Indian Tenders

Tender Notice

TDR 54803638
Tendering Authority Municipal Corporation Of Delhi
Tender No EE(E)-I/Sh.N/MCD/25-26/TC-61/2
Tender ID 2026_MCD_272733_1
Tender Brief Tender For Improvement Of Ei, Wiring, Conduting,In Mcp School Chauhan Bangar (Hindi,Urdu) In Ward No-227 Under Shahdara North Zone.
City Delhi
State Delhi
Document Fees INR 590 /-
EMD INR 26800.0 /-
Tender Value INR 12.72 Lakhs /-
Tender Type Tender
Bidding Type Open Tender
Competition Type Indian

Tender Details

Tender for Improvement Of Ei, Wiring, Conduting,In Mcp School Chauhan Bangar (Hindi,Urdu) In Ward No-227 Under Shahdara North Zone.

Key Dates

Publish Date 23-03-2026
Last Date of Bid Submission 30-03-2026
Tender Opening Date 30-03-2026

Contact Information

Company Name Municipal Corporation Of Delhi
Contact Person Executive Engineer (Elect)-I
Address OFFICE OF THE Ex. ENGINEER (ELECT)-I, SHAHDARA (N) ZONE, KeshavChowk, Delhi-110053

BOQ Items

Name of Work:- Improvement of EI, wiring, conduting,in mcp school Chauhan Bangar (Hindi,Urdu) in ward no-227 under Shahdara North Zone.
Sl. No. Item Description
1Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm
2Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 4 sq. mm
3Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 6 sq. mm
4Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 X 2.5 sq. mm
5Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connection etc. as required. (For light plugs to be used in non residential buildings).
6Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required.
7Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required (a)4 Module (125mmX75mm)
8(b ) 6 Module (200mmX75mm)
9(c) 8 Module (125mmX125mm)
10(d)12 Module (200mmX150mm)
11Supply & Fixing following modular switch/socket on the existing modular plate & switch box i/c connections but excluding modular plate etc.as reqd. (a)5/6 Amp.Switch
12(b)15/16 Amp.Switch
13(c)3 pin 5/6 Amp.Socket Outlet
14(d)6 pin 15/16 Amp.Socket Outlet
15Supply & Fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as reqd.
16Supplying and fixing PVC batten/ angle holder including connections etc. as required.
17Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator. 8 way, Double door
18Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator.12 way, Double door
19Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
20Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
21Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63 amps
22Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal( Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, suitable for operation with regulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply, Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required.1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) .
23Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required
24Providing and fixing 6 SWG dia G.I wire on surface or in recess for loop earthing as required.
25Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required.Upto 35 sq. mm
26Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. Upto 35 sq. mm (clamped with 1mm thick saddle)
27Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit along with 1 No 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required.
28Installation of exhaust fan in the existing opening, including making good the damage connection testing, commissioning etc. as required.Upto 450 mm sweep
29Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit,with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required. Group C
30Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required.Group C
31Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required. 32 mm
32Supply of XLPE insulated PVC sheathed Al. Conductor Armoured Cable 1.1KV grade conforming to IS-7098 of following size:-2C*4 sqmm
33Supply of XLPE insulated PVC sheathed Al. Conductor Armoured Cable 1.1KV grade conforming to IS-7098 of following size:-2C*25 sqmm
34Supply of 250 mm (10 inch) sweep 1250 rpm exhaust fan Fresh Air Type complete with shutter blades etc. as required.
35P/F Hot press sheet moulded compound (SMC) fire retardant (Temp. resistance up to 200 C), IP 55 weather proof pole box of inner dimension 200x160x98mm (NS) complete with suitable arrangement for fixing of 2 nos of 6 to 32 amp single pole MCB & 63 Amp. Double pole isolator (MCB/Isolator excluded) with neutral link duly shorting on DIN Channel with2 Nos of MS clamps with SS back plate of suitable size with danger monogram property printed on the cover etc as reqd. as reqd.
36LED Flood Light, powder coated pressure die cast aluminium (System lumen efficacy ≥105 <120 lm/Watt). Supplying, Installation, Testing & Commissioning of Flood Light, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection,EMI-EMC as per CISPR -15, lenses for beamangle 30 deg-120deg as per the application and theproject requirement., suitable tilt able fitting, life time(LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumenmaintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K /4000°K / 5700°K /6500°K (As per ANSI Bin) ,SDCM(Standard Deviation Color Matching) <5,Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/cexternal connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductorsingle core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output .LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). .100 watt
37LED Batten light (System lumen efficacy >135 lm/Watt) Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85% ,Operating voltage AC 140 270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P.F.≥0.95, IP20, CRI >80, Flicker free (flicker shouldbe below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm) .18-22 Watt
38Repair/Rewinding of existing 1HP mono block pump set including replacement of parts like gun metal bush/ bearing condenser, impeller etc to make the pump functional as required.
39Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.200Amp, 16 KA, TPMCCB
40Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.100Amp, 16 KA, TPMCCB
41Providing and fixing 405 kg CO2 type fire extinguisher squeeze grip type, trolly wheel as well mounted type complete in all respect with ISI mark i/c fixing arrangement etc as required.
42Providing and fixing ABC (Aluminium Phosphate) power type fire extinguisher of 6kgs capacity complete in all respect with isi mark i/c fixing arrangement etc asrequired.
43Rewinding of AC ceiling fan of all sizes and make including oiling, greasing as required New Model (Light Weight).
44Replacement of ball bearing of size 117/120 NBC equivalent SKF make as required.
45Replacement of fan condenser 2.5 mF as required.
46SITC of metal clad, powder coated, compartmentalized cubical panel board as per CPWD electrical specifications including insulated aluminum bus bars, supports, interconnection, erection of switchgears with depth 30 cm to 60 cm and making provisions for termination of incoming/ outgoing cables/ bus ducting and making foundation etc as required. (Suitable for 400 Amp TP & N) Please Enable Macros to View BoQ information

Other Detail

Information Source https://etenders.gov.in/eprocure/app
Download FileName File Description File Size
Download 0dff34cd-f9de-4bcf-8bb8-9f92a71e9191.html Tender Documents 0 KB
Download BOQ_318253.xls Tender Documents 0 KB
Download Circular_1.pdf Tender Documents 0 KB
Download ConditionChauhanBangar.pdf Tender Documents 0 KB
Download GCC2024.pdf Tender Documents 0 KB
Download Tendernotice_1 (2).pdf Tender Documents 0 KB