Indian Tenders

Tender Notice

TDR 54645565
Tendering Authority Public Works Department
Tender No PWD/BLDG/TR/10520/2024_6_1_1/1
Tender ID 2026_PWD_837451_2
Tender Brief Tender For General-Animal Husbandry Department- Regional Disease Diagnostic Lab Kannur.-Sitc Of Generator And Airconditioners At First Floor-General Electrical Work
City Kannur
State Kerala
Document Fees INR 2015 /-
EMD INR 22839.0 /-
Tender Value INR 9.13 Lakhs /-
Tender Type Tender
Bidding Type Open Tender
Competition Type Indian

Tender Details

Tender for General-Animal Husbandry Department- Regional Disease Diagnostic Lab Kannur.-Sitc Of Generator And Airconditioners At First Floor-General Electrical Work

Key Dates

Publish Date 13-03-2026
Last Date of Bid Submission 18-03-2026
Tender Opening Date 21-03-2026

Contact Information

Company Name Public Works Department
Contact Person Assisstant Executive Engineer
Address Office of the Assisstant Executive Engineer PWD Electrical Subdivision Thalassery

BOQ Items

Name of Work:- GENERAL-Animal Husbandry Department- Regional Disease Diagnostic Lab Kannur.-SITC of Generator and Airconditioners at First Floor-General Electrical Work
Sl. No. Item Description
1SITC of Air conditioner at RDDL First Floor
2OD198300/2024-2025:SITC of Inverter type wall mounting split Air conditioner unit of the following ratings conforming to relevant IS suitable for operating on 230V, 50Hz single phase AC supply ,filled with R-410 A/R32 refrigerant gas, full copper condenser ,high energy efficient, RoHS complaint, capable of performing functions like cooling, dehumidifying ,air circulating ,filtering etc of following capacity including refrigerant copper piping 3m with insulation, control cable up to 5m,3m drain pipe, Condenser stant, microprocessor control with cordless remote control ,base frame etc. with comprehensive maintenance contract upto the end of 36 months from date commissioning including periodical services, gas topping etc. complete . 1.5 Tr single phase 3 Star rated inverter type Split Ac unit .Make Thosiba/Daikin/Carrier/Lloyd
3OD62243/2024-2025:Supply and Fixing of 4 KVA voltage stabilizer for split type A/C unit with voltage range of 175-275V and out put range of 210 - 240V (V-Guard or its equivalent)
490.10.3.32:Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )25A 3 pin plug top with indicator
5SITC of Generator and additional electrification to Rabies Lab
6OD232956/2024-2025:Supply, conveyance, Installation, testing & commissioning of 10 KVA DieselGenerator set with integral acoustic enclosure as per CPCB IV+norms with standaredacessories as per technical details given below. 1. Engine : a) Make of Engine -Leyland/cummins/caterpillar/volvo/kirloskar b) Type of Engine - Diesel Engine c)No. of Cylinders - As per manufactures standards. d) Method of Cooling - Watercooled with radiator. e) .natural aspiration f) Design - Suitablefor generating set operation 2.Standard accessories with Diesel Engine a) Fly wheel tosuit flexible coupling b) Close Coupling c) Air cleaner d) Radiator with fan providedwith fan guard. e) Fuel Pump f)) g) Fuel filter h) Lubricating oil filter i) in builtExhaust silencer j) EGR system k) Battery Charger/Generator 3. Engine InstrumentPanel with the following items a) Starting switch with key or button 1 b) Lubricatingoil pressure gauge. c) Water temperature gauge. d) RPM Indicator with hour meter e)Battery charging Ammeter 4. Safety Controls for Engine a) Trip for low lubricatingoil pressure b) Trip for high water temperature. 6. Brushless Alternator a) Make -Kirloskar/Crompton/Greaves/Stanford b) Type - Self exited and self regulated. c)Capacity - 10KVA/7.5 KW @ 0.8PF d) System of Voltage - 3 phase, 415 V, e)Frequency - 50 Hz f) Insulation - Class F/H The Alternator should confirm to IS4722. Operation and service manual, spares and tools shall be provided. 7. Fuel TankSuitable size built in type integrated with the acoustic enclosure Fuel connection shallbe done as per standards 8. Battery Suitable size built in type integrated battery withleads and terminals of appropriate AH capacity as per Manufactures requirement.Automatic Battery charger Solid state phase indication lamp for supply ON/OFF withHRC protection. standard control panel with 12V Batteries.standard control panel asper kerala Electrical Inspectorate requirements, with suitable size MCCB andaccessories such as Multi function meter and Energy meter etc. Complete
714.1:Excavation for foundation in soft soil including dressing of sides and ramming of bottoms, lift upto 1.5 m including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 metres.
814.7:Providing and laying in position cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc including form work etc as required.
914.11:Providing brick work (in width 225 mm or more) with F.P.S. bricks of class designation 7.5 in cement mortar 1:4 (1 cement : 4 coarse sand) at all levels.
1014.12:Providing 15mm thick cement plaster of mix 1:4(1 cement: 4 fine sand) at all levels
