Indian Tenders

Tender Notice

TDR 54371959
Tendering Authority Public Works Department
Tender No 1739 NIT 30/2025-26 EE PWD ELECT DIV ALWAR
Tender ID 2026_CEPWD_543516_3
Tender Brief Tender For Electric Renovation Work In A-Ward At Shishu Hospital Alwar
City Alwar
State Rajasthan
Document Fees INR 500 /-
EMD INR 17680.0 /-
Tender Value INR 8.84 Lakhs /-
Tender Type Tender
Bidding Type Open Tender
Competition Type Indian

Tender Details

Tender for Electric Renovation Work In A-Ward At Shishu Hospital Alwar

Key Dates

Publish Date 03-03-2026
Last Date of Bid Submission 11-03-2026
Tender Opening Date 12-03-2026

Contact Information

Company Name Public Works Department
Contact Person EXECUTIVE ENGINEER
Address XEN PWD ELECT DIV ALWAR

BOQ Items

Name of Work:- Electric renovation work in A-ward at Shishu hospital Alwar
Sl. No. Item Description
1Wiring of light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper earth conductor 1.1 kV grade (IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) PVC conduit & it's ISI marked (IS:3419-1988) accessories, Aluminum round tiles, 1.2 mm thick Hot Dipped Galvanized Modular Box with earth terminal, 6 A Modular switch, Modular face plate with grid plate, 3 pin ceiling rose / Holder /3 way connector, screws, making connections, testing etc. as required.
2Short point (up to 3 mtr.)
3Medium point (up to 6 mtr.)
4Long point (up to 10 mtr.)
5Wiring of 3/5 pin 6 amp. Light plug point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper earth conductor 1.1 kV grade(IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) PVC conduit & it's ISI marked (IS:3419-1988)accessories, Hot Dipped Galvanized Modular box of 1.2 mm thick with earth terminal, 6 A modular switch, 3/5 pin 6 A modular socket, Modular face plate with grid plate, screws, making connections, testing etc. as required.
6On board
7S&F following sizes (dia.) of ISI marked MMS ( IS:9537 P - III ) PVC conduit along with ISI marked (IS:3419-1988) accessories as required in recess including making jhiri in the wall,clamps at suitable spacing, covering conduit and making good the same as required.
820 mm
925 mm
1032 mm
11Supplying and laying FR PVC insulated & unsheathed flexible copper conductor of following nominal sizes with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from copper, stranding in acc. to IS:8130/IEC 60228 for lower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5, in existing surface or recessed PVC/ MS conduit/casing capping making connections with Copper Lugs of suitable size, Ferrules,testing etc. as required.
123x 1.5 sq.mm
131 x 1.5 sq.mm
142 x 2.5 sq. mm. + 1x1.5sqmm
152 x 4.0 sq. mm. + 1 x 2.5 sq. mm.
16Supplying and drawing PE Insulated & PVC Sheathed unarmoured telephone cable with 0.5 mm dia. Solid Annealed electrolytic grade bare Copper Conductor as per IS: 8130/84 &confirming to TEC specification GR / WIR/06-03 March 2002 in existing surface or recessed conduit/casing capping. including ferruling on each pair for Identification etc. as required. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR
172 pair
18Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load and site requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanism , energy limiting of class 3 as per IEC, minimum phase termination capacity of 25 sq.mm., conductor line load reversibility , IP 20 contact protection and fitted in existing distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating, 10,000 upto 63 A, 5000 for 80 A & above rating including making connections, testing etc. as required.
19Single pole MCB (With B / C curve tripping characteristics)
206 A to 32 A rating
21Double pole MCB (With B / C curve tripping characteristics)
226 A to 32 A rating
23Four pole MCB (With B / C curve tripping characteristics)
2450/63 A rating
2540 A rating
