}

Tender For General-Kakkott Vayal Li Scheme-Electrification Of Kakkottvayal Li Scheme At Kadannappalli Panappuzha Panchayath At Kalliasseri Lac -General Electrical Work - Electrification 2 90.14.1.2:Fabrication, Supply, Conveyance, Installation Testing A, Kannur-Kerala

Irrigation Department has published Tender For General-Kakkott Vayal Li Scheme-Electrification Of Kakkottvayal Li Scheme At Kadannappalli Panappuzha Panchayath At Kalliasseri Lac -General Electrical Work - Electrification 2 90.14.1.2:Fabrication, Supply, Conveyance, Installation Testing A. Submission Date for this Tender is 12-08-2025. Water Supply Project Tenders in Kannur Kerala. Bidders can get complete Tender details and download the document.




Tender Notice

50539588
Tender For General-Kakkott Vayal Li Scheme-Electrification Of Kakkottvayal Li Scheme At Kadannappalli Panappuzha Panchayath At Kalliasseri Lac -General Electrical Work - Electrification 2 90.14.1.2:Fabrication, Supply, Conveyance, Installation Testing A
Tender
Indian
Kerala
Kannur
12-08-2025

Tender Documents

Tender Details

Tender For General-Kakkott Vayal Li Scheme-Electrification Of Kakkottvayal Li Scheme At Kadannappalli Panappuzha Panchayath At Kalliasseri Lac -General Electrical Work - Electrification 2 90.14.1.2:Fabrication, supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/ devices & complying to IS 8623.Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The measurments will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc.Supply and fabrication of MV panel board using 1.6mm CRCA sheet, powder coated (excluding base frame) 3 90.14.2.1:Supply and providing 2mm SMC sheet as shrouding for bus interconnection / terminations etc. including required nut & bolt etc. 4 90.14.3.3:Supply and providing heavy duty A section neoprene gasket in the panel boardSupply and providing U section PVC beeding in the panel board 5 90.14.5:Supply and fabrication conveyance and installation of angle iron frame work for wall mounting panel board 6 90.14.6:Supply and providing copper bus bars including finger type SMC bus bar supports in the bus chamber, suitable size nut & bolt, providng heat shrink sleeves etc. as required. 7 90.14.7:Supply and providing copper earth bus in the panel board 8 90.14.4:Supply and fabrication conveyance and installation of base frame of panel board using 75 x 40 mm rolled steel channel (ISMC) 9 OD194586/2024-2025:Carrying out control wiring for panel with normal meters and indication lamps for interconnecting the control devices/ equipments including providingsuitable size insulated sockets at the termination points or soldered properly, providing numbering ferrules for the proper identification of the wiring,keeping the wiring firm by suitable tie/ tie mounts/ PVC duct etc as required.-1.50 sq mm single run with required sockets.- 10 OD194612/2024-2025:Painting letters or figures of the following sizes with enamel paint as identification mark to SB, DB, panel board etc as required in Panel board/DBs- 2.50 cm, 4 cm or 5 cm height 11 OD194594/2024-2025:Aluminium anodised Danger Notice Board of size 150 x 100 mm. with inscriptions ( both in English and Malayalam) and conventional Skull and Bone in Red colour. 12 OD194606/2024-2025:S/F Bus bar chamber, 100 x 40 mm aluminium anodised legend plates 13 OD194596/2024-2025:S/F Cable alley, 100 x 40 mm aluminium anodised legend plates 14 OD194605/2024-2025:Supply and providing LED indicators for all voltage ranges - Red, Green, Black, Yellow or Orange Colour 15 OD194587/2024-2025:Supply and providing LED indicators for all voltage ranges - Blue Colour 16 OD231663/2024-2025:Supplying and fixing2 A SP MCB (C curve), 10 kA breaking capacity complete with connections, testing and commissioning etc. as required. 17 OD194599/2024-2025:Supply and fitting Digital Multifunction meter to read:W, Wh, PF or VA, Vah, PF or V AR, V ,A Rh, PF - 3 phase accuracy class 1 LED- 18 OD194601/2024-2025:Supply and providing 2 mm thick synthetic PVC fire retardant insulating mat to withstand 3.3 KV dielectric strength conforming to IS . 19 OD231661/2024-2025: Supply and providing First Aid Chart duly framed and placed in a conspicuous location for clear vision. 20 OD231662/2024-2025:Supply of 15KV rubber hand glove 21 OD231659/2024-2025:Supply and installation of ABC type fire extinguisher of 6 kg. Capacity complete with initial filling charges and installation brackets. 22 OD231660/2024-2025:Supply and installation, testing and commissioning of CO2 type fire extinguisher with 4.5kg. Capacity complete withinstallation brackets with ISI mark IS:15222 23 90.14.10.4:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.16 A-100A, 25/35 kA (Ics=100%Icu), 4 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL 24 2.1.2:Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.63 Amp TP & N 25 2.1.1:Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.32 Amp TP & N 26 OD220250/2024-2025:Providing and fixing following capacity SP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.32 Amp SP & N 27 90.14.11.13:MCCB AccessoriesSupply and fixing rotary handle, External type (including BUC handle with door interlock ) in the existing MCCB of rating up to 250 A 28 90.14.11.1:MCCB AccessoriesSupply and fixing one number earth fault Relay up to 100A with CBCT. 29 90.14.11.12:MCCB AccessoriesSupply and fixing shunt release for all voltage range up to 630A. 30 90.14.11.17:MCCB AccessoriesSupply and fixing kastel interlock kit up to 250A. 31 90.14.24.17:Supply & fixingthe following Power Capacitors 3 phase delta connected in positon and giving connection.2 KVAr, 3 phase, 440 V, delta connected, standard duty Metalised Poly Propylene Capacitor, Box Type, suitable for direct connection to motors. 32 90.14.24.21:Supply & fixingthe following Power Capacitors 3 phase delta connected in positon and giving connection.6 KVAr, 3 phase, 440 V, delta connected, standard duty Metalised Poly Propylene Capacitor, Box Type, suitable for direct connection to motors. 33 1.17.24:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 4 sq. mm 34 90.6.4.56:Supply and drawing 650/1100 V grade FRLS PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.10.00 sq.mm 6 Run 35 90.12.7.28:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 35 sq mm with factory made clamp 36 9.1.21:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 35 sq. mm (32mm) 37 90.6.6.3:Supply and drawing FRLS PVC insulated & sheathed 650/1100 V grade 3 core copper conductor flat cable for submersible pump motor conforming to IS 694 part I 1990 as required including giving necessary connections of the following sizes.4 sq mm 38 90.6.6.5:Supply and drawing FRLS PVC insulated & sheathed 650/1100 V grade 3 core copper conductor flat cable for submersible pump motor conforming to IS 694 part I 1990 as required including giving necessary connections of the following sizes.10 sq mm 39 1.21.2:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm 40 1.21.3:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.32 mm 41 5.4:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. 42 OD231655/2024-2025:Supply and providing earth lead from the test joint to the earth electrode using the following sizesof conductors/ strips including cutting, drilling necessary holes (in case of strip) and fixing firmly with plate test joint etc as required. 25 mm X 3 mm G.I. strip 43 OD231656/2024-2025:Supply and providing test joint for the earthing system using 2 Nos of the following sizesof strips including cutting and bending to shape, drilling necessary holes and fixed to the watering pipe etc as required. 2 x 25 x 3 mm GI strip 44 90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG) 45 90.16.1.4:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required4.00 mm copper conductor ( 8 SWG) 46 90.16.5.3:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG) 47 90.16.5.4:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.4.00 mm (8 SWG) 48 OD194595/2024-2025:Supply and providing the following sizes of bolt and nut with washers on the existing MS box ,earth bus,earthing system etc. as required including drilling necessary holes as required - 25 x 3 mm brass bolt & nut- 49 OD194584/2024-2025:Supply and providing the following sizes of bolt and nut with washers on the existing MS box , earth bus,earthing system etc. as required including drilling necessary holes as required - 12 x 3mm- 50 OD194588/2024-2025:Supply and installation of dust and vermin proof wall mounting , sintex make meter box of size 700X480X210 mm GSMB 7450 ( IP65 ) or equivalent suitable for fixing KSEB meter,fuse units,CT etc hinged door construction ,double door,for the front side with compartments if necessary,providing vision panel for the meter compartment knock out for cable entry as required including fixing it ,making good the damages etc. as required. 51 OD231665/2024-2025:Supply and installation of switch gear units in sheet steel enclosure complete with handle assembly, door interlock and pad locking arrangement of the following ratings on existing angle iron frame work or directly to wall using necessary bolts & nuts, fixing the unit to wall, making good the damages, colour washing etc. including giving necessary connections as required.100 Amp TP&N with ISI marked HRC fuse 52 OD194611/2024-2025:Supply , Conveyance and fitting charge of 100 A, HRC Fuse Base with suitable HRC Fuse link in the existing Meter box. 53 OD194615/2024-2025:Supply , Conveyance and fitting 100 A, 2 Way neutral links in the existing Meter box.- 54 OD221069/2024-2025:Supply and fixing 100/5 A, 5 VA, accuracy class 1, Tape wound Metering CT in existing panel board and giving connection as required 55 OD220744/2024-2025:Suppy and providing M8 anchor bolt hook in wall/parapet for binding support for service main 56 OD231657/2024-2025:Supply and fixing 50 mm dia 6Kgff/cm2 PVC pipe including fixing the pipe with clamp/clips at 60cm spacing. etc as required (For Service Pipe) 57 90.11.1.14:Supply and installation ofsheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - double cover TPN vertical DB with provision for fixing 4P MCB / Isolator/ RCCB/ RCBO as incomer and SP/ TP MCB as outgoing (IP 42/43) 58 1.10.1:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVCinsulated copper conductor single core cable in surface / recessed medium class PVC conduit,with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLSPVC insulated copper conductor single core cable etc as required.Group A 59 1.33:Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required. 60 1.24.1:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch 61 1.24.3:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch 62 1.24.4:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet 63 1.24.5:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet 64 1.27.2:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm) 65 2.10.1:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, C curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole 66 2.10.4:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, C curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Triple pole 67 2.11:Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required. 68 2.13.1:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps 69 2.15.2:Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps 70 OD19152/2025-2026:Supply Conveyance, installation, testing and commissioning of 40W LED Flood light output greater than 120lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminum pressure die-cast Powder coated housing, acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be separately accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer) PHILIPS /Eqvt

Key Value

Document Fees
INR 585 /-
EMD
INR 6584.0 /-
Tender Value
INR 2.63 Lakhs /-

Attachment

FileName File Description File Size
Click here to download tender document Tender Documents 0 KB
Click here to download tender document Tender Documents 0 KB
Click here to download tender document Tender Documents 0 KB
Click here to download tender document Tender Documents 0 KB
Click here to download tender document Tender Documents 0 KB
Click here to download tender document Tender Documents 0 KB
Click here to download tender document Tender Documents 0 KB
Click here to download tender document Tender Documents 0 KB
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2025 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail