Indian Tenders

Tender Notice

TDR 53712543
Tendering Authority Military Engineer Services
Tender No 8759 GE SOUTH PUNE
Tender ID 2025_MES_738919_2
Tender Brief Tender For Repair / Maint Of External Water Supply System, Pump, Motor, Level Indicator, Pipe Line, Valve, Chambers, Cleaning Of Oht /Sump Andother Connected Works In New Chsc And Other Connected Area Under Age E/M-Ii Of Ge (South) Pune
City pune
State Maharashtra
Document Fees INR 500 /-
EMD INR 98000.0 /-
Tender Value INR 49 Lakhs /-
Tender Type Tender
Bidding Type Open Tender
Competition Type Indian

Tender Details

REPAIR / MAINT OF EXTERNAL WATER SUPPLY SYSTEM, PUMP, MOTOR, LEVEL INDICATOR, PIPE LINE, VALVE, CHAMBERS, CLEANING OF OHT /SUMP ANDOTHER CONNECTED WORKS IN NEW CHSC AND OTHER CONNECTED AREA UNDER AGE E/M-II OF GE (SOUTH) PUNE

Key Dates

Publish Date 29-01-2026
Last Date of Bid Submission 14-02-2026
Tender Opening Date 16-02-2026

Contact Information

Company Name Military Engineer Services
Contact Person GE SOUTH PUNE
Address No 1 Gen Bhagat Marg Pune 40

BOQ Items

Name of Work: REPAIR / MAINT OF EXTERNAL WATER SUPPLY SYSTEM, PUMP, MOTOR, LEVEL INDICATOR, PIPE LINE, VALVE, CHAMBERS, CLEANING OF OHT /SUMP ANDOTHER CONNECTED WORKS IN NEW CHSC AND OTHER CONNECTED AREA UNDER AGE E/M-II OF GE (SOUTH) PUNE
Sl. No. Item Description
1Provide skilled labour for attending the defect / complaints for checking of any type of water supply complaints like “No water supply, water leakage, air lock, low pressure, over flow” etc. complaint including carrying out minor repairs etc. as required at site and to make it functional by replacing necessary petty items like rubber gasket, grease, screws etc., complete all as specified and directed by Engr-in-charge. Note:- (i) Attending one number of complaint, shall be measured as one job.(ii) New materials required for to be fixed against old unserviceable GI fitting shall be measured and paid separately as “Supply only” under respective items of BOQ.(iii) One plumber (Possessed with all requisite tool) with one helper must be available at site every day from 0900 hrs to 1700 hrs failing which, Rs 1000 per day penalty will be levied. Attendance of plumber and helper will be recorded daily as per direction of Engr-in-charge.(iv) The contractor shall maintain proper record of repair / maintenance in a binded register duly bringing out the details of spares replaced and get it authenticated from concerned JE E/M on daily basis. The contractor shall put up the maintenance record register to Engr-in-charge for inspection every Monday or as and when asked for.(v). The contractor shall maintain sufficient stock of spares / material required for repair / maint with the concerned JE E/M.
2S&F in replacement 65mm bore foot valve\"s brass assembly, ISI Marked, complete all as specified and directed.
3S&F in replacement 80mm bore foot valve\"s brass assembly, ISI Marked, complete all as specified and directed.
4Supply only grease of suitable grade for spare parts of pumps complete all as specified and directed. Make:- INDIAN OIL SERVO MP-3 or equivalent in HP
5S & F in repairs 80 mm bore ball type check valve (NRV), ISI Marked with cast iron body, strainer, nitrile rubber coated ball with Tin bronze seat ring suitable of size, complete all as specified and directed.
6S & F in repairs 100 mm bore ball type check valve (NRV), ISI Marked with cast iron body, strainer, nitrile rubber coated ball with Tin bronze seat ring suitable of size, complete all as specified and directed.
7S & F in repairs 150 mm bore ball type check valve (NRV), ISI Marked with cast iron body, strainer, nitrile rubber coated ball with Tin bronze seat ring suitable of size, complete all as specified and directed.
8Demolition of stone slab & tiles of any description or thickness infloor, aprons etc., laid, bedded and pointed in any mortar, complete all as specified and directed.
9M&L for precast coloured, chequered cement concrete tiles, glossy finish of size 300 x 300mm x 25mm thick, conforming to IS-1237 (2006) set jointed and pointed in neat cement slurry in floor laid over and including 20mm thickscreedbed in CM (1:6) complete all as specified and directed.
10S&F in replacement gun metal gate valves (Class I), with iron wheel head,screwed both ends for iron pipe, ISI marked, complete all as specified and directed by Engr-in-charge for the following bore dia of pipe:-(a) 15mm bore.
11(b) 25mm bore.
12(c) 40mm bore.
13(d) 50mm bore.
14(e) 80mm bore.
15S&F in replacement stop valve, ISI marked, cast copper alloy, screwed down, high pressure with crutch or butterfly handle, screwed both ends for iron pipe or for unions as per site requirement complete all as specified and directed by Engr-in-charge for the following bore of pipe:-(a) 15mm bore.
16(b) 25mm bore.
17(c) 40mm bore.
18(d) 50mm bore.
19M&L for drilling and tapping of 150 mm bore CI / DI water main (in position) for insertion of branch connection complete all as specified and directed by Engr-in-charge.
20M&L for drilling and tapping of 200 mm bore CI / DI water main (in position) for branch connection complete all as specified and directed by Engr-in-charge.Note for item no.12 &13 :- Excavation and earth work shall be measured and paid separately under respective items of BOQ.
