Tender For Construction Work Of Sattelite Hospital At Digari Kalla, District Jodhpur (Including Internal Electrification Work), jodhpur-Rajasthan

Medical Health And Family Welfare has published Tender For Construction Work Of Sattelite Hospital At Digari Kalla, District Jodhpur (Including Internal Electrification Work). Submission Date for this Tender is 05-12-2022. Electrification Work Tenders in jodhpur Rajasthan. Bidders can get complete Tender details and download the document.




Tender Notice

34997921
Corrigendum : Tender For Construction Work Of Sattelite Hospital At Digari Kalla, District Jodhpur (Including Internal Electrification Work)
Open Tender
Indian
Rajasthan
jodhpur
05-12-2022

Tender Details

Construction Work Of Sattelite Hospital At Digari Kalla, District Jodhpur ( Including Internal Electrification Work )

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 30-Nov-2022 Technical Bid Technical Bid 05-12-2022

Key Value

Document Fees
INR 5000 /-
EMD
INR 3282000.0 /-
Tender Value
INR 16.41 Crore /-

BOQ Items

Name of Work: Construction Work of Sattelite Hospital at Digari Kalla, District Jodhpur (including internal electrification work)
Sl. No. Item Description
1Building BSR 2019 Jodhpur District (Part A :- Civil Work) Surface dressing of the ground including removing vegetation and inequalities not exceeding 15cm deep and disposal of rubbish lead upto 50mtr. and lift upto 1.5Mtr.All kind of soil.
2Earth work in excavation by mechanical means (Hydraulic Excavator)/ manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan) including dressing of sides and ramming of bottoms, lift upto 1.5 m, including taking out the excavated soil and depositing and refilling of jhiri with watering & ramming and disposal of surplus excavated soil as directed with in a lead of 50 meter. All kinds of soils
3Add extra for foundations /trenches/ drains for every additional lift of 1.5 Mtr. or part thereof upto 4.5Mtr. depth.Ordinary or Hard soil.
4Providing and laying in position cement concrete including curing compaction etc. of specified grade excluding the cost of centering and shuttering All up to plinth level IS 456-2000:1:4:8 (1Cement :4 Course Sand :8 Graded stone aggregate 40 mm nominal size (Crusher Broken)
5Centering and shuttering with plywood or steel sheets including strutting, propping, bracing both ways and removal of formwork for foundations in basements rafts, footings, strap beams, bases of columns, etc. up to plinth level.
6Providing and laying in position specified grade of reinforced cement concrete including curing compaction finishing with rendering in cement sand mortar 1:3 (1-Cement:3-coarse sand) and making good the joints excluding the cost of centering, shuttering and reinforcement.All work up to plinth levelIS 456-2000:1:1.5:3 (1-Cement:1.5 coarse sand:3-graded stone aggregate 20 mm nominal size)
7Random Rubble stone masonary for foundation and plinth in Cement Sand Mortar above 30 Cm. thick wall IS 1597 (Part-I) 1992 in :Cement Sand Mortar 1:6 (1-Cement:6-Sand).
8Filling available excavated earth (excluding rock) in trenches, plinth side of foundation etc. in layers not exceeding 20 cm. in depth, consolidatingeach deposited layer by ramming and watering including lead upto 50Mtr. and lift upto 1.5Mtr.
9Carriage of Building Rubish Stone metal (Grit and Ballast etc.) with all lead & lift.
10Filling in plinth with river sand under floors including watering ramming consolidating and dressing complete including cost of sand.
11Random rubble dry stone Kharanja under floor.
12Providing and injecting Chloropyrifous Emulsifiableconcentrate 20 % with 1 % concentration for PRE-CONSTRUCTIONAL Anti termite treatment as per IS 6313 part III and amended from time to time and creating a continous chemical barrier under and around the column pits, wall trenches, basement excavation, top surface of plinth filling, junction of wall and floor along the external perimeter of building expansion joints, over the top surface of consolidated earth of which aproch is to be laid surrounding of pipes and conduits etc. complete as per specification (Plinth floor area only shall be measured for payment.)
13Centering and shuttering with plywood or steel sheets including strutting, propping, bracing both ways with wooden members andremoval of formwork for superstructure up to 4.5 mtr aboveplinth,for: Columns, pillars, posts and struts etc.
14Suspended floors, roofs, landings, staircases, balconies, girders, cantilevers, bands , coping, bed plates, anchor blocks, sills, chhajjas lintel, beam etc.
15Add extra over item Nos. 4.12.to 4.12.11 for doing centering and shuttering work for each subsequent storey.
16Reinforced cement concrete work in walls (any thickness) including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. up to floor three level including curing, compaction, finishing with rendering in cement sand mortar 1:3 (1-Cement:3-coarse sand) and making good the joints excluding cost of centering shuttering and reinforcement IS 456-2000:1:1.5:3 (1-Cement:1.5 coarse sand:3-graded stone aggregate 20 mm nominal size).
17Reinforced cement concrete work in beams, suspended floors, roofs, girders having slopes up to 15o, landings, balconies, shelves, chajjas, lintels, bands, plain windows sills, staircases and spiral staircases, up to floor three level including curing, compaction, finishing with rendering in cement sand mortar 1:3 (1-Cement:3-coarse sand) and making good and joints excluding the cost of centering, shuttering and reinforcement IS 456-2000:with 1:1.5:3 (1-Cement:1.5 coarse sand:3-graded stone aggregate 20 mm nominal size).
18Providing and fabricating reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding (including cost of binding wire) all complete up to floor three level.Thermo Mechanically treated bars
19Brick masonary in foundation and plinth with bricks of class designation 75 mm. IS 2212-1991 in : Cement Sand Mortar 1:6 (1-Cement:6-coarse sand). Add extra over item No. 5.1 for brick work in superstructure up to third storey IS 1077-1986.
20Half brick masonry in foundation & plinth using bricks of designation 75 with nominal hoop reinforcement (2 Nos. 6mm MS bar) at every fourth course.Cement Sand mortar 1:4 (1-Cement:4-coarse sand).
21Plaster on new surface on walls in cement sand mortar 1:6 including racking of joint etc. complete fine finish : 20 mm thick
2225 mm thick
23Finishing with neat cement (Punning).
24Making grooves as per design in plaster 10mm to 20mm wide.
25Providing and fixing Ist quality standard White Ivory straight edge Glazed Tiles ISI marked [IS:13753]of size 450mm x 300mm in walls, floors, steps, pillars etc. laid on a bed of neat cement slurry finished with flush pointing in white cement mixed with pigment to match the shade of tile complete (excluding the cost of cement plaster).
26Providing and laying water proofing treatment in sunken portion of WCs, bathroom etc., by applying Polymen modified cementous slurry mixed with armour cerete of M/s The Structural Water Proofing Company Pvt. Ltd., or Tapecrete of M/s Cico Engineer Service or Hydro Proof of Fosroc consisting of appering :1 First layer of slurry of cement @ 0.488Kg./sqm mixed with Armourcrete or Tapecrete @ 0.253 Kg/sqm.This layer will be allowed to air cure for 4 hours.2. Second layer of slurry of cement @ .242 Kg./sqm mixed with Armourcrete or Tapecrete @ 0.126 Kg./Sam.This layer will be allowed to air cure for 4 hours followed by water curing for 48 hours.Note- Rendering /plastering as protective layer, if require will be paid separately.
27Filling of sunk portion of roof with earthen pots of required height including filling voids with 1:2:4 light concrete, using brick bats complete levelingand dressing the surface by 50mm thick cement concrete 1:2:4 as per specification.
28Grading roof water proofing treatment with :Cement concrete 1:2:4 (1-Cement:2-coarse sand :4-graded stone aggregate 20mm nominal size).
29Supplying and fixing white soorsagar stone coping 13 Cm thick & 45 cm wide with 3 set back groove & one projection with sloped tope edge including cutting, moulding and chamffering etc.
30Providing batta (gola) 75mm x 75mm in cement concrete (1:2:4) including finished with cement mortar 1:3 as per standard design.
31Providing and laying 20 to 25 mm size glazed tiles pieces for rooof treatment having colour and shade as approved by the Engineer incharge over 25 mm thick layer of cement mortar mix 1:4 with application of cement slurry including finishing of joints with ordinary cement and curing etc. complete in all respect. Washing with acid.
32Providing and applying white cement based puttyover plastered surface to prepare the surface even and smooth complete
33Wall painting with plastic emulsion paint of approved brand and manufacture to give an even shade: Two or more coats on new work including preparation of base with primer, & touching of existing putty, lippy complete in all respect.
34Distempering with oil bound washable distemper of approved brand and manufacture to give an even shade including all scaffolding:New work (two or more coats) over and including scrapping and priming coat with cement primer.
35Painting with enamel paint of approved brand and manufacture to give an even shade: Two or more coats on new work.
36Providing and fixing Ist quality MAT finished ceremic tile size 300x300mm confirming to IS : 13753 colour such as white, grey, ivory, fume red brown in walls, floors, steps, pillars etc. laid on a bed of neat cement slsurry including nicely finished joints using water proof joint filler power and finishing with flush pointing in white cement mixed with pigment to match the shade of tile complete (excluding the cost of cement plaster).
37Providing & laying vitrified skid free, scratch resistant.Natural Rustic Finish for floor,skirting, Dado, Border tiles size 600mmx600mm, 10 mm thick flooring over 20 mm thick bed mortar 1:4 mix or fixed with chemical materials of approved company make and 2-3 mm thick joint to be filled with cementious grout or polymer based non shrink grout make of metaling colour in all shades including cutting of stone/doors etc. if any, as per requirement at site complete with all respect as approved by Engineer-in-charge.
38Providing and fixing Granite stone slab mirror polished and machine edge cut in Walls, Pillars, Steps, Shelves, Sills, Counters. Floors etc. laid on 12mm (Av.) thick base of cement mortar 1:3 jointing with white cement mortar 1:2 (1 white cement: 2 marble dust) with pigment to match the shade of the marble slab complete including grinding, rubbing and polishing ofIS 3316-1974 :Green/Black/Other granite Above 3601 Cm2 Slab.
39Extra for providing edge moulding to 18 mm thick marble stone counters, vantities etc. over item No. 7.1 & 7.2 including machine polishing to edge to give high gloss finish etc. complete as per design approved by Engineer-in-Charge. Granite work.
40Supplying and fixing in walls machine cut and polished stone shelves, tands andin CM 1:3 with machine cut edges : Kota stone minimum 30mm thick.
41Polished Blue Kota Stone slab in steps, walls, pillars having fine machine cut edges laid on 12mm (Av.) thick cement mortar 1:3 and jointed with grey cement slurry mixed with pigment to match the shade of the slab, including rubbing and polishing complete :30 mm thick slab area upto 2001 to 5000 Sq.Cm.
42Polished Blue Kota Stone flooring skirting, laid over 20 mm thick base of C.M. 1:4 and jointed with grey cement slurry to match the shade of the slab including rubbing and polishing complete :For area of each slab up to 2001 to 5000Sq. Cm :25 mm thick slab.
43Providing & laying Chequerred terrazzo tiles of approved make 22 mm thick with marble chips of size upto 6mm, in floors, jointed with neat cement slurry mixed with pigment to match the shade of tiles including rubbing and polishing complete in all respect as per specification, on 28 mm thick bed of C.M. 1:4 Dark shade using ordinary cement.
44Providing and laying Chequerred plain cement concrete embossed specially manufactured non-slipping tiles of approved make 20 mm thick laid on 20 mm thick bed of cement mortar 1:6 jointed with neat cement slurry complete.Add extra for chequerred coloured plain cement concrete or specially manufactured non-slipping tiles of approved make 20 mm thick.
45P & F Plain Fiber glass sheet (FRP sheet fiber Reinforcement product sheet confirming to IS:12866-1989 having minimum thickness as below including fixing with nuts bolts hooks and bitumen washer etc. complete.) 3.0 mm thick (Wt.5.0 Kg./Mtr.Sq.)
46Structural steel work riveted or bolted in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete above plinth level up to 4.5 Mtr. height in R.S. joist flats, tees, angles and channels.
47Providing and 30mm thickFactory made Solid Panel PVC Door shutter consisting of frame made out of M.S. tubes of 19 gauge thickness and size of 19mm for stiles & 15mmx15mm for top and bottom rails. M.S. frame shall have a coat of steel primers of approved make and manufacture. M.S. frame shall be covered with 5mm thick heat moulded PVC "C" Channel of size 30x50mm forming stiles, and 5mm thick, 75mm wide PVC sheets for top rail, lock rail and bottom rail on either side, & 10mm (5mmx2) thick, 20mm wide cross PVC sheets as gap insert for top rail & bottom rail. Panelling of 5mm thick PVC sheet to be fitted in the M.S. Frame welded/sealed to the stiles & rail with 30mm wide x 5mm thick PVC sheet beading on either side and joined together with solvent cement adhesive. An additional 5mm thick PVC strip o f 20mm width is to be stuck on the interior side of "C" Channel using PVC solvent cement adhesive etc. complete as per direction of Engineer-in-charge, manufacturer"s specification & drawing (For W.C. & Bathroom shutters).
