| 1 | Design, fabrication, supply of Type Tested LT panel in 2RD substation in compliance with IEC 61439 Part 1 & 2.The details of the LT panel is as given below. Please refer technical specification for complete details.1.Busbar: TPN Al.2.Incomer Breaker: ACB: 2000A, 4-pole, 50kA, electrically operated, draw-out type with µp based LSIG protection – 1 No.3.Incomer Bus duct: 2500A, TPN, Al. (5 mtr aprrox.)4.Outgoing Breakersa)MCCB: 400A,4-pole, 36kA, thermal-magnet overload type – 2 Nosb)MCCB: 630A,4-pole, 36kA, thermal-magnet overload type – 3 Nosc)MCCB: 250A,4-pole, 36kA, thermal-magnet overload type – 1 Nod)MCCB: 100A,4-pole, 25kA, thermal-magnet overload type – 1 Noe)ACB: 2000A, 4-pole, 50kA, electrical operation, draw-out type with µp based LSIG protection – 1 Nof)ACB: 1600A, 4-pole, 50kA, electrical operation, draw-out type with µp based LSIG protection – 1 Nog)ACB: 1250A, 4-pole, 50kA, electrical operation, draw-out type with µp based LSIG protection – 2 Nosh)ACB: 800A, 4-pole, 50kA, electrical operation, draw-out type with µp based LSIG protection – 1 No5.Metering & Indicationsa)RYB indication on incomerb)ON/OFF/TRIP indication on incomer and alloutgoingsc)RS485 enabled Multifunction (V, A, f, kW, kWh) meters on incoming and all outgoings. |