21Supply and fix in replacement 80mm bore sluice valve, PN-1.6 with stainless steel spindle and wedge nut ISI marked (Conforming to IS-14846) complete with iron wheel, complete all as specified and directed by Engr-in-charge
22Supply and fix in replacement 100mm bore sluice valve, PN-1.6 with stainless steel spindle and wedge nut ISI marked (Conforming to IS-14846) complete with iron wheel, complete all as specified and directed by Engr-in-charge
23Supply and fix in replacement 150mm bore sluice valve, PN-1.6 with stainless steel spindle and wedge nut ISI marked (Conforming to IS-14846) complete with iron wheel, complete all as specified and directed by Engr-in-charge
24Supply and fix in replacement 200mm bore sluice valve, PN-1.6 with stainless steel spindle and wedge nut ISI marked (Conforming to IS-14846) complete with iron wheel, complete all as specified and directed by Engr-in-charge
25Supply and fix in replacement 250mm bore sluice valve, PN-1.6 with stainless steel spindle and wedge nut ISI marked (Conforming to IS-14846) complete with iron wheel, complete all as specified and directed by Engr-in-charge
26M&L for taking out 80 mm bore sluice valves for re-facing, grinding, packing glands in stuffing box to prevent the leakage from valve and re-fixing the same after carried out the said repairs, complete all as specified and directed by Engr-in-charge.
27M&L for taking out 100 mm bore sluice valves for re-facing, grinding, packing glands in stuffing box to prevent the leakage from valve and re-fixing the same after carried out the said repairs, complete all as specified and directed by Engr-in-charge.
28M&L for taking out 150 mm bore sluice valves for re-facing, grinding, packing glands in stuffing box to prevent the leakage from valve and re-fixing the same after carried out the said repairs, complete all as specified and directed by Engr-in-charge.
29M&L for taking out 200 mm bore sluice valves for re-facing, grinding, packing glands in stuffing box to prevent the leakage from valve and re-fixing the same after carried out the said repairs, complete all as specified and directed by Engr-in-charge.
30M&L for taking out 250 mm bore sluice valves for re-facing, grinding, packing glands in stuffing box to prevent the leakage from valve and re-fixing the same after carried out the said repairs, complete all as specified and directed by Engr-in-charge.
31Taking up or down 100 mm bore Cast Iron/ Ductile Iron water mains of any class including all fittings with spigot and socket ends of any type of joints, keeping in safe custody for reuse of serviceable pipes after necessary cleaning complete all as specified and directed.
32Taking up or down 150 mm bore Cast Iron/ Ductile Iron water mains of any class including all fittings with spigot and socket ends of any type of joints, keeping in safe custody for reuse of serviceable pipes after necessary cleaning complete all as specified and directed.
33Taking up or down 200 mm bore Cast Iron/ Ductile Iron water mains of any class including all fittings with spigot and socket ends of any type of joints, keeping in safe custody for reuse of serviceable pipes after necessary cleaning complete all as specified and directed.
34Taking up or down 250 mm bore Cast Iron/ Ductile Iron water mains of any class including all fittings with spigot and socket ends of any type of joints, keeping in safe custody for reuse of serviceable pipes after necessary cleaning complete all as specified and directed.
35Re-fixing / re-laying and testing of 100 mm bore CI /DI pipes (Serviceable pipe obtained from item no.24 to be used under this item) including filling joints with lead and ensure to make the joints leak proof, complete all as specified and directed
36Re-fixing / re-laying and testing of 150 mm bore CI /DI pipes (Serviceable pipe obtained from item no.25 to be used under this item) including filling joints with lead and ensure to make the joints leak proof, complete all as specified and directed
37Re-fixing / re-laying and testing of 200 mm bore CI /DI pipes (Serviceable pipe obtained from item no.26 to be used under this item) including filling joints with lead and ensure to make the joints leak proof, complete all as specified and directed
38Re-fixing / re-laying and testing of 250 mm bore CI /DI pipes (Serviceable pipe obtained from item no.27 to be used under this item) including filling joints with lead and ensure to make the joints leak proof, complete all as specified and directed
39Supply, laying and testing ductile iron pipe with internal cement mortar lining and external zink pipes confirming to IS : 18329 - 2000 with class of pipe K-7 of size 100 mm including bends, sockets, tee, branches etc. complete all as specified and directed
40Supply, laying and testing ductile iron pipe with internal cement mortar lining and external zink pipes confirming to IS : 18329 - 2000 with class of pipe K-7 of size 150 mm including bends, sockets, tee, branches etc. complete all as specified and directed
41Supply, laying and testing ductile iron pipe with internal cement mortar lining and external zink pipes confirming to IS : 18329 - 2000 with class of pipe K-7 of size 200 mm including bends, sockets, tee, branches etc. complete all as specified and directed
42Supply, laying and testing ductile iron pipe with internal cement mortar lining and external zink pipes confirming to IS : 18329 - 2000 with class of pipe K-7 of size 250 mm including bends, sockets, tee, branches etc. complete all as specified and directed
43M & L for cutting of 100mm bore CI/DI pipe in required length according to position for insertion of new tee / branches etc. complete all as specified and directed by Engr-in-charge.
44M & L for cutting of 150mm bore CI/DI pipe in required length according to position for insertion of new tee / branches etc. complete all as specified and directed by Engr-in-charge.
45M & L for cutting of 200mm bore CI/DI pipe in required length according to position for insertion of new tee / branches etc. complete all as specified and directed by Engr-in-charge.
46M & L for cutting of 250mm bore CI/DI pipe in required length according to position for insertion of new tee / branches etc. complete all as specified and directed by Engr-in-charge.
47Taking up or down carefully of following sizes of GI / steel water tubing and connection from trenches, wall & under floors including cleaning of serviceable pipes for re-fixing complete all as specified and directed.(a). 15mm bore.
48(b). 25mm bore.
49(c). 40mm bore.
50(d). 50mm bore.
51(e). 80mm bore.
52(f). 100mm bore.
53Re-fixing & testing of serviceable GI / steel water tubing obtained from item nos. 40 to 40.50 and connections in new or old position (wall / floor / ceilling / trecheh etc) with and including all fittings and fixtures, complete all as specified and directed of following sizes:-(a). 15mm bore.
54(b). 25mm bore.
55(c). 40mm bore.
56(d). 50mm bore.
57(e). 80mm bore.
58(f). 100mm bore.
59Supply and fixing and testing of GI tubing medium grade galvanized incluidng with all fitting and fixtures, fixed complete to walls / ceilings or laid in floors complete all as specified & directed of the following sizes :- (a). 15 mm bore
60(b). 40mm bore.
61(c). 50mm bore.
62Laying & testing of GI tubing of any grade, galvanized including incluidng with all fitting and fixtures complete, fixed to walls / ceilings or laid in floors complete all as specified & directed of the following sizes :-Note:- Following sizes GI pipe will be issued under schedule ‘B’ free for fixing only(a). 25mm bore.
63(b). 80mm bore.
64(c). 100mm bore.
65M&L for cutting and testing of existing GI pipe for alteration or addition of sizes including screwing existing GI tubing for tapping & making new connection etc. with and including necessary fittings and fixtures, complete all as specified & directed of the following sizes:-(a). 15 mm bore
66(b). 25mm bore.
67(c). 40mm bore.
68(d). 50mm bore.
69(e). 80mm bore.
70(f). 100mm bore.
71M&L for periodical and preventive maintenance of AC, 3 Phase Induction motor of capacity 10/15 HP by dismantling the motor completely without damaging any parts and applying air dry insulating varnish, of appropriate Grade (make- Doctor Bake/ Appex), cleaning bearings, re-fixing at its existing position with bearing grease, checking terminals and thimbles, tightening the all terminal joints, replace terminal plates where necessary, re-install the motor at existing position, connecting electric connections and testing etc. complete all as directed by Engineer-in-charge.
72M&L for periodical and preventive maintenance of AC, 3 Phase Induction motor of capacity 5 HP by dismantling the motor completely without damaging any parts and applying air dry insulating varnish, of appropriate Grade (make- Doctor Bake/ Appex), cleaning bearings, re-fixing at its existing position with bearing grease, checking terminals and thimbles, tightening the all terminal joints, replace terminal plates where necessary, re-install the motor at existing position, connecting electric connections and testing etc. complete all as directed by Engineer-in-charge.
73M&L for periodical and preventive maintenance of AC, 3 Phase Induction motor of capacity 2 HP by dismantling the motor completely without damaging any parts and applying air dry insulating varnish, of appropriate Grade (make- Doctor Bake/ Appex), cleaning bearings, re-fixing at its existing position with bearing grease, checking terminals and thimbles, tightening the all terminal joints, replace terminal plates where necessary, re-install the motor at existing position, connecting electric connections and testing etc. complete all as directed by Engineer-in-charge.
74S&F in repairs terminal plate made of bakelite as per the existing shape and size of the motor complete all as specified and directed.
75M&L for shaft balancing of Pump and motor as per OEM setting arrangement with required T&P complete all as specified and directed .
76M&L for Taking out unserviceable / defective open well submersible pump of capacity 12.5 HP, AC single phase, 50 HZ, make any type by disconnecting pipe and electric connections and carrying out to workshop for repair and return back to its original position. Repair works shall be comprising with the following: -(i) Taking out open well submersible pump set with the help of Crane or any other means required at site without damaging the pump or existing structure.(ii) Re-winding of motor complete by replacing existing burnt winding wire as per the existing gauge & turn to achieve desired r.p.m and discharge. (iii) Re-install the pump set at its existing position after satisfactory repair and testing at site.Note (i) Replacement of spares if required shall be measured and paid separately.(ii) Machining required to existing shaft (If required) shall be done by the contractor and rate for the same shall be deemed to be included in unit quoted rate of this item.
77S&F in replacement mechanical joints, ISI marked, with and including nut, bolts, washers & rubber gaskets etc. complete suitable for 150 mm bore pipe complete all as specified and directed.
78S&F in replacement mechanical joints, ISI marked, with and including nut, bolts, washers & rubber gaskets etc. complete suitable for 200 mm bore pipe complete all as specified and directed.
79S&F in replacement mechanical joints, ISI marked, with and including nut, bolts, washers & rubber gaskets etc. complete suitable for 250 mm bore pipe complete all as specified and directed.
80Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth for laying of pipes etc. and getting out in Soft / Loose soil, complete all as specified and as directed.
81Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth for laying of pipes etc. and getting out in hard / dense soil, complete all as specified and as directed.
82M&L for Taking out unserviceable / defective open well submersible pump of capacity 3-5 HP, AC single phase, 50 HZ, make any type by disconnecting pipe and electric connections and carrying out to workshop for repair and return back to its original position. Repair works shall be comprising with the following: -(i) Taking out open well submersible pump set with the help of Crane or any other means required at site without damaging the pump or existing structure.(ii) Re-winding of motor complete by replacing existing burnt winding wire as per the existing gauge & turn to achieve desired r.p.m and discharge. (iii) Re-install the pump set at its existing position after satisfactory repair and testing at site.Note (i) Replacement of spares if required shall be measured and paid separately.(ii) Machining required to existing shaft (If required) shall be done by the contractor and rate for the same shall be deemed to be included in unit quoted rate of this item.
83Returning, filling in, including spreading, levelling, watering and well ramming in layers ofsoil not exceeding 25cm thick complete all as specified and as directed.
84Removal of excavated material to a distance not exceeding 50m and depositing where directed at a level not exc 1.5m above the starting point of soil or rocks where directed complete all as specified and as directed by the Engineer - in - Charge.
85M&L for plain cement concrete 1:3:6type C-1, using 20 mm graded stone aggregate for coping of valve pit including use and waste of form work for fair finished surface etc. complete all as specified and directed.
86M&L for PCC (1:4:8) type D-2, using 40 mm graded stone aggregate as floor / paths fencing etc including necessary form work and finishing the surfaces fair and smooth without using extra cement etc. complete all as specified and directed.
87M&L for construction of valve pit chamber of size 1200 x 1200 x 900 mm (internal dimensions) with and including the following provisions, complete all as directed : -(i) 15cm thick PCC 1:4:8 type D-2 (using 40mm size graded stone aggregate) as in foundation concrete.(ii) PCC solid block masonry 200 mm thick using grade C-5 block, built in CM 1:6.(iii)Rendering 15mm thick in CM 1:4 finished the surfaces fair and even.(iv)100mm thick PCC 1:3:6 type C-1 (using 20mm graded stone aggregate) as in coping.(v) 3mm thick MS sheet cover along with MS angle iron frame 40x40x6mm duly embedded in coping concrete including with necessary locking arrangement.(vi)Painting to MS sheet cover and frame with two coats of synthetic enamel paint over a coat of red oxide primer.(Note :- Necessary excavation and earthwork shall also be deemed to be included in quoted rates)
88All as item no. 61 above but of internal dimension 1200 x 1200 x 1000 mm, complete all as specified and directed.
89S & F in replacement MS sheet cover for valve pit made out of 3.15 mm thick MS sheet with handle and locking arrangement, duly painted both sides with synthetic enamel paint over a coat of red oxide primer, complete all as specified and directed.
90M & L for painting of valve pit MS covers on both sides after preparing of old painted surfaces and applying one coat of synthetic enamel paint black in colour complete all as specified and directed.
91S&F in replacement automation valve size 50 mm PN-1.0 suitable for 220 Volts AC, Temp-90 degree centigrade, CF8 type disc, Seat - NBR, BFV type valve, flanged, ISI marked of model-MBF-C-50 of Cair valve automation complete with iron wheel as per site requirement, complete all as specified and directed by Engr-in-charge.
92S&F in replacement Rust Proof, Maintenance free, Magnetic Float switch Sensors for Underground / OH Sumps with following specifications etc complete all as directed Engr-in-charge:-(i). Principle: Magnetic, Magnet: Ferrite Ring(ii). Float and Guide: ABS, Switch: Reed(iii). Reed switch connecting cable: 2 core Teflon cable
93M&L for installation, testing and commissioning of IoT Sensor for OH Tank comprising of Level sensor, IoT transmitter, battery backup and AC power complete all as directed by Engr-in-charge.
94M&L for GSM gateway required for IoT sensor comprising of IoT SIM, wireless transmitter & receiver unit, battery backup and AC adapter complete all as directed by Engr-in-charge.
95S&F in replacement Motor Actuated Butterfly valve, with the following specifications including all accessories as required at site, complete all as specified & as directed.a) Valve size: 50 mm dia.b) Designed line pressure: 4-kg/sq cm.c) Operating Angle: 90 degreesd) Disc Material: C.I. with Nylon coatinge) Limit switches: 02 No\"s. for open and closef) Mounting: Splash proof – Direct on Valve.g) Input Supply: 230V, A.C, 50 Hz
96M&L for cleaning of UG / semi UG sumps by scraping of inner walls of sumps with suitable chemicals & cleaning with wire brush, taking out all dirt, scales etc and applying two coats of white washing on walls after cleaning walls from inside and by using chlorine for disinfection of sump of 2.25 Lakh Glns capacities, complete all as directed by Engr-in-charge.
97All as per item no. 70 above but sumps capacity 320000 Ltrs, complete all as directed by Engr-in-charge.
98All as per item no. 70 above but sumps capacity 240000 Ltrs, complete all as directed by Engr-in-charge.
99All as per item no. 70 above but sumps capacity 150000 Ltrs, complete all as directed by Engr-in-charge.
100All as per item no. 70 above but sumps capacity 100000 Ltrs, complete all as directed by Engr-in-charge.
101All as per item no. 70 above but sumps capacity 50000 Ltrs, complete all as directed by Engr-in-charge.
102All as per item no. 70 above but sumps capacity 5000 Gallons, complete all as directed by Engr-in-charge.
103All as per item no. 70 above but sumps capacity 3000 Gallons, complete all as directed by Engr-in-charge.
104M&L for Cleaning of Overhead Tank by scraping the inner walls of tank with suitable chemicals & cleaning with wire brush, taking out all dirt, scales etc and applying two coats of white washing after cleaning & preparation walls surfaces from inside and applying chlorine for disinfection of 50000 Gallons capacity overhead tanks, complete all as specified and directed by Engr in charge.
105M&L for Cleaning of Overhead Tank by scraping the inner walls of tank with suitable chemicals & cleaning with wire brush, taking out all dirt, scales etc and applying two coats of white washing after cleaning & preparation walls surfaces from inside and applying chlorine for disinfection of 50000 litres capacity overhead tanks, complete all as specified and directed by Engr in charge.
106All as per item no. 79 above but overhead tanks capacity 30000 Ltrs, complete all as directed by Engr-in-charge.
107All as per item no. 79 above but overhead tanks capacity 27500 Ltrs, complete all as directed by Engr-in-charge.
108M&L for cleaning of pump house / sub-station, surrounding area by surface excavation up to 10 cm depth including removing shrubs, grass, mini-plants and other unwanted materials and levelling complete as in soft / loose soil complete all as specified and directed.
109Supply only Bleaching Powder complete as approved Engr-in-charge.
110S&F in repair CI impeller along with lock key suitable for Openwell submersible pumps of capacity 12.5 HP as per existing size and specification complete all as specified and directed.
111S&F in repair CI impeller along with lock key suitable for Openwell submersible pumps of capacity 3 to 5 HP as per existing size and specification complete all as specified and directed.
112S&F in repair Journal / Thrust bearing of same size as existing suitable for Openwell submersible pumps of capacity 12.5 HP complete all as specified and directed
113S&F in repair Journal / Thrust bearing of same size as existing suitable for Openwell submersible pumps of capacity 3-5 HP complete all as specified and directed
114S&F in repair Pump shaft of same size as existing suitable for Openwell submersible pumps of capacity 12.5 HP complete all as specified and directed
115S&F in repair Pump shaft of same size as existing suitable for Openwell submersible pumps of capacity 13-5 HP complete all as specified and directed
116Supply and fix in replacement of 500 litres capacity rotational moulded polyethylene water storage tanks (vertical cylindricalwith closed top) double layered with ISI marked with existing inlet, outlets and provision of washouts, vent pipe etc. complete all as directed by Engr-in-Charge
117Supply and fix in replacement of 1000 litres capacity rotational moulded polyethylene water storage tanks (vertical cylindricalwith closed top) double layered with ISI marked with existing inlet, outlets and provision of washouts, vent pipe etc. complete all as directed by Engr-in-Charge
118Supply and fix in replacement of 2000 litres capacity rotational moulded polyethylene water storage tanks (vertical cylindricalwith closed top) double layered with ISI marked with existing inlet, outlets and provision of washouts, vent pipe etc. complete all as directed by Engr-in-Charge
119Supply only DE or NDE Ball bearing housing of same size as existing suitable for centrifugal pumps of capacity 15HP/10 HP complete all as directed by Engr-in-Charge.
120Supply only DE or NDE Ball bearing housing of same size as existing suitable for centrifugal pumps of capacity 5 HP complete all as directed by Engr-in-Charge.
121Supply only DE or NDE Ball bearing housing of same size as existing suitable for centrifugal pumps of capacity 2 HP complete all as directed by Engr-in-Charge.
122S&F in repairs DE or NDE Ball bearing housing of same size as existing suitable for centrifugal pumps of capacity 15HP/10 HP complete all as directed by Engr-in-Charge.
123S&F in repairs DE or NDE Ball bearing housing of same size as existing suitable for centrifugal pumps of capacity 5 HP complete all as directed by Engr-in-Charge.
124S&F in repairs DE or NDE Ball bearing housing of same size as existing suitable for centrifugal pumps of capacity 2 HP complete all as directed by Engr-in-Charge.
125Supply only CI impeller along with lock key suitable for centrifugal mono-block / split casing pumps as per existing suitable for 15 HP / 10 HP HP motor complete all as specified and directed.
126Supply only CI impeller along with lock key suitable for centrifugal mono-block / split casing pumps as per existing suitable for 5 HP motor complete all as specified and directed.
127Supply only CI impeller along with lock key suitable for centrifugal mono-block / split casing pumps as per existing suitable for 2 HP motor complete all as specified and directed.
128M&L for rubber gasket joints (Tyton joint)and fittings complete all as specified and directed suitablr for thesizes of80 / 100 / 150 / 200 / 250 mm bore complete all as directed by engr in charge.
129S & F in repair ball (float) valves high pressure of brass with epoxy coated brass rod and high density plastic ball, screwed for 15mm bore iron pipe, including replacement of adjacent GI fittings (Like socket, nipple, reducer socket, etc.) where necessary complete all as directed by Engineer-in-charge
130Supply and fixing of MCB SP 2 Amps, C curve 415 volts complete all as specified and as directed
131Supply and fixing of MCB SP 6 to 32 Amps, C curve 415 volts complete all as specified and as directed
132Supply and fixing of MCB TP 16 to 40 Amps, C curve 415 volts complete all as specified and as directed
133Supply and fixing of MCB TPN 16 to 40 Amps, C curve 415 volts complete all as specified and as directed
134S & F in repair ball (float) valves high pressure of brass with epoxy coated brass rod and high density plastic ball, screwed for 25mm bore iron pipe, including replacement of adjacent GI fittings (Like socket, nipple, reducer socket, etc.) where necessary complete all as directed by Engineer-in-charge
135S & F in repair ball (float) valves high pressure of brass with epoxy coated brass rod and high density plastic ball, screwed for 40mm bore iron pipe, including replacement of adjacent GI fittings (Like socket, nipple, reducer socket, etc.) where necessary complete all as directed by Engineer-in-charge
136M&L for cleaning and removing all scale and dirt, etc, from exc. 250 litres but n. exc. 500 litres capacity tanks and from mouths of circulating pipes, etc., including writing date of cleaning on tanks with white / black synthetic enamel paint complete all as specified and directed.
137M&L for cleaning and removing all scale and dirt, etc, from exc. 500 litres but n. exc. 1000 litres capacity tanks and from mouths of circulating pipes, etc., including writing date of cleaning on tanks with white / black synthetic enamel paint complete all as specified and directed.
138M&L for cleaning and removing all scale and dirt, etc, from exc. 1000 litres but n. exc. 2000 litres capacity tanks and from mouths of circulating pipes, etc., including writing date of cleaning on tanks with white / black synthetic enamel paint complete all as specified and directed.
139Supply and fix in replacement tank cover of PVC suitable for tanks of any capacity tanks with locking arrangement device, complete all as directed by Engr-in-charge.Make- Sintex / Ashish or equivalent
140M&L for fabrication, supplying, fixing and commissioning of informatory boards at E/M installation to display the technical details as provided by Engr-in-Charge of various installations made out of 3 mm thick aluminium composite panel (ACP) fully covered with white/green/blue (as directed) Retro reflective sheeting of nikkalite Brand Ultralite (UL) grade with using pressure sensitive adhesive and Retro Reflective cut out border and message in the sensitive adhesive, size of the board of required size to be fixed on wall including proper fixing arrangement complete all as directed by Engr-in-Charge.Note :- (a) Before fabrication of board, the contractor has to produce a paper printout detailing all dimensions and matter to be displayed so as to get it inspected and passed by Engr-in-Charge.(b) Matter to be displayed, colour of the ACP sheet and colour of Retro Reflective sheet shall be as directed by Engr-in-Charge.(c) The quoted rate shall be deemed to be inclusive of cost of the labour and materials required for fixing of the informatory board at the location complete as directed by Engr-in-Charge.
141M&L for printing of informatory self adhesive poster of size not more than 450 mm x 300 mm to display the details as provided by Engr-in-Charge made out of suitable weatherproof material complete all as specified and directedNote :- Before fabriction of the poster, the contractor has to produce a paper printout detailing all dimensions and matter to be displayed so as to get it inspected and passed by Engr-in-Charge.
142S&F in replacement Pressure Booster Pump 1 HP with 24 Ltr Tank Capacity 25x 25mm S/D pipe including with all necesarry fixing arrengement complete all as direcred by Engr-in-Charge. Make : Crompton Model CFCHM2-6C-V24 or equivalent in Havells/ Kirloskar
143Labour only for inspection of fault in panel, starter, motors and replacement of unserviceable electronic parts including taking down and testing complete all as directed by Engr-in -Charge.Note: (i). Spare parts of panel, starter etc. will be measured and paid separately under respective items of BOQ. (ii). The cost of all T&P and TPT required at site shall be deemed to be included in unit quoted rates of this item.
144Supply only Power contactor AC3 rating of 18 Amps Make: L&T MNX18 or equivalent in Legrand/Schneider/ABB, complete all as direcred by Engr-in-Charge.
145Supply only Power contactor AC3 rating of 12 Amps Make: L&T MNX12 or equivalent in Legrand/Schneider/ABB, complete all as direcred by Engr-in-Charge.
146Supply only Power contactor AC3 rating of 9 Amps Make: L&T MNX9 or equivalent in Legrand/Schneider/ABB, complete all as direcred by Engr-in-Charge.
147Supply only Power contactor AC1 rating of 63 Amps Make: L&T MCX12 or equivalent in Legrand/Schneider/ABB, complete all as direcred by Engr-in-Charge.
