Gurugram Metropolitan Development Authority-GMDA has published Tender For Design, Supply And Erection Of 66/11 Kv Outdoor Substation At Basai Water Works, Gurugram By Providing 2 X 12.5 16 Mva 66/11 Kv Transformer And Its Associated 66Kv Single Circuit Line On Krr Design For Double Circuit 66 Kv Towers (Dcss. Submission Date for this Tender is 13-01-2023. Transformer Supply Tenders in gurugram Haryana. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 20-Dec-2022 | Corrigendum | Date | 05-01-2023 |
2 | 05-Jan-2023 | Corrigendum1 | Date | 13-01-2023 |
Sl. No. | Item Description |
1 | Design, Manufacturing, Testing at Manufacturer`s works, Forwarding and packing, transportation, Delivery at site, Storage, Erection, Site Testing, Commissioning and handing over of the following equipments/ items, complete with all accessories and as per enclosed specification, data sheets, drawings etc. Please refer the bid document for the completeness of the scope and the general technical requirements for each item given under. (Data Sheets and Guaranteed Technical particulars for allthe equipments are required to be attached with bid). The quantities are given under, however requirements shall be as per the technical specification and detailed engineering to be carried out by the bidder.upply , installation and commissioning of 72.5KV ,1250A, 25KA for 1 sec, SF6 Circuit Breaker, 3 Ph gang operated complete with operating mechanism andsupport structure. |
2 | Design, Manufacturing, Testing at Manufacturer`s works, Forwarding and packing, transportation, Delivery at site, Storage, Erection, Site Testing, Commissioning and handing over of the following equipments/ items, complete with all accessories and as per enclosed specification, data sheets, drawings etc. Please refer the bid document for the completeness of the scope and the general technical requirements for each item given under. (Data Sheets and Guaranteed Technical particulars for allthe equipments are required to be attached with bid). The quantities are given under, however requirements shall be as per the technical specification and detailed engineering to be carried out by the bidder.Supply , installation and commissioning 72.5KV ,800A,3 Ph gang operated double break type manual operated disconnector (Isolator) with solid core post insulator(Without earth switch). |
3 | Design, Manufacturing, Testing at Manufacturer`s works, Forwarding and packing, transportation, Delivery at site, Storage, Erection, Site Testing, Commissioning and handing over of the following equipments / items, complete with all accessories and as per enclosed specification, data sheets, drawings etc. Please refer the bid document for the completeness of the scope and the general technical requirements for each item given under. (Data Sheets and Guaranteed Technical particulars for all the equipments are required to be attached with bid). The quantities are given under, however requirements shall be as per the technical specification and detailed engineering to be carried out by the bidder. 66 KV Equipments Supply , installation and commissioning 72.5KV ,800A, 3 Ph gang operated double break type manual operated disconnector (Isolator) with solid core post insulator (With earth switch). |
4 | Design, Manufacturing, Testing at Manufacturer`s works, Forwarding and packing, transportation, Delivery at site, Storage, Erection, Site Testing, Commissioning and handing over of the following equipments / items, complete with all accessories and as per enclosed specification, data sheets, drawings etc. Please refer the bid document for the completeness of the scope and the general technical requirements for each item given under. (Data Sheets and Guaranteed Technical particulars for all the equipments are required to be attached with bid). The quantities are given under, however requirements shall be as per the technical specification and detailed engineering to be carried out by the bidder. 66 KV EQUIPMENTS Supply , installation and commissioning of 72.5KV Out door single phase current transformers of ratio Line feeder:600-300-150/1-1-1-1A, refer CT design parameters as per the Technical specifications |
5 | Design, Manufacturing, Testing at Manufacturer`s works, Forwarding and packing, transportation, Delivery at site, Storage, Erection, Site Testing, Commissioning and handing over of the following equipments / items, complete with all accessories and as per enclosed specification, data sheets, drawings etc. Please refer the bid document for the completeness of the scope and the general technical requirements for each item given under. (Data Sheets and Guaranteed Technical particulars for all the equipments are required to be attached with bid). The quantities are given under, however requirements shall be as per the technical specification and detailed engineering to be carried out by the bidder. 66 KV EQUIPMENTS Supply , installation and commissioning of 66 KV capacitive voltage transformer (66/v3/110V/v3/110V/v3/110V/v3) CORE-1 CL:0.2,50VA, CORE-2 CL:3P,50VA and CORE-3 CL:3P,50VA. |
6 | Substation Bay Hardware Supply , Installation and commissioning of Single tension line hardware fitting bolted type clamp suitable for single tension insulated string of 6 no. 11 KV 90 KN Disc insulators, Shackle suitable for 20 mm anchoring hole on beam side, without turn buckle forSINGLE ACSR ZEBRA conductor. |
7 | Substation Bay Hardware Supply , Installation and commissioning of Single tension line hardware fitting bolted type clamp suitable for single tension insulated string of 6 no. 11 KV 90 KN Disc insulators, Shackle suitable for 20 mm anchoring hole on beam side, with turn buckle forSINGLE ACSR ZEBRA conductor. |
8 | Substation Bay Hardware Supply , Installation and commissioning of Single suspension linehardware fitting boltedtypesuitablefor 1x5 nos. 11kV, 70kN EMS disc insulatoralong shackle suitablefor 20 mm anchoring hole on beamsuitable for SINGLE ACSR ZEBRA conductor complete with U BOLT and I BOLT ETC. DROP TYPE. |
9 | Substation Bay Hardware Supply , Installation and commissioning of 90 KN Disc insulator BandS type. |
10 | Substation Bay Hardware Supply , Installation and commissioning of 70 KN Disc insulator BandS type. |
11 | Substation Bay Hardware Supply , Installation and commissioning of Tee Connector and Power connectors of suitable current rating for individual equipment terminal pad and Single Zebra ACSR conductors on 66 KV side , Tee connector for single Zebra conductor through and same tee off. |
12 | Substation Bay Hardware Supply , Installation and commissioning of Tee Connector and Power connectors of suitable current rating for individual equipment terminal pad and Single Zebra ACSR conductors on 66 KV side , Terminal connector for 72.6kV Isolator to receive SINGLE ACSR ZEBRA Conductor. |
13 | Substation Bay Hardware Supply , Installation and commissioning of Tee Connector and Power connectors of suitable current rating for individual equipment terminal pad and Single Zebra ACSR conductors on 66 KV side , Terminal connector for 72.6kV SF6 Circuit Breaker to receive SINGLE ACSR ZEBRA Conductor |
14 | Substation Bay Hardware Supply , Installation and commissioning of Tee Connector and Power connectors of suitable current rating for individual equipment terminal pad and Single Zebra ACSR conductors on 66 KV side , Terminal connector for 72.6kV Current Transformer to receive SINGLE ACSR ZEBRA Conductor. |
15 | Substation Bay Hardware Supply , Installation and commissioning of Tee Connector and Power connectors of suitable current rating for individual equipment terminal pad and Single Zebra ACSR conductors on 66 KV side , Terminal connector for 60kV Lightning Arrester to receive Single ACSR Zebra Conductor. |
16 | Substation Bay Hardware Supply , Installation and commissioning of Tee Connector and Power connectors of suitable current rating for individual equipment terminal pad and Single Zebra ACSR conductors on 66 KV side , Terminal connector for 72.6kV CVT connector to receive Single ACSR ZEBRA Conductor. |
17 | Substation Bay Hardware Supply , Laying of ZEBRA ACSR conductor |
18 | Substation Bay Hardware Supply , Installation and commissioning of Earth Wire Connector (PG Clamps). |
19 | Substation Bay Hardware Supply , Laying of 7/3.15 mm GSS wire for shielding . |
20 | Substation Bay Hardware Supply , Installation and commissioning of Hardware for 7/3.15 mm GSS wire pad type clamps. |
21 | LT CABLE , 1.1 KV PVC insulated and sheathed, steel armoured cable of the following size including cable support (For AC supply and yard lighting) Supply and Laying of 3 core x 2.5 sqmm Cu conductor cable (GI round wire armoured) for control Gear to Lamp fixture. |
22 | LT CABLE , 1.1 KV PVC insulated and sheathed, steel armoured cable of the following size including cable support (For AC supply and yard lighting) Supply and Laying of 4 core x 10 sqmmAl.Conductor cable (GI round wire armoured)for Street light panel to light fitting Control gear. |
23 | LT CABLE , 1.1 KV PVC insulated and sheathed, steel armoured cable of the following size including cable support (For AC supply and yard lighting) Supply and Laying of 4 core x 16 sqmmAl. Conductor cable (GI round wire armoured) for Street light panel from ACDB. |
24 | LT CABLE , 1.1 KV PVC insulated and sheathed, steel armoured cable of the following size including cable support (For AC supply and yard lighting) Termination with double compression gland andlugs for item 4 core x 16 sqmm , 4 core x 10 sqmm , 3 core x 2.5 sqmm. |
25 | LT CABLE , 1.1 KV PVC insulated and sheathed, steel wire armoured Aluminum conductor cable of the following size (For AC and DC Supply) , Supply and laying of 3.5 core x 50 sqmm Al conductor cable ( GI Strip armoured) for ACDB to Battery charger. |
26 | LT CABLE , 1.1 KV PVC insulated and sheathed, steel wire armoured Aluminum conductor cable of the following size (For AC and DC Supply) , Supply and laying of 2 core x 50 sqmmcopper conductor cable (For DC) Battery charger to Battery. |
27 | LT CABLE , 1.1 KV PVC insulated and sheathed, steel wire armoured Aluminum conductor cable of the following size (For AC and DC Supply) , Double compression glands and Cu/Al lugs with sleeves for 1100V grade PVC insulated, multicore aluminum conductor auxiliary power cables of the following sizes: Supply and erection of 3 1/2 core x 50 sqmmAl. cable. |
28 | LT CABLE , 1.1 KV PVC insulated and sheathed, steel wire armoured Aluminum conductor cable of the following size (For AC and DC Supply) , Double compression glands and Cu/Al lugs with sleeves for 1100V grade PVC insulated, multicore aluminum conductor auxiliary power cables of the following sizes: Supply and erection of 2 core x 50 sqmmcopper cable |
29 | Supply and Erection of Double compression glands and terminations(including ferruling, suitable Cu Lugs to meet the system requirements) for 1100V grade PVC insulated multicore Copper stranded conductor control cables ofthe following sizes: 3 core 2.5 sqmm , 5 core 2.5 sqmm , 7 core 2.5 sqmm , 10 core 2.5 sqmm , 19 Core 2.5 sqmm , 4Core 4 sqmm ( For CT supply) , 2 Core 6 sqmm (For D.C.) , 4 Core x 10 sqmm (Aluminum) , 4 Core x 16 sqmm (Aluminum) , 3.5 Core x 35 sqmm (Aluminum). |
30 | Lighting , Supply and Erection of Flood light fitting with 150 W LED lamp. |
31 | Lighting , Supply and Installation of Steel tubular pole 10 mtr long, SP -33 with base plate and cross arm 1.5 mtr long with arrangement for fixing the luminaire 85 W LED fitting with suitable junction box. |
32 | Lighting , Supply and installation of Lighting junction box for each Light at tower suitable for out door installation comprising of 8 no. CBT M 4 type terminal connector for light connections or loop in / loop out cable. |
33 | EARTHING ANDLIGHTNING PROTECTION , Supply and Erection of Main Earth mat, Aux Earth mat and Earthing Risers for Main Equipmentsand structures etc ( 75 x 12 mm G I flat). |
34 | EARTHING AND LIGHTNING PROTECTION , Supply and Erection of Earthing conductor for connection of , L.T panel, Junction box, and building Lightning risers and peak Connection etc(50x6 GI flat). |
35 | EARTHING AND LIGHTNING PROTECTION , Supply and Erection of 50x6 mm MS flat for cable trench earthing. |
36 | EARTHING AND LIGHTNING PROTECTION , Supply and Erection of 40 mm dia 3 m long GI pipe earth electrode with treated earth Pit for LA and CVT. |
37 | EARTHING AND LIGHTNING PROTECTION , Supply and Erection of 40 mm Dia 3 mtr longM.S. rod earth electrode (driven) for each peak tower, building lightning protection and yard earth mat. |
38 | Control and Relay Panel , Indoor floor mounted, simplex type control and relay panels, with mimic and annunciation panelfor 66kV system as per specification and data sheet comprising of : 66kV Ckt. Breaker control panel without auto reclose and Line Protection Panel |
39 | Safety equipment , Fire Extinguishers , Supply and installation of CO2 type 5 Kg . |
40 | Cable Supports and Trays , Supply and Installation of Sheet steel (thickness 2.5 mm) Galvanized ladder and perforated type cable trays with its accessories to be laid in outdoor and indoor cable trenches ( of following various sizes ).600mm, 450 mm, 300mm, 150mm and 100mm width, as per requirement for dressing , Cable Trays , (600 X 50 mm Ladder type ). |
41 | able Supports and Trays , Supply and Installation of Sheet steel (thickness 2.5 mm) Galvanized ladder and perforated type cable trays with its accessories to be laid in outdoor and indoor cable trenches ( of following various sizes ).600mm, 450 mm, 300mm, 150mm and 100mm width, as per requirement for dressing , Cable Trays , (450 X 50 mm Ladder type ). |
42 | Cable Supports and Trays , Supply and Installation of Sheet steel (thickness 2.5 mm) Galvanized ladder and perforated type cable trays with its accessories to be laid in outdoor and indoor cable trenches ( of following various sizes ).600mm, 450 mm, 300mm, 150mm and 100mm width, as per requirement for dressing , Cable Trays , (300 X 50 mm Ladder type). |
43 | Structural Steel , Supply and erection of Substation Galvanized Steel Structure for Towers and Beam |
44 | Cable Supports and Trays , Supply , testing and Installation of Sheet steel (thickness 2.5 mm) Galvanized ladder and perforated type cable trays with its accessories to be laid in outdoor and indoor cable trenches ( of following various sizes ).600mm, 450 mm, 300mm, 150mm and 100mm width, as per requirement for dressing , Cable Trays , (150 x50 mm perforated type). |
45 | Cable Supports and Trays , Supply , testing and Installation of Sheet steel (thickness 2.5 mm) Galvanized ladder and perforated type cable trays with its accessories to be laid in outdoor and indoor cable trenches ( of following various sizes ).600mm, 450 mm, 300mm, 150mm and 100mm width, as per requirement for dressing , Cable Trays , (100 x 50 mm Perforated Type ). |
46 | Structural Steel , Supply and erection of Nuts and bolts for Substation Galvanized Steel Structure for Towers and Beam. |
47 | Structural Steel , Supply and erection of Substation Galvanized Steel Structure for equipments. |
48 | Structural Steel , Supply and erection of Nuts and bollts for Substation Galvanized Steel Structure for equipments. |
49 | Structural Steel , Supply and erection of Anchor bolts. |
50 | Supply and installation of Dewatering pump (portable type) 415 V, 1 HP as per requirement. |
51 | Supply and installation of Bay marshalling kiosk made of 2.5 mm. Thick sheet steel , IP 55 enclosure protection as per specification. |
52 | Substation Bay Hardware , Single tension hardware fitting bolted type clamp suitable for single tension insulated string of 6 no. 11 KV 90 KN Disc insulators, Shackle suitable for 20 mm anchoring hole on beam side, without turn buckle for Double ACSR ZEBRA conductor. |
53 | Substation Bay Hardware , Single tension line hardware fitting bolted type clamp suitable for single tension insulated string of 6 no. 11 KV 90 KN Disc insulators, Shackle suitable for 20 mm anchoring hole on beam side, with turn buckle for Double ACSR ZEBRA conductor . |
54 | Substation Bay Hardware , Single suspension linehardware fitting boltedtype suitablefor 1x5 nos. 11kV, 70kN EMS disc insulator along shackle suitablefor 20 mm anchoring hole on beamsuitable for Double ACSR ZEBRA conductor complete with U BOLT and I BOLT ETC. DROP TYPE |
55 | Supply and erection of Tension Fittings for 7/3.15mm Earthwire |
56 | Supply and erection of Hardware for 7/3.15 mm GSS wire-Cleat type clamps. |
57 | Supply and laying of Copper Control Cable , 1100 V grade, PVC insulated, PVC sheathed, steel round wire armoured, strandedcontrol cables of the following sizes: 3 core2.5 sqmm , 5 core2.5 sqmm , 7 core2.5 sqmm , 10 core2.5 sqmm , 19 Core 2.5 sqmm , 4Core4 sqmm ( For CT supply) , 2 Core 6 sqmm (For D.C.). |
58 | Control and Relay Panel , 66 kV Busbar Panel Argumentation for one number line bay (including in all respect) , The control, metering and protection system shall be complete with Numerical relays and compatible for performing the functions as per the electrical specifications and shall be fully compatible with substation automation /SCADA. |
59 | Substation Automation and SCADA system aurgumentation (as per the technical specification) along with local work station with necessary hardware(for present bays) and software(for present and future bays) and fiber optic cabling and ethernet and PU to complete the work. The system shall be complete with Numerical Relay compatible with substation automation with Existing station system. The numerical relays along with other measuring / indicating instruments shall be part of the integrated system to be mounted on the switch gear. |
60 | Aluminum Power Cables , Supply and Laying of 1100 V grade, PVC insulated, PVC sheathed, steel round wire armoured, stranded control cables of the following sizes: 4 Core x 10 sqmm (Aluminum) , 4 Core x 16 sqmm (Aluminum) , 3.5 Core x 35 sqmm (Aluminum). |
61 | Design, Manufacturing, Testing at Manufacturer`s works, Forwarding and packing, transportation, Delivery at site, Storage, Erection, Site Testing, Commissioning and handing over of the following equipments / items, complete with all accessories and as per enclosed specification, data sheets, drawings etc. Please refer the bid document for the completeness of the scope and the general technical requirements for each item given under. (Data Sheets and Guaranteed Technical particulars for all the equipments are required to be attached with bid). The quantities are given under, however requirements shall be as per the technical specification and detailed engineering to be carried out by the bidder. 66 KV EQUIPMENTS Supply and installation 60KV,10KA,Zinc oxide type, heavy duty, station class, lightning arrestor. |
