Indian Tenders

Tender Notice

TDR 54902932
Tendering Authority Military Engineer Services
Tender No 81620/E8
Tender ID 2026_MES_758532_1
Tender Brief Corrigendum : Tender For Special Repair/Replacement Of Leftover Ber Distribution Transformer & Power Transformer And 33Kv Vcbs Alongwith Connected Items In Mrs Yard At Af Stn Bareilly.
City Bareilly
State Uttar Pradesh
Document Fees INR 1000 /-
EMD INR 187100.0 /-
Tender Value INR 1.12 Crore /-
Tender Type Tender
Bidding Type Open Tender
Competition Type Indian

Tender Details

Tender for Special Repair/Replacement Of Leftover Ber Distribution Transformer & Power Transformer And 33Kv Vcbs Alongwith Connected Items In Mrs Yard At Af Stn Bareilly.

Corrigendum Details

Sr No CorrigendumDate Corrigendum CorrigendumType NewSubmissionDate
1 08-05-2026 Corrigendum 08 Date 21-05-2026
2 04-05-2026 Corrigendum 07 Date 14-05-2026
3 04-05-2026 Corrigendum 07 Date 14-05-2026
4 24-04-2026 Corrigendum 06 Date 09-05-2026
5 24-04-2026 Corrigendum 06 Date 09-05-2026
6 23-04-2026 Corrigendum 05 Date 02-05-2026
7 23-04-2026 Corrigendum 04 Other 02-05-2026
8 23-04-2026 Corrigendum 03 BOQ 02-05-2026
9 23-04-2026 Corrigendum 05 Date 02-05-2026
10 23-04-2026 Corrigendum 04 Other 09-05-2026
11 23-04-2026 Corrigendum 03 BOQ 09-05-2026
12 23-04-2026 Corrigendum 05 Date 02-05-2026
13 23-04-2026 Corrigendum 04 Other 14-05-2026
14 23-04-2026 Corrigendum 03 BOQ 14-05-2026
15 17-04-2026 Corrigendum Date 30-04-2026
16 17-04-2026 Corrigendum Date 30-04-2026
17 17-04-2026 Corrigendum Date 30-04-2026
18 17-04-2026 Corrigendum Date 30-04-2026

Key Dates

Publish Date 08-05-2026
Last Date of Bid Submission 21-05-2026
Tender Opening Date 29-05-2026

Contact Information

Company Name Military Engineer Services
Contact Person CWE (AF) BAREILLY
Address HQ Commander Works Engineers (AF) Military Engineer Services Bareilly 243002

BOQ Items

Name of Work:- SPECIAL REPAIR/REPLACEMENT OF LEFTOVER BER DISTRIBUTION TRANSFORMER & POWER TRANSFORMER AND 33KV VCBs ALONGWITH CONNECTED ITEMS IN MRS YARD AT AF STN BAREILLY.
Sl. No. Item Description
1Supply, install, commissioning and testing of Transformer capacity 100 KVA, 11/0.433KV 3phase 50Hz ONAN cooled oil immersed copper wound outdoor type, , step down Transformer complete with first filling of IS 335 ISI marked filtered and dehydrated transformer oil and other standard fittings/accessories and 7 position with OFF LOAD tap changer tapping range up to + 5% to -10% in step of 2.5 % BEE compliance level III. The Transformer shall be of DYN -11 vector group and conforming to Latest IS-1180 complete all as specified and directed. The transformer shall have following accessories :-
2(a) Oil Conservator with filling hole and drain cock.(b) Oil Level Gauge. ( C ) Oil seal type transparent breather with silica gel.(d) Two numbers earthing terminals with lugs. (e) Oil drain Valve/filter valve(f) Radiators with valves. (g) Lifting lugs with fastening holes.(h) Thermometer dial type 0-120 degree C.(j) rating & Specification plate.(k) 4 Nos plain cast steel bi-directional detachable rollers.(l) Explosion vent with diaphragm & sight glass. (m) transformers must have its neutral brought out for earthing on LV side. (n) Transformers must be earthed by two independent earthings with GI Strips for body and another two independent earths for neutral. Neutral earthing of transformers should be done by using GI earth plate and GI earth strip.(o ) Transformer Shall be installed as described in IS-10028 (Part-II and in conforming with IE rule.
3Supply, install, commissioning and testing of Transformer capacity 250 KVA, 11/0.433KV 3phase 50Hz ONAN cooled oil immersed copper wound outdoor type, , step down Transformer complete with first filling of IS 335 ISI marked filtered and dehydrated transformer oil and other standard fittings/accessories and 7 position with OFF LOAD tap changer tapping range up to + 5% to -10% in step of 2.5 % BEE compliance level III. The Transformer shall be of DYN -11 vector group and conforming to Latest IS-1180 complete all as specified and directed. The transformer shall have following accessories :-
4(a) Oil Conservator with filling hole and drain cock.(b) Oil Level Gauge. ( C ) Oil seal type transparent breather with silica gel.(d) Two numbers earthing terminals with lugs. (e) Oil drain Valve/filter valve(f) Radiators with valves. (g) Lifting lugs with fastening holes.(h) Thermometer dial type 0-120 degree C.(j) rating & Specification plate.(k) 4 Nos plain cast steel bi-directional detachable rollers.(l) Explosion vent with diaphragm & sight glass. (m) transformers must have its neutral brought out for earthing on LV side. (n) Transformers must be earthed by two independent earthings with GI Strips for body and another two independent earths for neutral. Neutral earthing of transformers should be done by using GI earth plate and GI earth strip.(o ) Transformer Shall be installed as described in IS-10028 (Part-II and in conforming with IE rule.
5Supply, install, commissioning and testing of Transformer capacity 200 KVA, 11/0.433KV 3phase 50Hz ONAN cooled oil immersed copper wound indoor type, , step down Transformer complete with first filling of IS 335 ISI marked filtered and dehydrated transformer oil and other standard fittings/accessories and 7 position with OFF LOAD tap changer tapping range up to + 5% to -10% in step of 2.5 % BEE compliance level III. The Transformer shall be of DYN -11 vector group and conforming to Latest IS-1180 complete all as specified and directed. The transformer shall have following accessories :-
6(a) Oil Conservator with filling hole and drain cock.(b) Oil Level Gauge. ( C ) Oil seal type transparent breather with silica gel.(d) Two numbers earthing terminals with lugs. (e) Oil drain Valve/filter valve(f) Radiators with valves. (g) Lifting lugs with fastening holes.(h) Thermometer dial type 0-120 degree C.(j) rating & Specification plate.(k) 4 Nos plain cast steel bi-directional detachable rollers.(l) Explosion vent with diaphragm & sight glass. (m) transformers must have its neutral brought out for earthing on LV side. (n) Transformers must be earthed by two independent earthings with GI Strips for body and another two independent earths for neutral. Neutral earthing of transformers should be done by using GI earth plate and GI earth strip.(o ) Transformer Shall be installed as described in IS-10028 (Part-II and in conforming with IE rule.NOTE for Srl item No 1 to 3 :- (i) Design, drawings, Technical specifications shall be approved by the Garrison Engineer.(ii) Transformer shall be tested by rep of Accepting Officer before despatch from factory premises.
7M & L for earthing comprising of copper earth plate electrode 600 mm X 600 mm X 3.15 mm thick buried directly in ground (earth pit not less than 2.25 m below ground level) with top edge of earth plate not less than 1.50 m below normal ground level, connected to copper earth strip of size 20 X 3 mm by means of nut-bolts, check nuts and washers of galvanised iron or steel all as shown on electrical plate No. 3 of MES schedule 2020, Part–I (Specifications) including excavation, and earth work in any type of soil disposal of soil providing alternate layers of charcoal and common salt construction of PCC earth chamber in mix 1:3:6 type C-1 with 40 mm thick 1:2:4 type B-1 cover reinforced with 8 mm dia MS bars both ways with lift hook made out of 8 mm dia bar,watering arrangement. Note : Main earth lead beyond 7.5 meter shall be measured and paid separately.
8Material and Labour for earth continuity conductor or copper strip of size 20x3 mm burried in ground, fixed to wall, any other indicated situation for loop earthing and the like upto test point on necessary insulators and fastning screws, rawl plugs complete all as specified and directed.NOTE: - The joints of each lead strip shall be welded / brazed and the cost of brazing / welding shall deemed to be included in unit rate of this item.
9M&L for cable jointing kit for 11 KV (E) grade cable for outdoor end termination cold shrink type complete with jointing material and accessories suitable for XLPE armoured aluminium conductor cable of size 95 sqmm 3 core complete all as specified and directed.
10M&L for cable jointing kit for 11 KV (E) grade cable for indoor end termination cold shrink type complete with jointing material and accessories suitable for XLPE armoured aluminium conductor cable of size 95 sqmm 3 core complete all as specified and directed.
11M&L for earthing complete with galvanised steel earth plate electrode 60cm x 60cm x 6mm thick burried directly in ground (earth pit not less than 2.5 mtr below normal ground level ) with top edge of earth plate not less than 1.5 mtr below normal ground level connected to main earth lead GI strip 32x 6mm as earth lead by means of bolts, nuts, checknuts and washers of galvanised iron or steel as shown in electrical plate No. 3, including excavation, and earth work in any type of soil disposal of soil providing alternate layers of charcoal and common salt construction of PCC earth chamber in mix 1:3:6 type C-1 with 40 mm thick 1:2:4 type B-1 cover reinforced with 8 mm dia MS bars both ways with lift hook made out of 8 mm dia bar, watering arrangement. Note : Main earth lead beyond 7.5 meter shall be measured and paid separately. Please Enable Macros to View BoQ information
12M&L for earthing complete with galvanised steel earth plate electrode 60cm x 60cm x 6mm thick burried directly in ground (earth pit not less than 2.5 mtr below normal ground level ) with top edge of earth plate not less than 1.5 mtr below normal ground level connected to main earth lead GI strip 32x 6mm as earth lead by means of bolts, nuts, checknuts and washers of galvanised iron or steel as shown in electrical plate No. 3, including excavation, and earth work in any type of soil disposal of soil providing alternate layers of charcoal and common salt construction of PCC earth chamber in mix 1:3:6 type C-1 with 40 mm thick 1:2:4 type B-1 cover reinforced with 8 mm dia MS bars both ways with lift hook made out of 8 mm dia bar, watering arrangement. Note : Main earth lead beyond 7.5 meter shall be measured and paid separately. Please Enable Macros to View BoQ information

Other Detail

Information Source https://defproc.gov.in/nicgep/app
Download FileName File Description File Size
Download 39ee5e1a-be4b-4622-ba91-e7258ffc9da2.html Tender Documents 0 KB
Download 81620TENDERFINALamd5pm.pdf Tender Documents 0 KB
Download BOQ_849601.xls Tender Documents 0 KB
Download Tendernotice_1 (2).pdf Tender Documents 0 KB
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.