48Providing and fixing factory made polyvinyl chloride (PVC) Door Frame of the size 50x47 mm with a wall thickness of 5mm made out of extruded 5mm, made out of extruded 5mm PV foam sheet, mitre cut at two corners and joining with 2 nos. of 150mm long brackets of 15x15mm M.S. Square tube. The two vertical door profiles are to be reinforced with 19x19mm M.S. square tube or 19 gauge. EPDM rubber gasket weather seal to be providing through out the frame shall be fixed to the wall using 65/100mm long M.S. screws through the frame by using PVC fastoners. A minimum of 4 nos. of screws to be provided for each vertical member and minimum 2 nos. for horizontal member etc. complete as per manufactures specification and direction of Engineer in Charge.
49Providing and fixing pressed steel mitred door frames manufactured from commercial mild steel sheet of 1.25 mm (16 gauge) thickness including hinges jamb, lock jamb, head and if required angle threshold of mild steel angle of section 50x25mm, or base ties of 1.25 mm pressed mild steel welded or rigidly fixed together by mechanical means, adjustable lugs with split end tail to each jamb including steel butt hinges 2.5 mm thick with mortar guards, lock strike-plate and shock absorbers as specified and applying a coat of approved steel primer after pre-treatment of the surface as directed by Engineer-in-charge.Profile "C"
50Providing & fixing MS sheet single leaf door shutters in angle iron frame 35x35x5 mm suitablly diagonally braced with 25x3mm flat ironabove and below lock rail of size 50x5 mm beading extra includingall fittings, as per direction of Engineer incharge but excluding cost of chokhats including two coats of anti corrositve red oxide primer panit.MS sheet 20 SWG
51Providing & fixing anodizing alumium work (Anodizing to be got done from approved Anodizer) for doors, windows, ventilators and partition with extruded built up standard tubular and other sections of approved make confirming to IS : 733 and IS : 1285 anodised transparent 81 dyed to required shade according to IS : 1868 (Minimum anodic coating of grade AC 15), fixed with rawl plugs and screws or with fixing clips or with expansion hold fasteners including necessary filling up of gas at junctions, at top, bottom and sides with required PVC/neoprene felt etc. Aluminium section shall be smooth, rust free, straight, mitred and jointed mechanically wherever required inlcuding cleat angle Aluminum snap beading for glazing/paneling, C.P. Brass/ Stainless Steel screws, Al. Tower bolt & Al. handle & Al. Aldrop etc. all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing and peneling to be paid for separately). For Fixed portion
52For shutters of doors, windows & ventilators incl. providing and fixing hinges/ rollers etc. and making provision for fixing of fittings wherever reqd. (lockes shall be paid for separately).
53Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with PVS/ neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge (Cost. of aluminium snap beading shall be paid in basic item.) With glass panes of 5.0mm thickness (weight not less than 13.75 Kg/Sqm) as per IS : 2835
54P&F expanded grill made of anodised aluminium as per design and drawing having members section of size 7.5mm x 6.0mm and opening of size 102mm x 99mm to aluminium window/ vent with reqd. screws, Y and H aluminium sec (as per drawing) at the ends and middle joints respectively complete in all respect as per direction of engineer in charge.
55Providing and fixing brass lock without handle for aluminium door, or approved quality, make & design as directed by Engineer incharge
56P&F double action hydraulic floor spring of approved brand and manufacture to aluminium door shutter confirming to IS : 6315 incl. costof cutting floors as reqd. embedding in floor and cover plate etc. complte as per direction of Engineer in charge.
57Providing and fixing in position collapsible steel shutters with vertical M.S. Channels 20x10x2mm and brackets with flat iron diagonals 20x5mm, size with top and bottom rail of T-iron 40x40x6mm, with 40 mm dia steel pulleys / ball bearing complete with bolts, nuts locking arrangements inside and outside stoppers, handles etc. as per specification including applying a priming coat of approved steel primer. (To be measured and paid as per outer dimension). IS 10521-1983.With 75 mm opening when closed.
58Providing and Fixing 12mm thick prelaminated three layer medium density (exterior grade) particle board Grade-I, Type-II confirming to IS 12823 bonded formaldehyde synthetic resin of approved brand and manufacture in paneling fixed in aluminium doors, windows/ stainless steel screws etc. complete as per architectural drawings and direction of engineer-in-charge. Pre-laminated particle board with decorative lamination on one side and balancing lamination on other side.
59Providing and fixing external grade board solid core single leaf flush door shutters ISI 2202-67 marked using Phenol formaldehye resin, in glue both sides with approved steel fittings complete as per Annexure ‘A’ IS 2202 (Part I & II) 1999/1983. Commercial Veneer both side 35 mm thick shutter
60Add extra for Flush doors For double leaf shutter
61For Internal teak wood lipping in 25mm depth in single leaf.
62Add extra for Vision Panel
63Supplying and fixing fixed wire gauge of 14 mesh x 24 gauge to the metal frame of rolled section by metal beading 20x3mm with suitable screw at not exceeding 150mm distance.
64Supply and fixing in cement mortar welded hand railing made out of M.S. round or square bars, flats etc. for staircase or verandah as per design complete in all respect (wooden or PVC hand railing to be paid extra) with priming coat of red oxide.
65Providing and fixing steel gate grating and grills made of angles, tees, square bars or other flats black pipe with holdfast and fittings complete as per design and drawing including cutting welding and fabrication with priming coat of red oxide.
66Providing and fixing acoustic false ceiling 13mm thick. As per design with white powder coated zincoliur metal section frame work including wall angle 24x24x 3.5mm to be fixed on the wall & ceiling section made of main runner of 12" length of size 24 x 32.7 x 3.5 mm at 1200mm c/c with cross runner of 600 x 1200 mm c/c the frame work should be suspended by means 3mm soft galvanised suspension circular, rod, clip & rod bracket from the existing ceiling by means of M.S. rawl plug of 12.5 mm dia x 35mm with 6mmdia bolt screw at 1200 mm/cc. The perforated bold band boutique & vinyle laminated tiles made up of gypsum with synthetic fibres of 4" x 2" or 2" x 2" size should be fixed in the suspended frame work as per design & drawing complete in all respect as per direction of Engineer-in-charge.
67Providing and fixing cow catcher made of R.S. joist angles channels MS rounds including cutting welding and fabrication with priming coat of red oxide (as per design).
68Providing and fixing in position Aluminium plate as per design for expansion joints.
69Providing and fixing SILFIL (Armour Board) of 20mm thickness (Thickness Built-up using minimum 10mm thick specifically extruded high Performance sheet) using double side to the casted surface to form the expansion joint. 25 mm
70Random Rubble stone masonary for superstructure above plinth level one storey height above 30 Cm. thick walls IS 1597 (Part-I) 1992 in :Cement Sand Mortar 1:6 (1-Cement:6-Sand).
71Extra for facing as per design and detailed specifications IS 1597 (Part-II) 1992 including additional cost of stonesover item No. 6.1 & 6.2 for : Course rubble facing First Sort.
72Course rubble facing Second Sort.
73Add extra for rock facing using Jodhpur white sand stone with porper projection and chiesel dressing of edges of stone 2 line dressing for building corners,jambs including uniform joints.
74Deep groove pointing on stone masonry in white cement sand mortar (1:3) with colour pigment of approved shade for all type of masonry incl. racking of joint as per specification complete in all respect.
75(Part B :- Sanitary Work) P & F Indian type white glazed vitreous china Ist quality W.C. orissa pan (IS:2556 Mark) with 100 mm vitreous china P or S trap including cutting and making good the wall and floor :Size 580x440 mm.
76P & F European type white glazed vitreous china Ist quality Double symphonic W.C. (IS:2556 Mark) with P or S trap including cutting and making good the wall and floor.
77P & F CPVC Pipes in SDR 11 (Internal work) with CPVC fittings (IS:15778 Mark)including cutting and making good the walls and floors :(B) Concealed pipe in wall(i) 20mm dia
78(ii) 25mm dia
79P & F CPVC Pipes in SDR 11 (Internal work) with CPVC fittings (IS:15778 Mark)including cutting and making good the walls and floors : 20 mm nominal outer dia pipes
8032 mm nominal outer dia pipes
81P & F Bib Cock (IS:8931 Mark) Superior quality of approved make : C.P. Brass bib cock, 15 mm nominal bore.
82C.P. Brass Long body, 15 mm nominal bore weight not less than 690 gm.
83C.P. Brass Elbow action, 15 mm nominal bore.
84C.P. Pillar cock, Swan-neck with castedspout, 15 mm nominal bore.
85P & F Inlet Connection (Angle Valves) Superior quality, of approved make, for Wash basin, Gyser etc.C.P. Inlet connection 15 mm Brass (IS:8931 marked).
86P & F 15 mm. Dia Connection pipe of approved quality/make:PVC pipe with C.P. Brass nuts 450 mm..
87P & F Full-way valve (IS:778 Mark) or wheel valve of approved make : Gun-metal 15 mm nominal bore.
88Gun-metal 25 mm nominal bore.
89Construction of Cement concrete chamber 125mm dia on depressed floor upto 45cm height from floor with :Stainless Steel Sheet Grating
90P & F WVC Wash basin (Ist quality IS:2556 Mark) of approved make with C.I. brackets duly painted 1 No. 15 mm C.P. Pillar cock (IS:8934 Mark) & 32 mm C.P. brass waste coupling of approved make 25 mm G.I. waste pipe complete including cutting & making good the wall :Size 550 mm x 400 mm dia for counter top.
91P & F PVC Storage Tank (IS:12701 marked indicating the BIS license No.) of approved make with cover, 25 mm dia 1 M long G.I. over-flow pipe & 25 Cm. long wash out pipe with plug & socket, including making connection etc. complete of approved design. (a) 500 litres capacity
92(b) 1000 litres capacity
93Hoisting Charges for each floor :(a) 500 litres capacity
94(b) 1000 litres capacity
95Providing and fixing unplasticized Poly Vinyl Chloride (UPVC) SWR pipes type `B" for sciland waste dischareg system (IS : 13592: 1992 marked) of approved quality/ make. 110 mm dia
96Providing and fixing unplasticized Poly Vinyl Chloride (UPVC) SWR pipes type `B" for sciland waste dischareg system (IS : 13592: 1992 marked) of approved quality/ make Nahni Trap with Jali 4", 110mm dia
97Bend 87.5 Dg. 110 mm Dia
98Single Tee 110 mm Dia
99Coupler 110 mm Dia
100Single tee with door 110 mm Dia
101Vent Cowel 100mm 110 mm Dia
102Pipe clip 110 mm Dia
103Construction of chamber in all type of soil with 300 mm thick masonry in Cm 1:6 m 100mm thick C.C. 1:5:10 in foundation, 20mm thick insider plaster in Cm 1:6, finished with floating neat cement, 50mm thick M-15 grade C.C. flooring , earthwork etc. complete as per design including disposal of surplus earth within a lead of 50 mtr. Inside size 300x300mm depth upto 0.5m & 5Kg C.I. cover with frame
104Construction of manhole in all type of soil inner size 90 X 60 Cm. thick masonry in CM 1:6, 10 Cm. thick cement concrete 1:5 10 in foundation, 20 mm thick inside plaster in CM 1:6, finished with floating neat cement, 50mm thick M-15 grade C.C. flooring,making channels, 80mm thick stone slab covering with 40mm thick M-15 grade C.C.flooring , 25 Kg. CI cover with frame of 40mm dia, earthwork etc. complete as per design including disposal of surplus earth within 50 mtr. lead. Depth upto 0.5mtr
105Construction of Man hole, in all types of soil inner size 1.5 x 1.2 M, with, 450mm thick masonry in CM 1:6, 10 Cm. thick cement concrete 1:5:10 in foundation, 20mm thick inside plaster in CM 1:6, finished with floating neat cement, 50 mm thick M-15 grade C.C. flooring making channels, 80 mm thick stone slab covering with 40 mm thick M-15 grade C.C.flooring, 38 Kg. C.I. cover with frame of 450mm dia, earthwork etc. complete including disposal of surplus earth within 50 mtr. lead as per design :Depth upto 1.5mtr
106Construction of soakage well in all type of soil 300 mm thick dry masonry top and bottom 300 mm course in CM 1:6, 80 mm thick stone slab, jointing of slab in CM 1:3, Ralthal, Kharanja, 40 mm thick M-15 grade C.C. flooring, earth work complete as per approved drawing including disposal of earth within a lead of 50 mtr. : Size 300 Cm. dia outside & 300 Cm. depth.
107Construction of septic tank in all type sof soil with 40cm thick masonry in CM 1:6 15cm thick CC bed of 1:5:10 M-15 grade CC flooring & over stone slab covering, 80mm thick slab jointing of slab in CM 1:3, Ralthal, Kharanja, 50mm thick stone partiton walls, 20mm thick plaster in CM 1:6 finished with neat floating cement, 4Nos C.I. foot rests of approved design, two No. 450mm dia 25Kg each C.I. cover with frame, earth work etc. complete as per approed drawing incl. disposal of surplus earth wtihin a lead of 50mtr. IS 2470 (Part-I) 1985. Size 400x140x150cm (for 50users)
108P & F kitchen & Lab Sink of approved make with C.I. brackets duly painted, 40 mm C.P. waste coupling, C.P. Brass chain with rubber plug, 40 mm G.I. waste pipe up to floor level complete including cutting and making good the wall & floorIS 771 (Part-II) -1985.WVC Lab Sink (IS:2556 Mark) size 530x430x180 mm.
109P & F Flush Cock/Flush Valve (IS:9758 Mark) or WC of approved quality make : C.P. brass push type exposed 25 mm nominal bore.
110P & F Ist quality WVC Urinal (IS:2556 mark) with 25 mm dia G.I. waste pipe, dome couplings, concealed iron brackets or screws etc. complete. Flat Back (small) size 440x265x315 mm.
111C.P. brass Towel rail elbow type with concealed screws size 600mm (heavy duty)
112C.P. brass towel ring revolving type
113P&F looking mirrors with PVC frame of approved ISI make.Size 500x400mm
114P&F Soap dish or tray of approved quality/ make.C.P. brass heavy and superior quality.
115P & F Marble Urinal Partition slab both sides polished of approved design cut from marble size 900x600mm. IS 2556 (Part VI Sec.4)-1995. Makrana II quality marble having light spots.
116P&F rigid PVC Pipe (IS:4985 mark) class II(4 Kg. /Cm.) approved quality /makeincluding joining the pipe with solvent cement rubber ring and lubricant 110mm dia
117P&F rigid PVC pipe fittings (IS: 4985 mark) of approved quality /make including joining the pipe with solvent cement rubber ring and lubricant: Coupler (110mm dia)
118Bend 87.5 (110mm dia)
119Pipe clip (110mm dia)
120(Part C :- Firefighting and Detection Mechanism Work) Surface dressing of the ground including removing vegetation and inequalities not exceeding 15cm deep and disposal of rubbish lead up to 50 Mtr. and lift up to 1.5 Mtr.: All kinds of soil
121Excavation work by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains not exceeding 1.5 m in width or 10 sqm on plan including dressing of sides and ramming of bottoms lift upto 1.5 m, including gettingout the excavated soil anddisposal of surplus excavated soil as directed with a lead in a 50 meter including stacking of useful material if available :
122Add extra over item No. 1.8 and 1.9 for every additional lift of 1.5 Mtr. or part thereof : All Kind of soil
123Supplying and Filling in plinth with river sand under floors including watering ramming consolidating and dressing complete including cost of sand
124Random rubble dry stone Kharanja under floor.
125Providing and laying in position cement concrete including curing, compaction etc. complete in specified grade excluding the cost of centering and shuttering - 1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size)..
126Centering and Shuttering with plywood or steel sheets including strutting, propping bracing both ways and removal of formwork for superstructure up to 4.5 Mtr. above plinth for :Walls (any thickness) including attached pilasters,buttressesplinthandstring course.
127Suspended floors, roofs, landings, staircases, balconies, girders, cantilevers, bands, coping bed plates,anchorblocks,sills,chhajjas,lintel,beam, plinth beam etc.
128Providing and laying in position machine batched, machine mixed and machine vibrated design mix cement concrete of specified grade for reinforced cement concrete structural elements, excluding the cost of centering, shuttering and reinforcement including curing, compaction, finishing with rendering in cement sand mortar 1:3 (1-Cement:3-coarse sand) and making good the joints and Admixtures in recommended proportions as per IS : 9103 to accelerate, retard setting of concrete improve workability without impairing strength and durability as per direction of Engineer-in-charge. M-20 grade reinforced cement concrete.All work up to plinth level.
129Providing and laying in position machine batched, machine mixed and machine vibrated design mix cement concrete of specified grade for reinforced cement concrete structural elements, excluding the cost of centering, shuttering and reinforcement including curing, compaction, finishing with rendering in cement sand mortar 1:3 (1-Cement:3-coarse sand) and making good the joints and Admixtures in recommended proportions as per IS : 9103 to accelerate, retard setting of concrete improve workability without impairing strength and durability as per direction of Engineer-in-charge. M-20 grade reinforced cement concrete. Beams, plinth beams, girders, bressumers, cantilevers, suspended floors, lintels, roofs and staircases including spiral staircases, shelves etc.
130Brick work with F.P.S. bricks of class designation 75 in superstructure above plinth level upto floor V level in all shapes and sizes in : Cement mortar 1 : 6 (1 cement : 6 coarse sand)
131Add extra for providing richer mixes respectively at all floor levels Providing M-25 grade concrete by using min 410 kg of cement per cum instead ofM-20 grade design mix.
132Providing and fabricating reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding (including cost of binding wire) all complete up to floor three level.Thermo Mechanically treated bars
133Plaster on new surface on walls in cement sand mortar 1:6 including racking of joint etc. complete fine finished: 12 mm
134Grading roof for water proofing treatment withwater proffing compoundCement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size)
135Providing and laying 20 to 25 mm size glazed tiles pieces for rooof treatment having colour and shade as approved by the Engineer incharge over 25 mm thick layer of cement mortar mix 1:4 with application of cement slurry including finishing of joints with ordinary cement and curing etc. complete in all respect. Washing with acid.
136Providing and fixing Ist quality standard White Ivory Glazed Tiles ISI marked [IS:13753] of size 300mm x 200mm in walls, floors, steps, pillars etc. laid on a bed of neat cement slurry finished with flush pointing in white cement mixed with pigment to match the shade of tile complete (excluding the cost of cement plaster).
137Providing and fixing steel gate grating and grills made of angles, tees, square bars or other flats black pipe with holdfast and fittings complete as per design and drawing including cutting welding and fabrication with priming coat of red oxide.
138Providing and applying white cement based puttyover plastered surface to prepare the surface even and smooth complete
139Distempering with oil bound washable distemper of approved brand and manufacture to give an even shade including all scaffolding:New work (two or more coats) over and including scrapping and priming coat with cement
140Construction of tube-well from ground level and upto 100 Meter depth and above sizes in all types of soils in alluvium strata by “bailing” method and without gravel packing as per IS: 2800 (Part - I& II) 1979 specifications (The work includes formation of cavity well at bottom by development with appropriate air compressor or bailer pumping and also lowering of casing pipe but excluding cost of the casing pipe. The tube-well should have a throughout bore as per nominal bore of casing pipe. The work would be completed after obtaining sand free water.) 150 mm dia
141Construction of Tube-well upto 100 Meter depth and above in all type of rocks by DTH system and over burden, to accommodate casing pipe of following sizes in all types of soils and over burden including lowering of casing pipes, but excluding cost of casingpipes as per IS : 2800 (Part I & II) 1979 specifications. The work would be completed after obtaining sand free water. The tube well should have a throughout bore as per nominal dia of casing pipe: 200 mm –do-
142Supply of ERW M.S. black casing pipe ISI marked (IS:4270/1992) of grade Fe410 of following sizes at site of work.200 mm Nominal bore of pipe
143S & F tube well cover ofM.S.sheet (6mm thick) with nuts and bolts complete for casing size:200 mm Nominal bore of pipe
144Development of tube well as per IS specification using suitable compressor to give sand free water for required yield of the gravel packed tube well.
145S & F M.S. clamp, set of 50 ×6mm flat iron with nuts and bolts etc. for holding the riser pipe assembly of submersible pump set.
146(Part D :- Manifold Room, Gas Plant and ST Mieter Room) Surface dressing of the ground including removing vegetation and inequalities not exceeding 15cm deep and disposal of rubbish lead up to 50 Mtr. and lift up to 1.5 Mtr.: All kinds of soil
147Excavation work by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains not exceeding 1.5 m in width or 10 sqm on plan including dressing of sides and ramming of bottoms lift upto 1.5 m, including gettingout the excavated soil anddisposal of surplus excavated soil as directed with a lead in a 50 meter including stacking of useful material if available :
148Add extra over item No. 1.8 and 1.9 for every additional lift of 1.5 Mtr. or part thereof : All Kind of soil
149Providing and laying in position cement concrete including curing, compaction etc. complete in specified grade excluding the cost of centering and shuttering - 1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size)..
150Random Rubble stone masonry for with hard stone in foundation and plinth in Cement Sand mortar above 30 CM thick wall in: Cement Mortar 1:6 ( 1-Cement : 6-Sand).
151Centering and Shuttering with plywood or steel sheets including strutting, propping bracing both ways and removal of formwork for foundation , footings,strap beam, raft , bases of columns etc.
152Providing and laying in position specified grade ofcement concrete forall RCC structural elements upto plinth level including curing, compaction, finishing with rendering in cement sand mortar 1:3 (1 cement: 3 coarse sand) and making good the joints and cost of plastizers( if required) excluding the cost of centering, shuttering and reinforcement. M20 grade Nominal Mix / Design Mix
153Brick work with F.P.S. bricks of class designation 75 in superstructure above plinth level upto floor V level in all shapes and sizes in : Cement mortar 1 : 6 (1 cement : 6 coarse sand)
154Centering and shuttering with plywood or steel sheets including strutting, propping, bracing both ways with wooden members andremoval of formwork for superstructure up to 4.5 mtr aboveplinth,for:Columns, pillars, posts and struts etc.
155Suspended floors, roofs, landings, staircases, balconies, girders, cantilevers, bands , coping, bed plates, anchor blocks, sills, chhajjas lintel, beam etc.
156Reinforced cement concrete work in beams, suspended floors, roofs, girders having slopes up to 15o , landings, balconies, shelves, chajjas, lintels, bands, plain windows sills, staircases and spiral staircases, up to floor three level including curing, compaction, finishing with rendering in cement sand mortar 1:3 (1-Cement:3-coarse sand) and making good and joints excluding the cost of centering, shuttering and reinforcement: 1:1.5:3 (1-Cement:1.5 coarse sand:3-graded stone aggregate 20 mm nominal size).
157Reinforced cement concrete work in walls (any thickness) including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. up to floor three level including curing, compaction, finishing with rendering in cement sand mortar 1:3 (1-Cement:3-coarse sand) and making good the joints excluding cost of centering shuttering and reinforcement : 1:1.5:3 (1-Cement:1.5 coarse sand:3-graded stone aggregate 20 mm nominal size).
158Add extra for providing richer mixes respectively at all floor levels Providing M-25 grade concrete by using min 410 kg of cement per cum instead ofM-20 grade design mix.
159Providing and fabricating reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding (including cost of binding wire) all complete up to floor three level.Thermo Mechanically treated bars
160Filling available excavated earth (excluding rock) in trenches, plinth side of foundation etc. in layers not exceeding 20 cm. in depth, consolidatingeach deposited layer by ramming and watering including lead upto 50Mtr. and lift upto 1.5Mtr.
161Random rubble dry stone Kharanja under floor.
162Kota stone slab flooring 25 mm thick over 20 mm (average) thickbase laid over and jointed with grey cement slurry mixed with pigment to match the shade of the slab including rubbing and polishing completewith base of cement mortar 1 : 4 (1 cement : 4 coarse sand) For area of each slab from 2001 to 5000 Sq.Cm
163Grading roof for water proofing treatment withwater proffing compoundCement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size)
164Cement concrete flooring grade 1:2:4 (1-Cement:2-Coarse sand:4-graded stone aggregate) rounding off edges etc. but excluding the cost of nosing of steps etc. complete IS 2571-1970 :50 mm thick with 20 mm thick nominal size aggregate.
165Providing batta (gola) 75mm x 75mm in cement concrete (1:2:4) including finished with cement mortar 1:3 as per standard design.
166Providing and laying 20 to 25 mm size glazed tiles pieces for rooof treatment having colour and shade as approved by the Engineer incharge over 25 mm thick layer of cement mortar mix 1:4 with application of cement slurry including finishing of joints with ordinary cement and curing etc. complete in all respect. Washing with acid.
167Plaster on new surface on walls in cement sand mortar 1:6 including racking of joint etc. complete fine finished: 20 mm thick.
168Providing and applying white cement based puttyover plastered surface to prepare the surface even and smooth complete
169Distempering with oil bound washable distemper of approved brand and manufacture to give an even shade including all scaffolding:New work (two or more coats) over and including scrapping and priming coat with cement primer.
170Wall painting with plastic emulsion paint of approved brand and manufacture to give an even shade: Two or more coats on new work including preparation of base with primer, & touching of existing putty, lippy complete in all respect.
171Supplying and fixing of rolling shutters of approved make, made of 80x1.25mm ms laths interlocked together through their entire length and jointed together at the end by end locks mounted on specially designed pipe shaft with brackets, side guides and arrangments for in side and out side locking with push and pull operation complete including cost of spring hooks, providing and fixing necessary 25.3 cm long wire spring grade No 2 and ms top cover 1.25 mm thick for rolling shutters as per design(Clear openable area to be measured for payment.) IS 6248-1979.
172Providing and fixing ball bearing for rolling shutters
173Providing and fixing pressed steel mitred door frames manufactured from commercial mild steel sheet of 1.25 mm (16 gauge) thickness including hinges jamb, lock jamb, head and if required angle threshold of mild steel angle of section 50x25mm, or base ties of 1.25 mm pressed mild steel welded or rigidly fixed together by mechanical means, adjustable lugs with split end tail to each jamb including steel butt hinges 2.5 mm thick with mortar guards, lock strike-plate and shock absorbers as specified and applying a coat of approved steel primer after pre-treatment of the surface as directed by Engineer-in-charge.Profile C
174Providing and fixing external grade board solid core single leaf flush door shutters ISI 2202-67 marked using Phenol formaldehye resin, in glue both sides with approved steel fittings complete as per Annexure ‘A’ IS 2202 (Part I & II) 1999/1983.Commercial Veneer both side 35 mm thick shutter
175Supplying and fixing of Steel windows made out (65x40mm), hollow metal pressed section of 1.25 mm thick sheet F4 & F7 standard rolled section conforming to IS 1038 with wholly openable shutter of 0.80 mm thick (out side & inside) opening C.R. sheet embossed panels, joints matted and flush welded with suitable hinges, steel lugs & screws with approved oxidized steel handles, fittings, peg stays (casement stays) etc. complete in all respect including providing 10 mm square M.S. bars 10 Cm. C/C and applying priming coat of red oxide paint.
176Supplying and fixing fixed wire gauge of 14 mesh x 24 gauge to the metal frame of rolled section by metal beading 20x3mm with suitable screw at not exceeding 150mm distance.
177Providing and fixing Square bars or other flat welded to window, ventilators etc.
178Painting with enamel paint of approved brand and manufacture to give an even shade: Two or more coats on new work.
179(Part E :- Road and Development Work) Providing & laying interlocking terrzo cloured block plastic moulded.80 mm thickness having min. crushing strangth 40 N/mm2 laid over 40 mm thick river sand bed complete as per drawing and approved by Engineer In Charge , Complete with all respect .
180Banking excavated earth in layers not exceeding 20 Cm. In depth breaking clods watering, rolling each layer with ½ tonne roller, or stone or steel rammers, and rolling every 3rd and top most layer with power roller of 8-10 tonne capacity and dressing up in embankments for roads, flood banks marginal banks, and guide banks etc. lead up to 50 Mtr. and lift up to 1.5 Mtr.: All kinds of soil.
181Providing and laying in position cement concrete including curing compaction etc. of specified grade excluding the cost of centering and shuttering =All up to plinth level IS-456-2000: 1:4:8 (1Cement :4 Course Sand :8 Graded stone aggregate 40 mm nominal size (Crusher Broken)
182Supply and installation of Multi Rib Proofing/cladding Sheet Manufacture out of0.50mm TCT (Total Coated Thickness) high tensile Zinc aluminum alloy coated galvaiumeseel (as per 150gsm zinc aluminum coated 550Mpa tuekd strength) confirming to IS: 1397/astm A-792 sheet to have wide pens 30mm high NB at 250 centre and centre width of 1020mm shets be casted with regular modified plyster system on a continuous with line on centre for face and with a polyster coating respectively sheet shall have proportionality with siphoned plate at made at to prevent leakage sheet shall be fixed by more of sell drilling lift tapping hot dip zinc coated hox head fasterner of size 12x14x55mm long. The sheet shall be supplied in cost one length and foe a minimum up to 12mts with all scaffolding.0.50 mm thick.
183Steel work in built up tubular trusses including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer, welded and bolted including special shaped washers etc. complete above plinth level up to 4.5Mtr. height as perIS 1161-1998.Hot finished welded type tubes
184Supply and fixing Jodhpur sand stone Machine cut Kerb stone (10cm wide 40 cm. height)fixed in white cement sand mortar 1:4 with pigment including EarthWork.
185Providing and laying in position cement concrete including curing, compaction etc. complete in specified grade excluding the cost of centering and shuttering - All work up to plinth level.M15 grade Nominal Mix 1: 2: 4 (1 cement : 2 coarse sand : 4 graded stoneaggregate 20mm nominal size).
186Painting with enamel paint of approved brand and manufacture to give an even shade: Two or more coats on new work.
187(Part F :- Morchry Work) Earth work in excavation by mechanical means (Hydraulic Excavator)/ manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan) including dressing of sides and ramming of bottoms, lift upto 1.5 m, including taking out the excavated soil and depositing and refilling of jhiri with watering & ramming and disposal of surplus excavated soil as directed with in a lead of 50 meter.All kinds of soils
188Filling available excavated earth (excluding rock) in trenches, plinth side of foundation etc. in layers not exceeding 20 cm. in depth , consolidatingeach deposited layer by ramming and watering including lead upto 50Mtr. and lift upto 1.5Mtr.
189Providing and injection Chloropyrifous Emulsifiableconcentrate 20 % with 1 % concentration for PRE-CONSGTRUCTIONAL Anti termite treatment as per IS 6313 part III and amended from time to time and creating a continous chemical barrier under and around the column pits, wall trenches, basement excavation, top surface of plinth filling, junction of wall and floor along the external perimeter of building expansion joints, over the top surface of consolidated earth of which aproch is to be laid surrounding of pipes and conduits etc. complete as per specification (Plinth floor area only shall be measured for payment.) Heptachlor E.C. 20% with 10% concentration
190Providing and laying in position cement concrete including curing compaction etc. of specified grade excluding the cost of centering and shuttering =All up to plinth level 1:4:8 (1Cement :4 Course Sand :8 Graded stone aggregate 40 mm nominal size (Crusher Broken)
191Providing and laying in position specified grade of reinforced cement concrete including curing compaction finishing with rendering in cement sand mortar 1:3 (1-Cement:3-coarse sand) and making good the joints excluding the cost of centering, shuttering and reinforcement.All work up to plinth level : 1:1.5:3 (1-Cement:1.5 coarse sand:3-graded stone aggregate 20 mm nominal size)
192Reinforced cement concrete work in beams, suspended floors, roofs, girders having slopes up to 15o , landings, balconies, shelves, chajjas, lintels, bands, plain windows sills, staircases and spiral staircases, up to floor three level including curing, compaction, finishing with rendering in cement sand mortar 1:3 (1-Cement:3-coarse sand) and making good and joints excluding the cost of centering, shuttering and reinforcement: 1:1.5:3 (1-Cement:1.5 coarse sand:3-graded stone aggregate 20 mm nominal size).
193Centering and shuttering with plywood or steel sheets including strutting, propping, bracing both ways and removal of formwork for foundations in basements rafts, footings, strap beams, bases of columns , etc. up to plinth level.
194Centering and shuttering with plywood or steel sheets including strutting, propping, bracing both ways with wooden members andremoval of formwork for superstructure up to 4.5 mtr aboveplinth,for: (a) Suspended floors, roofs, landings, staircases, balconies, girders, cantilevers, bands , coping, bed plates, anchor blocks, sills, chhajjas lintel, beam etc.
195Providing and fabricating reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding (including cost of binding wire) all complete up to floor three level.Tremo Mechanically treated bars
196Half brick masonry in foundation & plinth using bricks of designation 75 with nominal hoop rainforsed (2 Nos. 6mm MS bar) at every fourth course in for hoop rainforcement 1Sqm. 6mm MS bar 2x2x1.00 = 4.00 Cement mortar 1:4 (1-Cement:4-coarse sand).Add extra over item No. 5.8 for half brick masonary in superstructure up to third story.
197Random Rubble stone masonary for foundation and plinth in Cement Sand Mortar above 30 Cm. thick wall in : Cement Mortar 1:6 (1-Cement:6-Sand).
198Random Rubble stone masonary for superstructure above plinth level one storey height above 30 Cm. thick walls in : Cement Mortar 1:6 (1-Cement:6-Sand).
199Extra for facing as per design and detailed specifications including additional cost of stones for : Course rubble facing Second Sort.
200Add extra for rock facing using Jodhpur white sand stone with porper projection and chisal dressing of edges of stone 2 line dressing for building corners,jambs including uniform joints.
201Supplying and fixing machine cut and polished stone shelves, tands and sills in CM 1:3 with machine cut edges: Kota stone 25 to 30 mm thick.
202Supplying and fixing Soorsagar Bhura or Equivalent ashlar sills, lintels and dassa, bearing, bed & top surface made perfenctly even, jambs, skirting steps etc. rough dressed: Upto 15 cm. thick
203Providing and fixing Ist quality standard White Ivory Glazed Tiles ISI marked [IS:13753] of size 300mm x 200mm in walls, floors, steps, pillars etc. laid on a bed of neat cement slurry finished with flush pointing in white cement mixed with pigment to match the shade of tile complete (excluding the cost of cement plaster). (A) Category-I :
204Providing and fixing Ist quality MAT finished ceremic tile size 300x300mm confirming to IS : 13753 coloured tile expect white, grey, ivory, fume red brown in walls, floors, steps, pillars etc. laid on a bed of neat cement slurry including nicely finished joints using water proof joint filler power (Untile or Roffe make) and finishing with flush pointing in white cement mixed with pigment to match the shade of tile complete (excluding the cost of cement plaster). Add extra over item No. 7.3, 7.4, & 7.5 for floor work due to extra cost of cement mortar 1:4 (1-Cement:4- fine sand) 20 mm thick.
205Providing and fixing T-iron frames for doors, windows and ventilators of mild steel Tee-sections, joints mitred and welded with 15x3 mm lugs 10 Cm. long embedded in cement concrete blocks 15x10x10 Cm. of 1:3:6 (1-Cement:3-coarse sand:6-graded stone aggregate 20 mm nominal size) or with wooden plugs and screws or rawl plugs and screws or with fixing clips or with bolts and nuts as required including fixing of necessary butt hinges and screws and applying a priming coat of approved steel primer.
206Supply and fixing in cement mortar welded hand railing made out of M.S. round or square bars, flats etc. for staircase or verandah as per design complete in all respect (wooden or PVC hand railing to be paid extra) with priming coat of red oxide.
207Supply & fixing of steel window made out 100x40 mm hollow metal pressed section of 16 gauge thick sheet partly openable and partly fixed panel shutter with 5 mm thick plain glass panes outside openable and wire gauge 14x24 gauge inside openable shutter with M.S. square bar 10 mm side, fixed, portion of window should be glazed by 5 mm thick plain glass of TG welded to M.S. frame and approved make putty with glazing clips inching joints mitred and plug welded with suitable hinges hold fast steel lug and screws with approved oxidized steel handles fittings peg stays etc. complete in all respect including providing 10 mm square MS bars 15 cm. center to cernter and applying priming coat of red oxide paints as per approved drawing by Engineer"s incharge ground floor/ first floor
208Providing batta (gola) 75mm x 75mm in cement concrete (1:2:4) including finished with cement mortar 1:3 as per standard design.
209Providing and laying 20 to 25 mm size glazed tiles pieces for rooof treatment having colour and shade as approved by the Engineer incharge over 25 mm thick layer of cement mortar mix 1:4 with application of cement slurry including finishing of joints with ordinary cement and curing etc. complete in all respect. Washing with acid.
210Cement concrete flooring grade 1:2:4 (1-Cement:2-Coarse sand:4-graded stone aggregate) rounding off edges etc. but excluding the cost of nosing of steps etc. complete : 50 mm thick with 20 mm thick nominal size aggregate.
211Providing and laying Chequerred plain cement concrete embossed specially manufactured non-slipping tiles of approved make 20 mm thick laid on 20 mm thick bed of cement mortar 1:6 jointed with neat cement slurry complete.
212Providing & laying vitrified dianomite floor tile, skirting, dedo, (Johnson, Euro, Naveen, Bell or equivalent etc.) size 600x600, 10 mm thick flooring over 20 mm thick bed mortar 1:4 mix with 2-3 mm thick joint to be filled with cementious grout or polymer based non shrink grout make Rofee/ Bell adhesive/ pidite etc of matching colour as per requirement of site.
213Plaster on new surface on walls in cement sand mortar 1:6 including racking of joint etc. complete fine finished: 25 mm thick.
214Deep groove pointing on stone masonry in white cement sand mortar (1:3) with colour pigment of approved shade for all type of masonry incl. racking of joint as per specification complete in all respect.
215Painting with enamel paint of approved brand and manufacture to give an even shade: Two or more coats on new work.
216Grading roof water proofing treatment with : Cement concrete 1:2:4 (1-Cement:2-coarse sand :4-graded stone aggregate 20mm nominal size).
217Finishing wall with water proofing cement paint of approved brand and manufacture and or required shade to give an even shade including all scaffolding:New work (Three or more coats).
218Distempering with oil bound washable distemper of approved brand and manufacture to give an even shade including all scaffolding: New work (two or more coats) over and including scrapping and priming coat with cement primer.
219Providing and fixing external grade board solid core single leaf flush door shutters ISI 2202-67 marked using Phenol formal, dehydreresin in glue both sides with approved steel fittings complete as per Annexure ‘A’ Commercial Veneer both side. 30 mm thick shutter
220Add extra for Flush doors For Internal teak wood lipping in 25mm depth in single leaf.
221Add extra for Flush doors For Internal teak wood lipping in 25 mm depth in Double leaf.
222Add extra for Flush doors For double leaf shutter
223Polished Blue Kota Stone slab in steps, walls, pillars having fine machine cut edges laid on 12mm (Av.) thick cement mortar 1:3 and jointed with grey cement slurry mixed with pigment to match the shade of the slab, including rubbing and polishing complete : 25 mm thick slab area upto 901 to 2000Sq.Cm.
224Supplying and fixing ashlar sills, jambs, skirting, steps etc. rough dressed: (A) Upto 15 cm thick White Ashlar
225Extra for wall up to 30 Cm. and less thickness.
226Pillar masonry including bed plates as per specifications.Bed plate to be paid separately.
227Providing and fixing steel gate grating and grills made of angles, tees, square bars or other flats black pipe with holdfast and fittings complete as per design and drawing including cutting welding and fabrication with priming coat of red oxide.
228Providing and fixing welded mesh/expanded metal mesh in frame work, flat iron beading 20x3mm including top cross laps inside and out sides welding, iron bolts, crews, clips etc. complete (excluding frame work) of size. Welded mesh 25x25mmx16 gauge.
2296mm cement plaster to ceiling of mix 1:3 (1 Cement : 3 fine sand)
230Providing and fixing in position collapsible steel shutters with vertical M.S. Channels 20x10x2mm and brackets with flat iron diagonals 20x5mm, size with top and bottom rail of T-iron 40x40x6mm, with 40 mm dia steel pulleys / ball bearing complete with bolts, nuts locking arrangements inside and outside stoppers, handles etc. as per specification including applying a priming coat of approved steel primer. (To be measured and paid as per outer dimension). With 75mm opening when closed.
231Providing and fixing Granite stone slab mirror polished and machine edge cut in Walls, Pillars, Steps, Shelves, Sills, Counters. Floors etc. laid on 12mm (Av.) thick base of cement mortar 1:3 jointing with white cement mortar 1:2 (1 white cement: 2 marble dust) with pigment to match the shade of the marble slab complete including grinding, rubbing and polishing of: Green/Black/Other granite Size above 3601 Cm2
232Providing and fixing precast R.C.C. slab mix 1:2:4 (1-Cement:2-sand:4-stone aggregate 12.5 mm nominal size) as per design up to 30 mm thick for shelves etc. including cost of reinforcement consisting of wire mesh 100x100x4mm with fine finish.
233Filling in plinth withlocally available river shingle under floors including watering ramming consolidating and dressing complete including cost of shinglessand.
234Electrical BSR 2022 Rajasthan Jaipur (Part G:- Electrical Work) Rewiring of light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV gradeand 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694) in recessedISI marked MMS ( IS:9537 P - III ) virgin material PVC conduit & it"s ISI marked (IS:3419-1988) accessories, round tiles, 1.2 mm thick MS box with earth terminal, 6 A switch, 3 pin ceiling rose/holder / 3 way connector , 3.0 mm thick ISI marked (IS:2036-1995) phenolic laminated sheet, Al.alloy / Cadmium plated iron/brassscrews, cup washers, making connections, testing etc. as required. For specification of copperConductor,Phenolic Laminated sheet"s & Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E - 07 For additional technical parameters of product / work refer Annexure "A" attached with this BSR. Short point (up to 3 mtr.)
235Medium point (up to 6 mtr.)
236Long point(up to 10 mtr.)
237Rewiring of twin control light / fan / call bell point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV gradeand 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694) inrecessed ISI marked MMS ( IS:9537 P - III ) virgin materialPVC conduit & it"s ISI marked (IS:3419-1988) accessories, round tiles, 2 Nos 1.2 mm thick MS box with earth terminal, 2 Nos 6 A two way switch,3 pin ceiling rose / holder/ 3 way connector,3.0 mm thick ISI marked (IS:2036-1995) phenolic laminated sheet, Al.alloy / Cadmium plated iron/ brassscrews, cup washers, making connections, testing etc. as required.For specification of copperConductor,Phenolic Laminated sheet"s & Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E - 07 For additional technical parameters of product / work refer Annexure "A" attached with this BSR. Medium point (up to 6 mtr.)
238Long point(up to 10 mtr..)
239Wiring of 3/5 pin 6 amp. Light plug point with 1.5 sq. mm nominal sizeFR PVC insulated unsheathed flexible copper conductor 1.1 kV gradeand 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade(IS:694) inrecessed ISI marked MMS ( IS:9537 P - III ) PVC conduit & it"s ISI marked (IS:3419-1988)accessories, Hot Dipped GalvanizedModular box of 1.2 mm thick with earth terminal, 10 A modularswitch, 3/5 pin 6 A modular socket, Modular face plate with grid plate, screws, making connections, testing etc. as required.For specification of copperConductor,Phenolic Laminated sheet"s & Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E - 07 For additional technical parameters of product / work refer Annexure "A" attached with this BSR. On board
240Supplying and fixing of power plug point with Modular accessories as per PWD specification for electrical Works, on hot dipped galvanized modular box of 1.2 mm thick with earthing terminal/connector on surface or in recessed with suitable size of modular face place with grid plate and cover plate including cost ofISI marked modular 16 amp. Switch (IS :3854) and 6/16 amp. socket outlet (IS:1293) making connection , testing , etc. as required. For specification ofWiring accessories refer ChapterE - 07related item & For additional technical parameters of product / work refer Annexure "A" attached with this BSR
241S&F following sizes (dia.) of ISI marked virgin material MMS ( IS:9537 P - III ) PVC conduit along withISI marked (IS:3419-1988) accessories as requiredinrecessincludingcutting the wall, covering conduit and making good the same as required. For additional technical parameters of product / work refer Annexure "A" attached with this BSR. 20mm
24225 mm
24332 mm
244Supplying and drawing FR PVC insulated & unsheathed flexible copper conductor as per PWD specification for electrical Works with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from99.90 % purity copper, class 5 stranding in acc. to IS:8130/IEC 60228 forlower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5,in existingsurface or recessed PVC/ MS conduit/casing capping making connections with Copper Lugs of suitable size, Ferrules,testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for wires. For additional technical parameters of product / work refer Annexure "A" attached with this BSR. 1 x 1.5 sq.mm
2452 x 2.5 sq. mm. + 1x1.5sqmm
2462 x 4.0 sq. mm. + 1 x 2.5 sq. mm.
2472 x 6.0 sq. mm. + 1 x 2.5 sq. mm.
2481 x 4.0 sq.mm
2491 x 6.0 sq.mm
2504 x 6.0 sq.mm
2514 x 10.0 sq.mm
2524 x 16.0 sq.mm
253Providing & Fixing ofISI marked (IS:371) 6 amp surface type 3 pin ceiling rose with CM/L no. printed and made out from industrial grade Polycarbonate or fire resistant ABS material, brass terminal & captive screws including making connection testing etc. as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
254Providing & Fixing of ISI marked (IS:1258) batten/angle lampholder with CM/L no. printed and made out from industrial grade Polycarbonate or fire resistant ABS material, brass terminal & captive screwsincluding making connection testing etc. as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
255Providing & Fixing of ISI marked surface type buzzer (IS:2268-1994) with CM/L no. printed including making connection testing etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
256P & F phenolic laminated sheet 2.0 mm thick of following size . Including screws, cup washer as required.For additional technical parameters of product / work refer Annexure "A" attached with this BSR. 75 mm dia
257P & F 1.2mm thickM.S. Recessed fan box, hexagonal/ round of size 130 mm dia, depth 75mm,12 mm dia rod fan hook with 100 mmlength extended on each side . All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure "A" attached with this BSR
258Providing & Fixing of modular type 120 W Step Fan regulator duly ISI marked (IS 11037:1984 ) with CM/L no. printedmade out of unbreakable and fire retardant vergin poly carbonate with brass terminals and captive screws & silver alloy contact tipwith IP-20 rating ,includingall as per pre approved by Engineer in charge,making connections, testing etc. as required.For additional technical parameters of product / work refer Annexure "A" attached with this BSR. 5 step fan regulator 2 Module 360 dgree rotating
259Providing & Fixing of following modular accessories as per PWD specification for electrical Works,made out of unbreakable and fire retardant vergin poly carbonate with brass terminals and captive screws & silver alloy contact tipwith IP-20 rating , includingall as per pre approved by Engineer in charge,making connections, testing etc. as required.For additional technical parameters of product / work refer Annexure "A" attached with this BSR. Blanking plate
26025 Amp. 2 Module Motor Starter with on / off Push button
261Providing & Fixing of modular type lockable feature socket dulymade out of unbreakable and fire retardant vergin poly carbonate with brass terminals and captive screws & silver alloy contact tipwith IP-20 rating , includingall as per pre approved by Engineer in charge,making connections, testing etc. as required. For additional technical parameters of product / work refer Annexure "A" attached with this BSR. 25 Amp. 2 Module Socket
262Providing & Fixing ofextra down rod of 15 mm dia . ERW (Electrical resistance welded ) of 1.6mm nominal thick medium duty steelpipe including cutting, threading, drilling, fixing quarter pin etc as reqd.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
263P & F of Gravity Louver shutter of superior quality made out of frame of18 swg M.S. sheet & Louvers made from 24 swg MS Sheetwith enamel paint including cost of nuts, bolts, etc as reqd.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . Up to 380 mm size
264Supplying and drawing PE Insulated & PVC Sheathed unarmoured telephone cable with 0.5 mm dia. Solid Annealed electrolytic grade bare Copper Conductor as per IS: 8130/84 &confirming to TEC specification GR / WIR/06-03 March 2002in existingsurface or recessed conduit/casing capping. including ferruling on each pair for Identification etc. as required. For additional technical parameters of product / work refer Annexure "A" attached with this BSR. 2 pair
26510 pair
26620 pair
267P & F Krone module with base framein the recess / surface made out of 1.2 mm thicksheet steel box, front openable, having locking arrangements duly powder painted,including dressing, ferrulingandpunchingof telephone cable with krone tool etc. as required. For additional technical parameters of product / work refer Annexure "A" attached with this BSR. 10 Pairs
26820 Pairs
269P & F 1.2 mm thickG. I. / M .S. Sheet boxes duly finished with two coats of red oxide and with earthing terminal of following sizes (nominal size) in recessed/surface as required.For additional technical parameters of product / work refer Annexure "A" attached with this BSR. 1.2 mm thickM. S. Sheet boxes 175mm x 100mm x 60mm
270P & F paper phenolic resin bondedlaminates confirming to IS : 2036 -1995 for boxes/ frames including making holes for switches etc, with brass screws, washers/ zinc platednut and bolts as required. For additional technical parameters of product / work refer Annexure "A" attached with this BSR. 3.0 mm thick
271Providing & Fixing of flush typenon modular single line telephone jackmade out fromindustrial grade Polycarbonate or fire resistant ABS material, including making connection testing etc. as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
272Supply, Drawing and Testing of 4 pair, 23 AWG Solid Bare Copper wire insulated with PVC, UTP (Unshielded Twisted Pair), Category 6, Class E, 100 Ohm Impedance, Indoor Cable as per latest ammendments of ANSI/TIA/EIA-568 , The copper conductors should be balanced twisted in pairs, seperated by a cross-member fluted pair divider & protected byPVC Jacket. Certified performance in a 4-connector configuration upto 100 Mtrs channel requirements & transmission frequencies up to 250 Mhz. in existing MS/PVC Conduits/casing capping including making connections to Information outlets and Patch Panels with jack &ferruling at both ends for identification with necessary tools for punching, stripping, crimping and testing etc as required complete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
273Supply and Installation of unsheilded/360 degree sheilded Information outlets made of high impact plastic body with ABS, FR Grade halogen free material with provision for protection against dust in jack, suitable for Cat 6/6A application complying to latest ammendments, According. to Cat. 6/6A channel, It should support channel as well as components requirements of Cat.6/6A standards at frequencies of up to 250 to 500 Mhz. Cat 6/6A unshielded/shielded Jack should be suitable to terminate 4 pair, 23/24 AWG solid/stranded wire diameters, using 100 Ohm unshielded/shielded balance twisted pair cable, the jack should have tooless/impact termination on reliable copper tin plated Insulation displacement contact, with easy lock mechanism, It supports IEC 60603-7-4 and complied with ANSI/TIA/EIA 568 C.2 standard. jack should be RJ11,RJ12 & RJ45 compatible. Should support Ethernet 1.2 Gb/s ATM,Digital video and broadband/baseband analog video, Voice over internet protocal (VOIP) Specifications in existing modular/MS Boxes along with necessory connections as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . Cat 6, Un-sheilded Information Outlet
274Supply & fixing of square Faceplate for Flush / Surface Mount Information Outlets Single/Dual or Quad Aperture ,material should bePC+ABS body, Suitable for RJ45 unshielded/shielded connection modules. Should match with I. O. OEM. Dimensions should be 86mm X 86mm as required complete in all respect.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . Single Aperture
275Supply, Installation, & Testing of 19" 1U Rack Mounted/ surface mounted aluminum/ CRCA 1.2mm powder coated, Singlemode glass Fiber Optic Cable Patch panel/LIU loaded with flangless/screwable duplex adapters for ST/E-2000/SC/LC/MT-RJ/PC type, It should have easy removable Top plate with push buttons, there should be a splice tray installed in the Patch panel/LIU which can handle the fiber cores, splice tray should be PC+ABS material, it should include accessories like mounting hardware, gormetts, heat shrink tubes/sleevs, screws, nuts to install the panel for rack/wallmount applications as per requirment complete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .24 Ports
276Supply , Installation and Testing of 4 pair, 100 Ohm impedance, Cat 6/6A /Class E/Ea patch cords should be constructed of minimum 23/24 AWG, stranded bare Copper cable with FRPVC/LSZH Jacket, with an enhanced performance by factory moulded RJ45 connectors with strain relief boots as per ANSI/TIA/EIA 568-C.2 suitable for Cat 6/6A application complying to latest ammendments Category 6/6A Standards, According. to TIA568C.2, ISO/IEC 11801, EN 50173, IEC 60603-7-51, EN 60603-7, IEEE 802.3an minimum requirement for 1G BASE-T to 10G BASE-T performance. Patch cords shall be straight thru cable compatible with both T568-A and T568-B wiring schemes, should support IEEE 802.3af / IEEE 802.3at for POE applications, Minimum 750 to 1000 mating cycles in plug contacts for long durability, Should support Ethernet 10GBASE-T, 1.2 Gb/s ATM, Token ring 4/16, Digital video and broadband/baseband analog video, Voice over internet protocal (VOIP).All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . Cat 6, U/UTP (Unscreened/Un-sheilded Twisted Pair) Patch Cord 1 Mtr
277Supply & Installation of IP-20 & IK-08 , UL ListedWall mounted Double Section Communication enclosure (Rack) made from powder coated (60 to 80 Micron) CRCA sheet, front sturdy sheet steel frame folded from one piece and welded with minimum 5mm toughened glass door,Vertical Mounting Rail 1.6 MM with "U"Marking , with All round protective channel on the door aperture, lock integrated on front door, top and bottom cover with cable entry provision with gland plates, integrated side walls, 2 pair of 19" angles with wall mounting provision on wall. Accessories like: 1 No of 19" 1U Horizontal Cable manager, 1 No of 90 cfm 230V AC Fan with 1 mts long cable, mounting hardware , 1 No of 19" 1U, mountable socket strips with 5 nos of 5A universal sockets with 2 mts long power chord for supplying power to switches, fans etc along with earth continuity kit, indicator, moulded power supply cable. fixing on wall with Suitable Anchor fastneretc as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .12 U Rackwith Width 600 mm &Depth 400 mm + 100 mm
278Supply , Installation, Testing and Comissioning ofManaged Layer-2 Intelligent 10/100 Ethernet Switch providing 24 x 10/100/1000 MBPS Giga Ethernet ports / with min 2 SFP Giga Ports (provision for Fiber Giga connectivity) with related LAN Base Software including making connections etc as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
279Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load andsite requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanisum , energy limiting ofclass 3 as per IEC,minimum phase termination capacity of 35sq.mm. , conductor line load reversibility , IP 20 contact protection and fitted inexisting distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating and 10,000 upto 63 A, 5000 for 80 A & above ratingincluding making connections, testing etc. as required. OEM shall have submitNABL / CPRI / ERDA accrediated lab type test reports& All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure "A" attached with this BSR. Single pole MCB (With B/C curve tripping Characteristics)6 A to 32 A rating
280Double pole MCB(With B/C curve tripping Characteristics) 6 A to 32 A rating
281Triple pole MCB(With B/C curve trippingCharacteristics) 6 A to 32 A rating
28250/63 A rating
283Four pole MCB (With B/C curve tripping Characteristics) 6 A to 32 A rating
28450/63 A rating
285Providing & Fixing of Recessed/surface mounting heavy duty horizontal type Double Door ( Metal / Glazed )Distribution board with Metal end box made out from Galvanized steel / CRCA sheet not less then 1.2 mm thick  conforming to IS-8623-1 & 3 /  IEC 61439- 1 & 3, powder painted complete with reversible door (for double door DB only )100 amp.  insulated copper bus bar/shorting link , copper neutral link, copper earth link , color coded interconnecting wire set  of suitable rating and din bar,masking sheet,  making internal DB  terminations with copper lugs, Ferrules,  detachable gland plate, including making connections, testing etc. as required. OEM shall have submitNABL / CPRI / ERDA accrediated lab type test reports& All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure "A" attached with this BSR. Metal door (Three phase) IK-09 and IP-43with Metal end box 6 Way
2868 Way
287P & F of Industrial plug and socket conforming to IEC 60309-1/2 made out of self extinguishing engineering polymer / polyamide, nickel plated brass sleeve and pins, socket with shutter including making connection etc as reqd. For additional technical parameters of product / work refer Annexure "A" attached with this BSR. IP -67 Panel mounted socket 32 A 3 pin(2P+E)
288Providing & Fixing of Recessed/surface mounting heavy duty Vertical TPN Distribution board with Metal end box with provision of incomer suitable for 3/4 pole MCCB and SP / TP MCB as outgoing ,made out from Galvanized steel / CRCA sheet not less then 1.2 mm thick  conforming to IS-8623-1 & 3 /  IEC 61439- 1 & 3. powder painted with reversible door (for double door DB only ) complete with insulated 160 (upto 160 A Incomer) / 250 Amp.  copper bus bar, neutral bars with shrouds,  earth bar , color coded interconnecting wire set  of suitable rating and din bar,masking sheet,  making internal DB  terminations with copper lugs, ferrules,  detachable gland plate, including making connections, testing etc. as required.  OEM shall have submitNABL / CPRI / ERDA accrediated lab type test reports& All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure "A" attached with this BSR. Double door IP-43 & IK-09 with Provision of Incomer MCCB 160 A Rating with Metal end box 6 Way
289Providing & Fixing ofrecessed/surface mounting heavy duty sheet steel 1.6 mm thick End Box as per PWD specificationfor electrical Works for distribution board duly phophatised powder coatedcomplete asrequired. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . For TPN 6 way DB
290For TPN 8 way DB
291For all VTPN DB
292Supplyandinstallationofhigh tensile low carbon steel rod molecularly bonded with 99.9 % Copperthickness (250 microns) andconfirming toUL 467, IS/IEC 62561-2of following size and length and as per point mentioned (a), (b), [c), (d), (e) below :-(a) Bore a hole of dia. 100 mm of required length, Place the rod in the centre of Hole (b)filled with anti corrosiveconductivecompounds with the permanent sealings at both the ends, CPRI/ ERDAtested with RMS capacity of minimum 30 KA for withstanding 1 second .To ensure the moisture content and electrical conductivity, 25 kg for 2000 mm & 50 Kgs for 3000mm of resistance lowering earth enhancement material shall be used as a backfill compound. The compound shall be tested form NABL acredeated labfor lowresistivity ( less than 0.12 Ohm - meter ) & high conductivity in nature with carbon as a major contentas per referance of IS 3043-1987,IEEE 80-2013 (clause 14.5d) , IEEE 837 & IER 1956 with latest amendemnts. © Connect the rod with copper Strip/Conductor/Wire with suitable clamp made from tinned copper and SS 304 Bolt. (d) Place Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height250 to 300 mm. (d)Testing of earth resistance for value of 5 ohms or lessas required & must record by engineer in charge during site visit and ensure to enter in measurment book. (e) Test certificatesfor confirming above standards from OEM is mandatory. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 17.2 mm thick and 3 Mtr. Long
293Plate Earthing as per IS:3043 withcopper Earth plate of purity >95% of size 600mm x 600mm x 3.0mm by embodying3 mtr. below the ground level with 20mm dia. G.I. "B" class watering Pipe ,including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, and Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height250 to 300 mm. and embodying the pipecomplete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or lessas required & must record by engineer in charge during site visit and ensure to enter in measurment book. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
294Supply & Laying following size earth stripin horizontal or vertical run in surface by means of Earth strip DMC Insulatorincluding riveting/ soldering/ welding, Jointing shall be done by overlapping and with 2 set of Brass (for Cu strip) / GI (for GI Strip) nut bolt & spring washer spaced at 50cm making connection etc. as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 25mm x 3mm copper strip
29525mm x 3mm G.I. ( Hot Dipped) Strip
296Providing & Fixing ofBEEStar rated copper wounded double ball bearing capacitor start, aluminium body & Metallicblade ceilingfanConforming to all the performance requirements laid down in IS 374:2019 including all amendments, as applicable ; & Carry BIS licensing (i.e. ISI marking) with down rod up to 80 cm with secondary support safety cable ( steel rope) , cotter pin with 3 x 1.5 sq.mm pvc insulated flexible copper conductor making connection testing etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 1200 mm Sweep BEE 3 Star rated (service value >=5.0 to< 5.5 )
297Providing & Fixing of Heavy duty capacitor start, copper woundDouble ball bearing900/1400 RPM single phaseExhaustfan conforming to IS:2312 ISI marked in existing opening including making connections testing etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 380 mm sweep(900/1400 RPM)
298Providing & Fixing ofof Double ball bearing, copper wounded capacitor startsingle phase metallicblade fresh air fan, in existing opening including cost of hardware , flexible 3 core copper conductor ,making connections, testing etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 300 mm sweep
299Providing & Fixing of 450 mm SweepOscillating type Wall mounting / Pedestal typefans with Three speed, ON andOFF position, Sintered Iron bush oil impregnated,with metal front and back 120 or moreribs guard; Three no. Aluminiumblades, minimum Air delivery 100 Cum. / Minute , Minimum Service Value 1.11 Cum./min/watt, noise level should be <= 75 dB, power consumption <= 120 watts, motor protection through thermal overload protection device, including fixing with anchor bolts, making connection testing etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . Wall mounting type with Adjustable Vertical Angle
300Providing & Fixing of energy efficient direct fit (Retrofit)Polycarbonate/ GlasshousingSMD Mid Power LED tube rod(with integral driver & alumn. heat sink ), on existing fixture.system lumen efficacy = 100 lm/Watt output, internal surge protection of 2.5 KV ,THD < 20% ,p.f.=0.95,CRI >80 , life time of minimum35000 Burning Hours with , 70% of intial Lumen maintaned till life ends, CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be ofBIS standard andtrade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing onhousing. OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 & LM80)certificate / Report from OEM shall be submitted.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 1200mm , Min. Lumens output 2000 lmLED Tube rod with Polycarbonate Housing
301Providing & Fixing of IP20, 2"x2" LED Surface/ Recessedmounting Mid power SMD type LED Light fixture not less than 50mm housing depth made from CRCA sheet steel housing, high purity / transmisivity UV stabilized Non -yellowish diffuser for uniform light distribution. High efficiency with 4 KV internal/external surge protection BIS certified isolated driver having efficiency > 85% , with Short & Open circuit protection(Integral with light fixture). System lumen efficacy of = 120 lm/Watt ,THD < 10 % , p.f.=0.95,CRI >80 ,life time of minimum50000 Burning Hours with , 70% of intial Lumen maintaned till life ends, CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be ofBIS standard andtrade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing onhousing. OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 & LM80) certificate / Report from OEM shall be submitted.All as per pre approved by Engineer in charge. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . Recessed Mounting Minimum lumen output 3600 lm
302Providing & Fixing of IP-20 LED Recessed / Surface Mounted, Round / SqaureSMD Mid Power LED Downlight with power coated die-cast aluminum housingwith UV Stabilized non yellowish Diffuser withBIS complience 2.5 KV surge protected Isolated driver, with Short & Open circuit protection, having efficiency > 85% . System Lumen efficacy of = 110 lm / watt, THD < 10 % , Pf.=0.95, CRI >80,life time of minimum50000 Burning Hours with , 70% of intial Lumen maintaned till life ends, CCT 3000°K / 4000°K/5700°K /6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be ofBIS standard andtrade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing onhousing. OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 & LM80) certificate / Report from OEM shall be submitted. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . Surface Mounting (with extruded alumn. Housing ) Minimum lumen output 1300 lm
303Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed ArrmouredAluminiumcable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV withH4- Grade electrolyticaluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) includingtesting etc. as required of following size. OEM must have it"s own in house NABL accrediated Laboratory for testing procedure as per IS:10810.For additional technical parameters of product / work refer Annexure "A" attached with this BSR. 4.0 Sq. mm 4 core
3046.0 Sq. mm 4 core
30510.0 Sq. mm 4 core
30616.0 Sq. mm 4 core
30725.0 Sq. mm 3.5 core
30850.0 Sq. mm 3.5 core
30970.0 Sq. mm 3.5 core
310120.0 Sq. mm 3.5 core
311Supplying and making one end termination with Nickel plated heavy duty brass single compression gland (as per IS 12943-1990)) SIBG type consisting of Check Nut, Gland Body, Metal Washer(3 Nos.), Outer Seal Rubber Ring,Compression Nut,heavy duty aluminium lugs (as per IS 8309 -1993) duly crimped with crimping tool, PVC tape as perIS 8337-1976offollowing size ofPVC insulated & PVC sheathed/ XLPE aluminium conductor cable of 1100 volt grade as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 4 x 6.0 sq.mm
3124 x 10.0 sq.mm
3134 x 16.0 sq.mm
3143.5 x 70.0 sq.mm
3153.5 x 50.0 sq.mm
3163.5 x 120.0 sq.mm