62 | Lighting , 415V, 3 Phase, 4 Wire , outdoor type , IP65,Astronomical Type ,Microprocessor controlled, Time of day sequencing, Auto/manual type, street light panel comprising of 100A MCCB as incomer and 4 Nos ,63 Amps MCB outgoing with self chargable 24Hr. Timer for on/off.415 / 230V, complete with internal wiring, Al. Bus Bars, Link sets ,cable termination lugs for connecting outgoing cables of 4x25 sq.mm,PVC and 4 x 16 Sq.mm PVC Al, cables, indication, Metering , support channels, rain sheds, complete in all respects.The OGA and Scheme of the panel shall be as per the approved drawing. 1 no`s Metering with RYB indicating lamp LED type, Voltmeter with selector switch, ammeter with selector switch , suitable CT`s and 2A TPNMCB for backup protection of voltmeter and indication light , 1 no`s 70A 4P CONTACTOR , 24 Hr timer for auto Operation , Auto manual selector switch , I set push button for on/off operation , 4 No`s Outgoing feeder 63A TPNMCB at daultabad end. |
63 | Design, Manufacturing, Testing at Manufacturer`s works, Forwarding and packing, transportation, Delivery at site, Storage, Erection, Site Testing, Commissioning and handing over of the following equipments/ items, complete with all accessories and as per enclosed specification, data sheets, drawings etc. Please refer the bid document for the completeness of the scope and the general technical requirements for each item given under. (Data Sheets and Guaranteed Technical particulars for allthe equipments are required to be attached with bid).Supply , installation and commissioning of 12.5/16MVA, 66/11kV, 3 Ph, `YnYn0 ONAN/ONAF Transformer with OLTC and RTCC panel. with bushing NCT as per SLD. HV and LV side of the transformer shall have open type bushing for terminating ACSR `Single Zebra`. |
64 | Design, Manufacturing, Testing at Manufacturer`s works, Forwarding and packing, transportation, Delivery at site, Storage, Erection, Site Testing, Commissioning and handing over of the following equipments/ items, complete with all accessories and as per enclosed specification, data sheets, drawings etc. Please refer the bid document for the completeness of the scope and the general technical requirements for each item given under. (Data Sheets and Guaranteed Technical particulars for allthe equipments are required to be attached with bid). The quantities are given under, however requirements shall be as per the technical specification and detailed engineering to be carried out by the bidder.upply , installation and commissioning of 72.5KV ,1250A, 25KA for 1 sec, SF6 Circuit Breaker, 3 Ph gang operated complete with operating mechanism andsupport structure. |
65 | Design, Manufacturing, Testing at Manufacturer`s works, Forwarding and packing, transportation, Delivery at site, Storage, Erection, Site Testing, Commissioning and handing over of the following equipments/ items, complete with all accessories and as per enclosed specification, data sheets, drawings etc. Please refer the bid document for the completeness of the scope and the general technical requirements for each item given under. (Data Sheets and Guaranteed Technical particulars for allthe equipments are required to be attached with bid). The quantities are given under, however requirements shall be as per the technical specification and detailed engineering to be carried out by the bidder.Supply , installation and commissioning 72.5KV ,800A,3 Ph gang operated double break type manual operated disconnector (Isolator) with solid core post insulator(Without earth switch). |
66 | Design, Manufacturing, Testing at Manufacturer`s works, Forwarding and packing, transportation, Delivery at site, Storage, Erection, Site Testing, Commissioning and handing over of the following equipments / items, complete with all accessories and as per enclosed specification, data sheets, drawings etc. Please refer the bid document for the completeness of the scope and the general technical requirements for each item given under. (Data Sheets and Guaranteed Technical particulars for all the equipments are required to be attached with bid). The quantities are given under, however requirements shall be as per the technical specification and detailed engineering to be carried out by the bidder. 66 KV Equipments Supply , installation and commissioning 72.5KV ,800A, 3 Ph gang operated double break type manual operated disconnector (Isolator) with solid core post insulator (With earth switch). |
67 | Design, Manufacturing, Testing at Manufacturer`s works, Forwarding and packing, transportation, Delivery at site, Storage, Erection, Site Testing, Commissioning and handing over of the following equipments / items, complete with all accessories and as per enclosed specification, data sheets, drawings etc. Please refer the bid document for the completeness of the scope and the general technical requirements for each item given under. (Data Sheets and Guaranteed Technical particulars for all the equipments are required to be attached with bid). The quantities are given under, however requirements shall be as per the technical specification and detailed engineering to be carried out by the bidder. 66 KV EQUIPMENTS Supply , installation and commissioning of 72.5KV Out door single phase current transformers of ratio Line feeder:600-300-150/1-1-1-1A, refer CT design parameters as per the Technical specifications. |
68 | Design, Manufacturing, Testing at Manufacturer`s works, Forwarding and packing, transportation, Delivery at site, Storage, Erection, Site Testing, Commissioning and handing over of the following equipments / items, complete with all accessories and as per enclosed specification, data sheets, drawings etc. Please refer the bid document for the completeness of the scope and the general technical requirements for each item given under. (Data Sheets and Guaranteed Technical particulars for all the equipments are required to be attached with bid). The quantities are given under, however requirements shall be as per the technical specification and detailed engineering to be carried out by the bidder. 66 KV EQUIPMENTS Supply , installation and commissioning of 72.5KV Out door single phase current transformers of ratio Transformer feeder:600-300-150/1-1-1-1A, refer CT design parameters as per the Technical specifications. |
69 | Design, Manufacturing, Testing at Manufacturer`s works, Forwarding and packing, transportation, Delivery at site, Storage, Erection, Site Testing, Commissioning and handing over of the following equipments / items, complete with all accessories and as per enclosed specification, data sheets, drawings etc. Please refer the bid document for the completeness of the scope and the general technical requirements for each item given under. (Data Sheets and Guaranteed Technical particulars for all the equipments are required to be attached with bid). The quantities are given under, however requirements shall be as per the technical specification and detailed engineering to be carried out by the bidder. 66 KV EQUIPMENTS Supply , installation and commissioning of 72.5KV Out door type, single phase bus potential transformer: 66KV/v3/110V/v3 /110V/v3 /110V/v3CORE-1 CL:3P,50VA, CORE-2 CL:3P,50VA and CORE-3 CL:0.2,30VA. |
70 | Design, Manufacturing, Testing at Manufacturer`s works, Forwarding and packing, transportation, Delivery at site, Storage, Erection, Site Testing, Commissioning and handing over of the following equipments / items, complete with all accessories and as per enclosed specification, data sheets, drawings etc. Please refer the bid document for the completeness of the scope and the general technical requirements for each item given under. (Data Sheets and Guaranteed Technical particulars for all the equipments are required to be attached with bid). The quantities are given under, however requirements shall be as per the technical specification and detailed engineering to be carried out by the bidder. 66 KV EQUIPMENTS Supply , installation and commissioning of 66 KV capacitive voltage transformer (66/v3/110V/v3/110V/v3/110V/v3) CORE-1CL:0.2,50VA, CORE-2 CL:3P,50VA and CORE-3CL:3P,50VA. |
71 | Substation Bay Hardware Supply , Installation and commissioning of Single tension line hardware fitting bolted type clamp suitable for single tension insulated string of 6 no. 11 KV 90 KN Disc insulators, Shackle suitable for 20 mm anchoring hole on beam side, without turn buckle forSINGLE ACSR ZEBRA conductor. |
72 | Substation Bay Hardware Supply , Installation and commissioning of Single tension line hardware fitting bolted type clamp suitable for single tension insulated string of 6 no. 11 KV 90 KN Disc insulators, Shackle suitable for 20 mm anchoring hole on beam side, with turn buckle forSINGLE ACSR ZEBRA conductor. |
73 | Substation Bay Hardware Supply , Installation and commissioning of Single suspension linehardware fitting boltedtypesuitablefor 1x5 nos. 11kV, 70kN EMS disc insulatoralong shackle suitablefor 20 mm anchoring hole on beamsuitable for SINGLE ACSR ZEBRA conductor complete with U BOLT and I BOLT ETC. DROP TYPE. |
74 | Substation Bay Hardware Supply , Installation and commissioning of 90 KN Disc insulator BandS type. |
75 | Substation Bay Hardware Supply , Installation and commissioning of 70 KN Disc insulator BandS type. |
76 | Substation Bay Hardware Supply , Installation and commissioning of Tee Connector and Power connectors of suitable current rating for individual equipment terminal pad and Single Zebra ACSR conductors on 66 KV side , Tee connector for single Zebra conductor through and same tee off. |
77 | Substation Bay Hardware Supply , Installation and commissioning of Tee Connector and Power connectors of suitable current rating for individual equipment terminal pad and Single Zebra ACSR conductors on 66 KV side , Terminal connector for 72.6kV Isolator to receive SINGLE ACSR ZEBRA Conductor. |
78 | Substation Bay Hardware Supply , Installation and commissioning of Tee Connector and Power connectors of suitable current rating for individual equipment terminal pad and Single Zebra ACSR conductors on 66 KV side , Terminal connector for 72.6kV SF6 Circuit Breaker to receive SINGLE ACSR ZEBRA Conductor. |
79 | Substation Bay Hardware Supply , Installation and commissioning of Tee Connector and Power connectors of suitable current rating for individual equipment terminal pad and Single Zebra ACSR conductors on 66 KV side , Terminal connector for 72.6kV Current Transformer to receive SINGLE ACSR ZEBRA Conductor. |
80 | Substation Bay Hardware Supply , Installation and commissioning of Tee Connector and Power connectors of suitable current rating for individual equipment terminal pad and Single Zebra ACSR conductors on 66 KV side , Terminal connector for 60kV Lightning Arrester to receive Single ACSR Zebra Conductor. |
81 | Substation Bay Hardware Supply , Installation and commissioning of Tee Connector and Power connectors of suitable current rating for individual equipment terminal pad and Single Zebra ACSR conductors on 66 KV side , Terminal connector for 72.6kV BPT connecto to receive Single ACSR ZEBRA Conductor. |
82 | Substation Bay Hardware Supply , Installation and commissioning of Tee Connector and Power connectors of suitable current rating for individual equipment terminal pad and Single Zebra ACSR conductors on 66 KV side , Terminal connector for 72.6kV CVT connector to receive Single ACSR ZEBRA Conductor. |
83 | Substation Bay Hardware Supply , Installation and commissioning of Tee Connector and Power connectors of suitable current rating for individual equipment terminal pad and Single Zebra ACSR conductors on 66 KV side , Transformer Bushing Clamp ( H.T. Side ). |
84 | Substation Bay Hardware Supply , Installation and commissioning of Tee Connector and Power connectors of suitable current rating for individual equipment terminal pad and Single Zebra ACSR conductors on 66 KV side , Transformer Bushing Clamp ( L.T. Side ). |
85 | Substation Bay Hardware Supply , Installation and commissioning of Tee Connector and Power connectors of suitable current rating for individual equipment terminal pad and Single Zebra ACSR conductors on 66 KV side , Clamp for Neutral Bushing . |
86 | Substation Bay Hardware Supply , Laying of ZEBRA ACSR conductor |
87 | Substation Bay Hardware Supply , Laying of Tension Fittings for 7/3.15mm Earthwire. |
88 | Substation Bay Hardware Supply , Installation and commissioning of Earth Wire Connector (PG Clamps). |
89 | Substation Bay Hardware Supply , Laying of 7/3.15 mm GSS wire for shielding . |
90 | Substation Bay Hardware Supply , Installation and commissioning of Hardware for 7/3.15 mm GSS wire pad type clamps. |
91 | Substation Bay Hardware Supply , Installation and commissioning of Hardware for 7/3.15 mm GSS wire- Cleat type clamps. |
92 | 12KV Equipment Supply , installation and commissioning of 9KV, 5kA LIGHTNING ARRESTER perclain type. |
93 | CABLES , 12kV XLPE (E) insulated `PVC sheathed, aluminum round wire armored, aluminumconductor cable of the following size : Supply and laying of 1 core 630 sqmm(Aluminum round wire armored) Power transformers.(2 Runs/phase). |
94 | CABLES , 12kV XLPE (E) insulated `PVC sheathed, aluminum round wire armored, aluminum conductor cable of the following size : Supply and laying of 3 Core 185sqmm (Aluminum round armoured) for connecting with existing 11KV network . |
95 | CABLES , 12 KV Heat Shrink type termination Kit for the following size of 12 KV (E) XLPE Cables : 1Core 630 sq mm(Outdoor type). |
96 | CABLES , 12 KV Heat Shrink type termination Kit for the following size of 12 KV (E) XLPE Cables : 1Core 630 sq mm(Indoor type). |
97 | CABLES , 12 KV Heat Shrink type termination Kit for the following size of 12 KV (E) XLPE Cables : 3Core 185 sq mm( Outdoor type). |
98 | CABLES , 12 KV Heat Shrink type termination Kit for the following size of 12 KV (E) XLPE Cables : 3Core 185 sq mm( Indoor type). |
99 | CABLES , 12KV XLPE (E) insulated `PVC sheathed, steel round wire armoured, aluminumconductor cable , Supply and laying of 3 core 300 sqmm( wire armoured). |
100 | CABLES , 12kV Heat shrink type/ Pushon Type termination kit for 12kV (E) XLPE Cables of3 Core x 300 sqmm size (iNDOOR TYPE). |
101 | CABLES , 12kV Heat shrink type/ Pushon Type termination kit for 12kV (E) XLPE Cables of 3 Core x 300 sqmm size (OUTDOOR TYPE). |
102 | LT CABLE , 1.1kV XLPEinsulated `PVC sheathed, GI round wire armoured, aluminumconductor cable of the following sizes:. 3.5 core x 400 sq, mm for station transformer. |
103 | LT CABLE , 1.1kV XLPE insulated `PVC sheathed, GI round wire armoured, aluminum conductor cable of the following sizes: Termination with double compression gland and Al lugs for 3.5 core x 400 sq, mm cable. |
104 | LT CABLE , 1.1 KV PVC insulated and sheathed, steel armoured cable of the following size including cable support (For AC supply and yard lighting) Supply and Laying of 3 core x 2.5 sqmm Cu conductor cable (GI round wire armoured) for control Gear to Lamp fixture. |
105 | LT CABLE , 1.1 KV PVC insulated and sheathed, steel armoured cable of the following size including cable support (For AC supply and yard lighting) Supply and Laying of 4 core x 10 sqmmAl.Conductor cable (GI round wire armoured)for Street light panel to light fitting Control gear. |
106 | LT CABLE , 1.1 KV PVC insulated and sheathed, steel armoured cable of the following size including cable support (For AC supply and yard lighting) Supply and Laying of 4 core x 16 sqmmAl. Conductor cable (GI round wire armoured) for Street light panel from ACDB. |
107 | LT CABLE , 1.1 KV PVC insulated and sheathed, steel armoured cable of the following size including cable support (For AC supply and yard lighting) Termination with double compression gland andlugs for item 4 core x 16 sqmm , 4 core x 10 sqmm , 3 core x 2.5 sqmm. |
108 | LT CABLE , 1.1 KV PVC insulated and sheathed, steel wire armoured Aluminum conductor cable of the following size (For AC and DC Supply) , Supply and laying of 3.5 core x 50 sqmm Al conductor cable ( GI Strip armoured) for ACDB to Battery charger. |
109 | LT CABLE , 1.1 KV PVC insulated and sheathed, steel wire armoured Aluminum conductor cable of the following size (For AC and DC Supply) , Supply and laying of 2 core x 50 sqmmcopper conductor cable (For DC) Battery charger to Battery. |
110 | LT CABLE , 1.1 KV PVC insulated and sheathed, steel wire armoured Aluminum conductor cable of the following size (For AC and DC Supply) , Double compression glands and Cu/Al lugs with sleeves for 1100V grade PVC insulated, multicore aluminum conductor auxiliary power cables of the following sizes: Supply and erection of 3 1/2 core x 50 sqmmAl. cable. |
111 | LT CABLE , 1.1 KV PVC insulated and sheathed, steel wire armoured Aluminum conductor cable of the following size (For AC and DC Supply) , Double compression glands and Cu/Al lugs with sleeves for 1100V grade PVC insulated, multicore aluminum conductor auxiliary power cables of the following sizes: Supply and erection of 2 core x 50 sqmmcopper cable |
112 | Copper Control Cable , Supply and Laying of 1100 V grade, PVC insulated, PVC sheathed, steel round wire armoured, stranded control cables of the following sizes: 3 core2.5 sqmm , 5 core2.5 sqmm , 7 core2.5 sqmm , 10 core2.5 sqmm , 19 Core 2.5 sqmm , 4Core4 sqmm ( For CT supply) , 2 Core 6 sqmm (For D.C.). |
113 | Supply and Erection of Double compression glands and terminations(including ferruling, suitable Cu Lugs to meet the system requirements) for 1100V grade PVC insulated multicore Copper stranded conductor control cables ofthe following sizes: 3 core 2.5 sqmm , 5 core 2.5 sqmm , 7 core 2.5 sqmm , 10 core 2.5 sqmm , 19 Core 2.5 sqmm , 4Core 4 sqmm ( For CT supply) , 2 Core 6 sqmm (For D.C.) , 4 Core x 10 sqmm (Aluminum) , 4 Core x 16 sqmm (Aluminum) , 3.5 Core x 35 sqmm (Aluminum). |
114 | Lighting , Supply and Erection of Flood light fitting with 150 W LED lamp. |
115 | Lighting , Supply and Installation of Post top lantern with 38/35W LED lamp. |
116 | Lighting , Supply and Installation of Steel tubular pole 10 mtr long, SP -33 with base plate and cross arm 1.5 mtr long with arrangement for fixing the luminaire 85 W LED fitting with suitable junction box. |
