Tender For Repair And Maintenance Of Ht Lt Oh Lines Ug Cables Transformers Vcbs God Lt Panle Mccbs Acbs Street Lights Security Lights Gate Lights Garden Lights And Repair Maint Of Eot Hot Cranes And Periodical Testing Of Cranes With Allied Works At Vrde A, pune-Maharashtra

Military Engineer Services-MES has published Tender For Repair And Maintenance Of Ht Lt Oh Lines Ug Cables Transformers Vcbs God Lt Panle Mccbs Acbs Street Lights Security Lights Gate Lights Garden Lights And Repair Maint Of Eot Hot Cranes And Periodical Testing Of Cranes With Allied Works At Vrde A. Submission Date for this Tender is 13-12-2022. Cranes Tenders in pune Maharashtra. Bidders can get complete Tender details and download the document.




Tender Notice

34997320
Corrigendum : Tender For Repair And Maintenance Of Ht Lt Oh Lines Ug Cables Transformers Vcbs God Lt Panle Mccbs Acbs Street Lights Security Lights Gate Lights Garden Lights And Repair Maint Of Eot Hot Cranes And Periodical Testing Of Cranes With Allied Works At Vrde A
Open Tender
Indian
Maharashtra
pune
13-12-2022

Tender Details

Tender For Repair And Maintenance Of Ht Lt Oh Lines Ug Cables Transformers Vcbs God Lt Panle Mccbs Acbs Street Lights Security Lights Gate Lights Garden Lights And Repair Maint Of Eot Hot Cranes And Periodical Testing Of Cranes With Allied Works At Vrde Ahmednagar - 06

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 29-Nov-2022 Corrigendum BOQ 06-12-2022
2 06-Dec-2022 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 13-12-2022

Key Value

Document Fees
INR 500 /-
EMD
INR 64000.0 /-
Tender Value
INR 31.95 Lakhs /-

BOQ Items

Name of Work: REPAIR AND MAINT OF HT/LT OH LINES, UG CABLES, TRANSFORMERS, VCBs, GODs, LT PANEL, MCCBs, ACBs, STREET LIGHTS, SECURITY LIGHTS, GARDEN LIGHTS AND REPAIR/ MAINT OF EOT/HOT CRANES, PERIODICAL TESTING OF CRANES AND CERTAIN ALLIED WORKS AT VRDE AHMEDNAGAR - 06
Sl. No. Item Description
1Excavation in trenches, not exceeding 1.5 metre wide and not exceeding 1.5 metre in depth for poles, laying of electric cable and GI tubing (where provided for protection of cables) and getting outtrimming the sides, forming bottom surface to required level in soft/loose soil complete all as specified and as directed.
2Returning, filling in , including spreading, leveling, watering and well ramming in layers not exceeding 25 centimetrethick after laying and testing of cable, laying of GI tubing etc complete all as specified and as directed.
3Removing excavated material not exceeding 50 metre and depositing where directed at a level not exceeding 1.5 metre above the starting point complete all as specified and as directed.
4Material and labour for spread well dried sand cushioning in trenchescomplete all as specified and as directed. Note:- Thickness of sand cushioning shall be measured as punned thickness for the purpose of payment.
5Dismantling of cross arms of MS channel or angle section etc.complete all as specified and as directed.
6M &Lfor40mm dia GI pipe "light grade"including all fittings for road crossing / on wall / on pole for cableprotection including taking out U/s old Gi pipe all as specified and directed.
7All as per above item No.6.00 but 50 mm dia.
8All as per above item No. 6.00 but 100 mm dia.
9Supply and fix lightening arrester NON LINEAR RESISTER type, complete with all fittings, transmission classes, discharge capacity 65 Kilo amps suitable for 11 KV out door type complete including dismalting of old U/s lightning arresters complete set all as specified and directed. Make : ELPRO or equivalent of BHEL/ PACTIL.
10Supply and fix in replacement pin type porcelain, vitreous, white brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 150mm height, 150mm, dia for 11KV grade complete all as specified and directed.
11Supply and fix in replacement disc type insulator, porcelain, vitreous, white, brown or green 145 mm height and 255 mm dia ball and socket type single disk assembly for tension with tension clamp for conductor working pressure 11 KV grade complete all as specified and directed.
12S & F in replacement post insulator 11 KVforDO FUSE/AIR BRAKE ISSOLATING switch complete all as specified and directed. Make Jaipuria/Rastriya/Pactil
13Supply and fixing in replacementLT Pin type, porcelain, vitreous, white, brown or green insulator including one galvanized mild steel spindle, two galvanizediron washers and one galvanized iron nut, 100 mm height, 65 mm dia for 1100 volt grade complete all as specified and as directed.
14Supply and fixing in replacement shackle type, porcelain,insulator for working pressure 1100 voltwith hardware fittingbolt, washers, nuts etc height 100mm, dia 115 mmcomplete all as specified and as directed.
15Supply, fabricating and fixing in repair mild steel cross arms bracings supports, D-clamps, back plates, clamps fabricated from structural steel section such as angle iron, channel, plate and flats etc includingbolts, washers, welding, bending cold or hot , drilling holes for bolts , in any shape or size including two coats of synthetic aluminium paint over a coat of red oxide primer after preparation of steel surface complete all as specifiedand as directed.
16M & L for taking out all elect connections from LT paneland taking out the cable loop of any size of cable & checking the cablethoroughlyincluding cleaning , cutting & removing the defective portion including provide new Alu lugs and re-fixing thecable in LT panel and relaying cable loop properly and testing complete all as specified and directed. Note : Cost of Alu lugs, labour for earth work shall deemed to be included in the quoted rate.
17Repairs to LT panel boardany size out door/in door type by removing the U/S door hinges and S&F new door hinges of suitable size by welding including levelling the door by removing bends/dents and aligning the door for proper closing complete all as specified and directed by Engr-in-Charge.
18Supply & Laying 50 mm outside dia double wall corrugated pipe (DWC) of HDPE ISI Mark for enclosing cable below ground / road surface, to a required depth, including suitable size coplers for jointing of pipe all as per site requirement and all as directed.
19Supply & Laying 75 mm outside dia double wall corrugated pipe (DWC) of HDPE ISI Mark for enclosing cable below ground / road surface, to a required depth, including suitable size coplers for jointing of pipe all as per site requirement
20M&L for painting with spray pump of LT panel Indoor/outdoor any size any type from outside with two coat of synthetic enamelled paint (colour approved by Engr-in-Charge)over a coat of red oxide and cleaning of LT panelMCCB"s terminals and LT panelfrom inside with air blower and waste cloths complete all as specified & directed.
21M&L for painting to LT MS tubular Pole 8.5/9 mtr long with two coats of synthetic enamelled aluminium paint over prepared surfaces complete all as specified and directed.
22M&L for painting to HT MS tubular pole 11 Mtr long with two coats of synthetic enamelled aluminium paint incl cross arms (for single pole), clamps etc. complete all as specified and directed.
23M&L for painting of HT 11 Mtr long 6 pole structurewith two coat of synthetic enamelled aluminium paint including channel,clamps & accessories in erected position and 1.2 mtr height from ground level in alternate band of approved colour with synthetic enamel paintover prepared surfaces complete all as specified and as directed.
24All as above item No - 23.00 but 4 Pole structure.
25All as above item No - 23.00 but 2 Pole structure.
26Takingdowntheexisting defectiveLTUGcableof4 sq mm x2/3/3.5/4 core upto 70 sqmm x 3/3.5/4 core from trenches / pipes/ pole all as specified and as directed .
27All as per above item No - 26.00 but size 95 sqmm x 3.5 core upto 400 sqmmx 3.5 core.
28Takingdowntheexisting defectiveHTUGcable of 95 sqmm to 185 sqmm 3 corefromtrenches / pipes/ polecomplete all as specified and directed.
29Supply, laying, jointing and testing of under ground electric cable, XLPE sheathed HT 11000 volts, grade, heavy duty, armoured with aluminium multi stranded conductor cross sectional area of cable 95 Sqmm, 3 core conforming to IS laid in trenches, under floor, through the roads fixed along wall/pole/GI pipe complete all as specified and as directed.
30Supply, laying, jointing and testing of under ground electric cable, XLPE sheathed LT 1100 volts, grade, heavy duty, armoured with aluminium multi stranded conductor cross sectional area of cable 400 Sqmm, 3.5 core conforming to IS laid in trenches, under floor, through the roads fixed along wall/pole/GI pipe with proper clamps complete all as specified and as directed.
31All as per above item No-30.00 but of 240 Sqmm, 3.5 core.
32All as per above item No-30.00 but of 95 Sqmm, 3.5 core.
33All as per above item No-30.00 but of 70 Sqmm, 3.5 core.
34All as per above item No-30.00 but of 35 Sqmm, 3.5 core.
35All as per above item No-30.00 but of 25 Sqmm, 4 core.
36All as per above item No-30.00 but of 16 Sqmm, 4 core.
37All as per above item No-30.00 but of 10 Sqmm, 4 core.
38All as per above item No-30.00 but of 6 Sqmm, 2 core.
39Supply & laying unreinforcedprecast concrete type 2flat cable cover,class HV, type -1,flat, size 300mm x 180mm x 40 mm completeallasperSSR part-II & as directed.
40Material and labourfor PCC 1:4:8 type D-2 (using 40mm graded stone aggregate) as in base and surrounding the pole and stay complete all as specified and as directed.
41Material and Labour for PCC 1:2:4 type B-1 (using 20 mm graded stone aggregate) as in foundation for feeder pillars, LT Paneland coping of poles including necessary form work and fair finished to exposed surfaces without using extra cement complete all as specified and as directed.
42Supply and fix in replacement of switch air break gang operated triple pole mechanically operated mounted on HT insulator (09 insulator , Vertical type) and Mild steel framewith operating mechanism worked fromground levelincluding operating rod for currentrating up to 400 amps, 11000 voltscompletewith 6 leverpadlockingarrangements, MS Clamp, nuts, bolts and washers etc including two coats of aluminium paint over a coat of red oxide primer on MS work complete all as specified & directed.
43Supply and fixing in replacementdrop out fuses HT, 11 KV Triple pole, rating 100 ampswith base frame and insulator complete all as specified and as directed.
44Supply & fixing Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for LT, 20cmx15cm size complete all as specified and directed.
45All as per item No 44.00 but HT, 25cmx20cm size complete all as specified and directed.