317SITC of IP-42 and general construction confirming to IS:8623 : 1993, wall/ free standing floor mounted dust and vermin proof compartmentalisedcubical panel as specifications andOther parameters requiredas per point (a) ,(b), (c),(d), (e), (f), (g), (h) as below:- (a)Thickness of CRCA sheet shallbe 2.0 mm,cable alley compartments having concealed hinged type doors with key type lock with / withoutdetachable extension type structure. Removable 3 mm. thick sheet steel gland plates with appropriate size of knockouts for cables shall be provided. (b)complete panel shall undergo a process of degreasing, Water rinsing, Activation, derusting,pickling in acid bath, phosphatising & shall be subjected to nine tank process and then Powder coated with approved shade of minimum 70 microns on both side of panel.The panel having PE foam/ Neoprene rubber gasket of not less than 3mm thickness ,required hardware , concealed hinged door with key type locking arrangement for equipment/switchgear earthed with 2.5 sq.mm braided copper wire. [c)Interconnection between bus bar and switchgears /cable shall be rigidly supported and made out by flexible copper wires (up to 63 amp ) and by solid bus bar(>63 amp ) . control wiring will be carried out with 1.5 Sq.mm, Earth wire with 2.5 Sq.mm and CT with 2.5 sq.mm flexible copper wire only.All joints / interconnections of copper bus bar shall be dully tinned . Clearance between main bus bar and risers / metal parts shall be at least 10 mm additional to width of bus bar Bus bar is insulated by Heat Shrinkable sleeves . Earth and Neutral bus bar shall be half of the size of phase bus bar. ( Cost of Bus bar/ Flexible wire for Interconnection between Main busbar and Switchgearis to be Paid Extra ) (d)Wiring between components within switchgear and Incoming / outgoing cableshall be done through the terminal block only. Direct connection shall not be permitted. Each terminal block shall be one piece moulded, barrier type, 650 volt grade, complete with washers, heads, studs with two nuts and identification strips and shall have adequate continuous current rating. For tap-offs, adjacent terminals with shorting strips shall be used. 10% Spare terminal blocks shall be provided. Wire identification on marking strip shall correspond to the designation of the wiring diagrams. All wire terminals on the equipment shall also be marked with designation corresponding to those of the wiring diagram. (e)All wiring shall be enclosed in plastic channels and neatly bunched and closed in metering chamber, Wiring between terminals of various devices shall be ‘point to point’ (no wire splitting or tee connections) with wires neatly trucked along the back of the panels, adequately supported to prevent sagging. (f)Floor mounted panel shall be mounted on Base frame of ISMCchannel size 100 x 50 x 5 mm( to be paid Extra ) (g) Tests: The insulation resistance (with 1000 V Megger) and High voltage Power frequency test (by applying a voltage of 2.5KV for one minute) shall be measured between phases, between phase and neutral and between phase and earth. both before and after high voltage power frequency test. The insulation resistance shall not be less than three megaohm. CT Secondary current injection test shall also be carried out. (h) only outer surface area on all sides shall be measured & panel to be fabricated only from CPRI approved fabricator only (CPRI Test certificates to be submitted)All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
318Supplying and fixing of Aluminium (IEC 60105 ISO 209-1,2) / Copper (IEC 60028) bus bar by means of SMC / DMC type insulatorwith standard short circuit withstand capacity, high tensile nuts and bolts spring washers in existing panel including bending , cutting in required shape and size and colour coding with heat shrinkable PVC sleeves. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . Electrolytic grade Aluminium bus bar 6010 grade
319Providing & Fixing of IS: 13875 & IEC :61326 confirming LED Digital type(up to 500) V range Volt meter / Direct- Ammeter /CT oertated ammeter/ Frequency meter / KWH meter / Multi Function Meter / Power analyzer of class 1 accuracyas per IS : 1248 of size 96mm x 96 mm including making connection by PVC insulated copper conductor with PVC sleeves / channel etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . Single Phase Voltmeter
320Single Phase Ammeter
321Providing & Fixing of BIS approvedCurrent Transformeras per PWD specification for electrical Works ,ISI marked as perIS 2705-1992/ conforming to IEC 60044-1, with secondary terminalof CT shall be brought out suitable to a terminal block which shall be easier accessible for testing and terminal connection , with all necessary support in existing panel including connection etc. as requiredCurrent transformer Ring Type Tape Wound/Resin Cast Wound as per IS 16227 with, Accuracy Cl, CT ratio and burden as specified. ISF<=5, Cu cross section of secondary wire 1.5sqmm (minimum), including all necessary support in existing panel including connection etc. as required . All as per pre approved by Engineer in charge.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . Ring type tape wound CT C T Class 1, Ratio upto 150/5, Burden 5 VA
322C T Class 1, Ratio 200/5 to 300/5, Burden 10 VA
323Providing & Fixing of selector switch of 10 A for voltmeterusing high grade engineering materialto international standards with cam assemblyinsulation of glass filled polyamide with high tracking index. For reliable and stable electrical and mechanical endurance double butt contacts with silver bi-metal on copper should provided . contact assembly is of operating temp range -25 degree C to 55 degree C, frequency upto 10 KHz. switch life under std. op. conditions shall be mechanically minimum 50000 operations @300 cycles/ hour and electrically 10,000 operations at 100% rated duty for 100 cycles/ hour including making connection etc.as required . All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . Voltage Between Phases with OFF ( 4 Position )
324Providing & Fixing of CT linked selector switch of 10 AforAmpere meter (4 position )using high grade engineering materialto international standards with cam assemblyinsulation of glass filled polyamide with high tracking index. For reliable and stable electrical and mechanical endurance double butt contacts with silver bi-metal on copper should provided . contact assembly is of operating temp range -25 degree C to 55 degree C, frequency upto 10 KHz. switch life under std. op. conditions shall be mechanically minimum 50000 operations @300 cycles/ hour and electrically 10,000 operations at 100% rated duty for 100 cycles/ hour , including making connection etc.as required .All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
325Providing & Fixing of110/220 V, unibody LED Indicatinglamp IEC 60947with integral circuit, IP 65 above panel &IP 20 terminal block, Approx. body dia for panel not less then 20 mm, length min. 50mm, front LED cover dia min.29 mm, contact material phospher bronze for Led, PCB contacts shall be ofbrass (tin plated), impulsedielectric tested for 2.5 KV, Rated insulation resistance shall be 100 M ohm at 500VDCincluding connection etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . Red/yellow/Green colour
326Providing & Fixing of IS: 13875 & IEC :61326 confirming LED Digital type(up to 500) V range Volt meter / Direct- Ammeter /CT oertated ammeter/ Frequency meter / KWH meter / Multi Function Meter / Power analyzer of class 1 accuracyas per IS : 1248 of size 96mm x 96 mm including making connection by PVC insulated copper conductor with PVC sleeves / channel etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . Threephase AMP+HZ+PF+KW+KVA+KVAR+T.ENERGY+THD-I, THD-V & RUN HRS
327Providing & Fixing of Electricalinsulating rubber matts as per PWD specification for electrical Works, ISI marked confirming to IS: 15652 /2006with one sideanti skid abberation marks and pasting the mat with synthetic rubber adhesive as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 11 KV,Class B 2.5 mm thick with proof voltage 22 KV AC (rms) and Break Down Voltage45 KV AC (rms)
328Providing & Fixing of self healing IP20 MPP type shunt capacitor (banks) conforming to IS:13340-41 /IEC :831-1&2 OR IEC : 60831-1& 2 in existing panel or parallel with load terminals , the capacitor shall be fitted with discharge resistors, pressure sensitive disconnector ( PSD ) and shall have dissipation factor less than 0.0025 at 50 Hz, Operating loss less than 0.30 Watt per KVAR. Min over current capacity 1.8 times rated current & peak inrush current min. 300 times of rated current, llife expectancy greater than 100000hrs(temp class - 25 D)in 440 V/480 V Capacitor and for 525 V should life expectancy minimum 1,65,000 hrs (temp class - 25 D)including making connections, testing etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . Heavy dutyThree phase 480 V, 50 Hzcylindrical type capacitor (Bank)
329Providing & Fixing of IP54 microprocessor based 3 CT’s for all 3 phasesensing compensationpower factor correction relay Size 139mm x 139 mm, Operating Voltage 415/440 V, IEC / EN 61000-6-(2&4)having 3 CT sensing, sensitivity up to 50 milli amp secondary current , self analysing auto c/k setting according to targeted power factor setting, the relay shall havedigit display unit for display of real power factor, targeted power factor, lag/lead capacitor switching status, alarm output for under current, over current, insufficient compensation, communication interface with RS 485,indication of switching on units, auto/manual status, and shall have over load protection, no volt release , having multi parameter like KW, KVA, KVAR, RMS Value, step switching time 2 sec to 1800 sec. Lead & Lag parameters, metering facility and3 no. Class- 0.5 Cast ResinCT ( refer CT specs in this chapter )for sensing the relay including making coonection with 1.5 Sq.mm copper wire etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 6 to 8 stage
330Providing & Fixing of440 Volt 3 pole capacitor(AC 6 B ) duty contactor with 3 no. early make and post break auxiliary contacts in series with quick discharge damping resistors/ reactors to limit the inrush current as per PWD specification for electrical Works,IS/IEC 60947-4-1 : 2000, insulation voltage 1000V, impulse withstand voltage 8 KV,Din rail mounting type including making connections, testing etc. as required. suitable for following capacity capacitor bank.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . up to 6 KVAR
33110 KVAR
332SITC of3 /4pole current limiting Moulded case circuit breaker (MCCB) made of flame retardent & heat resistant materialhaving following current rating, short circuitbreaking capacityat 440/415 V, 50 Hz; O/L & S/C settings , conforming to IS/IEC 60947 P -2 :2003 with frontface and centralised adjustable, trip free mechanisum, true contact position indicator,line load interchangeability,designed for both horizontal & vertical mounting without any adverse effect on electrical performance, suitable for operation upto 55 degree and without derating upto 40 degree,pollution degree 3, having positive isolation capability, push(test) to trip, trip time less then 10 ms under s/c condition, Breaking capacity Ics = 100% Icu. U imp =8 KV, rated insulation voltage690 V.provision for UVR , shunt trip , earth fault trip, door interlock, pad lock & rotary handle , including making connectionsetc. as required.OEM shall have submitNABL / CPRI / ERDA accrediated lab type test certificate before execution All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure "A" attached with this BSR. 3 pole MCCB With Thermal Magnetic release up to 100 Amp , 25 kA, adjustable O/L & adjustable S/C setting,
333SITC of3 /4pole current limiting Moulded case circuit breaker (MCCB) made of flame retardent & heat resistant materialhaving following current rating, short circuitbreaking capacityat 440/415 V, 50 Hz; O/L & S/C settings , conforming to IS/IEC 60947 P -2 :2003 with frontface and centralised adjustable, trip free mechanisum, true contact position indicator,line load interchangeability,designed for both horizontal & vertical mounting without any adverse effect on electrical performance, suitable for operation upto 55 degree and without derating upto 40 degree,pollution degree 3, having positive isolation capability, push(test) to trip, trip time less then 10 ms under s/c condition, Breaking capacity Ics = 100% Icu. U imp =8 KV, rated insulation voltage690 V.provision for UVR , shunt trip , earth fault trip, door interlock, pad lock & rotary handle , including making connectionsetc. as required.OEM shall have submitNABL / CPRI / ERDA accrediated lab type test certificate before execution All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure "A" attached with this BSR. 4 pole MCCB With Thermal Magnetic release up to 100 Amp , 25 kA, adjustable O/L & adjustable S/C setting,
334160 Amp , 25 kA, adjustable O/L & adjustable S/C setting,
335250 Amp , 35 kA, adjustable O/L & adjustable S/C setting,
336Providing & Fixing of IK08, IP 66 protected LED Street Light Luminaire on existing bracket/pole. Fixture made of powder coated single piece pressure die cast aluminummaterial with heat dissipation fins on housing with UV stabilized PC (UV stablization report submitted for UV cover ) /Toughened Glass coverand secondary lens on each LED & should be SMD type of 3 to 5 watt each . The System efficacy >=125 lm/ wt and potted driver& has a unique BIS R number withInput Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC and Auto resetting Safety , Power Factor >0.95 driverEfficiency >85%,THD(I) <10%Humidity 10% to 90% RH Working Temp -5C to 45C .driver current <750mA. The luminaireshall be BIS certified and Trade mark certified. Life ExpectancyEqual or more than 50000 burning hrs with Minimum 70% lumen maintened , CRI >70 and CCT 5700K +355K. Surge protection shall be min = 4 KV internal and min 10 KV external inside driver compartment. driver should be Phase to phase protection of 440 V for 4 Hrs.Manufactures Word Mark/Name Engraved/Embossing on die cast housing to allow traceability/authenticity. Fixture shall be AS PER IS 10322 Complianced.OEM Must have its own in house NABL lab setup for all testing facilities forLED fixtures.(LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . LED Street Light fixture with Minimum lumen output 3700 lm
337LED Street Light fixture with Minimum lumen output 8700 lm
338Providing & Fixing of Street light bracket made out from following size of " B " class , Medium class G.I. Pipe confirming to IS : 1239 P - 1 ( 2004 ) with heavy duty pole clamp, Saddles suitable fastners etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 32 mm Dia.
