Tender For Design, Supply And Erection Of 66/11 Kv Outdoor Substation At Basai Water Works, Gurugram By Providing 2 X 12.5 16 Mva 66/11 Kv Transformer And Its Associated 66Kv Single Circuit Line On Krr Design For Double Circuit 66 Kv Towers (Dcss, gurugram-Haryana

Gurugram Metropolitan Development Authority-GMDA has published Tender For Design, Supply And Erection Of 66/11 Kv Outdoor Substation At Basai Water Works, Gurugram By Providing 2 X 12.5 16 Mva 66/11 Kv Transformer And Its Associated 66Kv Single Circuit Line On Krr Design For Double Circuit 66 Kv Towers (Dcss. Submission Date for this Tender is 13-01-2023. Transformer Supply Tenders in gurugram Haryana. Bidders can get complete Tender details and download the document.




Tender Notice

35055000
Corrigendum : Tender For Design, Supply And Erection Of 66/11 Kv Outdoor Substation At Basai Water Works, Gurugram By Providing 2 X 12.5 16 Mva 66/11 Kv Transformer And Its Associated 66Kv Single Circuit Line On Krr Design For Double Circuit 66 Kv Towers (Dcss
Open Tender
Indian
Haryana
gurugram
13-01-2023

Tender Details

Design, Supply And Erection Of 66 / 11 Kv Outdoor Substation At Basai Water Works, Gurugram By Providing 2 X 12.5 16 Mva 66 / 11 Kv Transformer And Its Associated 66Kv Single Circuit Line On Krr Design For Double Circuit 66 Kv Towers ( Dcss Transmissi

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 20-Dec-2022 Corrigendum Date 05-01-2023
2 05-Jan-2023 Corrigendum1 Date 13-01-2023

Key Value

Document Fees
INR 1000 /-
EMD
INR 5166000.0 /-
Tender Value
INR 25.82 Crore /-

BOQ Items

Name of Work: Design, Supply and Erection of 66/11 KV Outdoor Substation at Basai Water works, Gurugram, by providing 2 x 12.5/ 16 MVA 66/11 KV transformer and its associated 66KV single circuit line on KRR Design for Double circuit 66 KV towers (DCSS Transmission Line) with Zebra conductor (adopted by HVPN) from 220 KV HVPN S/stn. Daultabad on turnkey basis. A/c Rs. 25.83 Crore
Sl. No. Item Description
1Design, Manufacturing, Testing at Manufacturer`s works, Forwarding and packing, transportation, Delivery at site, Storage, Erection, Site Testing, Commissioning and handing over of the following equipments/ items, complete with all accessories and as per enclosed specification, data sheets, drawings etc. Please refer the bid document for the completeness of the scope and the general technical requirements for each item given under. (Data Sheets and Guaranteed Technical particulars for allthe equipments are required to be attached with bid). The quantities are given under, however requirements shall be as per the technical specification and detailed engineering to be carried out by the bidder.upply , installation and commissioning of 72.5KV ,1250A, 25KA for 1 sec, SF6 Circuit Breaker, 3 Ph gang operated complete with operating mechanism andsupport structure.
2Design, Manufacturing, Testing at Manufacturer`s works, Forwarding and packing, transportation, Delivery at site, Storage, Erection, Site Testing, Commissioning and handing over of the following equipments/ items, complete with all accessories and as per enclosed specification, data sheets, drawings etc. Please refer the bid document for the completeness of the scope and the general technical requirements for each item given under. (Data Sheets and Guaranteed Technical particulars for allthe equipments are required to be attached with bid). The quantities are given under, however requirements shall be as per the technical specification and detailed engineering to be carried out by the bidder.Supply , installation and commissioning 72.5KV ,800A,3 Ph gang operated double break type manual operated disconnector (Isolator) with solid core post insulator(Without earth switch).
3Design, Manufacturing, Testing at Manufacturer`s works, Forwarding and packing, transportation, Delivery at site, Storage, Erection, Site Testing, Commissioning and handing over of the following equipments / items, complete with all accessories and as per enclosed specification, data sheets, drawings etc. Please refer the bid document for the completeness of the scope and the general technical requirements for each item given under. (Data Sheets and Guaranteed Technical particulars for all the equipments are required to be attached with bid). The quantities are given under, however requirements shall be as per the technical specification and detailed engineering to be carried out by the bidder. 66 KV Equipments Supply , installation and commissioning 72.5KV ,800A, 3 Ph gang operated double break type manual operated disconnector (Isolator) with solid core post insulator (With earth switch).
4Design, Manufacturing, Testing at Manufacturer`s works, Forwarding and packing, transportation, Delivery at site, Storage, Erection, Site Testing, Commissioning and handing over of the following equipments / items, complete with all accessories and as per enclosed specification, data sheets, drawings etc. Please refer the bid document for the completeness of the scope and the general technical requirements for each item given under. (Data Sheets and Guaranteed Technical particulars for all the equipments are required to be attached with bid). The quantities are given under, however requirements shall be as per the technical specification and detailed engineering to be carried out by the bidder. 66 KV EQUIPMENTS Supply , installation and commissioning of 72.5KV Out door single phase current transformers of ratio Line feeder:600-300-150/1-1-1-1A, refer CT design parameters as per the Technical specifications
5Design, Manufacturing, Testing at Manufacturer`s works, Forwarding and packing, transportation, Delivery at site, Storage, Erection, Site Testing, Commissioning and handing over of the following equipments / items, complete with all accessories and as per enclosed specification, data sheets, drawings etc. Please refer the bid document for the completeness of the scope and the general technical requirements for each item given under. (Data Sheets and Guaranteed Technical particulars for all the equipments are required to be attached with bid). The quantities are given under, however requirements shall be as per the technical specification and detailed engineering to be carried out by the bidder. 66 KV EQUIPMENTS Supply , installation and commissioning of 66 KV capacitive voltage transformer (66/v3/110V/v3/110V/v3/110V/v3) CORE-1 CL:0.2,50VA, CORE-2 CL:3P,50VA and CORE-3 CL:3P,50VA.
6Substation Bay Hardware Supply , Installation and commissioning of Single tension line hardware fitting bolted type clamp suitable for single tension insulated string of 6 no. 11 KV 90 KN Disc insulators, Shackle suitable for 20 mm anchoring hole on beam side, without turn buckle forSINGLE ACSR ZEBRA conductor.
7Substation Bay Hardware Supply , Installation and commissioning of Single tension line hardware fitting bolted type clamp suitable for single tension insulated string of 6 no. 11 KV 90 KN Disc insulators, Shackle suitable for 20 mm anchoring hole on beam side, with turn buckle forSINGLE ACSR ZEBRA conductor.
8Substation Bay Hardware Supply , Installation and commissioning of Single suspension linehardware fitting boltedtypesuitablefor 1x5 nos. 11kV, 70kN EMS disc insulatoralong shackle suitablefor 20 mm anchoring hole on beamsuitable for SINGLE ACSR ZEBRA conductor complete with U BOLT and I BOLT ETC. DROP TYPE.
9Substation Bay Hardware Supply , Installation and commissioning of 90 KN Disc insulator BandS type.
10Substation Bay Hardware Supply , Installation and commissioning of 70 KN Disc insulator BandS type.
11Substation Bay Hardware Supply , Installation and commissioning of Tee Connector and Power connectors of suitable current rating for individual equipment terminal pad and Single Zebra ACSR conductors on 66 KV side , Tee connector for single Zebra conductor through and same tee off.
12Substation Bay Hardware Supply , Installation and commissioning of Tee Connector and Power connectors of suitable current rating for individual equipment terminal pad and Single Zebra ACSR conductors on 66 KV side , Terminal connector for 72.6kV Isolator to receive SINGLE ACSR ZEBRA Conductor.
13Substation Bay Hardware Supply , Installation and commissioning of Tee Connector and Power connectors of suitable current rating for individual equipment terminal pad and Single Zebra ACSR conductors on 66 KV side , Terminal connector for 72.6kV SF6 Circuit Breaker to receive SINGLE ACSR ZEBRA Conductor
14Substation Bay Hardware Supply , Installation and commissioning of Tee Connector and Power connectors of suitable current rating for individual equipment terminal pad and Single Zebra ACSR conductors on 66 KV side , Terminal connector for 72.6kV Current Transformer to receive SINGLE ACSR ZEBRA Conductor.
15Substation Bay Hardware Supply , Installation and commissioning of Tee Connector and Power connectors of suitable current rating for individual equipment terminal pad and Single Zebra ACSR conductors on 66 KV side , Terminal connector for 60kV Lightning Arrester to receive Single ACSR Zebra Conductor.
16Substation Bay Hardware Supply , Installation and commissioning of Tee Connector and Power connectors of suitable current rating for individual equipment terminal pad and Single Zebra ACSR conductors on 66 KV side , Terminal connector for 72.6kV CVT connector to receive Single ACSR ZEBRA Conductor.
17Substation Bay Hardware Supply , Laying of ZEBRA ACSR conductor
18Substation Bay Hardware Supply , Installation and commissioning of Earth Wire Connector (PG Clamps).
19Substation Bay Hardware Supply , Laying of 7/3.15 mm GSS wire for shielding .
20Substation Bay Hardware Supply , Installation and commissioning of Hardware for 7/3.15 mm GSS wire pad type clamps.
21LT CABLE , 1.1 KV PVC insulated and sheathed, steel armoured cable of the following size including cable support (For AC supply and yard lighting) Supply and Laying of 3 core x 2.5 sqmm Cu conductor cable (GI round wire armoured) for control Gear to Lamp fixture.
22LT CABLE , 1.1 KV PVC insulated and sheathed, steel armoured cable of the following size including cable support (For AC supply and yard lighting) Supply and Laying of 4 core x 10 sqmmAl.Conductor cable (GI round wire armoured)for Street light panel to light fitting Control gear.
23LT CABLE , 1.1 KV PVC insulated and sheathed, steel armoured cable of the following size including cable support (For AC supply and yard lighting) Supply and Laying of 4 core x 16 sqmmAl. Conductor cable (GI round wire armoured) for Street light panel from ACDB.
24LT CABLE , 1.1 KV PVC insulated and sheathed, steel armoured cable of the following size including cable support (For AC supply and yard lighting) Termination with double compression gland andlugs for item 4 core x 16 sqmm , 4 core x 10 sqmm , 3 core x 2.5 sqmm.
25LT CABLE , 1.1 KV PVC insulated and sheathed, steel wire armoured Aluminum conductor cable of the following size (For AC and DC Supply) , Supply and laying of 3.5 core x 50 sqmm Al conductor cable ( GI Strip armoured) for ACDB to Battery charger.
26LT CABLE , 1.1 KV PVC insulated and sheathed, steel wire armoured Aluminum conductor cable of the following size (For AC and DC Supply) , Supply and laying of 2 core x 50 sqmmcopper conductor cable (For DC) Battery charger to Battery.
27LT CABLE , 1.1 KV PVC insulated and sheathed, steel wire armoured Aluminum conductor cable of the following size (For AC and DC Supply) , Double compression glands and Cu/Al lugs with sleeves for 1100V grade PVC insulated, multicore aluminum conductor auxiliary power cables of the following sizes: Supply and erection of 3 1/2 core x 50 sqmmAl. cable.
28LT CABLE , 1.1 KV PVC insulated and sheathed, steel wire armoured Aluminum conductor cable of the following size (For AC and DC Supply) , Double compression glands and Cu/Al lugs with sleeves for 1100V grade PVC insulated, multicore aluminum conductor auxiliary power cables of the following sizes: Supply and erection of 2 core x 50 sqmmcopper cable
29Supply and Erection of Double compression glands and terminations(including ferruling, suitable Cu Lugs to meet the system requirements) for 1100V grade PVC insulated multicore Copper stranded conductor control cables ofthe following sizes: 3 core 2.5 sqmm , 5 core 2.5 sqmm , 7 core 2.5 sqmm , 10 core 2.5 sqmm , 19 Core 2.5 sqmm , 4Core 4 sqmm ( For CT supply) , 2 Core 6 sqmm (For D.C.) , 4 Core x 10 sqmm (Aluminum) , 4 Core x 16 sqmm (Aluminum) , 3.5 Core x 35 sqmm (Aluminum).
30Lighting , Supply and Erection of Flood light fitting with 150 W LED lamp.
31Lighting , Supply and Installation of Steel tubular pole 10 mtr long, SP -33 with base plate and cross arm 1.5 mtr long with arrangement for fixing the luminaire 85 W LED fitting with suitable junction box.
32Lighting , Supply and installation of Lighting junction box for each Light at tower suitable for out door installation comprising of 8 no. CBT M 4 type terminal connector for light connections or loop in / loop out cable.
33EARTHING ANDLIGHTNING PROTECTION , Supply and Erection of Main Earth mat, Aux Earth mat and Earthing Risers for Main Equipmentsand structures etc ( 75 x 12 mm G I flat).
34EARTHING AND LIGHTNING PROTECTION , Supply and Erection of Earthing conductor for connection of , L.T panel, Junction box, and building Lightning risers and peak Connection etc(50x6 GI flat).
35EARTHING AND LIGHTNING PROTECTION , Supply and Erection of 50x6 mm MS flat for cable trench earthing.
36EARTHING AND LIGHTNING PROTECTION , Supply and Erection of 40 mm dia 3 m long GI pipe earth electrode with treated earth Pit for LA and CVT.
37EARTHING AND LIGHTNING PROTECTION , Supply and Erection of 40 mm Dia 3 mtr longM.S. rod earth electrode (driven) for each peak tower, building lightning protection and yard earth mat.
38Control and Relay Panel , Indoor floor mounted, simplex type control and relay panels, with mimic and annunciation panelfor 66kV system as per specification and data sheet comprising of : 66kV Ckt. Breaker control panel without auto reclose and Line Protection Panel
39Safety equipment , Fire Extinguishers , Supply and installation of CO2 type 5 Kg .
40Cable Supports and Trays , Supply and Installation of Sheet steel (thickness 2.5 mm) Galvanized ladder and perforated type cable trays with its accessories to be laid in outdoor and indoor cable trenches ( of following various sizes ).600mm, 450 mm, 300mm, 150mm and 100mm width, as per requirement for dressing , Cable Trays , (600 X 50 mm Ladder type ).
41able Supports and Trays , Supply and Installation of Sheet steel (thickness 2.5 mm) Galvanized ladder and perforated type cable trays with its accessories to be laid in outdoor and indoor cable trenches ( of following various sizes ).600mm, 450 mm, 300mm, 150mm and 100mm width, as per requirement for dressing , Cable Trays , (450 X 50 mm Ladder type ).
42Cable Supports and Trays , Supply and Installation of Sheet steel (thickness 2.5 mm) Galvanized ladder and perforated type cable trays with its accessories to be laid in outdoor and indoor cable trenches ( of following various sizes ).600mm, 450 mm, 300mm, 150mm and 100mm width, as per requirement for dressing , Cable Trays , (300 X 50 mm Ladder type).
43Structural Steel , Supply and erection of Substation Galvanized Steel Structure for Towers and Beam
44Cable Supports and Trays , Supply , testing and Installation of Sheet steel (thickness 2.5 mm) Galvanized ladder and perforated type cable trays with its accessories to be laid in outdoor and indoor cable trenches ( of following various sizes ).600mm, 450 mm, 300mm, 150mm and 100mm width, as per requirement for dressing , Cable Trays , (150 x50 mm perforated type).
45Cable Supports and Trays , Supply , testing and Installation of Sheet steel (thickness 2.5 mm) Galvanized ladder and perforated type cable trays with its accessories to be laid in outdoor and indoor cable trenches ( of following various sizes ).600mm, 450 mm, 300mm, 150mm and 100mm width, as per requirement for dressing , Cable Trays , (100 x 50 mm Perforated Type ).
46Structural Steel , Supply and erection of Nuts and bolts for Substation Galvanized Steel Structure for Towers and Beam.
47Structural Steel , Supply and erection of Substation Galvanized Steel Structure for equipments.
48Structural Steel , Supply and erection of Nuts and bollts for Substation Galvanized Steel Structure for equipments.
49Structural Steel , Supply and erection of Anchor bolts.
50Supply and installation of Dewatering pump (portable type) 415 V, 1 HP as per requirement.
51Supply and installation of Bay marshalling kiosk made of 2.5 mm. Thick sheet steel , IP 55 enclosure protection as per specification.
52Substation Bay Hardware , Single tension hardware fitting bolted type clamp suitable for single tension insulated string of 6 no. 11 KV 90 KN Disc insulators, Shackle suitable for 20 mm anchoring hole on beam side, without turn buckle for Double ACSR ZEBRA conductor.
53Substation Bay Hardware , Single tension line hardware fitting bolted type clamp suitable for single tension insulated string of 6 no. 11 KV 90 KN Disc insulators, Shackle suitable for 20 mm anchoring hole on beam side, with turn buckle for Double ACSR ZEBRA conductor .
54Substation Bay Hardware , Single suspension linehardware fitting boltedtype suitablefor 1x5 nos. 11kV, 70kN EMS disc insulator along shackle suitablefor 20 mm anchoring hole on beamsuitable for Double ACSR ZEBRA conductor complete with U BOLT and I BOLT ETC. DROP TYPE
55Supply and erection of Tension Fittings for 7/3.15mm Earthwire
56Supply and erection of Hardware for 7/3.15 mm GSS wire-Cleat type clamps.
57Supply and laying of Copper Control Cable , 1100 V grade, PVC insulated, PVC sheathed, steel round wire armoured, strandedcontrol cables of the following sizes: 3 core2.5 sqmm , 5 core2.5 sqmm , 7 core2.5 sqmm , 10 core2.5 sqmm , 19 Core 2.5 sqmm , 4Core4 sqmm ( For CT supply) , 2 Core 6 sqmm (For D.C.).
58Control and Relay Panel , 66 kV Busbar Panel Argumentation for one number line bay (including in all respect) , The control, metering and protection system shall be complete with Numerical relays and compatible for performing the functions as per the electrical specifications and shall be fully compatible with substation automation /SCADA.
59Substation Automation and SCADA system aurgumentation (as per the technical specification) along with local work station with necessary hardware(for present bays) and software(for present and future bays) and fiber optic cabling and ethernet and PU to complete the work. The system shall be complete with Numerical Relay compatible with substation automation with Existing station system. The numerical relays along with other measuring / indicating instruments shall be part of the integrated system to be mounted on the switch gear.
60Aluminum Power Cables , Supply and Laying of 1100 V grade, PVC insulated, PVC sheathed, steel round wire armoured, stranded control cables of the following sizes: 4 Core x 10 sqmm (Aluminum) , 4 Core x 16 sqmm (Aluminum) , 3.5 Core x 35 sqmm (Aluminum).
61Design, Manufacturing, Testing at Manufacturer`s works, Forwarding and packing, transportation, Delivery at site, Storage, Erection, Site Testing, Commissioning and handing over of the following equipments / items, complete with all accessories and as per enclosed specification, data sheets, drawings etc. Please refer the bid document for the completeness of the scope and the general technical requirements for each item given under. (Data Sheets and Guaranteed Technical particulars for all the equipments are required to be attached with bid). The quantities are given under, however requirements shall be as per the technical specification and detailed engineering to be carried out by the bidder. 66 KV EQUIPMENTS Supply and installation 60KV,10KA,Zinc oxide type, heavy duty, station class, lightning arrestor.
62Lighting , 415V, 3 Phase, 4 Wire , outdoor type , IP65,Astronomical Type ,Microprocessor controlled, Time of day sequencing, Auto/manual type, street light panel comprising of 100A MCCB as incomer and 4 Nos ,63 Amps MCB outgoing with self chargable 24Hr. Timer for on/off.415 / 230V, complete with internal wiring, Al. Bus Bars, Link sets ,cable termination lugs for connecting outgoing cables of 4x25 sq.mm,PVC and 4 x 16 Sq.mm PVC Al, cables, indication, Metering , support channels, rain sheds, complete in all respects.The OGA and Scheme of the panel shall be as per the approved drawing. 1 no`s Metering with RYB indicating lamp LED type, Voltmeter with selector switch, ammeter with selector switch , suitable CT`s and 2A TPNMCB for backup protection of voltmeter and indication light , 1 no`s 70A 4P CONTACTOR , 24 Hr timer for auto Operation , Auto manual selector switch , I set push button for on/off operation , 4 No`s Outgoing feeder 63A TPNMCB at daultabad end.
63Design, Manufacturing, Testing at Manufacturer`s works, Forwarding and packing, transportation, Delivery at site, Storage, Erection, Site Testing, Commissioning and handing over of the following equipments/ items, complete with all accessories and as per enclosed specification, data sheets, drawings etc. Please refer the bid document for the completeness of the scope and the general technical requirements for each item given under. (Data Sheets and Guaranteed Technical particulars for allthe equipments are required to be attached with bid).Supply , installation and commissioning of 12.5/16MVA, 66/11kV, 3 Ph, `YnYn0 ONAN/ONAF Transformer with OLTC and RTCC panel. with bushing NCT as per SLD. HV and LV side of the transformer shall have open type bushing for terminating ACSR `Single Zebra`.
64Design, Manufacturing, Testing at Manufacturer`s works, Forwarding and packing, transportation, Delivery at site, Storage, Erection, Site Testing, Commissioning and handing over of the following equipments/ items, complete with all accessories and as per enclosed specification, data sheets, drawings etc. Please refer the bid document for the completeness of the scope and the general technical requirements for each item given under. (Data Sheets and Guaranteed Technical particulars for allthe equipments are required to be attached with bid). The quantities are given under, however requirements shall be as per the technical specification and detailed engineering to be carried out by the bidder.upply , installation and commissioning of 72.5KV ,1250A, 25KA for 1 sec, SF6 Circuit Breaker, 3 Ph gang operated complete with operating mechanism andsupport structure.
65Design, Manufacturing, Testing at Manufacturer`s works, Forwarding and packing, transportation, Delivery at site, Storage, Erection, Site Testing, Commissioning and handing over of the following equipments/ items, complete with all accessories and as per enclosed specification, data sheets, drawings etc. Please refer the bid document for the completeness of the scope and the general technical requirements for each item given under. (Data Sheets and Guaranteed Technical particulars for allthe equipments are required to be attached with bid). The quantities are given under, however requirements shall be as per the technical specification and detailed engineering to be carried out by the bidder.Supply , installation and commissioning 72.5KV ,800A,3 Ph gang operated double break type manual operated disconnector (Isolator) with solid core post insulator(Without earth switch).
66Design, Manufacturing, Testing at Manufacturer`s works, Forwarding and packing, transportation, Delivery at site, Storage, Erection, Site Testing, Commissioning and handing over of the following equipments / items, complete with all accessories and as per enclosed specification, data sheets, drawings etc. Please refer the bid document for the completeness of the scope and the general technical requirements for each item given under. (Data Sheets and Guaranteed Technical particulars for all the equipments are required to be attached with bid). The quantities are given under, however requirements shall be as per the technical specification and detailed engineering to be carried out by the bidder. 66 KV Equipments Supply , installation and commissioning 72.5KV ,800A, 3 Ph gang operated double break type manual operated disconnector (Isolator) with solid core post insulator (With earth switch).
67Design, Manufacturing, Testing at Manufacturer`s works, Forwarding and packing, transportation, Delivery at site, Storage, Erection, Site Testing, Commissioning and handing over of the following equipments / items, complete with all accessories and as per enclosed specification, data sheets, drawings etc. Please refer the bid document for the completeness of the scope and the general technical requirements for each item given under. (Data Sheets and Guaranteed Technical particulars for all the equipments are required to be attached with bid). The quantities are given under, however requirements shall be as per the technical specification and detailed engineering to be carried out by the bidder. 66 KV EQUIPMENTS Supply , installation and commissioning of 72.5KV Out door single phase current transformers of ratio Line feeder:600-300-150/1-1-1-1A, refer CT design parameters as per the Technical specifications.
68Design, Manufacturing, Testing at Manufacturer`s works, Forwarding and packing, transportation, Delivery at site, Storage, Erection, Site Testing, Commissioning and handing over of the following equipments / items, complete with all accessories and as per enclosed specification, data sheets, drawings etc. Please refer the bid document for the completeness of the scope and the general technical requirements for each item given under. (Data Sheets and Guaranteed Technical particulars for all the equipments are required to be attached with bid). The quantities are given under, however requirements shall be as per the technical specification and detailed engineering to be carried out by the bidder. 66 KV EQUIPMENTS Supply , installation and commissioning of 72.5KV Out door single phase current transformers of ratio Transformer feeder:600-300-150/1-1-1-1A, refer CT design parameters as per the Technical specifications.
69Design, Manufacturing, Testing at Manufacturer`s works, Forwarding and packing, transportation, Delivery at site, Storage, Erection, Site Testing, Commissioning and handing over of the following equipments / items, complete with all accessories and as per enclosed specification, data sheets, drawings etc. Please refer the bid document for the completeness of the scope and the general technical requirements for each item given under. (Data Sheets and Guaranteed Technical particulars for all the equipments are required to be attached with bid). The quantities are given under, however requirements shall be as per the technical specification and detailed engineering to be carried out by the bidder. 66 KV EQUIPMENTS Supply , installation and commissioning of 72.5KV Out door type, single phase bus potential transformer: 66KV/v3/110V/v3 /110V/v3 /110V/v3CORE-1 CL:3P,50VA, CORE-2 CL:3P,50VA and CORE-3 CL:0.2,30VA.
70Design, Manufacturing, Testing at Manufacturer`s works, Forwarding and packing, transportation, Delivery at site, Storage, Erection, Site Testing, Commissioning and handing over of the following equipments / items, complete with all accessories and as per enclosed specification, data sheets, drawings etc. Please refer the bid document for the completeness of the scope and the general technical requirements for each item given under. (Data Sheets and Guaranteed Technical particulars for all the equipments are required to be attached with bid). The quantities are given under, however requirements shall be as per the technical specification and detailed engineering to be carried out by the bidder. 66 KV EQUIPMENTS Supply , installation and commissioning of 66 KV capacitive voltage transformer (66/v3/110V/v3/110V/v3/110V/v3) CORE-1CL:0.2,50VA, CORE-2 CL:3P,50VA and CORE-3CL:3P,50VA.
71Substation Bay Hardware Supply , Installation and commissioning of Single tension line hardware fitting bolted type clamp suitable for single tension insulated string of 6 no. 11 KV 90 KN Disc insulators, Shackle suitable for 20 mm anchoring hole on beam side, without turn buckle forSINGLE ACSR ZEBRA conductor.
72Substation Bay Hardware Supply , Installation and commissioning of Single tension line hardware fitting bolted type clamp suitable for single tension insulated string of 6 no. 11 KV 90 KN Disc insulators, Shackle suitable for 20 mm anchoring hole on beam side, with turn buckle forSINGLE ACSR ZEBRA conductor.
