| 1 | SITC of water protected outdoor hut type compartmentalized double door cubical panel of front surface area as mentioned with 400mm depth size suitable for 415 Volt, 3 phases, 50 Hz made out of 2 mm thick CRCA sheet with required hardware duly painted with powder coated. The panel having 500/415V 4 strip aluminum bus bar duly PVC sleeved, connection inter–connection with required current carrying capacity bus bars with switchgears, separate detachable gland plate, including angle iron base frame made out of 65mmx65mmx6mm angle iron of suitable size of the panel with legs 600 mm long, hinged door, with locking arrangement for inside/outside separately, earth bar/stud, i/c grouting the legs in 1:3:6 cement concrete foundation complete as required with following instruments mounted on it. (Panel should beas per design &drawing approved by Engg in charge) Instruments(Inside/outside)i) 0-500 Volts, Digital voltmeter of size 96Sqmmx96 sqmm flush mounting type with Selector switch-01 Setii ) 0-500 Amps, Direct Digital Ammeter of size 96Sqmmx96sqmm flush mounting type with CTs coiliii) Selector Switchesiv)LED Pilot light (22.5 MM dia) with03 Nos with 6 amp MCB on door closurev) Holder with switch |
| 2 | SITC of water protected outdoor hut type compartmentalized double door cubical panel of panel of front surface area as mentioned with 400mm depth size suitable for 415 Volt, 3 phases, 50 Hz made out of 2 mm thick CRCA sheet with required hardware duly painted with powder coated. The panel having 300A/415V 4 strip aluminum bus bar duly PVC sleeved, connection inter–connection with required current carrying capacity bus bars with switchgears, separate detachable gland plate, including angle iron base frame made out of 50mmx50mmx5mm angle iron of suitable size of the panel with legs 600 mm long, hinged door, with locking arrangement for inside/outside separately, earth bar/stud, i/c grouting the legs in 1:3:6 cement concrete foundation complete as required with following instruments mounted on it. (Panel should beas per design &drawing approved by Engg in charge) Instruments(Inside/outside) (Three or More Panel Box) i) 0-500 Volts, Digital voltmeter of size 96Sqmmx96 sqmm flush mounting type with Selector switch-01 Setii ) 0-300 Amps, Direct Digital Ammeter of size 96Sqmmx96sqmm flush mounting type with CTs coiliii) Selector Switchesiv)LED Pilot light (22.5 MM dia) with03 Nos with 6 amp MCB on door closurev) Holder with switch |
| 3 | Providing and fixing following rating and breakingcapacity and pole MCCB with thermomagneticrelease and terminal spreaders in existing cubiclepanel board including drilling holes in cubicle panel,making connections, Ics=100% Icu and OperationalVoltage 690V etc. as required. A) 400 A, 35 KA,TPMCCB |
| 4 | B) 250 A, 25 KA,TPMCCB |
| 5 | C) 200 A, 25 KA,TPMCCB |
| 6 | D) 125 A, 16 KA,TPMCCB |
| 7 | E) 100 A, 16 KA,TPMCCB |
| 8 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 9 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 10 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 11 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. A)3½ X 240 sq. mm (62mm) |
| 12 | B) 3½ X 185 sq. mm (57mm) |
| 13 | C) 3½ X 120 sq. mm (45mm) |
| 14 | D) 3½ X 150 sq. mm (45mm) |
| 15 | E) 3½ X 35 sq. mm (32mm) |
| 16 | F) 3½ X 70 sq. mm (38mm) |
| 17 | Providing and fixing of 315 A, 4 Pole On load Changeover with spreaders link in existing cubicle panel including drilling holes in cubicle panel, making connections, etc. as required. cat no.IS04 (Havells) or equivalent specification Standard/ Havells/ Siemens/ HPL/ Socomec/HPL |