Indian Tenders

Tender Notice

TDR 54601568
Tendering Authority Delhi Development Authority
Tender No 65 /EE/ELD-2/DDA/ 2025-26 ( Re Call )
Tender ID 2026_DDA_902047_1
Tender Brief Corrigendum : Tender For Maintenance Of Various Sports Complex.Sub Head : Miscellaneous Electrical Works At Various Sports Complex,Under Dda. (Rsc, Rskp,Mdcsc,Pdkp,Dgvsc)
City Delhi
State Delhi
Document Fees Refer document
EMD INR 52995.0 /-
Tender Value INR 26.49 Lakhs /-
Tender Type Works
Bidding Type Open Tender
Competition Type Indian

Tender Details

Tender For Maintenance Of Various Sports Complex.Sub Head : Miscellaneous Electrical Works At Various Sports Complex,Under Dda. (Rsc, Rskp,Mdcsc,Pdkp,Dgvsc)

Corrigendum Details

Sr No CorrigendumDate Corrigendum CorrigendumType NewSubmissionDate
1 13-03-2026 Modification in NIT Other 18-03-2026

Key Dates

Publish Date 13-03-2026
Last Date of Bid Submission 18-03-2026

Contact Information

Company Name Delhi Development Authority
Contact Person Executive Engineer
Address Electrical Division -02, Vikas Minar

BOQ Items

Name of Work:- M/o Various sports complex.Sub Head : Miscellaneous electrical works at various Sports Complex,under DDA. (RSC, RSKP,MDCSC,PDKP,DGVSC)
Sl. No. Item Description
1Supplying, Installation, Testing & Commissioning of Flood Light, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMI-EMC as per CISPR -15, lenses for beam angle 30 deg-120deg as per the application and the project requirement., suitable tilt able fitting, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin) , SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output .LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-inCharge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). (a) 200 watt
2150 Watt
3200 Watt
4Supplying, installation, Testing & Commissioning of LED Recessed / surface Down lighter (Round/ square/ Rectangular) SMD type of following body material with PMMA and prismatic diffuser and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80 , UGR (Unified Glare Rating) < 19, Flicker free (flicker should be below 5%), life time (LED,Driver & electrical circuitary), ofminimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends , CCT 3000°K / 4000°K/ 5700°K / 6500°K (As per ANSI Bin), SDCM (Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be confirming to relevant BIS standards and trade mark certificate (T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing Complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 and <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement.(Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C) Powder coated die cast /Extruded aluminium Body including trim
518 watt
6Supply and fixing of heavy duty exhaust fan of following size , single phase, fixing the same on wall with suitable nut bolt fixture and connection testing etc. as required.
7300 mm
8380 mm
9Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal( Aluminum alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al bodyPower Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%,remote (prefreably mobile app based) for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Ceiling Fan compliant to IS 374:2019 fan Supply, earthing etc. complete as req.
101200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum)
11Supplying, installation, Testing & Commissioning of Panel light 2x2 ft., of following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range -5 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free, (flicker should be below 5 %), life time (LED,Driver & electrical circuitary), of minimum 50000 Burning Hours with, 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K/ 5700°K /6500°K (As per ANSI Bin),SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder Coated CRCA Sheet Body (Thickness > 0.50 mm)
1236 watt
13Supplying, installation, Testing & Commissioning of 72 watt Street light LED fixture powder coatedpressure die cast aluminium body with driver as per the requirement with Driver efficiency >85%, Input voltage:140-270 Volt AC, freq 50/60 hz, Operating temp range -5 deg to 50 deg centigrade, internal surge protection of 5KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2 , P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMI-EMC As per CISPR 15 , lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED,Driver &electrical circuitary) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K/6500°K(As per ANSI Bin), SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C).
1472 watt
15Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85% ,Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range -5 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, Flicker free,(flicker should be below 5 %), life time (LED,Driver & electrical circuitary), of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate (T.C.). Manufactures Word Mark/Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output .LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement.(Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C).Powder coated die cast /Extruded aluminium Body(Thickness > 1.20 mm)
1618- 22 Watt
17Supplying, Installation, Testing and Commissioning of 45 watt LED Post top Luminaire with Die- cast aluminium graphite grey powder coated spigot and spun aluminium body with clear/opal diffuser IP-65 protection, driver with all accessories i/c connection, testing etc. complete as required.
18Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.
195/6 amps switch
2015/16 A switch
213 pin 5/6 A socket outlet
226 pin 15/16 A socket outlet
23Supplying & Installation of CO2 type Fire Extinguisher ISI marked conforming to IS: 15683. Capacity 4.5 Kg. Complete with delivery hose horn, wheel type release valve, locking arrangement, operation manual and bracket. Operating Temperature: - 30ºC to +60ºC etc complete as required
24Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable inthe existing surface/ recessed steel/ PVC conduit as required a)3 x 2.5 sq. mm
25Supplying & Installation of Hydra Guard pro best for softening the hard water of 1500-2000 ltr water tank conditioner.
26Supplying of following sizes of XLPE insulated, PVC sheathed Al. cond. Armoured power cable of 1.1 kV grade including connection, testing etc. as required.
274C x 70 sq mm
28Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket,bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct inground (75 cm below ground level) including excavation and refilling the trench but excluding sandcushioning and protective covering etc., complete as required.(a)63 mm dia (OD-63 mm & ID-51 mm nominal)
29Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade offollowing size in the existing RCC/ HUME/ METAL pipe as required. Above 120 sq. mm and upto 400 sq. mm Please Enable Macros to View BoQ information

Other Detail

Information Source https://eprocure.gov.in/eprocure/app
Download FileName File Description File Size
Download 48543672-2957-4751-a88a-df31864cfc54.html Tender Documents 0 KB
Download BOQ_948140.xls Tender Documents 0 KB
Download NIT65.pdf Tender Documents 0 KB
Download Tendernotice_1.pdf Tender Documents 0 KB
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.