73Substation Bay Hardware Supply , Installation and commissioning of Single suspension linehardware fitting boltedtypesuitablefor 1x5 nos. 11kV, 70kN EMS disc insulatoralong shackle suitablefor 20 mm anchoring hole on beamsuitable for SINGLE ACSR ZEBRA conductor complete with U BOLT and I BOLT ETC. DROP TYPE.
74Substation Bay Hardware Supply , Installation and commissioning of 90 KN Disc insulator BandS type.
75Substation Bay Hardware Supply , Installation and commissioning of 70 KN Disc insulator BandS type.
76Substation Bay Hardware Supply , Installation and commissioning of Tee Connector and Power connectors of suitable current rating for individual equipment terminal pad and Single Zebra ACSR conductors on 66 KV side , Tee connector for single Zebra conductor through and same tee off.
77Substation Bay Hardware Supply , Installation and commissioning of Tee Connector and Power connectors of suitable current rating for individual equipment terminal pad and Single Zebra ACSR conductors on 66 KV side , Terminal connector for 72.6kV Isolator to receive SINGLE ACSR ZEBRA Conductor.
78Substation Bay Hardware Supply , Installation and commissioning of Tee Connector and Power connectors of suitable current rating for individual equipment terminal pad and Single Zebra ACSR conductors on 66 KV side , Terminal connector for 72.6kV SF6 Circuit Breaker to receive SINGLE ACSR ZEBRA Conductor.
79Substation Bay Hardware Supply , Installation and commissioning of Tee Connector and Power connectors of suitable current rating for individual equipment terminal pad and Single Zebra ACSR conductors on 66 KV side , Terminal connector for 72.6kV Current Transformer to receive SINGLE ACSR ZEBRA Conductor.
80Substation Bay Hardware Supply , Installation and commissioning of Tee Connector and Power connectors of suitable current rating for individual equipment terminal pad and Single Zebra ACSR conductors on 66 KV side , Terminal connector for 60kV Lightning Arrester to receive Single ACSR Zebra Conductor.
81Substation Bay Hardware Supply , Installation and commissioning of Tee Connector and Power connectors of suitable current rating for individual equipment terminal pad and Single Zebra ACSR conductors on 66 KV side , Terminal connector for 72.6kV BPT connecto to receive Single ACSR ZEBRA Conductor.
82Substation Bay Hardware Supply , Installation and commissioning of Tee Connector and Power connectors of suitable current rating for individual equipment terminal pad and Single Zebra ACSR conductors on 66 KV side , Terminal connector for 72.6kV CVT connector to receive Single ACSR ZEBRA Conductor.
83Substation Bay Hardware Supply , Installation and commissioning of Tee Connector and Power connectors of suitable current rating for individual equipment terminal pad and Single Zebra ACSR conductors on 66 KV side , Transformer Bushing Clamp ( H.T. Side ).
84Substation Bay Hardware Supply , Installation and commissioning of Tee Connector and Power connectors of suitable current rating for individual equipment terminal pad and Single Zebra ACSR conductors on 66 KV side , Transformer Bushing Clamp ( L.T. Side ).
85Substation Bay Hardware Supply , Installation and commissioning of Tee Connector and Power connectors of suitable current rating for individual equipment terminal pad and Single Zebra ACSR conductors on 66 KV side , Clamp for Neutral Bushing .
86Substation Bay Hardware Supply , Laying of ZEBRA ACSR conductor
87Substation Bay Hardware Supply , Laying of Tension Fittings for 7/3.15mm Earthwire.
88Substation Bay Hardware Supply , Installation and commissioning of Earth Wire Connector (PG Clamps).
89Substation Bay Hardware Supply , Laying of 7/3.15 mm GSS wire for shielding .
90Substation Bay Hardware Supply , Installation and commissioning of Hardware for 7/3.15 mm GSS wire pad type clamps.
91Substation Bay Hardware Supply , Installation and commissioning of Hardware for 7/3.15 mm GSS wire- Cleat type clamps.
9212KV Equipment Supply , installation and commissioning of 9KV, 5kA LIGHTNING ARRESTER perclain type.
93CABLES , 12kV XLPE (E) insulated `PVC sheathed, aluminum round wire armored, aluminumconductor cable of the following size : Supply and laying of 1 core 630 sqmm(Aluminum round wire armored) Power transformers.(2 Runs/phase).
94CABLES , 12kV XLPE (E) insulated `PVC sheathed, aluminum round wire armored, aluminum conductor cable of the following size : Supply and laying of 3 Core 185sqmm (Aluminum round armoured) for connecting with existing 11KV network .
95CABLES , 12 KV Heat Shrink type termination Kit for the following size of 12 KV (E) XLPE Cables : 1Core 630 sq mm(Outdoor type).
96CABLES , 12 KV Heat Shrink type termination Kit for the following size of 12 KV (E) XLPE Cables : 1Core 630 sq mm(Indoor type).
97CABLES , 12 KV Heat Shrink type termination Kit for the following size of 12 KV (E) XLPE Cables : 3Core 185 sq mm( Outdoor type).
98CABLES , 12 KV Heat Shrink type termination Kit for the following size of 12 KV (E) XLPE Cables : 3Core 185 sq mm( Indoor type).
99CABLES , 12KV XLPE (E) insulated `PVC sheathed, steel round wire armoured, aluminumconductor cable , Supply and laying of 3 core 300 sqmm( wire armoured).
100CABLES , 12kV Heat shrink type/ Pushon Type termination kit for 12kV (E) XLPE Cables of3 Core x 300 sqmm size (iNDOOR TYPE).
101CABLES , 12kV Heat shrink type/ Pushon Type termination kit for 12kV (E) XLPE Cables of 3 Core x 300 sqmm size (OUTDOOR TYPE).
102LT CABLE , 1.1kV XLPEinsulated `PVC sheathed, GI round wire armoured, aluminumconductor cable of the following sizes:. 3.5 core x 400 sq, mm for station transformer.
103LT CABLE , 1.1kV XLPE insulated `PVC sheathed, GI round wire armoured, aluminum conductor cable of the following sizes: Termination with double compression gland and Al lugs for 3.5 core x 400 sq, mm cable.
104LT CABLE , 1.1 KV PVC insulated and sheathed, steel armoured cable of the following size including cable support (For AC supply and yard lighting) Supply and Laying of 3 core x 2.5 sqmm Cu conductor cable (GI round wire armoured) for control Gear to Lamp fixture.
105LT CABLE , 1.1 KV PVC insulated and sheathed, steel armoured cable of the following size including cable support (For AC supply and yard lighting) Supply and Laying of 4 core x 10 sqmmAl.Conductor cable (GI round wire armoured)for Street light panel to light fitting Control gear.
106LT CABLE , 1.1 KV PVC insulated and sheathed, steel armoured cable of the following size including cable support (For AC supply and yard lighting) Supply and Laying of 4 core x 16 sqmmAl. Conductor cable (GI round wire armoured) for Street light panel from ACDB.
107LT CABLE , 1.1 KV PVC insulated and sheathed, steel armoured cable of the following size including cable support (For AC supply and yard lighting) Termination with double compression gland andlugs for item 4 core x 16 sqmm , 4 core x 10 sqmm , 3 core x 2.5 sqmm.
108LT CABLE , 1.1 KV PVC insulated and sheathed, steel wire armoured Aluminum conductor cable of the following size (For AC and DC Supply) , Supply and laying of 3.5 core x 50 sqmm Al conductor cable ( GI Strip armoured) for ACDB to Battery charger.
109LT CABLE , 1.1 KV PVC insulated and sheathed, steel wire armoured Aluminum conductor cable of the following size (For AC and DC Supply) , Supply and laying of 2 core x 50 sqmmcopper conductor cable (For DC) Battery charger to Battery.
110LT CABLE , 1.1 KV PVC insulated and sheathed, steel wire armoured Aluminum conductor cable of the following size (For AC and DC Supply) , Double compression glands and Cu/Al lugs with sleeves for 1100V grade PVC insulated, multicore aluminum conductor auxiliary power cables of the following sizes: Supply and erection of 3 1/2 core x 50 sqmmAl. cable.
111LT CABLE , 1.1 KV PVC insulated and sheathed, steel wire armoured Aluminum conductor cable of the following size (For AC and DC Supply) , Double compression glands and Cu/Al lugs with sleeves for 1100V grade PVC insulated, multicore aluminum conductor auxiliary power cables of the following sizes: Supply and erection of 2 core x 50 sqmmcopper cable
112Copper Control Cable , Supply and Laying of 1100 V grade, PVC insulated, PVC sheathed, steel round wire armoured, stranded control cables of the following sizes: 3 core2.5 sqmm , 5 core2.5 sqmm , 7 core2.5 sqmm , 10 core2.5 sqmm , 19 Core 2.5 sqmm , 4Core4 sqmm ( For CT supply) , 2 Core 6 sqmm (For D.C.).
