Hot & Connected Work At Zone B Under Ge (U) Bathinda Mil Stn

Corrigendum Details

Sr No CorrigendumDate Corrigendum CorrigendumType NewSubmissionDate
1 11-05-2026 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 18-05-2026
2 27-04-2026 CORR 2 Date 11-05-2026
3 22-04-2026 Corrigendum No. 1 BOQ 06-05-2026
4 22-04-2026 Corrigendum No. 1 BOQ 11-05-2026

Key Dates

Publish Date 11-05-2026
Last Date of Bid Submission 18-05-2026
Tender Opening Date 20-05-2026

Contact Information

Company Name Military Engineer Services
Contact Person Vipin Chandra Rai
Address GE UTILITY BATHINDA

BOQ Items

Name of Work:- Repair/Replacement of Area lighting, Garden light, Junction Box, Cable, decorative pole, Earthing infrastructure, APFC/SVRs/UPS/EOT/HOT & connected work at Zone B under GE (U) Bathinda Mil Stn
Sl. No. Item Description
1Material and labour servicing and cleaning of oil cooled servo voltage stabilizer including by transporting to workshop if neccessory, carefully lifting of core from the tank by opening cover, cleaning of tank, removing of sediments, cleaning of coils/ electrical connections, filtration of transformer oil ,fixing the core back in the tank, making electrical connections by replacing the consumble spares such as gaskets, rubber oil seals complete etc. Including electric connection and testing on load complete all as directed by Engr-in-charge capacity servo voltage stabilizer 10 to 20 KVA 3 phase.
2All as per serial item No.1.00 here-in-before capacity 50 KVA 3 phase.
3All as per serial item No.1.00 here-in-before capacity 100/120/150 KVA 3 phase.
4All as per serial item No.1.00 here-in-before capacity 200/250 / 300 KVA 3 phase.(i) Spare parts required to make serviceable of above oil cooled sevo voltage stabilizer shall be measured and paid separately under relevant item here-in-after.(ii) Rewinding of barrier assembly and transformer assembly will be measured and paid separately.)
5Supply & fix in replacement of voltmeter (digital) .
6Supply & fix Ammeter with CT (digital).
7Supply & fix in replacement of microprocessor based control card for each phase.
8Supply & fix PCB holder.
9Supply & fix in replacement of rotary switch 5 amps for RYB phases
10Supply & fix in replacement of servo motor 3 Kg torque.
11Supply & fix servo motor 10 Kg torque.
12Supply only in replacement of servo motor 20 Kg torque.
13Supply & fix in replacement of carbon brush (20 amps to 200 amps).
14Supply & fix carbon holder and spring.
15Supply & fix in replacement of servo motor gear pinion.
16Supply & fix in replacement of RC Net work for 3 Kg motor.
17Supply & fix in replacement of RC Net work for 10 Kg motor
18Supply & fix in replacement of RC Net work for 20 Kg motor.
19Supply & fix in replacement of drive assembly 20 KVA to 50 KVA per phase.
20Supply & fix in replacement of drive assembly 100 KVA per phase.
21Supply & fix in replacement of drive assembly 250 KVA per phase.
22Supply & fix in replacement of digital control panel with circuit board for high/ low voltage cut per phase suitable for 3 phase voltage stabilizer of capcity 20 KVA to 250 KVA.
23Supply & fix in replacement of front control with wiring kit
24Supply & fix in replacement of dimmer starter (barrier) for 50 KVA 3 phase servo-stabilizer with super enamel copper wounded .Complete all as specified and as directed
25Supply & fix dimmer in replacement of starter (barrier) for 100 KVA 3 phase servo-stabilizer with super enamel copper wonded Complete all as specified and as directed
26Supply & fix dimmer in replacement of starter (barrier) for 250/ 300 KVA. 3 phase servo-stabilizer with super enamel copper wounded Complete all as specified and as directed
27Supply & fix in replacement of transformer assembly for 50 KVA 3 phase stabilizer with super enamel copper wounded complete all as specified and as directed.
28Supply & fix in replacement of transformer assembly for 100 KVA 3 phase servo-stabilizer with super enamel copper wonded Complete all as specified and as directed.
29Supply & fix in replacement of transformer assembly for 250/300 KVA. 3 phase servo-stabilizer with super enamel copper wounded Complete all as specified and as directed.
30Supply only transformer oil of approved quality having dielectric strength not less than 60 KV, tested in 2.10 mm gap, ISI marked for filling in transformer for topping up all as directed .Make:Servo /HP/IOC/BP
31Supply only lead acid battery 12 volts DC 42 AH all as specified & directed.
32Supply only MCCB 63 Amps 16KA, 415 volts, 50 Hz, 4 phase with adjustable feature complete. Make :
33Material and labour servicing and cleaning of UPS and transporting to workshop if neccessory, checking , testing and locating faults including repairing to same by replacing new spares and cost of spare parts as\\" supply only shall be measured and paid separately at work site, working electrical connection all complete as directed by Engr-in-charge.any capacity of the UPS
34Supply only PCB suitable for 20 to 30 KVA UPS all as specified & directed by Engr-in- charge
35Supply only PCB suitable for 10 to 15 KVA UPS all as specified & directed by Engr-in- charge
36Supply only Transfarmer suitable for 10 to 30 KVA UPS all as specified & directed by Engr-in- charge
37Supply only IGBT suitable for 10 to 30 KVA UPS all as specified & directed by Engr-in- charge
38Supply only SER suitable for 10 to 30 KVA UPS all as specified & directed by Engr-in- charge
39Demolitiong of old earth pit and Material and Labour Earthing complete with galvanised iron earth plate electrode of size 600mm x 600mm x 6mm buried directly in ground (earth pit not less than 2.25 mtr deep below ground level ) with top edge of the plate not less than 1.5 metre below normal ground level, connected to and including GI strip 32mm X 6 mm by means of GI bolts/nuts/washers, protected by 40 mm bore GI light grade pipe. Earth plate shall be surrounded by alternate layer of charcoal or coke and common salt 15 cm thick all around bottom and top. 20 mm GI light grade pipe for watering and including funnel, wire mesh,RCC cover & frame, PCC (1:3:6) type C1 (using 20 mm graded crushed stone aggregate) as in earthing pit including necessary excavation & earth work, all as specified & shown in electrical plate No. 3 of SSR Part – I. Note:- (i) PCC chamber shall be constructed at least 1.5 metre away from the earth electrode and pipe for watering shall be provided in slanting manner.
40M & L for 25 x 6mm galvanised iron strip Please Enable Macros to View BoQ information

Other Detail

Information Source https://defproc.gov.in/nicgep/app
Download FileName File Description File Size
Download 8947TENDER.pdf Tender Documents 0 KB
Download BOQ_851736.xls Tender Documents 0 KB
Download cbb9e123-98fd-4748-9834-c5d96dd130d5.html Tender Documents 0 KB
Download Tendernotice_1 (2).pdf Tender Documents 0 KB
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.