46Material and labours earthings complete with galvanized steel earth plate electrode 600mm x 600mm x 6 mm thick, buried directly in ground (Earth pit not less than 2.25 metres deep below ground level) , surrounded from all direction with charcoal dust and salt in layers, the top edge of the earth plate not less than 1.5 metre below ground level, connected to galvanized iron strip 32×6mm as earthing lead and 40 mm bore GI pipe light grade for protection of GI strip. fixed by means of bolts, nuts and washers of galvanized iron and connected to earth test point andequipment and testing on completion including excavation and earthwork in any type of soil, PCC chamber in 1 :2:4 using 20 mm graded stone aggregate, CI cover, 20 mm GI pipe light grade for watering, funnel, wire meshcomplete all as specified and shown on electrical plate No 5 of MES Schedule Part ‘I’( 1991). Note - Cost of GI Strip and protection pipe upto 7.5 Rm is deemed to be included in the quoted rate.
47Supply and fix in repairs Time switch daily dial 240 v AC Base mounting type complete all as specified and directed. Make : L&T or equivalent of Havells/legrand
48Supply and fix in repairs Programmable time switch 24 Hrs, 240 volt complete all as specified and directed.Make : L&T or equivalent of Havells/legrand
49Supply and fixin repairs Power contactor 3 pole, MNX 110 , 415 V 110 Amp complete all as specified and directed. Make : L&T or equivalent of Legrand/Havells.
50Supply and fixin repairs Power contactor 3 pole, MNX 225 , 415 V 225 Amp complete all as specified and directed. Make : L&T or equivalent of Legrand/Havells.
51Supply and fix in repairs Power contactor ML3 type, 415 V, 40 A complete all as specified and directed. Make : L&T or equivalent of Legrand/Havells.
52Supply & Fixin repairs Power contactor FP, 415 volt, 16 Amps complete all as specified and directed. Make : L&T/Havells.
53Supply & fixin repairs power control relay 3.2 to 5 Amps complete all as specified and directed. Make : L&T/Havells.
54Supply and fixin repairs MCB SPN 40 A, 230 volt. "C" curve complete all as specified and directed.
55Supply and fixin repairs MCB TPN/FP 40 A, 415 volt."C" curve complete all as specified and directed.
56Supply and fixin repairs MCB TPN/FP63 A, 415 volt."C" curve complete all as specified and directed.
57Supply and fixin repairs MCB TPN/FP100 A, 415 volt."C" curve complete all as specified and directed.
58Supply and fixin repairs MCB TP63 A, 415 volt."C" curve complete all as specified and directed.
59Supply and fixing in replacement MCCB, 630 amps, FP 415 volt, 50 KA capacity with suitable terminals in existing LT panel including drilling hole, nut bolt and washers and making electrical connections complete all as specified and as directed.
60Supply and fixing in replacement MCCB, 250 amps, FP 415 volt, 36 KA capacity with suitable terminals in existing LT panel including drilling hole, nut bolt and washers and making electrical connections complete all as specified and as directed.
61Supply and fixing in replacement MCCB, 200 amps, FP 415 volt, 36 KA capacity with suitable terminals in existing LT panel including drilling hole, nut bolt and washers and making electrical connections complete all as specified and as directed.
62All as per above item No-61.00 but 100 Amps, TP, 16 KA complete all as specified and as directed
63All as per above item No-61.00 but 63 Amps, TP, 16 KA complete all as specified and as directed
64Supply & fixheat shrink cablejointingkitfor 1.1 KV grade cablefor straight throughjoint kitcompletewithjointingmaterial andaccessoriessuitablefor 2/3.5/4core XLPE/ PVCarmouredAluminium Conductorcableofsize 16 Sqmm to 35 Sqmm. Make: DENSON / MAHINDRA / REYCHEM / 3M ( m -seal cable jointing kit). Note:- Earth work shall be measured and paid separately.
65All as per above item No-64.00 but for 50 Sqmm to 95 sqmm 3.5Core complete all as specified and as directed
66Supply and fixing in replacement ofheat shrinkable end termination out door joint kit of 3 core 95 sqmm suitable for 11000 volt with accessories and testing complete all as specified and as directed by Engineer in charge.
67All as per above item No-66.00 but for size 120 to 185 Sqmm.
68Supply and fixing in replacement ofheat shrinkable straight through joint kit of UG cable 3 core 95 sqmm to 120 sqmm suitable for 11000 volt with accessories and testing complete all as specified and as directed by Engineer in charge.Note:- Earth work shall be measured and paid separately.
69Dismantling of old/rusted aluminium conductor steel reinforced of any size and removing the same from site of work all as specified and directed by Engineer-in-Charge.
70Material and labour for aluminium conductor steel reinforced [ACSR] straining properly on insulators and bindingwith aluminium tape/binding wire, connectors,jumpers etc on required places complete all as directed by Engr-in-charge.
71Material and labour for painting of transformer complete with radiator of capacity up to 500 KVA, 11/.433 KV outdoor type with two coat spray painting with synthetic enamelled gray paint after preparation of transformer surfacecomplete all as specified and directed.
72Restringing of existing ACSR conductor of LT/HT OH line on PCC/steel tubular poles properly on insulators and rebinding with aluminium binding wire connectors, jumpers etc complete to the entire satisfaction of Engineer-in-Charge.
73Disconnecting and dismantling the ACB breaker rating 400 to 800 Amps make Crompton Greaves/C&S/ L&T by carrying out repair/ servicing , checking and renewing the defective shunt trip coil &UV trip 415 V AC, checking and rectifying the defective CTs and rectifying the mechanism operation including spring charge system, reinstalling the same in the panel and providing necessary line and connections all as directed by Engineer-in-charge.
74Surface excavation not exceeding 30 cm deep in hard and dense soil and getting out green vegetation, roots, bushes, etc surrounding ofpolestructure / substations /pumphouse as directedby Engr-in- charge.
75Material and labour for cutting of bituminous road / floor for laying of pipe / cables not exceeding 20cm wide and not exceeding 30 cm deep including refilling with material and, watering well ramming / compacting and making good with premixed bituminous macadam, 100mm thick complete all as specified anddirected by Engr-in-Charge.
76Servicing and alignment of existing 11 KVGODbycleaningthe contact/ pin insulatorwithCTC&applyingthepetroleum jellyatthe contact, replacement of jumpers as required ,adjusting thedownrod linksforsmoothoperationincludingreplacingtherusted/ corroded bolts & nuts and defectiveinsulator / contacts /copper stripofGODas requiredat site and as directed.Note :- Insulator /contacts /copper strip shall be measured andpaid separately under relevant items.
77Supply Male / Moving contact ( setof3 Nos ) complete all as specified and as directed
78Supply Female / Fixed contact ( setof3 Nos ) complete all as specified and as directed
79Supply Coppertinned strip ( setof3 Nos ) complete all as specified and as directed
80Cutting, trimming and vending tree branches falling on overhead head lines after arranging electrical shutdown from department or MSEB including taking all precautions while working on lines complete all as specified and as directed [Note:- (i) The length of span between two poles shall be measured in which trees are falling on overhead electric conductors. (ii) Required T & P will be arranged by the contractor at his own cost.
81Supply and fixing in repairs jumper connection at cut point on HT over head line with suitable size of ASCR conductor 6 / 1 x 3.00 mm (ferret/weasel) PG Clamps, lugs, alkathine sleaves,galvanised nut and bolts complete of required length not exceeding 3 mtr including testing on completion complete including dismantling of old U/s jumper all as specified and as directed.
82S&F in replacement of 3 phase LEDvoltmeter Cl 0.5 with suitable accessories and fixing arrangements complete all as specified and as directed. Make : L&T or equivalent of standard/ABB.
83S&F in replacement of 3 phase LEDAmpmeter Cl 0.5 with CTsand suitable accessories and fixing arrangements complete all as specified and as directed. Make : L&T or equivalent of standard/ABB. .
84Supply & fixin repair LTinsulation bushings 433V of suitable sizefor outdoor typetransformer of capacity up to 160 KVA complete all as specified and as directed
85All as per above item No- 84.00 but for 160KVA up to 500 KVA complete all as specified and as directed
86Supply & fixin repair HTinsulation bushings 11 KV of suitable size for outdoor type transformer ofcapacities up to 160 KVA complete all as specified and as directed
87All as per above item No- 86.00 but above 160 KVA up to 500 KVA complete all as specified and as directed
88Supply & fixin repair brass stud(for LT 433V side)of suitable size complete with one chuck nut, two nuts, washers and rubber seal, all as per sample for outdoor typetransformer of the capacity up to 160KVA complete all as specified and directed.
89All as per above item No- 88.00 but above 160 KVA up to 500 KVA complete all as specified and as directed
90Supply & fix in repair brass stud (for HT 11 KV side) of suitable size complete with one chuck nut, two nuts, washers and rubber seal, all as per sample for outdoor typetransformer of the capacity up to 160KVA complete all as specified and as directed
91All as per above item No- 90.00 but above 160 KVA up to 500 KVA complete all as specified and as directed
92M&L for disconnecting the transformer of capacity 50KVA to 100 KVA and taking out the complete HT/LT cable/ Jumper connections and terminal box by removing all nuts/bolts/gasket etc.. Cleaning the HT and LT bushings and terminals etc. and inspecting for any damaged winding or any loose connections, leakages of oil, tightening the clamps,and checking the winding for its proper functioning and reassembling by replacinga new gaskets of required size and shapes including draining, refilling of transformer oil and reconnecting HT and LT connections and testing & commissioning complete all as specified.Note : (i ) HT/LT bushings will be measured and paid separately under relevant item.
93All as per above item No-92.00but capacity 150 to 200 KVA complete all as specified and as directed
94All as per above item No-92.00 but capacity 250 to 315 KVA complete all as specified and as directed
95All as per above item No-92.00but capacity 400 to 500 KVA complete all as specified and as directed
96M&L for refilling / top up the transformer oil low viscosity conf to IS 335:1993 filteredofall as directed and sample of oil duly tested for di elect strength not less than 45 KV at 2.5 mm gap complete all as specified and as directed
97M&L for filtration/ dehydration of transformer oil ON LINE through mobile stream line transformer plant at siteand testing of sample of transformer oil before and after filtration for di electric strength up to 45 KV at 2.5 mm electrode gap complete all as specified and as directed .
98Opening of transformer and taking out old unserviceable tap changer and supply & installed new tap changer completesuitable for transformer outdoor type capacity up to 500 KVA complete all as specified and as directed
99Disconnecting all the electrical connections from H.T.and L.T. side of unserviceable transformer of capacity up to 160 KVA i.e. Jumpers/cable from the cable end box or bushings & earthing terminal of the transformers, loading and unloading oftransformer & transportation by vehicle/crane from substationto the repairing workshop including reinstallation, commissioning and testing complete all as specified and as directed
100Disconnecting all the electrical connections from H.T.and L.T. side of unserviceable transformer of cap above 160 KVA to 500 KVA i.e. Jumpers/cable from the cable end box or bushings & earthing terminal of the transformers, loading and unloading oftransformer & transportation by vehicle/crane from substationto the repairing workshop including reinstallation, commissioning and testing complete all as specified and as directed
101Opening thetransformer cover rating up to 160 KVA along with the conservator by removing the nut bolts then after removing the internal HT.& LT connections by taking them out by removing studs, bushings, taking out the core-winding assembly out of the tank of transformer having ratio 11/0.433KV, draining & decanting oftransformer oil and cleaning of sludge deposited in the tank with CTC for the transformer.Heating of core winding assembly in hot chamber for 48 hours and remove all the moisture present in it , removal of leakage of tank if any by welding, refillingtransformer oil into the tank after dehydration / filtration and checking of dielectric strength of oil , after putting the core-winding assembly into the tank, reassembling making the internal H.T. & L.T. connections by fixing the studs, bushings, fitting the top cover by replacing cork sheet gasket along with conservator, testing the transformer in the workshop duly filled with oil, complete all as specified and as directed. Note : U/S items required for repairs shall be measured and paid under relevant item of this schedule. Transformer oil if required with die electric strength not less than 40KV either new or filtered shall be filled and shall be measured and paid separately under respective item.
102All as per above item No-101.00 but of capacity above 160 KVA to 500 KVA complete all as specified and as directed
103Supply only super enamelled copper winding wire / strip of any size for HT coils of transformers complete all as specified and directed
104Supply only copper windingstrip of any size for LT coils of transformers including providing insulation as required complete all as specified and directed.
105Reconditioning of LT coil of copper wound transformer by turning the old paper insulations, straightening the entire LT Strip providing new paper insulations of superior quality and making coil of suitable design as original complete all as specified and directed
106Supply and fixin replacement oil temperature gauge meter suitable fortransformer up to 500 KVAtransformer complete all as specified and directed
107M & L for replacement of breather assembly of transparent plastic body with top and bottom portion pressed with metallic cover, filled with silica jel blue in colour and suitable for pipe entry of 15/20/25mm dia as per the site requirement, complete all as specified and complete all as specified and as directed
108Supply & fix in replacement LED 8W to11 W decorative garden light LED bollard in round/squared shapedwith opel acrylic diffuser and aluminium reflector IP 65 protection including necessary PCC cylinderical foundation with PCC 1:2:4 height not less than 30cm and dia 25cm above from ground for fixing of light fitting including connector and necessary electrical connections etc. complete all as specifiedand directed. Make - Havells Cat part No- CONEBLS8WLED830PSYMTOPC (0.6 M) or equivalent of Wipro/Crompton.
109Supply and fixing in replacement street lightmounting bracket made out of GI pipe 40 mm dia "medium Grade" not less than 0.75 m long in any shape with 2 nos ofclamps made out of MS flat of size 40 x5 mm and nutsand bolts complete all as specified and as directed
110Supply, installation, testing and commissioning in replacement of street light panel outdoor type on wall/pole comprising with Digital 24 Hrs timer-01 Nos, contactor 65 Amps, TP -01 Nos, MCB TPN 63 Amps -01 Nos copmlete with necessary electrical connections complete all as specified and directed. Make : Havells /L&T/Legrand.
111Supply, installation, testing and commissioning in replacement of Street light panel outdoor typefor Digital 24 Hrs time switch with 32 Amps3 phase 415 Volt contactor, suitable relay and 40 Amps SPN MCBfor automatic switch on and switch off complete all as specified and directed. Make - Havells/L&T / Legrand.
112Supply and fixing in replacement of unserviceable existing HPSV/HPMV/tube light fitting of any wattage on existing poles with LED security light 60 W IP 66 complete all as specifed and directed by Engineer-in-charge. Make- Wiproor equivalent of Havells/Crompton
113Supply and fixing in replacement of unserviceable existing HPSV/HPMV/tube light /LED lampfitting of any wattage on existing poles/High mast with LED flood light200 to 210 W IP 66 pressure die cast aluminium housingfor large area lighting complete including suitable MS clamps, nuts & botls with necessary electrical connection complete all as specified and as directed. Make- Crompton or equivalent of Havells/Wipro.
114S & F in repair pole mounting boxes( DB) factory made of FRP heavy duty internal dimention not less than 155x155x100mm. Make Sintex or National ISI markedcomprising with the following :- (a)Three phase copper connector on porcelain insulators complete including lugs and suitable size of MS clamps as per site requirement - 02 Nos, nut and bolts etc.all as directed by Engr In Charge.
115Supply & fix in replacementof unserviceable existing HPMV/HPSV post top lantern with LED 40 to 45 W decorative post top LED, made in cast aluminium with decorative opal polycarbonate diffuser with IP 65 protection including minor fabrication on top of existing pole according to luminaire diaall as directed and specified. Make- Wipro or equivalentof Havells/Crompton.
116S&F Solar Studd lights reflector (3W/2.5 mono-crystalline solar panel) Make: Hardoll-SRS-6RF-1
117M &L for GI pipe 40mm bore "Medium grade" for mounting of post top lantern, including cutting, fabricating and welding of suitable length as directed by Engr-in-Charge.
118Supply and fix in replacement electronic driver & panel for LED street light fitting 45/60/90 Watt & repair of fittings complete all as specified and directed.
119Supply and fix in replacement electronic driver & panel for LED street light /Panel light fitting 36 Watt & repair of fittings complete all as specified and directed.
120Supply & fix battery 12 V 150Ah for DG set. Make- Amaron/Exide
121Supply & fix battery 12V 100Ah for DG set. Make- Amaron/Exide
122Supply & fix battery charging unit 24 V 10A Battery charger- Make NHP
123Supply and fix in replacement of 1 Sqmm 3 core PVC insulated stranded copper cable from pole junction box to fitting all as directed.
124Dismantling the fuel injection pump assembly for overhauling and repairing by replacing of worn outparts such as gasket diafarm etc complete all as directed and calibration of FIP and refixing the same having capacity 250 KVA DG set. Make Kirloskar
125All as per item No. 124.00 above but of capacity 160 KVA DG set.
126Supply and replace the injector nozzles for 160KVA to 250 KVA DG set suitable for Kirloskar Engine complete all as specified and directed.
127Supply and replace water pump assembly suitable for 250 KVA capacity suitable for Kirloskar DG Set complete all as specified and directed.
128All as per item No. 127.00 above but suitable for capacity 160KVA suitable for Kirloskar Engine complete all as specified and directed.
129Supply and replace the V fan belt heavy duty for water pump of capacity 160 KVA to 250 KVA Kirloskar Engine complete all as specified and directed.
130S & F V fan belt for alternator of capacity 160 to 250 KVA DG Set complete all as specified and directed.
131M&L for carrying out the servicing of DG set make Kirloskar complete all as permanufacturer"s instructions and all as directed by the Engineer-in-Charge by replacement of the following parts of 250 KVA Capacity DG Setincluding carrying out minor addition/alternation and supply and fixing the parts for smooth functioning of DG Sets at Tech area. Make : Kirloskar [a] Element fuel filter with "O" ring - 2 Nos [b] All Oil filter element [c] Element air cleaner (Inner & Outer)- 1 Nos. [d] Checking and correcting up of water pump for excess play. [e] Cleaning and tightening of all electrical connections of DG sets upto the entire satisfaction of theEngr-in-Charge. [f] Cleaning of entire DG sets with proper cleaning material upto the entire satisfaction of the Engr-in-Charge. [g] Checking and tighting inlet & exhaust manifold bolts & nuts.[h)Taking down and cleaning and servicing of radiator from inside and outside throughly with cleaning solution and refixing the radiator assembly properly. [j]Replacing the radiator hose pipewithsuitable size with clamps. [k] Checking and making good vibration dampner. [l] Checking and correcting of inlet/exhaust valve, valve guide with grinding of valve and grinding of injector Nozzles and cleaning of head and calibration of rocker arm and refixing with head gasket.
132All as per item No.131.00 but DG set capacity 160 KVA. Make : Kirloskar.
133All as per item No.131.00 above but DG set capacity 40 KVA to 75 KVA. Make : Cummins
134All as per item No.131.00 above but DG set capacity 25 KVA to 30 KVA. Make : Cummins Note for item No 131 to 134 : Servicing and all above mentioned jobs will be carried out by authorised manufacturer"s representative only to the entire satisfaction of the Engineer-in-Charge. Engine Oil, coolent will be measured and paid as separate item complete all as specifed and directed.
135M&L for Repair to Radiator assy by disconnecting the radiator from engine frame and servicing/cleaning with acid and brazing where required to stop leaking tubes/joints etc. cleaning fins and refixing the same for DG set 160 KVA to 250 KVA complete all as specifed and directed.
136Repairs and overhauling of self starter complete including replacement of all worn out parts, bushing contact assembly complete after dismantling and refixing the same after repairs complete all as specifed and directed.
137Supply and replace the battery copper lead of 70 Sq mm size having 1.5 M length suitable terminal complete all as specifed and directed.
138All as per item No 137.00 but having 30 cm length complete all as specifed and directed.