113Supply and Erection of Double compression glands and terminations(including ferruling, suitable Cu Lugs to meet the system requirements) for 1100V grade PVC insulated multicore Copper stranded conductor control cables ofthe following sizes: 3 core 2.5 sqmm , 5 core 2.5 sqmm , 7 core 2.5 sqmm , 10 core 2.5 sqmm , 19 Core 2.5 sqmm , 4Core 4 sqmm ( For CT supply) , 2 Core 6 sqmm (For D.C.) , 4 Core x 10 sqmm (Aluminum) , 4 Core x 16 sqmm (Aluminum) , 3.5 Core x 35 sqmm (Aluminum).
114Lighting , Supply and Erection of Flood light fitting with 150 W LED lamp.
115Lighting , Supply and Installation of Post top lantern with 38/35W LED lamp.
116Lighting , Supply and Installation of Steel tubular pole 10 mtr long, SP -33 with base plate and cross arm 1.5 mtr long with arrangement for fixing the luminaire 85 W LED fitting with suitable junction box.
117Lighting , 415V, 3 Phase, 4 Wire , outdoor type , IP65,Astronomical Type ,Microprocessor controlled, Time of day sequencing, Auto/manual type, street light panel comprising of 100A MCCB as incomer and 4 Nos ,63 Amps MCB outgoing with self chargable 24Hr. Timer for on/off.415 / 230V, complete with internal wiring, Al. Bus Bars, Link sets ,cable termination lugs for connecting outgoing cables of 4x25 sq.mm,PVC and 4 x 16 Sq.mm PVC Al, cables, indication, Metering ,support channels, rain sheds, complete in all respects.The OGA and Scheme of the panel shall be as per the approved drawing. 1 no`s Metering with RYB indicating lamp LED type, Voltmeter with selector switch, ammeter with selector switch , suitable CT`s and 2A TPNMCB for backup protection of voltmeter and indication light , 1 no`s 70A 4P CONTACTOR , 24 Hr timer for auto Operation , Auto manual selector switch , I set push button for on/off operation , 4 No`s Outgoing feeder 63A TPNMCB .
118Lighting , Supply and installation of Lighting junction box for each Light at tower suitable for out door installation comprising of 8 no. CBT M 4 type terminal connector for light connections or loop in / loop out cable.
119EARTHING ANDLIGHTNING PROTECTION , Supply and Erection of Main Earth mat, Aux Earth mat and Earthing Risers for Main Equipmentsand structures etc ( 75 x 12 mm G I flat).
120EARTHING AND LIGHTNING PROTECTION , Supply and Erection of Earthing conductor for connection of , L.T panel, Junction box, and building Lightning risers and peak Connection etc(50x6 GI flat).
121EARTHING AND LIGHTNING PROTECTION , Supply and Erection of Transformer neutral earthing with 50x6mm copper flat upto water level.
122EARTHING AND LIGHTNING PROTECTION , Supply and Erection of 50x6 mm MS flat for cable trench earthing.
123EARTHING AND LIGHTNING PROTECTION , Supply and Erection of Transformer body earthing( 75 x 12 mm G I flat).
124EARTHING AND LIGHTNING PROTECTION , Supply and Erection of 40 mm dia 3 m long GI pipe earth electrode with treated earth Pit for LA and CVT.
125EARTHING AND LIGHTNING PROTECTION , Supply and Erection of 40 mm Dia 3 mtr longM.S. rod earth electrode (driven) for each peak tower, building lightning protection and yard earth mat.
126EARTHING AND LIGHTNING PROTECTION , Supply and Erection of Electrolytic grade copper plate 600mmx600mmx6mm for transformer neutral earthing to be provided in 4.5 mtr deep earth pit to be filled with salt and charcoal (as per standard earthing Practices).
127EARTHING AND LIGHTNING PROTECTION , Supply and Erection of Electrolytic grade copper plate 600mmx600mmx6mm for Instrumentation and SCADA System to be provided in 4.5 mtr deep earth pit to be filled with salt and charcoal (as per standard IS).
128PANEL SET , 11 KV Switchgear Panel (13 Panel Set) , 12kV, 500 MVA for1 Secs., 12500A, Indoor VCB switchgear panel with required PT`s, CT`s, protective relays, metering equipment, auxiliary equipment, extensible (both sides) copper bus bars, complete cable terminationkits as per cable sizes specified in SLD , 1250 A Incoming feeder=2 Nos., CTR : 1200-600/5-5 -5 A, refer CT design parameters as per technical specifications , 630 A station transformerfeeder =1 Nos.,CTR : 60- 30/5-5 A, refer CT design parameters as per technical specifications , 800 A outgoing feeder = 7 Nos., CTR : 600-300-150/5- 5 A, refer CT design parameters as per technical specifications , 1250A B/C Feeder=1Nos., CTR : 1200-600/5-5-5 A, refer CT design parameters as per technical specifications , 1 no. Spare Panel for addition/ deletion , 1 no`s BPT module alongwith with BR provision as per the requirement if any , Note :*The 11 KV Switchgear board shall be complete with Numerical relays and compatible with SCADA system as defined in the technical specifications. All outgoing feeders shall have separate Electronic Trivectr meter of accuracy class 0.2S for energy recording and have earth switch .All meters shall have recording facility as well as data download facility and MR provisions with software and laptops as per the requirements. All the panel, relays and meters etc. shall of same make, i.e. 11KV swithgear offered should come as complete unit from the manufacture and relays, meters, panel etc shall be of that manufacture only.All panels shall have TTBs in front for meter sealing.
129PANEL SET , 11 KV Switchgear Panel (26 No`s VCB in total) , 12kV, 500 MVA for 1 Secs., 12500A, Indoor VCB switchgear panel with required PT`s, CT`s, protective relays, metering equipment, auxiliary equipment, extensible (both sides) copper bus bars, complete cable termination kits as per cable sizes specified in SLD , VCB set (1 incomer ,3 outgoing)(1 incomer ,5 outgoing)(1 incomer )(1 incomer )(1 incomer ,2 outgoing)(1 incomer ,5 outgoing)(1 incomer ,4 outgoing) 800 A each , 12kV switchgear incomer with VCB, PT, CT, metering, Copper bus bar, auxiliary relay etc. as per specification. (includes incomer and outgoing panel, for interconnection with the existing 11KV network) , Note :*The 11 KV Switchgear board shall be complete with Numerical relays and compatible with SCADA system as defined in the technical specifications. All outgoing feeders shall have separate Electronic Trivector meter of accuracy class 0.2S for energy recording and have earth switch .All meters shall have recording facility as well as data download facility and MR provisions with software and laptops as per the requirements. All the panel, relays and meters etc. shall of same make, i.e. 11KV switchgear offered should come as complete unit from the manufacture and relays, meters, panel etc shall be of that manufacture only. All panels shall have TTBs in front for meter sealing.
130PANEL SET , 11 KV Switchgear Panel , 12kV, 500 MVA for 1 Secs., 12500A, Indoor VCB switchgear panel with required PT`s, CT`s, protective relays, metering equipment, auxiliary equipment, extensible (both sides) copper bus bars, complete cable termination kits as per cable sizes specified in SLD , For Addition / deletion of 1 no 630 A, 12kV switchgear outgoing feeder panel with VCB, CTS, Metering, Copper bus bar, cable sealing kit, auxiliary relays etc., as per specification.Note :*The 11 KV Switchgear board shall be complete with Numerical relays and compatible with SCADA system as defined in the technical specifications. All outgoing feeders shall have separate Electronic Trivectr meter of accuracy class 0.2S for energy recording and have earth switch .All meters shall have recording facility as well as data download facility and MR provisions with software and laptops as per the requirements. All the panel, relays and meters etc. shall of same make, i.e. 11KV swithgear offered should come as complete unit from the manufacture and relays, meters, panel etc shall be of that manufacture only.All panels shall have TTBs in front for meter sealing.
131Control and Relay Panel , Indoor floor mounted, simplex type control and relay panels, with mimic and annunciation panelfor 66kV system as per specification and data sheet comprising of : 66kV Ckt. Breaker control panel without auto reclose and Line Protection Panel
132Control and Relay Panel , Indoor floor mounted, simplex type control and relay panels, with mimic and annunciation panel for 66kV system as per specification and data sheet comprising of : 12.5/16MVA 66/11 kV Ckt. Breaker control panel without auto reclose and Transformer Protection Panel The control, metering and protection system shall be complete with Numerical relays and compatible for performing the functions as per the electrical specifications and shall be fully compatible with substation automation /SCADA.
133Control and Relay Panel , Indoor floor mounted, simplex type control and relay panels, with mimic and annunciation panel for 66kV system as per specification and data sheet comprising of : 66 kV Busbar panel Panel , The control, metering and protection system shall be complete with Numerical relays and compatible for performing the functions as per the electrical specifications and shall be fully compatible with substation automation /SCADA.
134Substation Automation , Substation Automation and SCADA system (as per the technical specification) along with local work station with necessary hardware(for present bays) and software (for present and future bays) and fiber optic cabling ane ethernet and PU to complete the work , The system shall be complete with Numerical Relay compatible with substation automation for 66 KV and 11 KVsystem. The numerical relays along with other measuring / indicating instruments shall be part of the integrated system to be mounted on the switch gear.
