| 1 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm |
| 2 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 4 sq. mm |
| 3 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 6 sq. mm |
| 4 | Supplying and fixing following piano type switch / socket on the existing switch box/ cover including connections etc. as required.5/6 amps switch |
| 5 | Supplying and fixing following piano type switch / socket on the existing switch box/ cover including connections etc. as required.3 pin 5/6 amp socket outlet |
| 6 | Supplying and fixing following piano type switch/socket on the existing switch box/ cover including connections etc. as required.a) 6 pin 15/16 A Socket |
| 7 | Supplying and fixing following piano type switch/socket on the existing switch box/ cover including connections etc. as requiredb) 15/16 A Switch |
| 8 | Supplying and fixing metal box of 150mm X 75mm X 60mm deep (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including providing and fixing 3 pin 5/6 A socket outlet and 5/6 A piano type switch, connections, painting etc. as required. |
| 9 | Supplying and fixing metal box of 180mm X 100mm X 60mm deep (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including providing and fixing 6 pin 5/6 & 15/16 A socket outlet and 15/16 A piano type switch, connections, painting etc. as required. |
| 10 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, & Ccurve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole |
| 11 | Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps |
| 12 | Brush Less Direct Current (BLDC) Motor Supply, Installation, Testing and Commissioning ofceiling fan with Brush LessDirectCurrent(BLDC)Motor,classofinsulation: B,3nos.metal( Aluminum alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%,suitable for operation withregulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Ceiling Fan compliant to IS 374:2019fan Supply,earthing etc. complete as req.1200mm,service value≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) |
| 13 | Rewinding of AC ceiling fan of all sizes andmake including oiling, greasing as required New Model (Light Weight) |
| 14 | Replacement of ball bearing of size 117/120 NBC equivalent SKF make as required. |
| 15 | Replacement of fan condenser 2.5 mfd as required. |
| 16 | Supplying and fixing extra conduit down rod of 20 cm length G.I. pipe 15 mm dia, heavy gauge including painting etc. as required. (Note : More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored) |
| 17 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required |
| 18 | Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required. |
| 19 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.Upto 35 sq. mm (clammped with 1mm thick saddle). |
| 20 | Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit along with 1 No 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 21 | Installation of exhaust fan in the existing opening, including making good the damage connection testing, commissioning etc. as required.Upto 450 mm sweep |
| 22 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with piano type switch, phenolic laminated sheet, suitable size M.S. box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required.Group C |
| 23 | Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required.Group C |
| 24 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required. 25 mm |
| 25 | Supply of XLPE insulated PVC sheathed Al. Conductor Armoured Cable 1.1KV grade conforming to IS-7098 of following size:-2C*10 sqmm |
| 26 | Supply of 250 mm (10 inch) sweep 1250 rpm exhaust fan Fresh Air Type complete with shutter blades etc. as required. |
| 27 | P/FHot press sheet mouldedcompound (SMC) fire retardant (Temp. resistance up to 200 C), IP 55 weather proof polebox of innerdimension 200x160x98mm (NS) complete with suitable arrangement for fixing of 2 nosof 6 to 32 amp single pole MCB & 63 Amp. Doublepole isolator (MCB/Isolator excluded) withneutral link duly shorting on DIN Channel with2 Nos of MS clamps with SS back plateof suitable size with danger monogram property printed on the coveretc asreqd. as reqd. |
| 28 | LED FloodLight, powdercoatedpressurediecastaluminum(Systemlumen efficacy ≥120 and <135lm/Watt). Supplying,installation,Testing&CommissioningofFloodLight,powdercoatedpressuredie cast aluminum body with built in or separate driver as per the requirement with Driver efficiency >85%,Input voltage: Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -15 degto 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2 , P. F.≥0.95,IP-66,IK-10,CRI>80,undervoltageandovervoltageprotection, EMI-EMCasper CISPR-15,lenses for beam angle 30 deg 120deg as per the application and the project requirement deg, suitable tilt able fitting, life time (LED,Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumenmaintained tilllife ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K/ 5700°K/6000°K/6500°K(AsperANSIBin),SDCM(Standard Deviation Color Matching) <5,Maximumpowerconsumptionshouldnotmore than the specified rating and Fixture shall be ofrelevant BIS standard completein allrespecti/cconnectionswith1.5sqmmFRLS,PVCinsulatedcopper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty.System lumen efficacy≥120 and <135lm/Watt output . LM79 & LM80 Test reportfromNABLlab foralltestingrequiredforLED fixtures as per BISshall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermalmanagement:heatsinkofaluminumhousing such that LED junction temperature shall not rise above 90°C).100 watt |
| 29 | LED Batten light (System lumen efficacy ≥105 <120 lm/Watt) Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body materialand construction as per IS : 10322 withdriver (Replaceable)as per the requirement with Driver efficiency.>85% ,Operating voltage AC140-270 Volt,freq 50/60 hz, Operating temp range -15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20,CRI>80, Flicker free, (flickershould be below 5 %), life time (LED,Driver & electrical circuitary), ofminimum 50000BurningHourswith,70%ofinitial Lumenmaintained tilllife ends, CCT3000°K/ 4000°K / 5700°K/6000°K/6500°K(AsperANSIBin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BISstandard andtrade markcertificate(T.C.).Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. completeinallrespecti/cconnectionswith1.5sqmmFRLS,PVCinsulatedcopper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty.System lumen efficacy≥105 <120lm/Watt output . LM79 & LM80 Test reportfromNABLlab foralltestingrequiredforLED fixtures as per BISshall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermalmanagement:heatsinkofaluminumhousing such that LED junction temperature shall not rise above 90°C).CRCA Sheet Body (Thickness ≥ 0.50 mm)18- 22 watt |
| 30 | Supply , Installation, Testing and Commissioning of Air Cooled Hi Wall split type Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cellelastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU),copper power cable upto 3.5 Mtr (IDU to ODU) i/c drain pipe R-32/R-410/ R407 Green Refrigerant, wireless Remote control, suitable for working between 180-260V with low & high voltage cutoff and 50 hz ,1 phase ACsupply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. The system shall be able to deliver 100% of the rated capacity upto 42 Degree Celsius. Min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB). Must comply : Electrical cable IS 694 or IS:9968 temperature sensing control IS /International Electro technical Commission (IEC) 60730, hermetic compressor IS 10617, heat exchanger IS 11329, capacitor IS 2993 and motor IS 12615. Complete as per CPWD specification and IS : 1391 Part II 2023. The system shall be able to operate up to 50 0C (out door ambient temperature).Inverter Type - Cooling only,1.5 TR with 5 Star BEE Rating |
| 31 | S/I/T/C of stand for split AC |
| 32 | S/I/T/C of drain pipe |
| 33 | S/I/T/C of 4 KVA Voltage Stabilizer having input voltage 150V-270V and output voltage 195-245V |
| 34 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.250Amp, 36 KA, FPMCCB |
| 35 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.100Amp, 30 KA, FPMCCB |
| 36 | Supplying and fixing 20 amps, 240 volts, SPN industrial type, socket outlet, with 2 pole and earth,metal enclosed plug top along with 20 amps "C" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. asrequired |
| 37 | SITC of 4MP varifocal lens Bullet IP Camera with following specifications:-Image Sensor: 1/3 4MP CMOSMinimum Illumination: 0.05 lux color, 0 lux with IR or better **Shutter Speed:1/3 – 1/100,000 sFrame Rate: 20 fps or better **Lens: 3.6 to 10mm Varifocal lensVideo Compression: H.265 or better **S/N Ratio: >45dBResolution: (2650x1440) or better **Protocol: should comply to IPv4/v6, TCP/IP, HTTP, HTTPS, FTP, PPPoE,DDNS, IEEE802.1XIR Range: Minimum:30mOperating Temperature: -20 to 55 deg CentWeatherproof Standard: IP66 or better **Safety standard: UL |
| 38 | SITC of 16 channel NVR with the following specifications:Camera resolution:upto8MPInterface: 1 HDMI, 1VGA minimumCompression :H.265or betterNetwork Throughput :80Mbps or better**USB Port: 2 USB port (USB2.0)minimumHard disk interface: 1 SATA port suitable for 6TB eachProtocol: IPv4/v6, TCP/IP, HTTP, HTTPS, FTP, PPPoE,DDNSOperating temp: -10 to 55 deg CentSafety standard: UL |
| 39 | SITC of 6 TB surveillance HDD |
| 40 | SITC of 8 port Giga PoE switch, 8(PoE 10/100) + 2(10/100) port long distance switch |
| 41 | SITC of following rack capacity with glass front door, steel rear door, power supply, MCB, cable manager, drawer shelves and wiring channels to accommodate CCTV systems equipment and complete with accessories as reqd.8 U |
| 42 | S/I/T/C offull HD LED Monitor,32INCHES complying with the following specifications:Resolution : Full HD : 1920 x 1080 or betterBacklight : LEDBrightness : 300 NITS min.Contrast : 1200 : 1 or betterPower supply : 230v + / - 10%, 50 Hz at sitewith connections andalong with all accessories etc.complete as required. |
| 43 | Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required. 1 run of cable |
| 44 | 2 run of cable |
| 45 | SITCIP65 box(without PoE switches)of dimention 310mmX160mmX140 mm onpole or wall with suitable arrangement for support/installation of 8 port Giga PoE switch and 1 nos. 15/16 amp modular switch socket set |
| 46 | Providing and fixing of 4.5 KG CO2 type fire extinguisher sqeeze grip type, trolly wheel as well mounting type complete in all respect with ISI mark i/c fixing arrangement etc as required. |
| 47 | Providing and fixing ABC (Aluminium Phosphate) power type fire extinguisher of 6kgs capacity complete in all respect with isi mark i/c fixing arrangement etc as required. |
| 48 | Supplying AND Installation of Reverse Osmosis (RO) water purifier of capacity 50 ltr/hr complete as required. |
| 49 | Supplying and fixing of full stainless steel body self-contained drinking water cooler with cooling capacity 150ltr per hr, storage capacity 150ltr and suitable for 230V supply as required. |