139Supply and filling in sump / topping up engine oil, multi grade 15w/40 in engine or replacement of engine oil complete all as specified and directed. Make: Indian oil / Hindustan petrolium / Castrol
140Supply and filling electrolyte of suitable Sp gravity for lead acid batteries in sealed containers complete all as specified and as directed
141Supply & fill for coolent of DG Set complete all as specified and as directed
142Supply and fix sediment filter suitable for water purifier. Make -Zero "B" complete all as specified and as directed
143Supply and fix carbon filter suitable for water purifier. Make -Zero "B" complete all as specified and as directed
144Supply and fix ultra violet filter (inside) suitable for water purifier. Make -Zero "B" complete all as specified and as directed
145Supply and fix Pre-Carbon filter (inside) suitable for water purifier. Make -Zero "B"complete all as specified and as directed
146Supply and fix UF filter (inside) suitable for water purifier. Make -Zero "B" complete all as specified and as directed
147Supply and fix in repair fuel pipe steel braided, steel stranded with benzo bolts and washers etc complete of length 30 cm long complete all as specified and as directed
148Supply and fix in repair fuel pipe steel braded, steel stranded with benzo bolts and washers etc complete of length 45 cm long complete all as specified and as directed
149Supply and fixin repair fuel pipe steel braded, steel stranded with benzo bolts and washers etc complete of length 60 cm long complete all as specified and as directed
150Supply and fixin repair fuel level indicator transparent PVC pipe of suitable dia for fuel level in tank complete all as specified and as directed
151Supply and fixin repair solenoid switch vertical/ horizontal type capacity upto 160 KVA DG set complete all as specified and as directed
152Dismantling and replacement of old LT panel and supply, installation, testing and commissioning of new LT panel board(CPRI Approved) made out of 3.15mm thick CRCA sheet steel enclosure OUTDOOR cubical type, double door with aprons, dust, vermin, weather proof duly powder coated with seven tank process and all as per IE rules,mounted on angle iron of size 50x50x6mm with two coats of black synthetic enamel paint over a coat of red oxide primer and height from ground level not less than 50 Cm including grouting with PCC 1:4:8 type D2 40 mm graded stonre aggregate including necessary excavation and earth work complete with necessary compartments, fitted with 4 Nos TPN of aluminium bus bar 200 Amps with colour code sleeves mounted on porcelain/SMsC/DMC insulators, including internal control wiring with PVC insulated copper wire of suitable size and panel shall have comprise/including of following items :- (a) Bus Chamber : (i) Aluminium Busbar 200 Amps rated- 04 Nos (b) INCOMING :- (i) MCCB 100 Amps, 4 Pole, 415 volt, 18 kA with thermal megnetic release - 01 Nos (c) OUTGOING :- (i) MCCB 63 Amps, 3 Pole, 415 volt, 18 kA with thermal megnetic release- 02 Nos(ii)Digital 24 Hrs time switch with 65 Amps 3 phase 415 Volt contactor, suitable relay and 63 Amps TPN MCBfor automatic switch on and switch off of street lights complete - 01 Nos (iii)Indication LED set of three (RYB) with integral circuit 01 Set for Incomming and 02 set for outgoing- 03 Set (iv) 3 Phase LED Voltmeter - 01 Nos (iv)3 PhaseLEDAmp Meter with CT"s. - 01 Set (v) Spare Space with mounting rail for MCB TPN -02 Nos. Note :- Cost of Cable glands, MCCB spreader terminals, cable lugs etc is deemed to be included in the quoted rate. Panel should be spacious for easy maintenance and cable connections etc.
153M&L for galvanized iron strip of size 25mmx4mm fixed to wall/roof or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation/position for lightening arrestor/earthing etc, including necessary supports, fixtures at any position/location complete all as specified and directed.
154Straigtening in proper alignment the existing galvanized iron strip of size 25mm x 4mm fixed to wall/roof or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation/position for lightening arrestor/earthing etc, including necessary supports, fixtures at any position/location complete all as specified and directed.
155M&L for cement concrete 1:2:4 type B1(using 20mm graded stone agreegate) cubes of size 150mmx150mmx150mm including necessary formwork for supporting to cable trench, GI duct, GI earthing strips fixed at any postion, location complete all as specifed and directed.
156REPAIR MAINT OF EOT/HOT CRANES PERIODICAL TESTING OF CRANES WITH ALLIED WORKS. Comprehensive Maintenance (Preventive and breakdown) of electrically operated travelling (EOT) crane of 1 Ton capacity (1No.), floor operated, comprising of hoist motor, micro motor, long travel motor, cross travel motor, gear box, control panel and other connected accessories installed at foundry shop Make RASI & Co. Sl No 1005/91 complete all as specified and directed.
157All as per above item No-156.00 but of capacity 2 Ton installed at :- (a) VEM workshop, Make - Cranex Ltd Sl No. 8701
158(b) Extn to M/C shop, Make - Eltech Sl. No. 1710
159(c) IC Engine lab Make Cranex Ltd Sl No. 8626
160(d) TIC Bldg. NCAT, Make - Electro Technique P Ltd.
161(e) IC Engine Lab Make - Dinesh S.No. 701
162(f) IC Engine lab Make - Dinesh S. No. 702
163(g) IC Engine lab Make - Dinesh S. No. 703
164All as per above item No-156.00 but of capacity 5 Ton installed at :- (a) Machine shop, Make - Cranex Ltd Sl. No. 8803
165(b) Fabrication shop, Make - Cranex Ltd Sl. No. 8702
166(c) MMG shop Make - Dinesh Sl. No. 608
167All as per above item No-156.00 but of capacity 15 Ton installed at ICV shop. Make - Dinesh Enterprises, Sl No. 304
168All as per above item No-156.00 but of capacity 15 Ton installed at UGV shop at NCAT Make REMI
169Comprehensive Maintenance (Preventive and breakdown) consisting of normal repairs & preventive maintenance of JIB crane with Electric hoist with motorised traveling trolly of capacity 1 Ton installed at (a) IC Engine lab Test Cell No. 1
170(b) IC Engine lab Test Cell No. 2 Note for Item No. 156.00 to 161.00 :- (i) The rate quoted by contractor are deemed to be included the cost of grease, cotton waste, nut/ bolts, washers and T&P etc. (ii) Rate quoted by the contractor is deemed to include petty repairs and consumables and no separate payment shall be made in this regard. (iii) Spares required for preventive and breakdown maintenance shall be measured and paid separately under relevant item. (iv) The rates quoted shall be deemed to include labour for fixing of supply only items .