26Providing & Fixing of Recessed/surface mounting heavy duty horizontal type Double Door (Metal / Glazed / Acrylic) Distribution board with Metal end box made out from Galvanized steel / CRCA sheet, powder coated conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3, complete with 100 amp. insulated copper bus bar/shorting link , brass neutral link with shrouds, brass earth link , door earthing arrangement, color coded interconnecting wire set of minimum 10.0 sqmm size and din bar,masking sheet, making internal DB terminations with copper lugs, Ferrules, detachable gland plate, including making connections, testing etc. as required.
27Metal door (single phase) IK-09 and IP-43 with Metal end box
284 Way
29Metal door (Three phase) Per phase isolation, Horizontal IK-09 and IP-43 with Metal end box
306Way {8 Incomer + 6 Sub Incomer (2+2+2) + 18 out going }
31P&F metal clad / Polyamide industrial plug top & socket unit with pin and sleeve type contact on porcelain/ bakelite base in Recessed/surface mounting heavy duty Enclosure made out from Galvanized steel / CRCA sheet , powder coated conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3. (without MCB) including making connections, testing etc.as required.
3220 amp, (2P + E), 1 Module
33Providing & Fixing of ISI marked (IS:302) ding dong/musical chime bell including making connection testing etc. as required.
34Providing & Fixing of modular type 100W Step Fan regulator duly ISI marked (IS 11037) with CM/L no. printed made out of unbreakable and fire retardant virgin poly carbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating , including making connections, testing etc as required.
355 step fan regulator 2 Module
36Providing & Fixing of following modular accessories, made out of unbreakable and fire retardant virgin poly carbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating, including making connections, testing etc as required.
37RJ-11 telephone jack single line
38Blanking plate
39Modular MCB 6 A to 32 A SP
40Providing & Fixing of following size mounting grid plates with cover plates made from fire retardent UV established high performance engineering plastic suitable for all universal metal boxes for front installation & removal direct fit type complete in all respect.
411/2 Module
424 Module
43Providing & Fixing of following size cover plates made from fire retardent UV established high performance engineering plastic suitable for all universal metal boxes for front installation & removal direct fit type complete in all respect.
441-2 Module
454 Module
46Supplying and fixing of power plug point with Modular accessories on hot dipped galvanized modular box of 1.2 mm thick with earthing terminal/connector on surface or in recessed with suitable size of modular face place with grid plate and cover plate including cost of ISI marked modular 16 amp. Switch (IS :3854) and 6/16 amp. socket outlet (IS:1293) making connection , testing , etc. as required.
47Providing & Laying XLPE insulated & P.V.C. sheathed Armoured Aluminium cable confirming to IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing commissioning etc. as required of following size.
4825.0 Sq. mm
493.5 core
5035.0 Sq. mm
513.5 core
5250.0 Sq. mm
533.5 core
54SITC of Strip in Pipe Earthing using hot-dip galvanized 'B' class G.I. pipe, as secondary conductor. The system shall incorporate a crystalline conductive compound between the primary and secondary conductors to enhance conductivity and long-term stability. of following size and length and as per point mentioned (a), (b), [c), (d), (e) (f) as below
55(a) Bore a hole of dia. 150 mm of required length, Place the rod in the centre of Hole
56(b)Earth enhancing compound to ensure the moisture content and electrical conductivity, 30 kg for 3000 mm. 20 Kg. for 2000 mm The compound shall be tested form NABL accredited lab for low resistivity (less than 0.12 Ohm - meter) & high conductivity in nature with carbon as a major content in accordance with IEC 62561-7
57© Connect the Strip Terminal (110 mm long) with copper Strip/Conductor/Wire with suitable clamp made from tinned copper and SS 304 Bolt
58(d) Place Heavy duty weather proof poly-propylene earth inspection chamber as per requirement of IS/IEC 62305 and tested as per IEC 62561-5 with lockable Jam free lid suitable for safe working load 60 kN of round / square size 250 mm, and Height 250 to 300 mm.
59(e) Testing of earth resistance for value of 5 ohms or less as required.
60(f) Test certificates for confirming above standards from OEM is mandatory.
61Outer Pipe - 76 mm dia GI pipe , Inner Conductor- GI strip 50x6 mm Length 3meter. Terminal 50x6mm GI.
62Supply & Laying following size earth strip in horizontal or vertical run in surface by means of Earth strip DMC Insulator including riveting/ soldering/ welding, Jointing shall be done by overlapping double the width of strip and with 2 set of Brass (for Cu strip) / GI (for GI Strip) nut bolt & spring washer spaced at 50cm making connection etc. as required.
6320mm x 3mm G.I. ( Hot Dipped ) Strip
64Providing & Fixing of BEE Star rated copper wounded with class of Insulation 'F', double ball bearing capacitor start, aluminium body & aluminium blade ceiling fan conforming to all the performance requirements laid down in IS 374:2019 with down rod up to 30 cm with secondary support safety cable ( steel rope) , cotter pin, shackle kit with 3 x 1.5 sq.mm pvc insulated flexible copper conductor and making connection testing etc. as required.
651200 mm Sweep BEE 3 Star rated (service value >=5.0 to< 5.5 )
66P & F 1.2 mm thick M.S. Recessed fan box and top lid screwed on Box, hexagonal/ round of size 130 mm dia, depth 75mm, 12 mm dia rod fan hook with 150 mm length extended on each side as required.
67Providing & Fixing of of Double ball bearing, copper wounded capacitor start single phase metallic blade fresh air fan, in existing opening including cost of hardware , flexible 3 core 1.5 Sq.mm copper conductor ,making connections, testing etc. as required.
68300 mm sweep Minimum air delivery 1600 Cum / hour
69Providing & Fixing of Heavy duty capacitor start, copper wound Double ball bearing 900/1400 RPM single phase Exhaust fan conforming to IS:2312 marked in existing opening including making connections testing etc. as required.
70380 mm sweep(900 RPM)
71SITC of IP20 SMD Mid Power LED batten type integrated light fixture made from Powder coated Extruded aluminium housing with in built driver , System lumen efficacy ≥ 110 lm/Watt output only at CW (5700K to 6500K) , internal surge protection of 4.0 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, CRI >80 , life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) as required.
721170mm(+/-10%) LED batten with min. lumen output 2200 lm
73SITC of IP20 SMD Mid Power LED batten with integrated box (min.1200mmx40mmx60mm including reflector) with replacable driver fixture made from Powder coated Extruded aluminium housing ,Min. lumen output 4800 lm, System lumen efficacy ≥ 120 lm/Watt output nly at CW (5700K to 6500K), internal surge protection of 4.0 KV with Short & Open circuit protection,THD < 10% , P. F.≥0.95, CRI >80 , life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) as required.
74SITC of IP-20 LED Recessed / Surface Mounted, Round / Square backlit & SMD Mid Power LED Downlight with power coated die-cast aluminum housing with UV Stabilized non yellowish Diffuser with BIS compliance 4.0 KV surge protected Isolated driver, with Short & Open circuit protection input 320VAC-48 hr protection, input 350VAC-2 hr protection), having efficiency > 85% . System Lumen efficacy of ≥ 110 lm / watt,at CW (5700K to 6500K) , THD < 10 % , Pf.≥0.95, CRI >80, life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) as required.
75Surface Mounting (with extruded alumn. Housing )
76Minimum lumen output 1300 lm
77Minimum lumen output 1950 lm
78Providing & Fixing of IK08, IP 66 protected LED Street Light Luminaire on existing bracket/pole. Fixture made of powder coated single piece pressure die cast aluminum material with heat dissipation fins on housing with UV stabilized PC (UV stablization report submitted for UV cover ) /Toughened Glass cover and secondary lens on each LED/ integrated lens diffuser & should be High power LED of 3 to 5 watt each . The System efficacy >=125 lm/ wt and integrated metal case potted driver & has a unique BIS R number ( as per IS 15885) with Input Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC & Low Voltage cutoff @>=90 V AC and Auto resetting Safety , Power Factor >0.95 driver Efficiency >85% ,THD(I) <10% Humidity 10% to 90% RH Working Temp -5C to 45C . LED driving output current <750mA. The luminaire shall be BIS certified (Fitting & driver both have separte BIS R number) and Trade mark certified. Life Expectancy Equal or more than 50000 burning hrs with Minimum 70% lumen maintened , CRI >70 and CCT 5700K +355K. Surge protection shall be min ≥ 4 KV internal and min 10 KV external inside driver compartment. driver should be Phase to phase protection of 440 V for 4 Hrs as required.
79LED Street Light fixture with Minimum lumen output 8750 lm
80LED Street Light fixture with Minimum lumen output 12500 lm
81Providing & Fixing of Street light bracket made out from following size of ' B ' class , Medium class G.I. Pipe confirming to IS : 1239 P - 1 ( 2004 ) with heavy duty pole clamp, Saddles suitable fastners etc. as required.
8225 mm Dia.
8332 mm Dia.
84Providing & Fixing of IP - 65 protected impact resistant polycarbonate / Polysterene enclosures with knock out for cable entry/out including fixing with nut, bolt, fatner etc as required complete in all respect of following sizes.
85250 x 200 x 115 mm
86Supply, Drawing and Testing of 4 pair, 23 AWG Solid Bare Copper wire insulated with PVC, U/UTP (Unscreened/Unshielded Twisted Pair), Category 6, Class E, 100 Ohm Impedance, Indoor Cable as per latest ammendments of ANSI/TIA/EIA-568 , The copper conductors should be balanced twisted in pairs, seperated by a cross-member fluted pair divider & protected by LSZH Jacket. Certified performance in a 4-connector configuration upto 100 Mtrs channel requirements & transmission frequencies ranging from 250 to 500 Mhz. in existing MS/PVC Conduits/casing capping including making connections to Information outlets and Patch Panels with jack & ferruling at both ends for identification with necessary tools for punching, stripping, crimping and testing etc as required complete in all respect.
87Supply and Installation of unshielded/360 degree shielded PCB based Information outlets made of high impact plastic body with ABS, Flammability rating UL 94 V-0 with provision for protection against dust in jack or Faceplate, suitable for Cat 6/6A application complying to latest amendments, According. to Cat. 6/6A channel, It should support channel as well as components requirements of Cat 6/6A standards at frequencies 250/ 500 MHz. Cat 6/6A unshielded/shielded Jack should be suitable to terminate 4 pair, 23/24 AWG solid/stranded wire diameters, using 100 Ohm unshielded/shielded balance twisted pair cable, the jack should have toolless/impact termination on reliable copper tin plated Insulation displacement contact, with easy lock mechanism, It supports IEC 60603-7-4 and complied with ANSI/TIA 568 C.2 & ISO/IEC 11801 or latest standard. jack should be RJ11,RJ12 & RJ45 compatible. Should support Ethernet 1.2 Gb/s ATM,Digital video and broadband/baseband analog video, Voice over internet protocol (VOIP) Specifications in existing modular/MS Boxes along with necessary connections as required. All as per pre approved by Engineer in charge.
88Cat 6, Un-sheilded Information Outlet
89Supply & fixing of square Faceplate for Flush / Surface Mount Information Outlets Single/Dual or Quad Aperture with dust cover, material should be High-impact, flame retardant, thermoplastic, UL listed material, Suitable for RJ45 unshielded/shielded connection modules. Should match with I. O. OEM. Dimensions should be 86mm X 86mm as required complete in all respect. All as per pre approved by Engineer in charge.