117 | Lighting , 415V, 3 Phase, 4 Wire , outdoor type , IP65,Astronomical Type ,Microprocessor controlled, Time of day sequencing, Auto/manual type, street light panel comprising of 100A MCCB as incomer and 4 Nos ,63 Amps MCB outgoing with self chargable 24Hr. Timer for on/off.415 / 230V, complete with internal wiring, Al. Bus Bars, Link sets ,cable termination lugs for connecting outgoing cables of 4x25 sq.mm,PVC and 4 x 16 Sq.mm PVC Al, cables, indication, Metering ,support channels, rain sheds, complete in all respects.The OGA and Scheme of the panel shall be as per the approved drawing. 1 no`s Metering with RYB indicating lamp LED type, Voltmeter with selector switch, ammeter with selector switch , suitable CT`s and 2A TPNMCB for backup protection of voltmeter and indication light , 1 no`s 70A 4P CONTACTOR , 24 Hr timer for auto Operation , Auto manual selector switch , I set push button for on/off operation , 4 No`s Outgoing feeder 63A TPNMCB . |
118 | Lighting , Supply and installation of Lighting junction box for each Light at tower suitable for out door installation comprising of 8 no. CBT M 4 type terminal connector for light connections or loop in / loop out cable. |
119 | EARTHING ANDLIGHTNING PROTECTION , Supply and Erection of Main Earth mat, Aux Earth mat and Earthing Risers for Main Equipmentsand structures etc ( 75 x 12 mm G I flat). |
120 | EARTHING AND LIGHTNING PROTECTION , Supply and Erection of Earthing conductor for connection of , L.T panel, Junction box, and building Lightning risers and peak Connection etc(50x6 GI flat). |
121 | EARTHING AND LIGHTNING PROTECTION , Supply and Erection of Transformer neutral earthing with 50x6mm copper flat upto water level. |
122 | EARTHING AND LIGHTNING PROTECTION , Supply and Erection of 50x6 mm MS flat for cable trench earthing. |
123 | EARTHING AND LIGHTNING PROTECTION , Supply and Erection of Transformer body earthing( 75 x 12 mm G I flat). |
124 | EARTHING AND LIGHTNING PROTECTION , Supply and Erection of 40 mm dia 3 m long GI pipe earth electrode with treated earth Pit for LA and CVT. |
125 | EARTHING AND LIGHTNING PROTECTION , Supply and Erection of 40 mm Dia 3 mtr longM.S. rod earth electrode (driven) for each peak tower, building lightning protection and yard earth mat. |
126 | EARTHING AND LIGHTNING PROTECTION , Supply and Erection of Electrolytic grade copper plate 600mmx600mmx6mm for transformer neutral earthing to be provided in 4.5 mtr deep earth pit to be filled with salt and charcoal (as per standard earthing Practices). |
127 | EARTHING AND LIGHTNING PROTECTION , Supply and Erection of Electrolytic grade copper plate 600mmx600mmx6mm for Instrumentation and SCADA System to be provided in 4.5 mtr deep earth pit to be filled with salt and charcoal (as per standard IS). |
128 | PANEL SET , 11 KV Switchgear Panel (13 Panel Set) , 12kV, 500 MVA for1 Secs., 12500A, Indoor VCB switchgear panel with required PT`s, CT`s, protective relays, metering equipment, auxiliary equipment, extensible (both sides) copper bus bars, complete cable terminationkits as per cable sizes specified in SLD , 1250 A Incoming feeder=2 Nos., CTR : 1200-600/5-5 -5 A, refer CT design parameters as per technical specifications , 630 A station transformerfeeder =1 Nos.,CTR : 60- 30/5-5 A, refer CT design parameters as per technical specifications , 800 A outgoing feeder = 7 Nos., CTR : 600-300-150/5- 5 A, refer CT design parameters as per technical specifications , 1250A B/C Feeder=1Nos., CTR : 1200-600/5-5-5 A, refer CT design parameters as per technical specifications , 1 no. Spare Panel for addition/ deletion , 1 no`s BPT module alongwith with BR provision as per the requirement if any , Note :*The 11 KV Switchgear board shall be complete with Numerical relays and compatible with SCADA system as defined in the technical specifications. All outgoing feeders shall have separate Electronic Trivectr meter of accuracy class 0.2S for energy recording and have earth switch .All meters shall have recording facility as well as data download facility and MR provisions with software and laptops as per the requirements. All the panel, relays and meters etc. shall of same make, i.e. 11KV swithgear offered should come as complete unit from the manufacture and relays, meters, panel etc shall be of that manufacture only.All panels shall have TTBs in front for meter sealing. |
129 | PANEL SET , 11 KV Switchgear Panel (26 No`s VCB in total) , 12kV, 500 MVA for 1 Secs., 12500A, Indoor VCB switchgear panel with required PT`s, CT`s, protective relays, metering equipment, auxiliary equipment, extensible (both sides) copper bus bars, complete cable termination kits as per cable sizes specified in SLD , VCB set (1 incomer ,3 outgoing)(1 incomer ,5 outgoing)(1 incomer )(1 incomer )(1 incomer ,2 outgoing)(1 incomer ,5 outgoing)(1 incomer ,4 outgoing) 800 A each , 12kV switchgear incomer with VCB, PT, CT, metering, Copper bus bar, auxiliary relay etc. as per specification. (includes incomer and outgoing panel, for interconnection with the existing 11KV network) , Note :*The 11 KV Switchgear board shall be complete with Numerical relays and compatible with SCADA system as defined in the technical specifications. All outgoing feeders shall have separate Electronic Trivector meter of accuracy class 0.2S for energy recording and have earth switch .All meters shall have recording facility as well as data download facility and MR provisions with software and laptops as per the requirements. All the panel, relays and meters etc. shall of same make, i.e. 11KV switchgear offered should come as complete unit from the manufacture and relays, meters, panel etc shall be of that manufacture only. All panels shall have TTBs in front for meter sealing. |
130 | PANEL SET , 11 KV Switchgear Panel , 12kV, 500 MVA for 1 Secs., 12500A, Indoor VCB switchgear panel with required PT`s, CT`s, protective relays, metering equipment, auxiliary equipment, extensible (both sides) copper bus bars, complete cable termination kits as per cable sizes specified in SLD , For Addition / deletion of 1 no 630 A, 12kV switchgear outgoing feeder panel with VCB, CTS, Metering, Copper bus bar, cable sealing kit, auxiliary relays etc., as per specification.Note :*The 11 KV Switchgear board shall be complete with Numerical relays and compatible with SCADA system as defined in the technical specifications. All outgoing feeders shall have separate Electronic Trivectr meter of accuracy class 0.2S for energy recording and have earth switch .All meters shall have recording facility as well as data download facility and MR provisions with software and laptops as per the requirements. All the panel, relays and meters etc. shall of same make, i.e. 11KV swithgear offered should come as complete unit from the manufacture and relays, meters, panel etc shall be of that manufacture only.All panels shall have TTBs in front for meter sealing. |
131 | Control and Relay Panel , Indoor floor mounted, simplex type control and relay panels, with mimic and annunciation panelfor 66kV system as per specification and data sheet comprising of : 66kV Ckt. Breaker control panel without auto reclose and Line Protection Panel |
132 | Control and Relay Panel , Indoor floor mounted, simplex type control and relay panels, with mimic and annunciation panel for 66kV system as per specification and data sheet comprising of : 12.5/16MVA 66/11 kV Ckt. Breaker control panel without auto reclose and Transformer Protection Panel The control, metering and protection system shall be complete with Numerical relays and compatible for performing the functions as per the electrical specifications and shall be fully compatible with substation automation /SCADA. |
133 | Control and Relay Panel , Indoor floor mounted, simplex type control and relay panels, with mimic and annunciation panel for 66kV system as per specification and data sheet comprising of : 66 kV Busbar panel Panel , The control, metering and protection system shall be complete with Numerical relays and compatible for performing the functions as per the electrical specifications and shall be fully compatible with substation automation /SCADA. |
134 | Substation Automation , Substation Automation and SCADA system (as per the technical specification) along with local work station with necessary hardware(for present bays) and software (for present and future bays) and fiber optic cabling ane ethernet and PU to complete the work , The system shall be complete with Numerical Relay compatible with substation automation for 66 KV and 11 KVsystem. The numerical relays along with other measuring / indicating instruments shall be part of the integrated system to be mounted on the switch gear. |
135 | AC Distribution Board , supply and installation of AC 415V, 500A ,50 KAfor 1 Sec cubicle type Indoor, floor mounted, auxiliary service board as per specification comprising of : 2 No. - Incoming feeders each with 400ATP ACB with O/C, S/C, E/F release. Suitable to operate from remote and all status to be taken to SCADA , 1 Nos. - Bus coupler feeder with 400A TPN ACB with O/C, S/F, E/F release. Suitable to operate from remote and all status to be taken to SCADA , 4 Nos. - Outgoing feeders with 100A TPN MCCB , 10 Nos. - Outgoing feeders with 63A TPN MCCB , 6 Nos. - Outgoing feeders with 32A TPN MCCB , 10 Nos. - Outgoing feeders with 32A DP MCCB. |