148Supply only Power contactor AC1 rating of 100 Amps Make: L&T MCX22 or equivalent in Legrand/Schneider/ABB, complete all as direcred by Engr-in-Charge.
149Supply only Power contactor AC1 rating of 200 Amps Make: L&T MCX33 or equivalent in Legrand/Schneider/ABB, complete all as direcred by Engr-in-Charge.
150Supply only Power contactor AC1 rating of 255 Amps Make: L&T MCX34 or equivalent in Legrand/Schneider/ABB, complete all as direcred by Engr-in-Charge.
151Supply only Front Mounting Add-on aux. Contact Block with 2 NO + 2 NC, complete all as direcred by Engr-in-Charge.
152Supply onlySingle phase preventer suitable for existing make and capacity, complete all as direcred by Engr-in-Charge.
153S&F in replacement CI butterfly valve class PN-1.6 with non- magnetic steel spindle ISI marked (IS-780 or latest revision) with flanged ends including necessary mounting nuts, bolts, washers and packing fibre gasket on both ends suitable for 150 mm nominal bore pipe complete all as specified and directed. Make- Kartar/ Sant/ Zoloto/Normex
154S&F in replacement CI butterfly valve class PN-1.6 with non- magnetic steel spindle ISI marked (IS-780 or latest revision) with flanged ends including necessary mounting nuts, bolts, washers and packing fibre gasket on both ends suitable for 100 mm nominal bore pipe complete all as specified and directed. Make- Kartar/ Sant/ Zoloto/Normex
155S&F in replacement CI butterfly valve class PN-1.6 with non- magnetic steel spindle ISI marked (IS-780 or latest revision) with flanged ends including necessary mounting nuts, bolts, washers and packing fibre gasket on both ends suitable for 80 mm nominal bore pipe complete all as specified and directed. Make- Kartar/ Sant/ Zoloto/Normex
156Supply onlyDigital panel volt meter, 3 phase,flush mounting 96x96mm, Accuracy Class-I, input voltage measurement range 17-520V AC (P-P), complete all as directed by Engr-in-charge.
157Supply onlyDigital panel ammeter, 3 phase 5 Amps,Flush Mounting 96x96mm, Accuracy Class-I, CT/PT Site programmable, complete all as directed by Engr-in-charge.
158Supply onlyElectronic Timer160-500V, for 12-120sec, complete all as directed by Engr-in-charge.
159Supply only Thermal overload relay with current range 9 A to 15 A Type MN2 suitable for MNX contactor of L&T make.
160Supply only Thermal overload relay with current range 6 A to 10 A Type MN2 suitable for MNX contactor of L&T make or equivalent, complete all as directed by Engr-in-charge.
161Supply only Thermal overload relay with current range 3 A to 5 A Type MN2 suitable for MNX contactor of L&T make or equivalent, complete all as directed by Engr-in-charge.
162Supply only Phase sequence relay of existing capacity & make complete all as directed by Engr-in-charge.
163Supply only control relay module of existing capacity & make complete all as directed by Engr-in-charge.
164Supply onlyIndicator lamp 3 phase of existing capacity & make complete all as directed by Engr-in-charge.
165Supply onlyON OFF push button of existing capacity & make complete all as directed by Engr-in-charge.
166Supply only selector switch suitable for existing make and capacity of existing capacity & make complete all as directed by Engr-in-charge.
167Supply only control wiring multistranded single core 1.5 sqmm complete all as directed by Engr-in-charge.
168Supply only control wiring multistranded Single core 2.5 sqmm complete all as directed by Engr-in-charge.
169Supply only control wiring multistranded Single core 4 sqmm complete all as directed by Engr-in-charge.
170S&F in replacement DOL starter in existing panel suitable for 1 HP to 5 HP 415 volts as per existingincluding wiring from motor to DOL starter with suitable size copper conductor cable complete all as specified and directed.
171S&F inreplacement in existing panelautomatic star delta starter suitable for 10 to 20 HP415 Voltscomplete all as specified and directed.
172S & F in replacement MCCB 4 Pole, 415 Volts, 63 Amp to 100 Amp, 25 KA Breaking capacity, thermal magnetic release type with Ics = 100% of Icu including suitable size of spreader links on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed.Make : L&T/Legrand/ABB/Siemens
173S & F in replacement MCCB 3 Pole, 415 Volts, 63 Amp to 100 Amp, 25 KA Breaking capacity, thermal magnetic release type with Ics = 100% of Icu including suitable size of spreader links on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed.Make : L&T/Legrand/ABB/Siemens
174S & F in replacement MCCB 3 Pole, 415 Volts, 160 Amp, 25 KA Breaking capacity, thermal magnetic release with Ics = 100% of Icu including suitable size of spreader links on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed.Make : L&T/Legrand/ABB/Siemens
175S & F in replacement MCCB 3 Pole, 415 Volts, 200 Amp, 25 KA Breaking capacity, thermal magnetic release with Ics = 100% of Icu including suitable size of spreader links on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed.Make : L&T/Legrand/ABB/Siemens
176S & F in replacement MCCB 3 Pole, 415 Volts, 250 Amp, 25 KA Breaking capacity, thermal magnetic release with Ics = 100% of Icu including suitable size of spreader links on both side and galvanised or cromium plated high tensile nuts, bolts and washers etc complete all as specified and directed.Make : L&T/Legrand/ABB/Siemens
177S&F in replacement of SMPS in automation panel having input 115/230 VAC, 2.8/1.4A, 47-63 Hz and providing output 24 V DC/ 5 A as per existing make complete all as specified and directed
178M&L for reprogramming of PLC panel as per logic provided by Engr-in-charge complete all as specified and directed
179S&F in replacement armoured copper conductor with 2 core, 2.5 sqmm, 1100 volts grade, PVC insulated, stranded copper conductor cable suitable for control wiring connection with lugs, ferrules etc. complete all as specified and as directed by the Engineer-in-charge
180S&F in replacement armoured copper conductor with 4 core, 1.5 sqmm, 1100 volts grade, PVC insulated, stranded copper conductor cable suitable for control wiring connection with lugs, ferrules etc. complete all as specified and as directed by the Engineer-in-charge
181Supply, laying , testing and commissioningPVC insulated and sheathed flat submersible cable with stranded copper conductor of 1100 volts grade cross sectional area of 6 sqmm 3 core complete all as specified and as directed by the Engineer-in-charge
182S&F in repairPVC insulated, strandedcopper conductor cable 1 core 16 sqmm, 1100 volts grade, including lugs, ferrules etc. complete all as specified and as directed by the Engineer-in-charge
183S&F in repairPVC insulated, strandedcopper conductor cable 1 core 10 sqmm, 1100 volts grade, including lugs, ferrules etc. complete all as specified and as directed by the Engineer-in-charge
184S&F in repairPVC insulated, strandedcopper conductor cable 1 core 50 sqmm, 1100 volts grade, including lugs, ferrules etc. complete all as specified and as directed by the Engineer-in-charge
185S&F in repairPVC insulated, strandedcopper conductor cable 1 core 70 sqmm, 1100 volts grade, including lugs, ferrules etc. complete all as specified and as directed by the Engineer-in-charge
186Supply and laying 77 mm outer dia, double walled corrugated (DWC) HDPE duct pipe conforming to IS-14930 Pt-II with antirodent and non flame propogating properties of approved colour complete with fittings for cable protection complete all as specified and as directed.
187Repairs/ additions / alterations to existing GI pipe line for insertion of branch connection / replacement of rusted fitting / making alteration with and including necessary excavation and earth work in all type of strata and making good to disturbed surface complete all as directed by Engr-in-charge.Note : a) GI Fittings will be paid and measured separately under respective items of BOQ as “Supply only”.b) Cost for excavation/ returning filling/ making good to disturbed surface will be deemed to be included in quoted rate.c) Replacement of fitting at more than 5 locations will be measured as one job.
188Supply only 25mm dia GI elbow, ISI marked, medium grade, complete all as specified and as directed.
189Supply only 40mm dia GI elbow, ISI marked, medium grade, complete all as specified and as directed.
190Supply only 50mm dia GI elbow, ISI marked, medium grade, complete all as specified and as directed.
191Supply only 80mm dia GI elbow, ISI marked, medium grade, complete all as specified and as directed.
192Supply only 25mm dia GI Tee, ISI marked, medium grade, complete all as specified and as directed.
193Supply only 40mm dia GI Tee, ISI marked, medium grade, complete all as specified and as directed.
194Supply only 50mm dia GI Tee, ISI marked, medium grade, complete all as specified and as directed.
195Supply only 80mm dia GI Tee, ISI marked, medium grade, complete all as specified and as directed.
196Supply only 25mm dia GI union, ISI marked, medium grade, complete all as specified and as directed.
197Supply only 40mm dia GI union, ISI marked, medium grade, complete all as specified and as directed.
198Supply only 50mm dia GI union, ISI marked, medium grade, complete all as specified and as directed.
199Supply only 80mm dia GI union, ISI marked, medium grade, complete all as specified and as directed.
200Supply only 25mm dia GI socket, ISI marked, medium grade, complete all as specified and as directed.
201Supply only 40mm dia GI socket, ISI marked, medium grade, complete all as specified and as directed.
202Supply only 50mm dia GI socket, ISI marked, medium grade, complete all as specified and as directed.
203Supply only 80mm dia GI socket, ISI marked, medium grade, complete all as specified and as directed.
204S&F in repair Air release valve 50 mm dia, CI body with single air outlet confirming to IS-14845 complete all as specified and directed.
205S&F in replacement CI/DI specials such as bends sockets tee\"s for spigot and socketed pipes upto 250mm dia bore complete all as specified and directed.
206M & L for painting of external surface of semi underground sump of max cap 2.25 Lakh Gallon capacity with one coat of acrylic water based exterior grade primer @ 0.9 litre (undiluted)/ 10sqm diluted with water in 1:1 ratio,applied with fully automatic airless spray machine and allow 6-8 hours to dry the surface for painting of subsequent coats complete and after that used water based premium acrylic smooth exterior emulsion of approved color with silicon additive excellent dirt pickup resistance with low VOC less than 50, antifungal / anti algae properties in two coats @ 1.79 liter (undiluted) / 10 Sqm diluted with water as per manufacturer\"s instruction applied over primed surface with fully automatic airless spray machine of paint application with a flow speed of minimum 1 liter per minutehaving a pressure of 3300 PSI. Allow 6-8 hrs to dry the surface in between 1st and subsequent coats of paint complete all as specified and directed.Make: Nerolac Excel Top guard / Asian Paints Ultima Protek / Berger weather coat long life10
207Opening the pump part by part without damaging any other parts, descaling and cleaning of all parts for inspection and finding serviceability / unserviceability of the parts & Carefully assembling of pumps by using existing serviceable parts including replacement of gasket packings, greasing etc and replacement of unserviceable parts as directed, installed at Pump House No 1, Make Kirloskar, 15 HP/ 10 HP capacity, complete all as directed by Engr-in-Charge.Note : (i) Spare parts required for replacement shall be measured and paid separately under respective items of BOQ as “supply only”.(ii) Decoupling carefully of pumps from electric motor, taking out from foundation & transporting pump body to workshop for necessary machining works & re-installing the pump to its original position shall be measured & paid for separately.(iii)A job to be completed within 8 hrs from time of assignment to avoid interruption of Essential service on account of breakdown else contractor is liable for penalty as decided by Accepting Officer.
208All as per item no 181 above but capacity of pump 5 HP, Make- Kirloskar, installed at Pump house no 2 , complete all as directed by Engr-in-Charge.
209All as per item no 181 above but capacity of pump 2 HP, Make- Kirloskar, installed at CMDC, complete all as directed by Engr-in-Charge.
210Supply only Pump shaft of same size as existing suitable for centrifugal pumps of capacity 15HP/10 HP complete all as directed by Engr-in-Charge.
211Supply only Pump shaft of same size as existing suitable for centrifugal pumps of capacity 5 HP complete all as directed by Engr-in-Charge.
212Supply only Pump shaft of same size as existing suitable for centrifugal pumps of capacity 2 HP complete all as directed by Engr-in-Charge.
213S&F Polytetrafluoroethylene (PTFE) (Teflon) gland packing 8-12mm suitable for any size of pumps complete all as directed by Engr-in-Charge.
214S&F Split Gland cover for pump sets of same size as existing suitable for centrifugal pumps for diameter upto 12.5 mm complete all as directed by Engr-in-Charge
215S&F in repair complete set of pump gasket fitting of suitable size complete all as directed by Engr-in-Charge
216S&F in repair Tyre coupling of same size as existing suitable for centrifugal pumps of capacity 15HP/10 HP complete all as directed by Engr-in-Charge
217Dismantling of existing unserviceable 10/15 HP motor centrifugal pump set from foundation and M&L for painting by synthetic enamelled paint, one coat, after cleaning and preparing surface for painting, reinstalling and testing complete at site on full load complete all as directed by Engr-in-Charge.
218Dismantling of existing unserviceable 5 HP motor centrifugal pump set from foundation and M&L for painting by synthetic enamelled paint, one coat, after cleaning and preparing surface for painting, reinstalling and testing complete at site on full load complete all as directed by Engr-in-Charge.
219Dismantling of existing unserviceable 2 HP motor centrifugal pump set from foundation and M&L for painting by synthetic enamelled paint, one coat, after cleaning and preparing surface for painting, reinstalling and testing complete at site on full load complete all as directed by Engr-in-Charge.
220Dismantling carefully all water connections, decoupling of pumps/ motor from electric motor, taking out from foundation & transporting pump body & motor to workshop for necessary machining works as directed & required at site and re-installing the pump after rectification to its original position and commissioning etc. complete all as directed by Engr-in-Charge
221M&L for repair & rewinding of electric induction motor of Centrifugal Pump set by using supper enamelled copper wire (Class -F) as per existing gauge heating and varnishing etc. complete. The electric motor of 3 phase, 415 Volt AC induction type of any make, the repair work involves taking out burnt winding coil from stator, cleaning of slots thoroughly, removing all dirt, grease and other unwanted particle etc. of motor 15 HP capacity complete all as directed by Engineer-in-charge.Note:(i) Unit rate shall be deemed to be included the cost of taking out motor from its position, shifting of motor from pump house to workshop, getting back to pump house after rectification, re-installing at site, connecting up, couple with the pump and testing etc. complete
222M&L for repair & rewinding of electric induction motor of Centrifugal Pump set by using supper enamelled copper wire (Class -F) as per existing gauge heating and varnishing etc. complete. The electric motor of 3 phase, 415 Volt AC induction type of any make, the repair work involves taking out burnt winding coil from stator, cleaning of slots thoroughly, removing all dirt, grease and other unwanted particle etc. of motor 10 HP capacity complete all as directed by Engineer-in-charge.Note:(i) Unit rate shall be deemed to be included the cost of taking out motor from its position, shifting of motor from pump house to workshop, getting back to pump house after rectification, re-installing at site, connecting up, couple with the pump and testing etc. complete
223M&L for repair & rewinding of electric induction motor of Centrifugal Pump set by using supper enamelled copper wire (Class -F) as per existing gauge heating and varnishing etc. complete. The electric motor of 3 phase, 415 Volt AC induction type of any make, the repair work involves taking out burnt winding coil from stator, cleaning of slots thoroughly, removing all dirt, grease and other unwanted particle etc. of motor 5 HP capacity complete all as directed by Engineer-in-charge.Note:(i) Unit rate shall be deemed to be included the cost of taking out motor from its position, shifting of motor from pump house to workshop, getting back to pump house after rectification, re-installing at site, connecting up, couple with the pump and testing etc. complete
224M&L for repair & rewinding of electric induction motor of Centrifugal Pump set by using supper enamelled copper wire (Class -F) as per existing gauge heating and varnishing etc. complete. The electric motor of 3 phase, 415 Volt AC induction type of any make, the repair work involves taking out burnt winding coil from stator, cleaning of slots thoroughly, removing all dirt, grease and other unwanted particle etc. of motor 2 HP capacity complete all as directed by Engineer-in-charge.Note:(i) Unit rate shall be deemed to be included the cost of taking out motor from its position, shifting of motor from pump house to workshop, getting back to pump house after rectification, re-installing at site, connecting up, couple with the pump and testing etc. complete
225S&F in repair Air release valve 50 mm dia, CI body with single air outlet confirming to IS-14845 complete all as specified and directed.
226M&L for maintenance free grounding Solution set earthing comprising of 17.2 mmpure copper earthing rod, 3m long, Copper terminal size of 40x6mm with 2 Nos M8 holes for termination. Electrode must be tested for a short circuit test of minimum 40 KA at CPRI/NABL. The earthing electrode will be placed in the ground after a bore is drilled to the depth of 3.5 Mtr. The bore drilling will be donewith the help of a Pneumatic boring machine, 50 Kgs BFC will be placed in the bore to cover the earthing rod from all sides. BFC will be poured in Slurry form in a properly mixed condition. The Earth pit cover Square 300x300x240 mm to be provided to cover the Earth Pit and shall be made of reinforced FRP and should be capable of carrying the weight of 5 Tons, complete all as directed by Engr-in-charge. Make : \"U-PROTEC\"earthingPvt Ltd or equivalent in Ashlok safe earthings electrode Ltd / JEF technology NOTE :- (a) Rates of boring 3.5 Mtr for earth electrode, copper strip 25x3 mm upto 7.5 m from earth electrode for each earthing will be deemed to be included in the quoted rate. (b)On testing, after completion, if the earth resistance <5 ohms is not obtained, earthing will be rejuvenated at no extra cost till the desired earth resistance not obtained
227M&L for collection of Drinking Water\"s sample from various point (user end point) periodically or as and when directed, by followed the standard procedure of sample collection and including transportation of samples safely from site to Govt Approved Lab for carrying out Water Testing for Chemical & Biological Analysis and submit the report within stipulated time period, complete all as specified and directed.

Other Detail

Information Source https://defproc.gov.in/nicgep/app
Download FileName File Description File Size
Download cd6a62a2-fa39-4436-a7b1-7cece34bf344.html Tender Documents 0 KB
Download 8759TD.pdf Tender Documents 0 KB
Download BOQ_840451.xls Tender Documents 0 KB
Download Tendernotice_1.pdf Tender Documents 0 KB
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.