90Single Aperture
91SITC of EN / LPCB certified conventional automatic fire Alarm Optical / Photoelectric type smoke detectors of photo-optic sensing chamber, 12 / 24 volt D.C., visual alarm indicator (LED's) Blink in stand by and \\"Steady - red\\" in alarm complete in all respects with base as required.including the cost of all accessories Etc. as required.
92SITC of UL 7th edition / FM certified Addessable Manual Call point (MCP) with LED / FIRE Indication Etc. as required.
93Supplying and drawing Fire Resistant flexible / stranded bare copper conductor, PVC / XLPE insulated, overall aluminium mylar tape shielded ATC drain wire and outer PVC sheathed industrial Instrumentation (shielded)cables voltage grade 300/500 V as per BS /EN 50288-7 in existing surface or recessed PVC/ MS conduit/casing capping / Cable tray / Open Duct making connections, testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for cables.
942 x 1.5 Sq.mm Unarmoured With Outer Sheath in Red Color
95SITC of wall type following zone (each zone accessing minimum 20 units (detectors/ devices )) Conventional Type microprocessor based with LCD display EN / LPCB/ UL listed / approved main control panel fabricated from 16 SWG CRCA sheet steel sealed maintenance free (SMF) batteries of min2X7AH of 12 V or as required.including the cost of all accessories, Etc. as required.
962 Zone
97SITC of EN / LPCB certified conventional type Manual call point resettable in sheet steel / polymer housing in surface / recess complete with Glass, hammer and chain etc.including the cost of all accessories Etc. as required.
98SITC of EN / LPCB/ UL certified conventional type Hooter cum strobe rated 80 dB 3 mtr. for audible annunciation and 115 cd flashing at 1 Hz for visual Indication including the cost of all accessories,Etc. as required.
99Supply & Fixing of Dry Powder Agent (as per IS 4308:2019), ABC type Fire Extinguisher (Stored Pressure type) conforming to IS:15683:2018 , Powder coated Internal & External Surface Deep drawn cylinder body of Mild Steel CR2 grade conforming to IS: 513, Squeeze grip Forged brass release valve with Inbuilt safety release device, Diaphragm Type, 0 to 28 bar range pressure gauge, 450 mm long EPDM discharge tube, QR code for Product Traceability including Fixing on wall with suitable Anchor Fasteners as required of following capacity. Test Certificates of all the Parameters along with Hydro test & Burst test (For Cylinder Body) Certificate from OEM / External NABL Accrediated Lab is to be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR .
100Supply & Fixing of CO2 type Fire Extinguisher conforming to IS:15683:2018, charged with CO2 gas (purity 99.7% conforming to IS 15222), Powder coated Internal & External Surface Manganese steel ISI marked as per IS 7285 cylinder body , Wheel type Forged brass release valve ISI Marked as per IS 3224 with Inbuilt safety release device ((Fusible plug and Rupture Disc Type), 1.0 Mtr. Metal wire braided hose having minimum bursting pressure of 140 Kgf/cm2, Horn with metallic thread connection, QR code for Product Traceability, including Fixing on wall with suitable Anchor Fasteners as required of following capacity. Test Certificates of all the Parameters along with Hydro test & Burst test (For Cylinder Body) Certificate from OEM / External NABL Accrediated Lab is to be submitted.
101Capacity 4.5 Kg. Please Enable Macros to View BoQ information

Other Detail

Information Source https://eproc.rajasthan.gov.in
Download FileName File Description File Size
Download Tendernotice_5.pdf Tender Documents 0 KB
Download 98c9d032-7bfb-4e87-9c1b-f05116569759.html Tender Documents 0 KB
Download BOQ_969261.xls Tender Documents 0 KB
Download Tendernotice_1.pdf Tender Documents 0 KB
Download Tendernotice_2.pdf Tender Documents 0 KB
Download Tendernotice_3.pdf Tender Documents 0 KB
Download Tendernotice_4.pdf Tender Documents 0 KB
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.