171M&L for 100% load testing of EOT crane of following crane of following cap for deflection test :- (a) 1 (one) Ton
172(b) 2 (Two) Ton
173(c) 5 (Five) Ton
174(d) 15 (Fifteen) Ton Note :- (i) Cost is deemed to include 100% load test for deflection test once in contract period but within six months from the commencement of contract. Load for testing will be arranged by the contractor at his own cost and no separate payment shall be made in this regard.Test will be carried out with 100% load for LT, CT and Hoisting at normal speed and micro motion and for deflection.Test certificate for load test will be submitted separately apart from Form 12. (ii) Test shall be done in the presence of competent authority (appointed by Directorate of Industrial safety and Health, Govt of Maharashtra or equivalent) for testing of cranes and certificate (Form 12 Prescribed for examination of lifting machines, ropes and tackles) to this effect shall be rendered regarding stability of crane.
175Supply only HRC fuse contacts complete with base in re-placement of old unsv from 5 to 16Amps capacityMake: EE/L&T
176Supply only HRC fuse contacts complete with base in re-placement of old unsv from 20A to 40 Amps capacityMk: EE/L&T
177Supply only brake shoe assembly complete (Thruster type) with lining set suitable for main hoist upto 5 ton cap. Make : Speed-o- Control or equivalent.
178Supply and fix for replacing the existing unsv Contactor 3 phase 415 Volts, of BCH/L&T/C&S/Siemens make suitable model/Voltageas requiredat siteof following sizes :- (a) 70 Amps Type ML 4 or equ of BCH/C&S/Siemens
179(b) 40 Amps Type ML 3 or equ of BCH/C&S/Siemens
180(c) 30 Amps Type ML 2 or equ of BCH/C&S/Siemens
181(d) 16 Amps Type ML 1 or equ of BCH/C&S/Siemens
182(e) 12 Amps Type ML 0 or equ of BCH/C&S/Siemens
183Supply only in repairs Over load electro pnematic relay contactor mounting type make: Siemens/BCH as required at siteof thefollowing capacity (a)8 – 12 Amps
184(b)5 – 8Amps
185(c) 2 – 3Amps
186(d) 1.25 – 2Amps
187Supply only of Hydrulic/ gear oil for upto 15 toncapacity of cranes all as directed by Engineer-in-charge.
188Supply only gasket for gear box /hoist for 1 ton capacity of crane.
189Supply only gasket for gear box /hoist for 2 ton capacity of crane.
190Supply only gasket for gear box /hoist for 5 ton capacity of crane.
191Supply only gasket for gear box /hoist for 15 ton capacity of crane.
192Supply only brake liner unit 100 mm dia
193Supply onlybrake liner unit 150 mm dia
194Supply onlylimit switch two way shut type 16 Amp
195Supply onlycarbon brush sqare for micro clutch
196Supply onlypendant push buttons
197Supply onlypendant indicators
198Supply onlyElectromagnetic brake coil 300VA Capacity
199Supply and fixcopper flexible multicore cable of size 1.5 sqmm x 19 core.
200Takingdowntheexisting defectiveLTUGcableof any size from wall/ duct/ceiling all as specified and directed by Engr-in-charge..
201Supply,Laying, testing and commissioningofLT UG cable25 sqmm 4 core, ISI marked XLPE insulatedarmouredand PVC shetahed1100 Volts grade with aluminium conductor multistrandedincluding cable conencting lugs, glands, jointing materials etc., laid in duct, floors, roof, & wall etc andfixing using clamps, saddles for wall complete all as directed by E-in-Charge.
202M&L for earthing complete withgalvanised steel earth plate electrode 600mm X 600mm X 6mm thick burried directly in ground ( earth pit not less than 2.25 mtr deep below the ground level ) with top edge of the plate not less than 1.5 mtr below the normal ground level, connection to GI earth strip 25X4 mm by means of nut, bolts, check nut,washer of galvanised iron or steel, 40mm bore GI protection pipe light grade, all as shown in electrical plate no 5 connected to the earth test point all as specified & indicated including testing on completion, with 40mm thick RCC 1:2:4 type B-1 as in cover using 8mm dia TMT bars @ 75mm c/c spacing, funnel for watering etc including necessary earth work and excavation complete all as specified and as directed. NOTE:- Cost of GI strip 25x 4 mm and protection pipe upto 7.5m shall deemed to be included in quoate rate.
203Supply only in repairs Time delay relay electro pnumatic with 2 NO+2 NC,PN type, 220 volts make BCH or equivalent of C&S/Siemens
204Supply and fix in replacement of unsv single phase preventor 415V,3 Phase Mk Minilec/ L&T/ C&S
205Supply and fix steel wire rope for upto 5 ton capacity of crane of size 12 mm dia IPS grade upto 1960 N/mm2complete all as specified and directed.
206Supply and fix PVC flexible Submain 2.5 sqmm 4 core copper conductor 1100 v grade complete all as specified and directed.