11OD204647/2024-2025:Supply and installation of switch gear units in sheet steel enclosure complete with handle assembly, door interlock and pad locking arrangement of the following ratings on existing angle iron frame work or directly to wall using necessary bolts & nuts, fixing the unit to wall, making good the damages, colour washing etc. including giving necessary connections as required. -32A A, 415 V, 50 Hz, AC 23 A duty, 4 pole on-load change over switch with indicators with MCB for KSEB and DG supply.
12OD109610/2024-2025:Supply and providing the following size of B class MS pipe conforming to relevant IS specifications complete with heavy guage specials such as bends, flanges etc welded and fixed at appropriate locations, providing cork sheet in between the flanges at the joints, bolting the flanges together, painting the pipe, flange etc with 2 coats of heat resistant paint suitable for outdoor applications, fixing the pipe firmly with fabricated structure/wall/any other mechanical support etc as required.- 50 mm dia B class MS pipe as extended exhaust pipe.
1390.12.7.40:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 10 sq mm with factory made clamp
1490.12.5.40:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.4 core 10 sq mm
159.1.32:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 10 sq. mm (25mm)
1690.16.2.3:Supply and laying of the following sizes of B class GI pipe laid 0.6 m below ground level including excavating trench of suitable size and refilling etc, as required.32 mm dia G.I pipe ( medium class)
1790.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG)
1890.16.5.3:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG)
195.4:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
20OD204820/2024-2025:Supply and providing test joint for the earthing system using 2 Nos of the following sizes of strips including cutting and bending to shape, drilling necessary holes and fixed to the watering pipe etc as required. 2 x 25 x 3 mm GI strip
21OD204821/2024-2025:Supply and providing earth lead from the test joint to the earth electrode using the following sizes of conductors/ strips including cutting, drilling necessary holes (in case of strip) and fixing firmly with plate test joint etc as required.25 mm X 3 mm G.I. strip
22OD114742/2024-2025:Supplying and laying 25 mm X 3 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm)
23OD114765/2024-2025:Providing and fixing earth bus of 25mm X 3 mm copper strip on surface for connections etc. as required.
24OD114775/2024-2025:Supply of HSD for testing of the DG set including loading at the fuel pump,conveyance,unloading at site,filling in the tank etc
25OD114778/2024-2025:Charges towards the preparation of necessary plan, scheme and other related papers for submission to KSELB & KSEB - Each Additional A3 Sheet
26OD114793/2024-2025:Charges towards the preparation of necessary plan, scheme and other related papers for submission to KSELB & KSEB (for preparing scheme & records for scrutiny & completion) Additional Sheet
27OD114844/2024-2025:Supply and fixing danger notice board of size,125x75mm.
28OD114848/2024-2025:supply and providing 9 litter capacity GI fire bucket painted in post office red with primer coat of red oxide and written with white paint FIRE mounted on MS angle frame work/ wall bracket filled with fine sand, painting the bracket/ floor sand including making good the damages, colour washing etc as required.
29OD114860/2024-2025:Supply and providing First Aid Chart duly framed and placed in a conspicuous location for clear vision.
30OD204987/2024-2025:Supply and providing 5Kg Dry Chemical Powder Type fire Extinguisher with hose and clamps including fixing it to wall as required.
311.17.12:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm
321.17.15:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 2.5 sq. mm
331.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
341.21.2:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm
352.10.1:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniaturecircuit breaker suitable for inductive load of following poles in the existing MCBDB complete with connections, testing and commissioning etc. as required.Single pole
361.27.2:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm)
371.24.3:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch
381.24.5:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet Please Enable Macros to View BoQ information

Other Detail

Information Source https://etenders.kerala.gov.in
Download FileName File Description File Size
Download BOQ_1431707.xls Tender Documents 0 KB
Download fa046b2a-372c-4082-8f31-29c71c9e4955.html Tender Documents 0 KB
Download MOM.pdf Tender Documents 0 KB
Download specificconditionNEW.pdf Tender Documents 0 KB
Download Tendernotice_1 (1).pdf Tender Documents 0 KB
Download viewnit.pdf Tender Documents 0 KB
Download viewsbd.pdf Tender Documents 0 KB