339SITC ofMNRE approved & confirming to IS:12933 P-1,2,3 & 5 Flat Plate Collector type solar hot water system havingcollector withZincalum sheet outer body ,Glass - line / Titanium Enamel coated Inner tank with Metal rust proof PUF insulated Body includingelectrical back up, Thermostat, Powder coated / Hot dipped galvanized MS standfor Collector & Tank etc. as required. of following capacity complete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 500 litre/ day
340SITC of Single Stage, water cooled, High Speed (2880 RPM), Horizontal, Centrifugal, Openwell Submersible pumps set pre filled with coolent water and fitted with mechanical seal - T/C Vs T/C, Thrust bearing shall be ofcarbon + S.S.The stator body of single phase pumpshall be of SS and rest of all shall be of cast iron. All casting parts should be cathod electro deposition (CED) coated and other construction material should be confirming to IS : 14220: 2018 . The overall performance of pump shall confirm to BEE energy efficiency level of 3 star. Valid BEE certificate from OEM must be submitted for the same. Motor should be IE2 class as per IEC 60034-2-1: 2007, IEC 60034-30: 2008,& IS12615:2011, including making connection etc as required complete in all respect. OEM shall have submitNABL / CPRI / ERDA accrediatedlab type test certificate before execution. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 1.0 HP, 1-Ø, (7 -12) Mtr, (405- 240) LPM
341Supply & fixing of GI pipes confirming to IS : 1239 P - 1 ( 2004 ) with flanges duly screwed & welded including rubber washer, nuts & bolts of 8mm dia complete in all respect.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .B class 50mm dia
342SITC of ContactorOEM Fabricated DOL/Star-Delta Starter panel with switchgear selection as per Type-2 Cordinatiom Chart andmade out from 1.6 mm thick powder coated CRCA sheet, enclosure comprising of over load protection relay, short circuit & single phasing protection, Illuminated ON / OFFpush buttons,ammeter, voltmeter, indicating lamps etc.suitable for following rating motors complete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .For Three phase Submersible / Mono block pump 3.0 HP to 5.0 HP ( Star / Delta starter )
343P/Laying ISI marked P.V.C. insulated submersible cable confirming to(IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from99.90 % purity copper, stranding in acc. to IS:8130/IEC 60228 forlower watt loss , oxygen freefor less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5,existing pipe / open trench / Cable tray / on surface including making connection etc. as required. For additional technical parameters of product / work refer Annexure "A" attached with this BSR. 6.0 Sq.mm 3 core flat / Round
344Supply, Fabricating & installing following sizes of perforated Hot dipped Galvanized iron cable tray ( Galvanized thickness not less then 50 microns) with perforation not more then 17.5% in convenient section including horizontal and vertical bends, reducers tees,cross members and other accessories as required and duly suspended from the ceiling with GI suspenders including GI bolts & nuts , fastners, supports etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 150mm x 50mm x 1.6mm
345P & F in position frame made out of M.S. angle (riveted or welded) finished with two coats of red oxide and two coats enamel paint including cutting, welding, holes etc.of following sizes as required.For additional technical parameters of product / work refer Annexure "A" attached with this BSR. 50mm x 50mm x 6mm
346Supply , Installation, Testing and Comissioning ofInverter type Air Cooled Hi Wall split type Air conditioners with latest star rating system as per BEE amended upto date complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU), R-32/R-410 Green Refrigerant, wireless Remote control, suitable for working between 230V +/- 10% with low & high voltage cutoff and50 hz , single phaseACsupply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 1.5 TR ISEER not less then 3.8
3472.0 TR ISEER not less then 3.8
348Supply & fixing MS powder coated stand suitable for 1.0/1.5/ 2.0 Tr outdoor type of Split AC.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
349Supply, Fixing and testing of following capacity ISO certified company made wall mounted stabilizer having output voltage variation from 200 V to 250 V(+/-5%) with input voltage variation from 170 V to 260 V, time delay facility from 2 to 4 minute and high cutoff at 270 V with providing of 16 Amp /20 Amp Industrialplug top making connection etc complete in all respect.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .4 kVA
3505 kVA
351Providing & Fixing of IS : 4985 - 2000 Class -4 (10 Kgf / Sqcm) UPVC drain water piping withfittings (IS:7834 & 10Kgf/sqcm) like elbow, socket, Tee, solvent cement jointing,support with MS hanger on ceiling or recessed in wallwith chasing & plastering with 6 mmthickclosedcellelastomeric nitrile rubberinsulation including leakage testing etc. as required of following Nominal sizes. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 25 mm
352SITC of Interconnecting refrigerantcopper pipe forsplit/Ductable/ Casseette AC of DHE Grade C12200- ASTM B68, B75, chemical composition of copper %- 99.0 Min and Phosphorus %- 0.015 to 0.040 . For Annealed copper tube :- Tensile strength = 210 Mpa wih elongation % = 40 Min . Ink MarkBrand Printing on Hard Tubes should be present. Piping between each set of indoor & outdoor units of different sizesas per OEM requirement & specifications including class "O" Nitrile rubber sleeves, chase cutting, supports, making good the same with sand cement plaster etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
353Supplying and drawing flexible / stranded bare copper conductor, PVC / XLPE insulated, overall aluminium mylar tape shielded ATC drain wire and outer PVC sheathed industrial Instrumentation (shielded)cables voltage grade 300/500 V as per BS /EN 50288-7 in existingsurface or recessed PVC/ MS conduit/casing capping/ Cable tray / Open Duct making connections, testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for cables. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . Armoured 4 core x 2.5 Sq.mm
354Providing & Fixing ofCam operated rotary (Auto/manual) switches on existing panel with 2 way and off position using high grade engineering materialto international standards with cam assemblyinsulation of glass filled polyamide with high tracking index. For reliable and stable electrical and mechanical endurance double butt contacts with silver bi-metal on copper should provided . contact assembly is of operating temp range -25 degree C to 55 degree C, frequency upto 10 KHz. switch life under std. op. conditions shall be mechanically minimum 50000 operations @300 cycles/ hour and electrically 10,000 operations at 100% rated duty for 100 cycles/ hour including making connection etc.as required . All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 10 AMP
35532 AMP
356Supply & Fixing of Dry Powder Agent (as per IS 4308:2019), ABC typeFire Extinguisher (Stored Pressure type) conforming to IS:15683:2018 , Powder coated Internal & External Surface Deep drawn cylinder body of Mild Steel CR2 grade conforming to IS: 513, Squeeze grip Forged brass release valve with Inbuilt safety release device, Diaphragm Type, 0 to 28 bar range pressure gauge, 450 mm long EPDM discharge tube, QR code for Product Traceability including Fixing on wall with suitable Anchor Fasteners as required of following capacity. Test Certificates of all the Parameters along with Hydro test & Burst test (For Cylinder Body) Certificatefrom OEM / External NABL Accrediated Lab is to be submitted. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 4 kg
357SITC of Radiator Cooled and Turbo charged Silent DG Set (As per latest CPCB emissionnorms) havingspecifications as per A, B, C, D, E, F,G,H & I. A) 1500 RPM Diesel Engine conforming to BS:649/5514 of suitable BHP(up to 82.5 kVA 6 cylinder or Below required, 125 kVA & Above ratings 6 cylinder or aboverequired ) capable of taking 10% over loading for one hour after 12 hours of continuous operation.,Dry exhaust mainfold with Hospital grade silencer and catalytic convertor(isolated from main DG chamber),up to 3 M exhaust piping (with LRB insulation & Alum. cladding ) as required . B)AC Brush less SPDP Alternator conform to BS 5000 (part 99) or IS/IEC 60034-1. . Alternator shall be self regulated with standard Alternator Protection( Over voltage , over speed & under voltage, under speed warning & shutdown).Engine & Alternator mounted on a common base Frame & coupled through a flexible coupling or close coupled. C) CPCB / ARAI approved Standard canopy with Weatherproof, powdercoated Accoustic enclosure for DG set for sound attenuation fabricated from 1.6 mm CRCA sheet steel (structure) with sidewall fabricated from 1.6 mm CRCA sheet & filled with glasswool (96Kg/m3) / Foam. as per IS8183 the doors of 28/40/50/85mm thick as perrating and fabricated from 1.6mm CRCA sheet packed with accoustic material, All doors/opening are sealed with neoprene /EPDNgaskets. The DG Set has Inbuilt / External in fuel tank to run 6 to 8 Hrs as per OEM standard, with protection and tripping of DG set against temperature of more than 50 degree centigrade. D) Electronic / Mechanical governor, Manual & electric Start ,Batteries with battry charger,Engine instruments panel,AVM pads All controls for operation of DG set are from outside the enclosure with DG control panel having Microprocessor based Genset monitoring like Running Hour, RPM, Low Lube Oil tripping & control system, Panel mounted MCCB/ACB of suitable rating, Ammeter, Voltmeter, PF meter, frequency meter, KWH meter,digital fuel display meter, Ind.lamps etc. mounted inside enclosure , visible and accessible from outside. The enclosure should be suitable for following capacity DG sets and alternator. Noise level shall be less than 75 dB at a distance of 1 Mtrs. duly certified by authorised agency etc. complete in all respect of following capacity : E) (i) Accoustic glass wool wall thickness should not be less then 40mm and not less then 20mm PU foam upto rating 100 KVA. (ii).Accoustic glass wool wall thickness should not be less then 65mm and not less then 50mm PU foam upto rating 250 KVA. (iii)Accoustic glass wool wall thickness should not be less then 100mm forrating above 250 KVA. F) First filling of the fuel tank shall be done by contractor and the prevailing fuel cost at that time shall be reimbursed to the contactor by department. G) Servicing Contract of DG Set from OEM"s Authorised Service Dealer as per OEM guidelines during the DLP period shall be done by contractor including all consumables, actual charges shall be reimbursed to the contractor by End User Department. H) Manufacturer / OEM must have its authorized service dealer in Rajasthan. Which can provide service within 6 Hours of compalint registration. I) DG set will be offered for Inspection and Testing at Manufacturer"s Works in presence of Departmental Engineers. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .140 KVA at 0.8 pf 415V 50Hz 3-?
358SITC of PLC Based Auto main failure (AMF) Panel fabricated from CRCA sheet steel 2 mmThick , Powder coated finish , Engine Start & Stopcommands, control Relays , Ammeter & Voltmeterwith selector switches, Control & 2 nos 4 pole Power Contactors with 2 no. of required size 4 pole MCCB, Timers, Electronic Hooter ,Visual & Alarm indication for faults, UPS, operator interface panel complete in all respect suitable for following capacity DG sets: Appropriate Test Certificate/ report of product/accessories from OEM/Panel Manufecturer shall be submitted. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 100 to 140 KVA
359Plate Earthing as per IS:3043 withcopper Earth plate of purity >95% of size 600mm x 600mm x 3.0mm by embodying3 mtr. below the ground level with 20mm dia. G.I. "B" class watering Pipe ,including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, and Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height250 to 300 mm. and embodying the pipecomplete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or lessas required & must record by engineer in charge during site visit and ensure to enter in measurment book. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
360Providing & Fixing of ISO certified company made on load change over switch, front handle operated, four pole 415 V as per PWD specificationfor electrical Works conforming to IS/lEC 60947-3 : 1999 including connections , testing etc. as required .in the following rating.Appropriate type test certificate / OEM test report shall be submitted .All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . Open execution type 250 A
361Supply and erection ofGalvanized Iron pole with galvanizing done in single dipping (Average coating thickness Minimum 65 Microns) continuously tapered poles having Octagonal / Circular cross-sections designed to withstand the maximum wind speed as per IS 875, The pole shaft shall be made from sheet steel (HT Steel Conforming to grade S355JO) and confirming to BSEN 10025 and shall be continuously tapered with single longitudinal welding. There shall not be any circumferential welding. The welding of pole shaft shall be done by Submerged Arc Welding (SAW) process. pole shafts shall be provided with the rigid flange plate of suitable thickness (Fe 410 conforming to IS 226 / IS 2062) with provision for fixing 4 no. foundation bolts, This base plate shall be fillet welded to the pole shaft at two locations i.e. from inside and outside.The octagonal Poles shall have lockable door of approximate 500 mm length at the elevation of 500 mm from the Base plate with bakelite sheet having 6A SP MCB and 16 sqmm stud type connector ( 4 nos) inside the pole at door opening for cable connection of following length and dimension as per table P-01 with base plate and foundation bolt on the Existing cement concrete foundation.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . Poles with Octagonal Cross Section 7 Mtr.
362Providing and fixing of IP 65 protected Polycarbonate / Polysterene fuse box moulded with inside knock outs of following size with hinged cover, transparent window,PU gasket, locking arrangement, duly holded with 2 nos. pole clamps of 20 mm x 3 mm flat with nut and bolts, The box shall be provided with Din rail, 4 / 8 way 10.0 / 16.0sq.mm heavy duty connector, earth terminal,complete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 160 mm X 225 mm X 100 mm
363Providing and fixing welded mesh/expanded metal mesh 25 mmx 25 mm x 3mm in frame work, flat iron beading 20x3mm including top cross laps inside and out sides welding, iron bolts, crews, clips etc. including two coat of red oxide and two coat of enamel paint or more requiredcomplete with frame work with 50 X 50 X 6mm angle iron post 30 cm in ground embeded in cement concrete 1:3:6 (30X30X45cm) at corner and every three mtr including painting with one coat of primer and two coat of enamel paint work will be done as per direction of engineer incharge of sizecomplete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
364Providing & Fixing offollowing size mounting grid plates with cover plates made from fire retardent UV established high performance engineering plastic suitable for all universal metal boxes for front installation & removal direct fit type complete in all respect.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 1/2 Module
3653 Module
366Providing & Fixing ofWiring Accessories OEM fabricated following size GI box of 1.2 mm thick with earthing terminal and adjustable floating clamp in recess/ surface suitable for modular accessories as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 1-2 Module
3673 Module
368Providing & Fixing of Vertical(BEE 5 star rated) / Horizontal( BEE 3 star rated) storage water heater with outer casing made of Engineering Plastic sheet (Upto 25 Ltr) / Metal rust proof Body (35 & 50 Ltr), Glass - line / Titanium Enamel coated Pressure Pump Compatible 8 bar pressure Inner tank, Glass Line Coated , mineral filled heating element, stem type, snap actionadjustable thermostat , Dual indicating lampsInjected PUF insulation, Multi Function Valve etc. as required held in position with 2/4 no. 10/12 mm anchor Fastener, duly wired with 3 core 2.5/4.0 Sqmm PVC insulated & sheathed copper conductor and 16 A/25A three pin plug top with Portable Residual Current Device ( PRCD ) , including making inlet, outlet Flexible alloyconnection, testing etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 15 Ltr.
369Supply and Fixing of Pole OEM fabricated hot dipped galvanised M.S. Overhang (48.3 X 3.25 mm) with cap (400 x 88.9 / 114.3 x 3.25 mm) over the existing poles. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . Single arm overhang
370Supply , Installation, Testing and Comissioning of IS:1475 marked self contained drinking water cooler withhermeticallysealed compressor,non CFC refrigerent suitable for operation on 230V/1pH/50Hz AC supply,Full stainless steel (SS304)body (0.8 mm thick)and tank (0.5 mm thick) , stainless steel water tray,minimum two nosBrass Chrome plated faucets and suitable drainage system complete in all respect with requiredheight MS fabricated and Painted Angle iron frame( Cost of frame to be paid Extra )complete in all respect of the following capacity.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR. cooling capacity 150 Ltr./Hr. and storage capacity 150 Ltrs
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail