Tender For creation of 63Kv For Astan Mohalla Khulora Under Cdf Grants Of Hmla Dh Pora 2025-26.- 1 Creation of 63 KVA Sub-stations along with HTLT network 2 Supply, Installation, Testing and commissioning of 63 kVA,11/0.433KV, 3-phase Distribution Transformers (level-II) with Bimetallic Terminal connrction and with LV Cable box having detachable Aluminium Gland Plate. Transformer should be arranged for vertical takeoff. 3 Supply,erection, testing and commissioning of S.T Pole 9mtr Long SP-33 with base plate & cap for HT. Strictly as per REC standards 4 Supply,erection, testing and commissioning of S.T Pole 8mtr Long SP-15 with base plate & cap for LT. Strictly as per REC standards 5 Supply, laying, strininging and commissiong of ACSR 30mmsq (Weasel) Conductor 6 Supply, laying, strininging and commissiong of ACSR 50mmsq (Rabbit) Conductor 7 Providing & fixing of GI Channel/Angle/Flat of sizes including clamps 8 Supplying and erection of GI V cross-arm with top Bracket including clamp(2 Nos) 9 Supplying and fixing of Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip as per REC standards. 10 Painting of poles with one coat of red oxide and two coats of Aluminium paint as per Standards. This also includes numbering of ploes with paint, submission of Pre and Post Execution photographs duly anthenticated by AEE concrened. 11 Supply,fixing, testing & commissioning of 11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type as per IS Standards 12 Supply,fixing, testing & commissioning of 11 kV Horn Gap Fuse Set 3 Phase 200A as per IS Standards 13 Supply,fixing, testing & commissioning of 11 kV Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type as per IS Standards 14 Providing and fixing of anticlimbing device complete with GI Barbed wire and clamps 15 Supply,fixing, testing & commissioning of 11 KV Pin Insulators (polymer/porcelain) with Pins(5KN) 16 Suppy, fixing and testing of 11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm 17 Providing & fixing of LT Shackle Insulator with GI mukey clamps including nuts & bolts 18 Cement bottoming 1:2:4 mix as per REC Standards 0.5cum/pole including muffing of pole. 19 Cement bottoming 1:2:4 mix as per REC Standards 0.45cum/pole including muffing of poles. 20 Providing & fixing of Sundry items like aluminium lugs, Jumpers, binding Tape etc 21 Supply, laying of 185 mmsq Single Core XLPE, FRLS unaroumed Cable 22 Supplying and fixing of Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover. 23 Providing, Fixing of GI nuts and bolts for fixing of x-arms and other accessories. 24 Providing and fixing of suitable LT Fuse Set as per the approved drawings of KPDCL. 25 Providing and fixing of suitable sign board (600x450 mm) fabricated out of sheet steel with suitable angle stand indicating name of work , Estimated cost ,DOS and DOC written with white paint on dark blue background 26 Providing and fixing of danger plate with clamps. Please Enable Macros to View BoQ information