Tender For Provision Of Fire Fighting System Of Phase-Ii Of Wsa At Afs Phalodi; 1 Supply and fix for testing & Commission of Flame Proof Mocro processer with Digital display fire control Panel complying BSEN 54 with 2 loop Panel of capacity for 99 Detector & 99 Module upto 200 detector & modules fitting with autoatic battery charger including Maint free battery, including lamp with all connected accessoriescomplete all as specified and as directed. 2 Supply and fix for Detector Complying with & type cetified to EN-45 Addressable type multisensor detector with heat and smoke combination /Optica with base with self built intelligence as per IS: 11360 complete all as specifiedand as directed. 3 Supply and fix for including Testing, Commmessioning of Explosive proof Manual call point resettable type including addresseble control module complete all as specified and as directed. 4 Supply and fix for Fire Alarm Sounders/ sirens Electronic type horizontal single stage continous normal operation for atlast 50 minutes with sound level 65 DB to 120 DB measured at 1.5 Mtr with sound out put variation of + 5 DB upto 500 mtr range complete all as specified. 5 Supply and fix for Fire Alarm Sounders/ sirens Electronic type horizontal single stage continous normal operation for atlast 50 minutes with sound level 65 DB to 120 DB measured at 1.5 Mtr with sound out put variation of +5 DB upto 3500 mtr range complete all as specified.. 6 Supply and fix for testing and commissioning of addressable response indicators having flashing green LED and Red LED for indication of fire and continuous monitoring including necessary connection to pin point loaction of fire complete all as specified 7 M & L for point wiring for smoke detector using approved colour coding as per IS with mutistranded FRLSH copper conductor of size 1.5 sqmm single core PVC insulated & unsheathed cable in & including ERW Conduit heavy duty, ISI Marked including fitting MS junction boxes & accessories including one run of FRLSH single core cable of size 1.5 sqmm unsheathed stranded copper conductor cable green in colour for earth continuity conductor & connected to common earth dolly all as per requirment of manufacture complete all as specified and as directed. 8 M&Lfor surface fiame proof Sub main wiring with two runs of 4 Sqmm single core PVC insulated unsheathed multistranded with copper conductor cable, 1100 Volts FRLSH grade ISI marked drawn through in and including ERW steel conduit with flame proof accessories and including two runs of FRLSH PVC insulated single core cabłe unsheathed stranded copper conductor cable green in colour for earth continuity conductor for 3 phase Power socket combination complete all as specified and directedNote:- Two runs single core cable and one run single core cable of earth wire and one run of ERW steel conduit pipe shall be measured as one length. 9 Excavation in trenches not exc 1.5 M wide and not exc 1.5 M in depth for laying of DI/Gl pipe line, UG cables in soft / loose soil getting out and levelling of bottom surface to required level complete all as specified and as directed 10 Retuming flling in, including spreading, leveling, watering and well ramming in layers not exc 25 Cm thick soft / loose soil complete al as specified and as directed. 11 Removing excavated material (Soil) from site to a distance not exc 50 M away and depositing where directed at a level not exc 1.5mtr above the starting point all complete all as specified and as directed. 12 M&L for Boring of holes under road, pavement, hard standing by trenchless technology using uitra sound technique and necessary machine including HDPE pipe of 150 mm dia suitable for 04 mpa working pressure for cable protection and making good as existing compiete all as specified and as directed 13 Supply and lay for double wall corrugated (DWC) high density polythene pipes having corrugation on fhe outer wall and plain surface on the inner wall Confirming to ISI 14930 (Part I and II) for protection of underground cables of size nominal outer dia 90 mm & nominal inner dia 76 mm dia with all fittngs laid in trenches road/ nallah or fixed alorig wail for cable protectioncomplete all as specified and as directed. 14 Supply, laying, testing and commissioning cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, elecric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 50 Sqmm 3.5 core complete all as specified and directed.Note:-(i) Cable may be laid in trenches, under road, across the Nallah, along poles/walls and ducts etc.(ii) The Rate of Excavation, earthwork, sand cushioning, cable cover, pipe for cable protection deemed to be included in unit quoted rate. 15 Supply and laying for gaivanised iron tubing 100 mm bore medium grade with and inciuding all fittings such as bends, elbows, tees, short pieces union etc laid on wall, PCC pedestal complete all as specified and as directed. 16 Supply and laying for gaivanised iron tubing 80 mm bore medium grade with and inciuding all fittings such as bends, elbows, tees, short pieces union etc laid on wall, PCC pedestal complete all as specified and as directed. 17 Supply and laying for gaivanised iron tubing 20 mm bore medium grade with and inciuding all fittings such as bends, elbows, tees, short pieces union etc laid on wall, PCC pedestal complete all as specified and as directed. 18 Supply, Laying, jointing & testing of Ductile iron (D) of size 100 mm dia, pressure pipe with flaged joints, centrifugally cast, class K.9, with cement mortar lining in inner side as per IS 8329/ 2000 (latest revision) and other relevant standards and metalic zinc coating followed by a finishing layer of epoxy paint in outer side including rubber gasket and suitable bolts and nuts washers etc in any length with inside cerment mortar lining laid in trenches/ over masonry pillar complete all as specifiedand as directed. 19 M&L for Ductile iron fitting for spigot socket pipe such as bends (any type, radius and angle) tapers any type (straight bend increasing, decreasing or double socket etc) Tee pieces single branch Y junction, double branch, cross (All socket or socket and Spigot) collars, restrained joint, mechanical joint, caps & plugs 80 mmn to 250 mm dia bore including cutting and jointing old/ new posıtions as specified and directed.Note - 1. Before laying of pipe line contractor has to submit layout diagram as per level difference and ensure proper alignment of the pipe.2. While laying the DI pipe cutting is required for inserting the new tee branches, bends etc deemed to be included in quoted rate3. Di specials shall be measured and paid seperately 20 Supply and fixing for Cast iron foot valve of 100 mm dia, confirming IS 4038, Installation, testing of foliowing sizes complete all asspecified and directed. 21 Supply and fixing for Cast iron foot valve of 80 mm dia, confirming IS 4038, Installation, testing of foliowing sizes complete all asspecified and directed. 22 Supply and fixing for Cast iron sluice valve with stainless steel spindle and cast iron hand wheel complying with IS 14846-2000, class PN 1.6 both ends flanged with 2 Nos rubber insertion gasket joints, nuts bolts & washers of required size & Nos of the size 10mm dia complete all as specified and as directed 23 Supply and Fixing for Cast iron body and brass gate heavy duty non return valve of 100 mm diawith by-pass arrangements, 1S-5312, 1SI marked (NRV) both ends flanged with 2 Nos rutber insertion gasket joints, nuts, bolts & washers of required size & Nos complete all as specified and as directed. 24 Supply and Fixing for Cast iron body and brass gate heavy duty non return valve of 80 mm diawith by-pass arrangements, 1S-5312, 1SI marked (NRV) both ends flanged with 2 Nos rutber insertion gasket joints, nuts, bolts & washers of required size & Nos complete all as specified and as directed. 25 Supply & Fixing for Butterty Valve of 100 mm dia, ISI marked, onfirming IS 13095 2020 complete all as specified and as directed. 26 Supply & Fixing for Butterty Valve of 80 mm dia, ISI marked, onfirming IS 13095 2020 complete all as specified and as directed. 27 Supply and fix for Gun metal gate valve with iron wheel head screwed both ends marked fixed to Gl pipe of size 20 mm dia complete all as specified and as directed. 28 Supply and fix for Yard hydrant Post / Stand Post 80mm Die GI/MS both flanged type 1.5m Height complete all as specified and as directed. 29 Supply and fix for Hydrant valve single headed of size 63 mm dia complete all as specified and as directed. 30 M & L for Branch pipe gun metal 63 mm dia instantaneous inlet, made threadedoutlet, 12.5 mm bore nozzle short complete all as specified and as directed. 31 Supply and fix for Gun metal fire brigade inlet connection 2 way complete with all accessories complete all as specified and as directed. 32 Supply and fix Hose box made of 18 gauge MS Sheet 800 mm x 600 mm x 250 mm with double door with 4 mm thick glasses and door frame made of 16 gauge CRCA sheet duly gun painted with two coats of fire red out side and brilliant white inside over a coat of red oxide primer yard and mounted on masonry platform complete all as specified and as directed. 33 M & L for RRL hose reel of 20 mm dia 30 mtr long conforming to IS-5132 with Male & Female coupling complete all as specified and as directed. 34 Supply and lay Pipes ERW Steel including specials, for nominal dia pipe 100 mm, for making header system as per IS 3589 (1981) thickness 5.4 mm with all accessories like all fittings including tees, elbows, reducers, union flanges, rubber gaskets, Gl nuts bolts, washer, including drilling hole/welding/ supporting/fixing the pipe on floor/wallicelling with clamps, hangers, angles, channels (using anchor fastners) with painting of one coat primer and 2 or more coats of synthetic enamel paint complete all as specifiedand as directed 35 S&F rotational moulded polythylene 1000 capacity literswater storage tankstripple layer (cylindrical verical with closed top ) hoisted and fixed in position all as specified in SSR Part -I complete all as specified and directed. 36 Supply, installation, testing and commissioning of Automisation of the Pressure switches universal type with necessary control wiring for priming line complete all as specified and as directed. 37 Supply, installation, testing and commissioning of Automisation of the Pressure gauge 4 dial 0-21 kgs rating for priming line complete all as specified and as directed. 38 Supply, installation, testing and commissioning Jockey pump horizontal end suction centrifugal type Confirming to IS-12469. 1988 with Cl casing, bronze impeller and stainless steel shaft mounted on heavy duty bearings suitable for automatic operation with nonover loading power characteristics for frequent start/stop operations for 440 Volts, 3 phase, 50 Hz 70 Mtr head 180 LPM discharge complete all as specifiedand as directed. 39 Supply, installation testing and commissioning of Fire pump diesel engine driven horizontal end suction, centrifugal type confirming to IS. 12469 1988 with Cl casing bronze impeller and stainless steel shaft mounted on heavy duty bearings suitable for continuous operation with range of operation 0% to 150% of rated capacity for 440 Volts. 3 phase, 50 Hz AC supply 70 Mtr head with discharge 1620 LPM including autamatic operation system with Diesel tank suiable capacity of 12 Volts Battery with Battery charger etc complete all as specified and as directed. 40 Supply, installation, testing and commissioning of Fire pump electrically driven horizontal end Suction, centrifugal type confirming to IS-12469 1988 with Cl Casing bronze impeller and Stainless steel shaft mounted on heavy duty bearings Suitable for continuous operation with range of operation 0% to 150% of rated capacity for 440 Volts 3 Phase 50 Hz 70 Mtr Head with discharge 1620 LPM complete all as specified and as directed. 41 Supply fabrication, installation and testing of Motor Control LT Panel factory made Type Test Assemble (TTA) Panel for working on 3 phase, 4 wire, 415 Volts, AC, 50Hz, cubical, indoor type, weather proof, water proof, dust proof, vermin proof, shock proof protection made out 20 mm thick CRCA sheet of suitable size accommodate accessories/ fittings with front and back double door opening/ lockable by the key from both side with IP 65 Protection and provn of suitable bus bar chamber and switch gear compartments for MCCB incoming & out going feeders etc with copper extension links. of surtable curent carrying capacitty not less than 1.5 times the rated current carrying capacity of MCCB individual feeder supported on DMC/ Epoxy insulator including provison for termination with incoming and out going cables with cable glands. Motor Control LT Panel shall be mounted on 50 x 50 x 6 mm size MS angle iron frame duly painted with two coats of black bituminus paint over a coat of red oxide primer including PCC foundation of suitable size with PCC 1.2.4 type B1(using 20 mm graded storie aggregate)complete and including the following accessories:-IN COMMING:-(a) Copper strip busbar of 200 Amps rated capaacity wrapped with PVC sleeves with maintained the colour code and provision of making holes with Copper nuts, bolts & washers for cable corinections including hydrograpic insulators with nuts & bolts at both ends 04 Nos(b) On load change over Switch TPN of capacity 160 Amps - 01 No (c) 4 Pole MCCB 160 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics 100% Icu. 35 KA breaking capacity including all fixing accessories with both ends spreader links 01 No (d) LED Neon indicator lamp (RYB) with holder and fuse holder 230/250 volts, AC-01 set (set of (e) Digital Multifunctional meter flush mounting type with CTs and selector switch-01 set 42 OUT GOING:-(a) 4 Pole MCCB 100 Amps with rotary handle adjustable thermal magnetic release type, 4 pole, 415 Volts Ics 100% Icu, 18 KA breaking capacity including all fixing accessories with both ends spreader links 01 No (b) 4 Pole MCCB 63 Amps with rotary handle, adjustable thermal magnetic release type. 4 pole. 415 Volts, Ics 100% Icu, 18 KA breaking capacity including all fixing accessories with both ends spreader links -02 Nos (c) 4 Pole MCB 16 Amps 10 KA breaking capacity C curve -01 No (d) Automatic star-delta starter (Soft Starter type) with suitable relay range conforming to IS-1347(Part IV) suitable for discharge capacity 2280 LPM (137.0 Cumt/Hr) at 70 Mtr head, 80.0 HP, including overload relay, auto timer & single phase preventer suitable range of digital ammemeter with selector switch, voltmeter with selector, Start/Stop Push buttons, indicating lamps (LED) & bakelite fuse showing RYB phase, internal wiring with copper conductor etc complete 01 No (Fire Pump) (e) DOL starter with sitable relay range conforming to IS-1347(Part IV) suitable for discharge capacity 180 LPM 11.80 Cumt/Hr) at 70 Mtr head, 4.50 KW/ 6.0 HP, including overload relay & single phase preventer suitable range of digital ammemeter with selector switch, voltmeter with selector switch, Start/Stop Push buttons, indicating lamps (LED) & bakelite fuse showing RYB phase, internal wiring with copper conductor etc complete -01 No (Jockey Pump) 43 M&L construction of Brick Masonry Valve Pit of size 900 mm x 900 mm x 900 mm internal dimension, Brick thick wall in cement mortar 1:4 on 100 mm thick PCC 1:4:8 ( 40mm graded aggregate) in Foundation, Rendering 15 mm thick internally and externally upto 150mm below GL, providing 3.0 mm thick MS Sheet Valve Pit Cover welded with 40 x 5mm Flat Iron Frame alround including provision of Hinges. Handie and Locking Arrangement and 40 x 40 x 6 mm angle Iron Frame fixed on Top of Valve Pit by means of Holdfast 150 mm long embedded in PCC 1:2:4 (20mm graded aggregate) of size 230 x 200 x 100 mm, applying two coats of anti-corrosive Paint over a coat of red oxide Zinc Chrome Primer after preparation of all exposed to Steel Surfaces including necessary Earth Work in any type of soil complete all as specified and as directed. 44 M&L Cement Concrete in foundationis, filling & mass concrete (1:2:4) type B2 (using 40 mm graded stone aggregate) for foundation & staging of shed for Fire Pump, Fire Engine & Fire Panel etc, finishing the exposed surface even and smooth with out using extra cement including necessary form work etc complete all as specified and directed. 45 M & L for maintenance free Chemical earthing of technology with copper bonded steel rod 3 mtr long 25.0 mm dia with 250-micron Copper bonded coating and UL isted There should be terminal for connection of 150 x 50 x 6 mm with 4 holes of 12 mm da along with 2 bags of 25 Kgs each of earth enhancing compound. The chemical compound should be tested and certified by any NABL accredited laboratory with 95 percent carbon content. The testing laboratory should be an ISO 9001 and 14001 certified The earth enhancing compound should be IEC 62321 The ph value of compound should be 7-8 Electrode should be duly tested and certified by CPRI Govt of India for a min short circuit current of 25 kA rms for 1 Sec including necessary boring of suitable dia upto required depth in any type of soil for inserting copper rod and filling of chemicals and Poly plastic pit cover of maternal polymer body & cover dimensions- 308 mm (L) x 308 mm (W) x 214 mm (H) beaning capacity 7.5 Ton approved from NABL approved Lab complete all as specified and as directed.Note: (i) Earthing is to be done infront of the Engr-n-Charge(ii) Test Results of earthing to be submitted by the contractor for all earthings(iii) The Contractor shall have to give written guarantee for maintenance earth resistance of less than 10 Ohm for the period of 10 9ten) years after certified date of completion and shall bdeposited 2000/- per earthing as security deposit for a period of Ten (10) Years(iv) Failing to maintain resistance of earthing less than 10 ohm new earthing to be provided by the contractor with out any extra cost(v) Necessary earth work excavation shall be carried out in any type of soil strata retuning, filling in and making good surronding area complete 46 M&L for Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing of size 20 x 3 mm thick copper strip complete all as specified and as directed.