Indian Tenders

Tender Notice

TDR 54349135
Tendering Authority military engineer services
Tender No 8507/E8
Tender ID 2026_MES_754946_1
Tender Brief Corrigendum : Tender For Renewal Of Various Size Of Lp Air Pipeline With Associated Fittings, Air Receiver Bottles, Air Separators, Valves And Fasteners In And Around Surya And Varuna Drydocks For Compressor Unit Located At Drydocks At Naval Dockyard Visakhapatnam Unde
City Visakhapatanam
State Andhra Pradesh
Document Fees INR 1000 /-
EMD INR 157480.0 /-
Tender Value INR 88.32 Lakhs /-
Tender Type Works
Bidding Type Open Tender
Competition Type Indian

Tender Details

Tender For Renewal Of Various Size Of Lp Air Pipeline With Associated Fittings, Air Receiver Bottles, Air Separators, Valves And Fasteners In And Around Surya And Varuna Drydocks For Compressor Unit Located At Drydocks At Naval Dockyard Visakhapatnam Under Ge (I) (Dm) Visakhapatnam

Corrigendum Details

Sr No CorrigendumDate Corrigendum CorrigendumType NewSubmissionDate
1 06-04-2026 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 11-04-2026
2 30-03-2026 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 06-04-2026
3 30-03-2026 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 06-04-2026

Key Dates

Publish Date 06-04-2026
Last Date of Bid Submission 11-04-2026
Tender Opening Date 13-04-2026

Contact Information

Company Name military engineer services
Contact Person GE (I) DM Visakhapatnam
Address GE (I) DM Visakhapatnam

BOQ Items

Name of Work:- RENEWAL OF VARIOUS SIZE OF LP AIR PIPELINE WITH ASSOCIATED FITTINGS, AIR RECEIVER BOTTLES, AIR SEPARATORS, VALVES AND FASTENERS IN AND AROUND SURYA AND VARUNA DRYDOCKS FOR COMPRESSOR UNIT LOCATED AT DRYDOCKS AT NAVAL DOCKYARD VISAKHAPATNAM UNDER GE (I) (DM) VISAKHAPATNAM
Sl. No. Item Description
1M&L for cross arms, T-pieces, bends, flanges and suitable accessories of MS material and brasings, supports, clapms and back plates fabricated from structural steel suctions, including nuts and bolts and washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat and one under coat and one finishig coat of paint, completed all as specified and directed
2Material & labour for PCC (1:2:4), type B1 (using 20 mm graded stone aggregate) as in pillar to support the pipe lines including necessary form work and finishing the exposed surfaces of concrete fair and even all as specified and directed
3Supply, laying,testing and commissioing of MS ERW pipeline(flanged) and making flanged joint between length including rubber gasket ,nut,bolt and washer etc alongwith clamping of pipe at every 3 mtrs interval using 50mm width 6 mm thickness MS flat bar complete all as specified and directed.
4150mm dia, 7.1 mm thickness
5100mm dia, 6 mm thickness
650mm dia, 3.9 mm thickness
7Supply and fixing of stainless steel ball valves made of 304 steel grade with class 300 flanged type as per ASE standarded complete all as specified and directed.
8100mm dia
950mm dia
10Supply and fixing of plug type Audco valve 150mm dia with screw type end fitting on both side complete all as specified and directed.
11M & L for Post pressure testing and cleaning of pipeline to remove surface rust/ dust and Supply including apply of one coat of sky blue ready mix paint finishing exterior conforming to IS 6951 to entire length of pipe all as specified and directed.
12Supply and fixing Installation of pressure gauge with cock complete all as specified and directed.
13Dismantling and taking out including old LP compressor assembly Comprehensive maintanence and refixing and testing and commissioning of LP Compressor Block Assembly Unit that includes total overhauling of compressor block, cooling water pumps and all associated fittings & accessories and sub-component units which are mentioned below LP Compressor Block Assembly Unit after carryout all repair works testing shall be carriedout to unit as per OEM recommendation. The technical details as followsModel - 2HN2 447-28Cylinder Bore:LP - 470 mmHP - 280 mmStroke - 150 mmNormal Speed - 800 RPMPiston Displacement - 41.48 cubic meter per minute Normal Working pressure - 7.03 (100) kg per sq cm g (Psig)Free air delivey - 34.50 (1219) cubic meter per minute (CFM)Recommended Motor Rating - 200 (265) kW (HP)
14Supply only Piston Rings and Oil wiper rings copmplete set all as specified and directed.
15Supply only Safety valves, Pressure Guage and Temperature Guage as requires and directed by Engineer In-Charge
16Supply only one in nubmer cooling water pump iclude motor set (7.5 HP) all as specified and directed.
17Supply only Gaskets and O-rings as requires all as specified and directed.
18M & L for chemical cleaning of Inter cooler and after cooler complete all as specified and directed,
19Overhauling of one in number cooling water pump-motor (7.5 HP) & LP compressor all as specified and directed.
20Repair to existing Suction and Discharge Valves includes repair of springs, valve plates,damper plates and all necessisate accessories for Audco valve -150mm Cock type manual operated complete all as specified and directed.
21Repair and servicing of 100 mm bore Sluice Valve by dismentaling all the parts after removing from site & replacement of all all parts like brass spindle GM lock nuts, gaskets nuts & washer etc to make fully serviceable and refixing the sams in original position including connection complete all as specified and directed.
22Repair and servicing of 50 mm bore by Sluice Valve by dismentaling all the parts after removing from site & replacement of all all parts like brass spindle GM lock nuts, gaskets nuts & washer etc to make fully serviceable and refixing the sams in original position including connection complete all as specified and directed.
23Supply and fixing LP Compressor Starter panel to suit the existing 270 HP motor as drive panel from Auto-Transformer Starter to variable frequency drive(VFD) Starter with temarature/ humidty control arrangement and provide By-pass arrangment with Star-Delta Starter if VFD failes by provisioning all necessiate components and fitting includes main contactors Aux contactors, Digital meters, timers OLR, control circuitary etc into the existing LT panels by keeping the same incomer chamber with the following specification.
24Removal and Dismantling of one in number Dry Cooling Tower (DCT) assembly Unit includes copper cooling assembly, cooling towers and all associated fittings & accessories complete all as specified and directed.
25Chemical cleaning of Dry cooling tower
26Pressure test of Dry Cooling Tower(DCT) Unit
27Supply only new unit for make-up water tank with associated pipelines and fittings accessories
28Overhauling of two in numbers Dry cooling tower motors
29Overhauling/ Repair and replace the necessary components of LT panel for DCT unit.
30Servicing of Air Receiver Tank as followsa) Measuring the Thicknessb) Pressure Testingc) Certifying by the Competent Authority by Rule 8
31M&L mild steel framed work with ends of bars souldered, welded or reveted or forced into spikes, framed guard bars, ladders,chequred plates framed balusters, walk ways, railings, gates, frame work of tank, valvepit and similar work incl painting with one coat of red oxide primer and one coats of anticorrosive black bituminous paint incl dismantling mild steel work of any description not otherwise specially provided for all as specified and directed.
32M & L for rendering 10mm thick cement plaster (1:4) on fair faces of brick work or concrete surfaces complete all as specified and directed.
33Supply and laying well burnt bricks sub class 'B' laid breath wise along the length of cable in trench for underground cable protection complete all as specified and directed.
34Replace with new unit for maintaining Dew Point of 3 deg C of Discharge Air using 2000 cfm Refrigerated type Air Dryer.
35Supply, laying,testing and commissioing of MS ERW pipeline(flanged) and making flanged joint between length including rubber gasket ,nut,bolt and washer etc alongwith clamping of pipe at every 3 mtrs interval using 50mm width 6 mm thickness MS flat bar complete all as specified and directed.
36150mm dia, 5mm thickness
37100mm dia, 5mm thickness
3850mm dia, 4mm thickness
3925mm dia, 4mm thickness
40Supply and fitment of CI double flanged raised spindle sluice valve with SS spindle and bronze box nut as per IS 780 range 150 to 100 mm dia IS 14846 (2000) PN1.0 complete all as specified and directed.
41100mm dia
4250mm dia
43Supply and fitment of plug type Audco valve with screw type end fitting on both side all as specified and directed.
44150mm dia
4550mm dia
4625mm dia
47Supply and fitment of TVS bolts and nuts with washer on both sides complete all as specified and directed.
4816 x 90mm
4914 x 60mm
5012 x 60mm
51Supply and installation of Air separator with manual drain cock at suitable length of pipe on 150mm dia pipe and at every cope point 50mm and 25mm all as specified and directed.
52Supply and Welding of following MS Bends all as specified and directed.
53150mm dia
54100mm dia
5550mm dia
5625mm dia
57Supply and fixing of Nitrile rubber gasket of 6mm thickness conforming to BS 2751 of shore hardness BA 70 complete all as specified and complete all as specified and directed.
58Supply,fix and Installation of Air Distribution Manifolds SS316 flange type Inlet 4’’ outlet 5 off SS304 ball valve ¾’’ with Universal coupling for hose connection all as specified and directed.
59Supply,fix and Installationof pressure gauge with cock at all the cope point all as specified and directed.
60Supply,fix and Installation of the hand gun with coil hose for 5 mtrs (industrial bay, stripping bay, MDP bay in SDD pump house and similar cope point in NDD pump house) all as specified and directed. Please Enable Macros to View BoQ information

Other Detail

Information Source https://defproc.gov.in/nicgep/app
Download FileName File Description File Size
Download 8507Tender.pdf Tender Documents 0 KB
Download b5b18dd4-7c29-4067-9255-0af5105f25c3.html Tender Documents 0 KB
Download BOQ_845565.xls Tender Documents 0 KB
Download Tendernotice_1.pdf Tender Documents 0 KB
Disclaimer :