136 | BATTERY, BATTERY CHARGER , Supply and installation of 220V DC, 200 AH lithium Ion battery of plante type complete with accessoriesas per specificationwith 10% spare acid in non-returnable container (In tier arrangement). |
137 | BATTERY, BATTERY CHARGER , Supply and installation of 220V DC battery charger suitable for float and Float cum boostcharger capable of supplying a DC continous load of 40 Amps as per specification and witha common DCDB comprising of : Battery Charger |
138 | BATTERY, BATTERY CHARGER , Supply and installation of 220V DC battery charger suitable for float and Float cum boost charger capable of supplying a DC continous load of 40 Amps as per specification and with a common DCDB comprising of : 1 No. incomer with 250A, DP DCMCCB and to terminate 2 core 50 sqmmAl. cable , 20 Nos. outgoing feeders each with 40/32A DP rotary switch with HRC fuses as per the requirement and as per the approved drawings. |
139 | Supply , installation , testing , commissioning of 3.6MVR 11KV Capacitor Bank. |
140 | Safety equipment , Fire Extinguishers , Supply and installation of CO2 type 5 Kg . |
141 | Safety equipment , Fire Extinguishers , Supply and installation of Dry powder chemical type 25 kg. |
142 | Safety equipment , Fire Extinguishers , Supply and installation of Dry powder chemical type 10 kg. |
143 | Safety equipment , Fire Extinguishers , Supply , testing and installation of 25Kg DCP Type. |
144 | Safety equipment , Fire Extinguishers , Supply , testing and installation of 4nos Fire Bucket with stand (required as per standard). |
145 | Cable Supports and Trays , Supply and Installation of Sheet steel (thickness 2.5 mm) Galvanized ladder and perforated type cable trays with its accessories to be laid in outdoor and indoor cable trenches ( of following various sizes ).600mm, 450 mm, 300mm, 150mm and 100mm width, as per requirement for dressing , Cable Trays , (600 X 50 mm Ladder type ). |
146 | able Supports and Trays , Supply and Installation of Sheet steel (thickness 2.5 mm) Galvanized ladder and perforated type cable trays with its accessories to be laid in outdoor and indoor cable trenches ( of following various sizes ).600mm, 450 mm, 300mm, 150mm and 100mm width, as per requirement for dressing , Cable Trays , (450 X 50 mm Ladder type ). |
147 | Cable Supports and Trays , Supply and Installation of Sheet steel (thickness 2.5 mm) Galvanized ladder and perforated type cable trays with its accessories to be laid in outdoor and indoor cable trenches ( of following various sizes ).600mm, 450 mm, 300mm, 150mm and 100mm width, as per requirement for dressing , Cable Trays , (300 X 50 mm Ladder type). |
148 | Structural Steel , Supply and erection of Substation Galvanized Steel Structure for Towers and Beam |
149 | Cable Supports and Trays , Supply , testing and Installation of Sheet steel (thickness 2.5 mm) Galvanized ladder and perforated type cable trays with its accessories to be laid in outdoor and indoor cable trenches ( of following various sizes ).600mm, 450 mm, 300mm, 150mm and 100mm width, as per requirement for dressing , Cable Trays , (150 x50 mm perforated type). |
150 | Cable Supports and Trays , Supply , testing and Installation of Sheet steel (thickness 2.5 mm) Galvanized ladder and perforated type cable trays with its accessories to be laid in outdoor and indoor cable trenches ( of following various sizes ).600mm, 450 mm, 300mm, 150mm and 100mm width, as per requirement for dressing , Cable Trays , (100 x 50 mm Perforated Type ). |
151 | Structural Steel , Supply and erection of Nuts and bolts for Substation Galvanized Steel Structure for Towers and Beam. |
152 | Structural Steel , Supply and erection of Substation Galvanized Steel Structure for equipments. |
153 | Structural Steel , Supply and erection of Nuts and bollts for Substation Galvanized Steel Structure for equipments. |
154 | Structural Steel , Supply and erection of Anchor bolts. |
155 | Supply and installation of Dewatering pump (portable type) 415 V, 1 HP as per requirement. |
156 | Air conditioning , supply and installation of Split Air-conditioning for Control room (capacity 1.5 Tonne). |
157 | Supply and installation of Bay marshalling kiosk made of 2.5 mm. Thick sheet steel , IP 55 enclosure protection as per specification. |
158 | Testing and Maintenance Equipment, Providing of Meggar 5 KV (Motorized) -1 No. Meggar 1 KV (Motorized) - 1 No. Automatic capacitor and Tan Delta measuring kit -1 No. Digital Multi meter-2 Nos. Leakage tester (Tong type) -2 Nos. Selective level meter -1 No. Signal generator -1 No. Micro-ohm meter -1 No. D-Spanner set (Insulated) -2 Nos. Ring-Spanner set (Insulated) - 2 Nos. Torque wrench set -2 Nos. Insulating gloves-5 sets Helmets -5 set. Spliced ladders 5mtr. - 2 set. Spliced ladders 10mtr. - 2 set. Polyamide or Braided white nylon rope-12 mm (100 mtr). Polyamide or Braided white nylon rope-14 mm(100 mtr). Polyamide or Braided white nylon rope-20 mm(100 mtr). Gapless zinc oxide LA tester-1 No. Oil BDV Kit 0-80 KV -1 No. Gas Evacuating and refilling device -2 set. Gas Leakge Monitor -2 Nos. Circuit Breaker Analyser -1 No. Portable Partial dischange monitoring system -1 No. Dew Point Meter -1 No. Gas Masks -1 No. Relay Test Kit -1 No. Primary Injection Set 1000 Amp -1 No. |
159 | Aluminum Power Cables , Supply and Laying of 1100 V grade, PVC insulated, PVC sheathed, steel round wire armoured, stranded control cables of the following sizes: 4 Core x 10 sqmm (Aluminum) , 4 Core x 16 sqmm (Aluminum) , 3.5 Core x 35 sqmm (Aluminum). |
160 | Design, Manufacturing, Testing at Manufacturer`s works, Forwarding and packing, transportation, Delivery at site, Storage, Erection, Site Testing, Commissioning and handing over of the following equipment`s / items, complete with all accessories and as per enclosed specification, data sheets, drawings etc. Please refer the bid document for the completeness of the scope and the general technical requirements for each item given under. (Data Sheets and Guaranteed Technical particulars for all the equipment`s are required to be attached with bid). Supply , installation , testing and commissioning of 250 KVA, Copper Wound 11/0.433kV 3ph, Dyn-11, outdoor type `with OFF load tap changer and cable box on HV?LV sides. |
161 | Design, Manufacturing, Testing at Manufacturer`s works, Forwarding and packing, transportation, Delivery at site, Storage, Erection, Site Testing, Commissioning and handing over of the following equipments / items, complete with all accessories and as per enclosed specification, data sheets, drawings etc. Please refer the bid document for the completeness of the scope and the general technical requirements for each item given under. (Data Sheets and Guaranteed Technical particulars for all the equipments are required to be attached with bid). The quantities are given under, however requirements shall be as per the technical specification and detailed engineering to be carried out by the bidder. 66 KV EQUIPMENTSsupply , installation and commissioning of 60KV,10KA,Zinc oxide type, heavy duty, station class, lightning arrestor. |
162 | Providing and installation ofof First Aid box and accident prevention chart. |
163 | Foundation for bay extention in Daultabad:- Steel structure for the following foundations:-Foundation of 66 KV CT Transformers , Foundation of 66 KV CT Metering , Foundation of 66 KV PT Metering , Foundation of 66 KV SF-6 BREAKER, Foundation of 66 KV CT LandE Switch , Foundation of 66 KV LA Line , Foundation of 66 KV CT Protection , Foundation of 66 KV PT PROTECTION ,Foundation of 66 KV PT bus bar , Foundation of 66 KV LA transformer , Foundation of 66 KV Isolator and Foundation of 66 KV CT-4 as needed and in accordance with approved design and drawings including excavation and refilling of soil complete in all respect and any other work contingent thereto as per sizes and specification given in DNIT (Steel reinforcement for R.C.C. work, where not included in the complete rate of RCC, including straightening, cutting, bending, placing in position, binding, wastage, overlaps, welded joints, spacer bars, chairs, stays, hangers and annealed steel wire etc. complete in all respect below plinth level Note:- Reinforcement shall be measured in length including hooks, if any, separately for different diameters as actually used in work , excluding overlaps. Wastage, overlaps, couplings, welded joints, spacer bars, chairs, stays, hangers and annealed steel wire or other methods of binding and placing shall not be measured and cost of these items shall be deemed to be included in the rates for reinforcement.Thermo- Mechanically Treated bars of grade Fe-500D kg or more ( for M-30) . |
164 | Earth mat:- Design , supply , and erection of earth mat work which includes 16mm thick rod and 20mm thick earth electrodes in accordance with approved design and drawings including excavation and refilling of soil complete in all respect and any other work contingent thereto as per sizes and specification given in DNIT.Thermo-Mechanically Treated bars of grade Fe- 500D kg or more( for M-30). |
165 | Yard : Steel reinforcement for R.C.C. work, where not included in the complete rate of RCC, including straightening, cutting, bending, placing in position, binding, wastage, overlaps, welded joints, spacer bars, chairs, stays, hangers and annealed steel wire etc. complete in all respect below plinth level Note:- Reinforcement shall be measured in length including hooks, if any, separately for different diameters as actually used in work , excluding overlaps. Wastage, overlaps, couplings, welded joints, spacer bars, chairs, stays, hangers and annealed steel wire or other methods of binding and placing shall not be measured and cost of these items shall be deemed to be included in the rates for reinforcement.Thermo- Mechanically Treated bars of grade Fe-500D kg or more ( for M-30) . |
166 | Foundationfor bay extension in Daultabad :- Design and construction of RCC Grade M30 Using Concrete Mixer C.C of M30 concrete platforms for Foundation of 66 KV CT Transformers , Foundation of 66 KV CT Metering , Foundation of 66 KV PT Metering , Foundation of 66 KV SF-6 BREAKER, Foundation of 66 KV CT LandE Switch , Foundation of 66 KV LA Line , Foundation of 66 KV CT Protection , Foundation of 66 KV PT PROTECTION ,Foundation of 66 KV PT bus bar , Foundation of 66 KV LA transformer , Foundation of 66 KV Isolator and Foundation of 66 KV CT-4 including excavation and back filling as required to the complete satisfaction of Engineer-in-charge as needed and in accordance with approved design and drawings including excavation and refilling of soil complete in all respect and any other work contingent thereto as per sizes and specification given in DNIT. |
167 | Yard for bay extention in daultabad :- Designing and construction of yard with 100mm thick C.C of M30 concrete after preparation of plinth( i.e compaction and filling of soil followed by 75mm M-10 concrete and so as to achieve the final plinth level which should be 0.75 meter above the existing road level of WTP Basai.) including cable trenches , all electrical , mechanical works in accordance with approved design and drawings and all other works contingent thereto as per sizes and specification given in DNIT(ITEM For M-30). |
168 | Yard for bay extention in Daultabad :- Designing and construction of yard with 100mm thick C.C of M30 concrete after preparation of plinth( i.e compaction and filling of soil followed by 75mm M-10 concrete and so as to achieve the final plinth level which should be 0.75 meter above the existing road level of WTP Basai) including cable trenches , all electrical , mechanical works in accordance with approved design and drawings and all other works contingent thereto as per sizes and specification given in DNIT(ITEM for M-10). |
169 | ERECTION PORTION (OverheadplusUnderground Line) , Detail Survey as per tentative route , which includes the following major activities-Pegging of line route, providing of survey pillar at an interval of 3-4 KM in the line route with required jungle clearance for survey, profile preparation of approved route on graph sheet and marking of offset on either side of the line, marking of side clearence for hills sand dunes etc as per specification and tower sheduling. |
170 | ERECTION PORTION (Overhead plus Underground Line) , Check survey as per approved route of line which Includes : Re-checklng of the line route as per approved profile, chainage. tower center marking, pit marking, bisection of angle tower as required at site. |
171 | ERECTION PORTION (Overhead plus Underground Line) , Soil Investigation , Detailed Soil Investigation upto a depth of 7 mtr in soil and 3 Mtr in rock Strata in Normal conditions and 40 mtr in Special Locations , All kinds of soil except fissured rock and hard rock |
172 | SETTING OF TEMPLATE and STUB/ANCHOR BOLT , Setting of template and stub/ anchor bolt and removal after concreting, excluding cost of excavation and concreting but including back filling with excavated/ borrowed earth (with lead and lift) in layers with ramming and watering as per specification , A) 66KV Double Circuit Tower uptoplus 6m, extension : (i) Suspension Tower (DA) |
173 | SETTING OF TEMPLATE and STUB/ANCHOR BOLT , Setting of template and stub/ anchor bolt and removal after concreting, excluding cost of excavation and concreting but including back filling with excavated/ borrowed earth (with lead and lift) in layers with ramming and watering as per specification , A) 66KV Double Circuit Tower upto plus 6m, extension : Medium angle Tower (DC) |
174 | SETTING OF TEMPLATE and STUB/ANCHOR BOLT , Setting of template and stub/ anchor bolt and removal after concreting, excluding cost of excavation and concreting but including back filling with excavated/ borrowed earth (with lead and lift) in layers with ramming and watering as per specification , A) 66KV Double Circuit Tower upto plus 6m, extension : Heavy angle cum dead end Tower (DD) |
175 | SETTING OF TEMPLATE and STUB/ANCHOR BOLT , Setting of template and stub/ anchor bolt and removal after concreting, excluding cost of excavation and concreting but including back filling with excavated/ borrowed earth (with lead and lift) in layers with ramming and watering as per specification , A) 66KV Double Circuit Tower upto plus 6m, extension : Xing Gantryand SS Gantry |
176 | EARTHING: (A) Earthing of towers with pipe type earthing excluding the supply of pipes, wires, flats and connectors, but including coke/charcoal, etc.,excavatlon,augering and backfilling in all types of soil. |
177 | ERECTION OF TOWERS: Erection of super structures Including D-shackles, ACD, Hangers, U-Bolts, step bolts, danger plate, phase plate, number plate etc. Also Including tack welding of bolts and nuts up to bottom cross arm/beam level Including application of Zinc rich paint.` (A) 66 KV Double Circuit Tower Upto 12 mtr. Ext (i) Suspension Tower (DA) ii) Light angle Tower (DB) (iii) Medium angle Tower (DC) (iv) Heavy angle cum dead end Tower (DD) (v) Xing Gantryand SS Gantry |
178 | CONDUCTOR STRINGING (A) Stringing of ACSR Zebra Including hoisting of Insulator string, laying, Jointing and tensioning of conductor, clamping with Armour rods and fixing of vibration damper per route KM of the line. (i) 3 conductor for D/C Line |
179 | EARTHWIRE STRING (A) Stringing of galvanised steel stranded wire Including laying jointing and tensioning, clamping.clipping and fixing vibration damper and earth bond etc. (i) One No. 7/3.15mm galvanised wire. |
180 | ERECTION OF XLPE CABLE ERECTION (0.2km) (A) Detailed Cable Survey |
181 | ERECTION OF XLPE CABLE ERECTION (0.2km) , 66kV,4Rx1Cx1200sqmm,XLPE cable with HDPE Pipe including jointing and termination etc. |
182 | XLPE CABLE TRENCHLESS CONSTRUCTION (A) Construction 2 meter width 1.5 meter depth and 200 meter long trench including brick work, send filling etc. for 66kV,4Rx1Cx1200sqmm,XLPE cable as per technical . |
183 | SUPPLY PORTION , TOWERS , EARTHWIRE HARDWARE`S : I)SUSPENSION ASSEMBLY |
184 | SUPPLY PORTION , TOWERS , EARTHWIRE HARDWARE`S : TENSION ASSEMBLY |
185 | SUPPLY PORTION , TOWERS , EARTHWIRE HARDWARE`S : MID SPAN COMPRESSION JOINT |
186 | SUPPLY PORTION , TOWERS , EARTHWIRE HARDWARE`S : VIBRATION DAMPER |
187 | SUPPLY PORTION , TOWERS , EARTHWIRE HARDWARE`S : FLEXIBLE COPPER BOND |
188 | SUPPLY PORTION , EARTHING : I) PIPE TYPE |
189 | SUPPLY PORTION , TOWER ACCESSORIES : Danger Plate |
190 | SUPPLY PORTION , TOWER ACCESSORIES : Number Plate |
191 | SUPPLY PORTION , TOWER ACCESSORIES : Phase Plate(sets of 3) |
192 | SUPPLY PORTION , TOWER ACCESSORIES : Anticlimbing Device |
193 | SUPPLY PORTION , TOWERS , Fabrication, galvanising and supply of various type of tower and tower parts, tower extensions (complete) including bolts and nuts, step bolts andhangers, D- shackles, pack washer etc butexcluding stubs. |
194 | SUPPLY PORTION , XLPE CABLE (960.00 Meter Approx) , Supply 66kV,4Rx1Cx1200sqmm,XLPE cable 960.00 meter approx with HDPE PIPE including jointing and termination kit, support structure, cable tie etc.` |
195 | SUPPLY PORTION , TOWERS , Fabrication, galvanisingand supply of stubs and cleats for various type of towers, tower extensions (complete) with pack washers, including bolts and nuts. |
196 | SUPPLY PORTION , TOWERS , Fabrication, galvanisingand supply of various type of Templates, Templates extensions (complete) with pack washers, including bolts and nuts |
197 | SUPPLY PORTION , TOWERS ,Supply of Galvanised Boltsand Nuts, pack washers, step bolt, hangers, D- shackles s etc.for Towers. |
198 | SUPPLY PORTION , LINE MATERIAL , ACSR ZEBRA CONDUCTOR. |
199 | SUPPLY PORTION , LINE MATERIAL , EARTHWIRE 7/3.15MM STEEL. |
200 | SUPPLY PORTION , LINE MATERIAL , INSULATORS : 120KN |
201 | SUPPLY PORTION , LINE MATERIAL , CONDUCTOR HARDWARE`S : SINGLE SUSPENSION ASSEMBLY |
202 | SUPPLY PORTION , LINE MATERIAL , CONDUCTOR HARDWARE`S : SINGLE TENSION ASSEMBLY |
203 | SUPPLY PORTION , LINE MATERIAL , CONDUCTOR HARDWARE`S : MID SPAN COMPRESSION JOINT |
204 | SUPPLY PORTION , LINE MATERIAL , CONDUCTOR HARDWARE`S :REPAIR SLEEV |
205 | SUPPLY PORTION , LINE MATERIAL , CONDUCTOR HARDWARE`S : Vibration damper |
206 | SUPPLY PORTION , TOWER ACCESSORIES : Bird Guard in all towers. |
207 | SUPPLY PORTION , LINE MATERIAL , INSULATORS : 90 KN |
208 | Excavation for Structures Earth work in excavation of foundation of structures as per drawing and technical specification, including setting out, construction of shoring and bracing, removal of stumps and other deleterious matter, dressing of sides and bottom and backfilling with approved material, Ordinary soil, Manual Means , Depth up to 3 m , Note:- 1. Dewatering if required , 10 per cent of labour cost Assessment for dewatering shall be made as per site conditions. 2.The excavated earth can be used partially for backfilling of foundation pit and partly for road work except for marshy soil. Hence cost of disposal has not been added except for marshy soil. This remark is common to all cases of item 15.1 excluding marshy soil. 3.The cost of shoring and shuttering, where needed, may be added @ 1 per cent on cost of excavation for open foundation. |
209 | Supply and erection of Steel including Cutting, bendlng.weldlng of joints if required .fixing and placing of steel reinforcementin accordance with approved design and drawings including excavation and refilling of soil complete in all respect and any other work contingent thereto as per sizes and specification given in DNIT(Thermo-Mechanically Treated bars of grade Fe- 500D or more). |
210 | C/C for tower foundation:- Providing and laying in position ready mixed plain cement concrete, using fly ash and cement content as per approved design mix and manufactured in fully automatic batching plant and transported to site of work in transit mixer for all leads, having continuous agitated mixer, manufactured as per mix design of specified grade for plain cement concrete work, including pumping of R.M.C. from transit mixer to site of laying and curing, excluding the cost of centering, shuttering and finishing, including cost of curing, admixtures in recommended proportions as per IS : 9103 to accelerate/ retard setting of concrete, improve workability without impairing strength and durability as per direction of the Engineer- in-charge. Note: Fly ash conforming to grade I of IS 3812 (Part-1) only be used as part replacement of OPC as per IS : 456. Uniform blending with cement is to be ensured in accordance with clauses 5.2 and 5.2.1 of IS: 456 -2000 in the items of BMC and RMC.M-10 grade plain cement concrete cum (cement content considered @ 220 kg/cum)1:4:8 Mix (M-10). |
211 | C/C for tower foundation:- Providing and laying in position ready mixed M-25 grade concrete for reinforced cement concrete work, using cement content as per approved design mix, manufactured in fully automatic batching plant and transported to site of work in transit mixer for all leads, having continuous agitated mixer, dewatering if needed , manufactured as per mix design of specified grade for reinforced cement concrete work, including pumping of R.M.C. from transit mixer to site of laying , excluding the cost of centering, shuttering finishing and reinforcement, including cost of admixtures in recommended proportions as per IS : 9103 to accelerate/ retard setting of concrete, improve workability without impairing strength and durability as per direction of the Engineer-in-charge. (Note :- Cement content considered in this item is@ 330 kg/cum. Less cement used as per design mix is recoverable. However no extra payment shall be made if excess cement is used as per design mix)1:1.5:3 Mix (M-25). |
212 | Control room building :- Designing and construction of RCC M-25 Framed structure building confirming to national building code for building in accordance with approved design and drawings with single story building height 5.00mtr or more as required, including cable trenches , all electrical , mechanicaland Sanitary works and all other works contingent thereto as per sizes and specification given in DNIT. |
213 | Road :- Designing and construction of 6m wide C.C road and the main road leading to 66KV switch yard shall have a embankment as gradient with 150mm thick (1:3:6) with concrete base and 200mm thick M-25 design mix concrete with kerb and channels in accordance with approved design and drawings , Supply and installation of 8.00 Mtr high LED solar street light at 30m c/c , main gates walkways , levelling etc. complete in all respect and any other work contingent thereto as per sizes and specification given in DNIT. |
214 | Foundation:- Steel structure for the following foundations:-Foundation of 66 KV CT Transformers , Foundation of 66 KV CT Metering , Foundation of 66 KV PT Metering , Foundation of 66 KV SF-6 BREAKER, Foundation of 66 KV CT LandE Switch , Foundation of 66 KV LA Line , Foundation of 66 KV CT Protection , Foundation of 66 KV PT PROTECTION ,Foundation of 66 KV PT bus bar , Foundation of 66 KV LA transformer , Foundation of 66 KV Isolator and Foundation of 66 KV CT-4 as needed and in accordance with approved design and drawings including excavation and refilling of soil complete in all respect and any other work contingent thereto as per sizes and specification given in DNIT(Steel reinforcement for R.C.C. work, where not included in the complete rate of RCC, including straightening, cutting, bending, placing in position, binding, wastage, overlaps, welded joints, spacer bars, chairs, stays, hangers and annealed steel wire etc. complete in all respect below plinth level Note:- Reinforcement shall be measured in length including hooks, if any, separately for different diameters as actually used in work , excluding overlaps. Wastage, overlaps, couplings, welded joints, spacer bars, chairs, stays, hangers and annealed steel wire or other methods of binding and placing shall not be measured and cost of these items shall be deemed to be included in the rates for reinforcement.Thermo- Mechanically Treated bars of grade Fe-500D kg or more ( for M-30) . |
215 | Foundation :- Design and construction of RCC Grade M30 Using Concrete Mixer C.C of M30 concrete platforms for Foundation of 66 KV CT Transformers , Foundation of 66 KV CT Metering , Foundation of 66 KV PT Metering , Foundation of 66 KV SF-6 BREAKER, Foundation of 66 KV CT LandE Switch , Foundation of 66 KV LA Line , Foundation of 66 KV CT Protection , Foundation of 66 KV PT PROTECTION ,Foundation of 66 KV PT bus bar , Foundation of 66 KV LA transformer , Foundation of 66 KV Isolator and Foundation of 66 KV CT-4 including excavation and back filling as required to the complete satisfaction of Engineer-in-charge as needed and in accordance with approved design and drawings including excavation and refilling of soil complete in all respect and any other work contingent thereto as per sizes and specification given in DNIT. |
216 | Earth mat:- Design , supply , and erection of earth mat work which includes 16mm thick rod and 20mm thick earth electrodes in accordance with approved design and drawings including excavation and refilling of soil complete in all respect and any other work contingent thereto as per sizes and specification given in DNIT (Steel reinforcement, including straightening, cutting, bending, placing in position, binding, wastage, overlaps, welded joints, spacer bars, chairs, stays, hangers and annealed steel wire etc. complete in all respect below plinth level.Thermo- Mechanically Treated bars of grade Fe-500D or more). |
217 | Yard : Steel reinforcement for R.C.C. work, where not included in the complete rate of RCC, including straightening, cutting, bending, placing in position, binding, wastage, overlaps, welded joints, spacer bars, chairs, stays, hangers and annealed steel wire etc. complete in all respect below plinth level Note:- Reinforcement shall be measured in length including hooks, if any, separately for different diameters as actually used in work , excluding overlaps. Wastage, overlaps, couplings, welded joints, spacer bars, chairs, stays, hangers and annealed steel wire or other methods of binding and placing shall not be measured and cost of these items shall be deemed to be included in the rates for reinforcement.Thermo- Mechanically Treated bars of grade Fe-500D kg or more ( for M-30) . |
218 | Yard :- Designing and construction of yard with 100mm thick C.C of M30 concrete after preparation of plinth( i.e compaction and filling of soil followed by 75mm M- 10 concrete and so as to achieve the final plinth level which should be 0.75 meter above the existing road level of WTP Basai.) including cable trenches , all electrical , mechanical works in accordance with approved design and drawings and all other works contingent thereto as per sizes and specification given in DNIT(ITEM For M-30) |
219 | Yard :- Designing and construction of yard with 100mm thick C.C of M30 concrete after preparation of plinth( i.e compaction and filling of soil followed by 75mm M- 10 concrete and so as to achieve the final plinth level which should be 0.75 meter above the existing road level of WTP Basai.) including cable trenches , all electrical , mechanical works in accordance with approved design and drawings and all other works contingent thereto as per sizes and specification given in DNIT(ITEM for M-10). |
220 | Boundary wall:- Designing and construction of boundary wall of 66 KV substation in WTP Basai with height shall be 1.50Mtr with RCC pillar @3Mtr C/C as per design / drawing foundation of boundary wall shall be minimum 0.90m below natural ground level. |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy