Indian Tenders

Tender Notice

TDR 54803983
Tendering Authority Military Engineer Services
Tender No CWE-ND/70/2025-26
Tender ID 2026_MES_757322_1
Tender Brief Tender For special Repair/ Replacement Of Mechanical Fire D Er Of Main Hospital Bldg P-100 And Adc P-105 At Ahrr Under Ge E/M repair renovation Hosp, Delhi Cantt-10
City Delhi
State Delhi
Document Fees INR 500 /-
EMD INR 98000.0 /-
Tender Value INR 49 Lakhs /-
Tender Type Tender
Bidding Type Open Tender
Competition Type Indian

Tender Details

Tender for special Repair/ Replacement Of Mechanical Fire D Er Of Main Hospital Bldg P-100 And Adc P-105 At Ahrr Under Ge E/M repair renovation Hosp, Delhi Cantt-10

Key Dates

Publish Date 23-03-2026
Last Date of Bid Submission 11-04-2026
Tender Opening Date 13-04-2026

Contact Information

Company Name Military Engineer Services
Contact Person CWE NEW DELHI
Address HQ CWE NEW DELHI, RAO TULA RAM MARG, DELHI CANTT-10

BOQ Items

Name of Work:- SPL REPAIR/ REPLACEMENT OF MECHANICAL FIRE D ER OF MAIN HOSPITAL BLDG P-100 AND ADC P-105 AT AHRR UNDER GE E/M RR HOSP, DELHI CANTT-10
Sl. No. Item Description
1Supply, Installation, Testing & Commissioning of motorised combined fire damper complete with control panel, inter connecting wiring including taking down manual fire damper complete all as specified and directed.
2(a) Fire dampers 18 SWG with local smoke and temperature sensor
3(b) Actuators of Belimo make, model No. NFA-S2, or approved equivalent from Siemens/Honeywell, spring-return, fail-safe, having nominal supply voltage of 24–240 V AC/24–125 V DC, minimum rated torque of 10 N·m, provided with a minimum of two (2) SPDT auxiliary switches, and a maximum angle of rotation not exceeding 95 degrees, complete in all respects and installed as per specifications and directions of the Engineer-in-Charge.
4(c) Control panel suitable for fire damper actuators, with outgoing connections for damper actuator control and AHU interlocking. The panel shall accept input signals from the Fire Alarm Control Panel (FACP), local temperature sensor, and smoke detector. On receipt of any fire signal, the panel shall command the fire dampers to close. The AHU shall be interlocked to shut down when the dampers are closed and shall be permitted to operate only when the dampers are in the open position
5Supply, installing, balancing, testing and commissioning of Galvanized steel sheet, including taking down of old ducting, rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter damper vanes, hangars, supports as per SMACNA specifications of following sheet thickness, complete all specified and directed as under:-
6(a) 22 gauge galvanised steel sheet
7(b) 20 gauge galvanised steel sheet
8M&L for modification/alteration of existing AHU panel wiring to provide power supply and control to fire damper control panel, including provision of step-down transformer (240V/24V) of suitable capacity (if required), relays, timers, contactors, and necessary interlocking of AHU motor with fire damper operation, complete in all respects as specified and as directed.
9S&F PVC insulated cable 1.5 sqmm 2 core copper cable fixed on wall with cable clip complete all as specified and as directed. Please Enable Macros to View BoQ information
10S&F PVC insulated cable 1.5 sqmm 2 core copper cable fixed on wall with cable clip complete all as specified and as directed. Please Enable Macros to View BoQ information

Other Detail

Information Source https://defproc.gov.in/nicgep/app
Download FileName File Description File Size
Download 8f3c4a27-9fff-47c7-811c-85e83f0890b4.html Tender Documents 0 KB
Download BOQ_848305.xls Tender Documents 0 KB