135AC Distribution Board , supply and installation of AC 415V, 500A ,50 KAfor 1 Sec cubicle type Indoor, floor mounted, auxiliary service board as per specification comprising of : 2 No. - Incoming feeders each with 400ATP ACB with O/C, S/C, E/F release. Suitable to operate from remote and all status to be taken to SCADA , 1 Nos. - Bus coupler feeder with 400A TPN ACB with O/C, S/F, E/F release. Suitable to operate from remote and all status to be taken to SCADA , 4 Nos. - Outgoing feeders with 100A TPN MCCB , 10 Nos. - Outgoing feeders with 63A TPN MCCB , 6 Nos. - Outgoing feeders with 32A TPN MCCB , 10 Nos. - Outgoing feeders with 32A DP MCCB.
136BATTERY, BATTERY CHARGER , Supply and installation of 220V DC, 200 AH lithium Ion battery of plante type complete with accessoriesas per specificationwith 10% spare acid in non-returnable container (In tier arrangement).
137BATTERY, BATTERY CHARGER , Supply and installation of 220V DC battery charger suitable for float and Float cum boostcharger capable of supplying a DC continous load of 40 Amps as per specification and witha common DCDB comprising of : Battery Charger
138BATTERY, BATTERY CHARGER , Supply and installation of 220V DC battery charger suitable for float and Float cum boost charger capable of supplying a DC continous load of 40 Amps as per specification and with a common DCDB comprising of : 1 No. incomer with 250A, DP DCMCCB and to terminate 2 core 50 sqmmAl. cable , 20 Nos. outgoing feeders each with 40/32A DP rotary switch with HRC fuses as per the requirement and as per the approved drawings.
139Supply , installation , testing , commissioning of 3.6MVR 11KV Capacitor Bank.
140Safety equipment , Fire Extinguishers , Supply and installation of CO2 type 5 Kg .
141Safety equipment , Fire Extinguishers , Supply and installation of Dry powder chemical type 25 kg.
142Safety equipment , Fire Extinguishers , Supply and installation of Dry powder chemical type 10 kg.
143Safety equipment , Fire Extinguishers , Supply , testing and installation of 25Kg DCP Type.
144Safety equipment , Fire Extinguishers , Supply , testing and installation of 4nos Fire Bucket with stand (required as per standard).
145Cable Supports and Trays , Supply and Installation of Sheet steel (thickness 2.5 mm) Galvanized ladder and perforated type cable trays with its accessories to be laid in outdoor and indoor cable trenches ( of following various sizes ).600mm, 450 mm, 300mm, 150mm and 100mm width, as per requirement for dressing , Cable Trays , (600 X 50 mm Ladder type ).
146able Supports and Trays , Supply and Installation of Sheet steel (thickness 2.5 mm) Galvanized ladder and perforated type cable trays with its accessories to be laid in outdoor and indoor cable trenches ( of following various sizes ).600mm, 450 mm, 300mm, 150mm and 100mm width, as per requirement for dressing , Cable Trays , (450 X 50 mm Ladder type ).
147Cable Supports and Trays , Supply and Installation of Sheet steel (thickness 2.5 mm) Galvanized ladder and perforated type cable trays with its accessories to be laid in outdoor and indoor cable trenches ( of following various sizes ).600mm, 450 mm, 300mm, 150mm and 100mm width, as per requirement for dressing , Cable Trays , (300 X 50 mm Ladder type).
148Structural Steel , Supply and erection of Substation Galvanized Steel Structure for Towers and Beam
149Cable Supports and Trays , Supply , testing and Installation of Sheet steel (thickness 2.5 mm) Galvanized ladder and perforated type cable trays with its accessories to be laid in outdoor and indoor cable trenches ( of following various sizes ).600mm, 450 mm, 300mm, 150mm and 100mm width, as per requirement for dressing , Cable Trays , (150 x50 mm perforated type).
150Cable Supports and Trays , Supply , testing and Installation of Sheet steel (thickness 2.5 mm) Galvanized ladder and perforated type cable trays with its accessories to be laid in outdoor and indoor cable trenches ( of following various sizes ).600mm, 450 mm, 300mm, 150mm and 100mm width, as per requirement for dressing , Cable Trays , (100 x 50 mm Perforated Type ).
151Structural Steel , Supply and erection of Nuts and bolts for Substation Galvanized Steel Structure for Towers and Beam.
152Structural Steel , Supply and erection of Substation Galvanized Steel Structure for equipments.
153Structural Steel , Supply and erection of Nuts and bollts for Substation Galvanized Steel Structure for equipments.
154Structural Steel , Supply and erection of Anchor bolts.
155Supply and installation of Dewatering pump (portable type) 415 V, 1 HP as per requirement.
156Air conditioning , supply and installation of Split Air-conditioning for Control room (capacity 1.5 Tonne).
157Supply and installation of Bay marshalling kiosk made of 2.5 mm. Thick sheet steel , IP 55 enclosure protection as per specification.
158Testing and Maintenance Equipment, Providing of Meggar 5 KV (Motorized) -1 No. Meggar 1 KV (Motorized) - 1 No. Automatic capacitor and Tan Delta measuring kit -1 No. Digital Multi meter-2 Nos. Leakage tester (Tong type) -2 Nos. Selective level meter -1 No. Signal generator -1 No. Micro-ohm meter -1 No. D-Spanner set (Insulated) -2 Nos. Ring-Spanner set (Insulated) - 2 Nos. Torque wrench set -2 Nos. Insulating gloves-5 sets Helmets -5 set. Spliced ladders 5mtr. - 2 set. Spliced ladders 10mtr. - 2 set. Polyamide or Braided white nylon rope-12 mm (100 mtr). Polyamide or Braided white nylon rope-14 mm(100 mtr). Polyamide or Braided white nylon rope-20 mm(100 mtr). Gapless zinc oxide LA tester-1 No. Oil BDV Kit 0-80 KV -1 No. Gas Evacuating and refilling device -2 set. Gas Leakge Monitor -2 Nos. Circuit Breaker Analyser -1 No. Portable Partial dischange monitoring system -1 No. Dew Point Meter -1 No. Gas Masks -1 No. Relay Test Kit -1 No. Primary Injection Set 1000 Amp -1 No.
159Aluminum Power Cables , Supply and Laying of 1100 V grade, PVC insulated, PVC sheathed, steel round wire armoured, stranded control cables of the following sizes: 4 Core x 10 sqmm (Aluminum) , 4 Core x 16 sqmm (Aluminum) , 3.5 Core x 35 sqmm (Aluminum).
160Design, Manufacturing, Testing at Manufacturer`s works, Forwarding and packing, transportation, Delivery at site, Storage, Erection, Site Testing, Commissioning and handing over of the following equipment`s / items, complete with all accessories and as per enclosed specification, data sheets, drawings etc. Please refer the bid document for the completeness of the scope and the general technical requirements for each item given under. (Data Sheets and Guaranteed Technical particulars for all the equipment`s are required to be attached with bid). Supply , installation , testing and commissioning of 250 KVA, Copper Wound 11/0.433kV 3ph, Dyn-11, outdoor type `with OFF load tap changer and cable box on HV?LV sides.
161Design, Manufacturing, Testing at Manufacturer`s works, Forwarding and packing, transportation, Delivery at site, Storage, Erection, Site Testing, Commissioning and handing over of the following equipments / items, complete with all accessories and as per enclosed specification, data sheets, drawings etc. Please refer the bid document for the completeness of the scope and the general technical requirements for each item given under. (Data Sheets and Guaranteed Technical particulars for all the equipments are required to be attached with bid). The quantities are given under, however requirements shall be as per the technical specification and detailed engineering to be carried out by the bidder. 66 KV EQUIPMENTSsupply , installation and commissioning of 60KV,10KA,Zinc oxide type, heavy duty, station class, lightning arrestor.
162Providing and installation ofof First Aid box and accident prevention chart.
163Foundation for bay extention in Daultabad:- Steel structure for the following foundations:-Foundation of 66 KV CT Transformers , Foundation of 66 KV CT Metering , Foundation of 66 KV PT Metering , Foundation of 66 KV SF-6 BREAKER, Foundation of 66 KV CT LandE Switch , Foundation of 66 KV LA Line , Foundation of 66 KV CT Protection , Foundation of 66 KV PT PROTECTION ,Foundation of 66 KV PT bus bar , Foundation of 66 KV LA transformer , Foundation of 66 KV Isolator and Foundation of 66 KV CT-4 as needed and in accordance with approved design and drawings including excavation and refilling of soil complete in all respect and any other work contingent thereto as per sizes and specification given in DNIT (Steel reinforcement for R.C.C. work, where not included in the complete rate of RCC, including straightening, cutting, bending, placing in position, binding, wastage, overlaps, welded joints, spacer bars, chairs, stays, hangers and annealed steel wire etc. complete in all respect below plinth level Note:- Reinforcement shall be measured in length including hooks, if any, separately for different diameters as actually used in work , excluding overlaps. Wastage, overlaps, couplings, welded joints, spacer bars, chairs, stays, hangers and annealed steel wire or other methods of binding and placing shall not be measured and cost of these items shall be deemed to be included in the rates for reinforcement.Thermo- Mechanically Treated bars of grade Fe-500D kg or more ( for M-30) .
164Earth mat:- Design , supply , and erection of earth mat work which includes 16mm thick rod and 20mm thick earth electrodes in accordance with approved design and drawings including excavation and refilling of soil complete in all respect and any other work contingent thereto as per sizes and specification given in DNIT.Thermo-Mechanically Treated bars of grade Fe- 500D kg or more( for M-30).
165Yard : Steel reinforcement for R.C.C. work, where not included in the complete rate of RCC, including straightening, cutting, bending, placing in position, binding, wastage, overlaps, welded joints, spacer bars, chairs, stays, hangers and annealed steel wire etc. complete in all respect below plinth level Note:- Reinforcement shall be measured in length including hooks, if any, separately for different diameters as actually used in work , excluding overlaps. Wastage, overlaps, couplings, welded joints, spacer bars, chairs, stays, hangers and annealed steel wire or other methods of binding and placing shall not be measured and cost of these items shall be deemed to be included in the rates for reinforcement.Thermo- Mechanically Treated bars of grade Fe-500D kg or more ( for M-30) .
166Foundationfor bay extension in Daultabad :- Design and construction of RCC Grade M30 Using Concrete Mixer C.C of M30 concrete platforms for Foundation of 66 KV CT Transformers , Foundation of 66 KV CT Metering , Foundation of 66 KV PT Metering , Foundation of 66 KV SF-6 BREAKER, Foundation of 66 KV CT LandE Switch , Foundation of 66 KV LA Line , Foundation of 66 KV CT Protection , Foundation of 66 KV PT PROTECTION ,Foundation of 66 KV PT bus bar , Foundation of 66 KV LA transformer , Foundation of 66 KV Isolator and Foundation of 66 KV CT-4 including excavation and back filling as required to the complete satisfaction of Engineer-in-charge as needed and in accordance with approved design and drawings including excavation and refilling of soil complete in all respect and any other work contingent thereto as per sizes and specification given in DNIT.
167Yard for bay extention in daultabad :- Designing and construction of yard with 100mm thick C.C of M30 concrete after preparation of plinth( i.e compaction and filling of soil followed by 75mm M-10 concrete and so as to achieve the final plinth level which should be 0.75 meter above the existing road level of WTP Basai.) including cable trenches , all electrical , mechanical works in accordance with approved design and drawings and all other works contingent thereto as per sizes and specification given in DNIT(ITEM For M-30).
168Yard for bay extention in Daultabad :- Designing and construction of yard with 100mm thick C.C of M30 concrete after preparation of plinth( i.e compaction and filling of soil followed by 75mm M-10 concrete and so as to achieve the final plinth level which should be 0.75 meter above the existing road level of WTP Basai) including cable trenches , all electrical , mechanical works in accordance with approved design and drawings and all other works contingent thereto as per sizes and specification given in DNIT(ITEM for M-10).
169ERECTION PORTION (OverheadplusUnderground Line) , Detail Survey as per tentative route , which includes the following major activities-Pegging of line route, providing of survey pillar at an interval of 3-4 KM in the line route with required jungle clearance for survey, profile preparation of approved route on graph sheet and marking of offset on either side of the line, marking of side clearence for hills sand dunes etc as per specification and tower sheduling.
170ERECTION PORTION (Overhead plus Underground Line) , Check survey as per approved route of line which Includes : Re-checklng of the line route as per approved profile, chainage. tower center marking, pit marking, bisection of angle tower as required at site.
171ERECTION PORTION (Overhead plus Underground Line) , Soil Investigation , Detailed Soil Investigation upto a depth of 7 mtr in soil and 3 Mtr in rock Strata in Normal conditions and 40 mtr in Special Locations , All kinds of soil except fissured rock and hard rock
172SETTING OF TEMPLATE and STUB/ANCHOR BOLT , Setting of template and stub/ anchor bolt and removal after concreting, excluding cost of excavation and concreting but including back filling with excavated/ borrowed earth (with lead and lift) in layers with ramming and watering as per specification , A) 66KV Double Circuit Tower uptoplus 6m, extension : (i) Suspension Tower (DA)
173SETTING OF TEMPLATE and STUB/ANCHOR BOLT , Setting of template and stub/ anchor bolt and removal after concreting, excluding cost of excavation and concreting but including back filling with excavated/ borrowed earth (with lead and lift) in layers with ramming and watering as per specification , A) 66KV Double Circuit Tower upto plus 6m, extension : Medium angle Tower (DC)
174SETTING OF TEMPLATE and STUB/ANCHOR BOLT , Setting of template and stub/ anchor bolt and removal after concreting, excluding cost of excavation and concreting but including back filling with excavated/ borrowed earth (with lead and lift) in layers with ramming and watering as per specification , A) 66KV Double Circuit Tower upto plus 6m, extension : Heavy angle cum dead end Tower (DD)
175SETTING OF TEMPLATE and STUB/ANCHOR BOLT , Setting of template and stub/ anchor bolt and removal after concreting, excluding cost of excavation and concreting but including back filling with excavated/ borrowed earth (with lead and lift) in layers with ramming and watering as per specification , A) 66KV Double Circuit Tower upto plus 6m, extension : Xing Gantryand SS Gantry
176EARTHING: (A) Earthing of towers with pipe type earthing excluding the supply of pipes, wires, flats and connectors, but including coke/charcoal, etc.,excavatlon,augering and backfilling in all types of soil.
177ERECTION OF TOWERS: Erection of super structures Including D-shackles, ACD, Hangers, U-Bolts, step bolts, danger plate, phase plate, number plate etc. Also Including tack welding of bolts and nuts up to bottom cross arm/beam level Including application of Zinc rich paint.` (A) 66 KV Double Circuit Tower Upto 12 mtr. Ext (i) Suspension Tower (DA) ii) Light angle Tower (DB) (iii) Medium angle Tower (DC) (iv) Heavy angle cum dead end Tower (DD) (v) Xing Gantryand SS Gantry
178CONDUCTOR STRINGING (A) Stringing of ACSR Zebra Including hoisting of Insulator string, laying, Jointing and tensioning of conductor, clamping with Armour rods and fixing of vibration damper per route KM of the line. (i) 3 conductor for D/C Line
179EARTHWIRE STRING (A) Stringing of galvanised steel stranded wire Including laying jointing and tensioning, clamping.clipping and fixing vibration damper and earth bond etc. (i) One No. 7/3.15mm galvanised wire.
180ERECTION OF XLPE CABLE ERECTION (0.2km) (A) Detailed Cable Survey
181ERECTION OF XLPE CABLE ERECTION (0.2km) , 66kV,4Rx1Cx1200sqmm,XLPE cable with HDPE Pipe including jointing and termination etc.
182XLPE CABLE TRENCHLESS CONSTRUCTION (A) Construction 2 meter width 1.5 meter depth and 200 meter long trench including brick work, send filling etc. for 66kV,4Rx1Cx1200sqmm,XLPE cable as per technical .
183SUPPLY PORTION , TOWERS , EARTHWIRE HARDWARE`S : I)SUSPENSION ASSEMBLY
184SUPPLY PORTION , TOWERS , EARTHWIRE HARDWARE`S : TENSION ASSEMBLY
185SUPPLY PORTION , TOWERS , EARTHWIRE HARDWARE`S : MID SPAN COMPRESSION JOINT
186SUPPLY PORTION , TOWERS , EARTHWIRE HARDWARE`S : VIBRATION DAMPER
187SUPPLY PORTION , TOWERS , EARTHWIRE HARDWARE`S : FLEXIBLE COPPER BOND
188SUPPLY PORTION , EARTHING : I) PIPE TYPE
189SUPPLY PORTION , TOWER ACCESSORIES : Danger Plate
190SUPPLY PORTION , TOWER ACCESSORIES : Number Plate
191SUPPLY PORTION , TOWER ACCESSORIES : Phase Plate(sets of 3)
192SUPPLY PORTION , TOWER ACCESSORIES : Anticlimbing Device
193SUPPLY PORTION , TOWERS , Fabrication, galvanising and supply of various type of tower and tower parts, tower extensions (complete) including bolts and nuts, step bolts andhangers, D- shackles, pack washer etc butexcluding stubs.
194SUPPLY PORTION , XLPE CABLE (960.00 Meter Approx) , Supply 66kV,4Rx1Cx1200sqmm,XLPE cable 960.00 meter approx with HDPE PIPE including jointing and termination kit, support structure, cable tie etc.`
195SUPPLY PORTION , TOWERS , Fabrication, galvanisingand supply of stubs and cleats for various type of towers, tower extensions (complete) with pack washers, including bolts and nuts.
196SUPPLY PORTION , TOWERS , Fabrication, galvanisingand supply of various type of Templates, Templates extensions (complete) with pack washers, including bolts and nuts
197SUPPLY PORTION , TOWERS ,Supply of Galvanised Boltsand Nuts, pack washers, step bolt, hangers, D- shackles s etc.for Towers.
198SUPPLY PORTION , LINE MATERIAL , ACSR ZEBRA CONDUCTOR.
199SUPPLY PORTION , LINE MATERIAL , EARTHWIRE 7/3.15MM STEEL.
200SUPPLY PORTION , LINE MATERIAL , INSULATORS : 120KN
201SUPPLY PORTION , LINE MATERIAL , CONDUCTOR HARDWARE`S : SINGLE SUSPENSION ASSEMBLY
202SUPPLY PORTION , LINE MATERIAL , CONDUCTOR HARDWARE`S : SINGLE TENSION ASSEMBLY
203SUPPLY PORTION , LINE MATERIAL , CONDUCTOR HARDWARE`S : MID SPAN COMPRESSION JOINT
204SUPPLY PORTION , LINE MATERIAL , CONDUCTOR HARDWARE`S :REPAIR SLEEV
205SUPPLY PORTION , LINE MATERIAL , CONDUCTOR HARDWARE`S : Vibration damper
206SUPPLY PORTION , TOWER ACCESSORIES : Bird Guard in all towers.
207SUPPLY PORTION , LINE MATERIAL , INSULATORS : 90 KN
208Excavation for Structures Earth work in excavation of foundation of structures as per drawing and technical specification, including setting out, construction of shoring and bracing, removal of stumps and other deleterious matter, dressing of sides and bottom and backfilling with approved material, Ordinary soil, Manual Means , Depth up to 3 m , Note:- 1. Dewatering if required , 10 per cent of labour cost Assessment for dewatering shall be made as per site conditions. 2.The excavated earth can be used partially for backfilling of foundation pit and partly for road work except for marshy soil. Hence cost of disposal has not been added except for marshy soil. This remark is common to all cases of item 15.1 excluding marshy soil. 3.The cost of shoring and shuttering, where needed, may be added @ 1 per cent on cost of excavation for open foundation.
209Supply and erection of Steel including Cutting, bendlng.weldlng of joints if required .fixing and placing of steel reinforcementin accordance with approved design and drawings including excavation and refilling of soil complete in all respect and any other work contingent thereto as per sizes and specification given in DNIT(Thermo-Mechanically Treated bars of grade Fe- 500D or more).
210C/C for tower foundation:- Providing and laying in position ready mixed plain cement concrete, using fly ash and cement content as per approved design mix and manufactured in fully automatic batching plant and transported to site of work in transit mixer for all leads, having continuous agitated mixer, manufactured as per mix design of specified grade for plain cement concrete work, including pumping of R.M.C. from transit mixer to site of laying and curing, excluding the cost of centering, shuttering and finishing, including cost of curing, admixtures in recommended proportions as per IS : 9103 to accelerate/ retard setting of concrete, improve workability without impairing strength and durability as per direction of the Engineer- in-charge. Note: Fly ash conforming to grade I of IS 3812 (Part-1) only be used as part replacement of OPC as per IS : 456. Uniform blending with cement is to be ensured in accordance with clauses 5.2 and 5.2.1 of IS: 456 -2000 in the items of BMC and RMC.M-10 grade plain cement concrete cum (cement content considered @ 220 kg/cum)1:4:8 Mix (M-10).
211C/C for tower foundation:- Providing and laying in position ready mixed M-25 grade concrete for reinforced cement concrete work, using cement content as per approved design mix, manufactured in fully automatic batching plant and transported to site of work in transit mixer for all leads, having continuous agitated mixer, dewatering if needed , manufactured as per mix design of specified grade for reinforced cement concrete work, including pumping of R.M.C. from transit mixer to site of laying , excluding the cost of centering, shuttering finishing and reinforcement, including cost of admixtures in recommended proportions as per IS : 9103 to accelerate/ retard setting of concrete, improve workability without impairing strength and durability as per direction of the Engineer-in-charge. (Note :- Cement content considered in this item is@ 330 kg/cum. Less cement used as per design mix is recoverable. However no extra payment shall be made if excess cement is used as per design mix)1:1.5:3 Mix (M-25).
212Control room building :- Designing and construction of RCC M-25 Framed structure building confirming to national building code for building in accordance with approved design and drawings with single story building height 5.00mtr or more as required, including cable trenches , all electrical , mechanicaland Sanitary works and all other works contingent thereto as per sizes and specification given in DNIT.
213Road :- Designing and construction of 6m wide C.C road and the main road leading to 66KV switch yard shall have a embankment as gradient with 150mm thick (1:3:6) with concrete base and 200mm thick M-25 design mix concrete with kerb and channels in accordance with approved design and drawings , Supply and installation of 8.00 Mtr high LED solar street light at 30m c/c , main gates walkways , levelling etc. complete in all respect and any other work contingent thereto as per sizes and specification given in DNIT.
214Foundation:- Steel structure for the following foundations:-Foundation of 66 KV CT Transformers , Foundation of 66 KV CT Metering , Foundation of 66 KV PT Metering , Foundation of 66 KV SF-6 BREAKER, Foundation of 66 KV CT LandE Switch , Foundation of 66 KV LA Line , Foundation of 66 KV CT Protection , Foundation of 66 KV PT PROTECTION ,Foundation of 66 KV PT bus bar , Foundation of 66 KV LA transformer , Foundation of 66 KV Isolator and Foundation of 66 KV CT-4 as needed and in accordance with approved design and drawings including excavation and refilling of soil complete in all respect and any other work contingent thereto as per sizes and specification given in DNIT(Steel reinforcement for R.C.C. work, where not included in the complete rate of RCC, including straightening, cutting, bending, placing in position, binding, wastage, overlaps, welded joints, spacer bars, chairs, stays, hangers and annealed steel wire etc. complete in all respect below plinth level Note:- Reinforcement shall be measured in length including hooks, if any, separately for different diameters as actually used in work , excluding overlaps. Wastage, overlaps, couplings, welded joints, spacer bars, chairs, stays, hangers and annealed steel wire or other methods of binding and placing shall not be measured and cost of these items shall be deemed to be included in the rates for reinforcement.Thermo- Mechanically Treated bars of grade Fe-500D kg or more ( for M-30) .
215Foundation :- Design and construction of RCC Grade M30 Using Concrete Mixer C.C of M30 concrete platforms for Foundation of 66 KV CT Transformers , Foundation of 66 KV CT Metering , Foundation of 66 KV PT Metering , Foundation of 66 KV SF-6 BREAKER, Foundation of 66 KV CT LandE Switch , Foundation of 66 KV LA Line , Foundation of 66 KV CT Protection , Foundation of 66 KV PT PROTECTION ,Foundation of 66 KV PT bus bar , Foundation of 66 KV LA transformer , Foundation of 66 KV Isolator and Foundation of 66 KV CT-4 including excavation and back filling as required to the complete satisfaction of Engineer-in-charge as needed and in accordance with approved design and drawings including excavation and refilling of soil complete in all respect and any other work contingent thereto as per sizes and specification given in DNIT.
216Earth mat:- Design , supply , and erection of earth mat work which includes 16mm thick rod and 20mm thick earth electrodes in accordance with approved design and drawings including excavation and refilling of soil complete in all respect and any other work contingent thereto as per sizes and specification given in DNIT (Steel reinforcement, including straightening, cutting, bending, placing in position, binding, wastage, overlaps, welded joints, spacer bars, chairs, stays, hangers and annealed steel wire etc. complete in all respect below plinth level.Thermo- Mechanically Treated bars of grade Fe-500D or more).
217Yard : Steel reinforcement for R.C.C. work, where not included in the complete rate of RCC, including straightening, cutting, bending, placing in position, binding, wastage, overlaps, welded joints, spacer bars, chairs, stays, hangers and annealed steel wire etc. complete in all respect below plinth level Note:- Reinforcement shall be measured in length including hooks, if any, separately for different diameters as actually used in work , excluding overlaps. Wastage, overlaps, couplings, welded joints, spacer bars, chairs, stays, hangers and annealed steel wire or other methods of binding and placing shall not be measured and cost of these items shall be deemed to be included in the rates for reinforcement.Thermo- Mechanically Treated bars of grade Fe-500D kg or more ( for M-30) .
218Yard :- Designing and construction of yard with 100mm thick C.C of M30 concrete after preparation of plinth( i.e compaction and filling of soil followed by 75mm M- 10 concrete and so as to achieve the final plinth level which should be 0.75 meter above the existing road level of WTP Basai.) including cable trenches , all electrical , mechanical works in accordance with approved design and drawings and all other works contingent thereto as per sizes and specification given in DNIT(ITEM For M-30)
219Yard :- Designing and construction of yard with 100mm thick C.C of M30 concrete after preparation of plinth( i.e compaction and filling of soil followed by 75mm M- 10 concrete and so as to achieve the final plinth level which should be 0.75 meter above the existing road level of WTP Basai.) including cable trenches , all electrical , mechanical works in accordance with approved design and drawings and all other works contingent thereto as per sizes and specification given in DNIT(ITEM for M-10).
220Boundary wall:- Designing and construction of boundary wall of 66 KV substation in WTP Basai with height shall be 1.50Mtr with RCC pillar @3Mtr C/C as per design / drawing foundation of boundary wall shall be minimum 0.90m below natural ground level.
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail