Tender For Maintenance Of Dg Sets, Voltage Stabilizers, Booster / Submersible Pumps, Lt Panels And Other Connected Works At Ge (Af) Ambala, ambala-Haryana

Military Engineer Services-MES has published Tender For Maintenance Of Dg Sets, Voltage Stabilizers, Booster / Submersible Pumps, Lt Panels And Other Connected Works At Ge (Af) Ambala. Submission Date for this Tender is 12-12-2022. Voltage Stabiliser Tenders in ambala Haryana. Bidders can get complete Tender details and download the document.




Tender Notice

34992363
Corrigendum : Tender For Maintenance Of Dg Sets, Voltage Stabilizers, Booster / Submersible Pumps, Lt Panels And Other Connected Works At Ge (Af) Ambala
Open Tender
Indian
Haryana
ambala
12-12-2022

Tender Details

Tender For Maintenance Of Dg Sets, Voltage Stabilizers, Booster / Submersible Pumps, Lt Panels And Other Connected Works At Ge ( Af ) Ambala

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 01-Dec-2022 DATE AMENDMENT Date 12-12-2022

Key Value

Document Fees
INR 500 /-
EMD
INR 90000.0 /-
Tender Value
INR 45 Lakhs /-

BOQ Items

Name of Work: MAINTENANCE OF DG SETS, VOLTAGE STABILIZERS, BOOSTER / SUBMERSIBLE PUMPS, LT PANELS AND OTHER CONNECTED WORKS AT GE (AF) AMBALA
Sl. No. Item Description
1Periodical, preventive and comprehensive maintenance of DG set of Cap 30 to 40KVA by Rep of authorised service centre as per manufacturer manual and checking of fuel supply system, Lubrication system, cooling system, battery ignition system and rectification of defect, inspection/testing of engine and alternator for smooth functioning of the DG set and including the replacement of following :- (i) fuel/ lub filter one set (ii) coolent in radiator (iii) Testing of engine control panel (iv) Cleaning of radiator, minor repair of leakages to be rectified. (v) hose pipe set (vi) fuel pipe/lubricant pipe (vii) Engine oil. Make of DG set: Kirloskar/Cummins Note: (i) The rates shall be deemed to be inclussive of one visit per quarter & unlimited breakdown complaints and repairs. (ii) Worn out parts repair/replacement if any other than above shall be measured and paid seprately.
2Periodical, preventive and comprehensive maintenance of DG set of Cap 62.5 to 100 KVA by Rep of authorised service centre as per manufacturer manual and checking of fuel supply system, Lubrication system, cooling system, battery ignition system and rectification of defect, inspection/testing of engine and alternator for smooth functioning of the DG set and including the replacement of following :- (i) service kit for elements of fuel/air/lub filter one set (ii) top up of coolent in radiator (iii) Testing of engine control panel (iv) Cleaning of radiator, minor repair of leakages to be rectified. (v) hose pipe set (vi) fuel pipe/lubricant pipe (vii) Engine oil. Make of DG set: Kirloskar/Cummins Note: (i) The rates shall be deemed to be inclussive of one visit per quarter & unlimited breakdown complaints and repairs. (ii) Worn out parts repair/replacement if any other than above shall be measured and paid seprately.
3Supply only following spare parts of DG set of kirloskar/Cummins DG set all as specified and directed.
4V belt
5Battery Terminal
6Automatic Voltage Regulator for 30 to 40KVA DG set (Solid state voltage regulator type)
7Automatic Voltage Regulator for 62.5 to 100KVA DG set
8Battery lead 1 mtr long (Red for +ve, & Black for -ve)
9Battery 120AH, maintenance fee 12volts Make: Exide/Amaron/ Microtch
10Charging alternator 12V/35A (DC) for 30 to 40KVA Make: Lukas/TVS
11Selfstarter Motor 12V (DC)for 30 to 40KVA. Make: Lukas/TVS
12Charging alternator 12V/35A (DC) for 62.5 to 100KVA. Make: Lukas/TVS
13Selfstarter Motor 12V (DC)for 62.5 to 100KVA. Make: Lukas/TVS
14Microprocessor based engine control panel
15S& F in replacement Acoustic enclosure for DG set of Make CUMMINS engine Ltd India,Capacity 82.5KVA. Acoustic enclosure shall be powder coated and fabricated out of 1.6mm thickness MS sheet, compartmentalized design, acoustic panel assembled with nut bolt and washer. The silent canopy shall be of nut bolt type construction. Powder coating should be done after surface treatment process of sheet metal. Canopy panel and doors shall have inside lining of Fire Retardant Foam as acoustic material. Hinged doors shall be provided to canopy, one door shall have glass window for control panel having standard fitment as per CPCB Norms.” Note : Including the cost for disconnection of cables deataining of fuel and refiiling, dismantling of engine, alternator, control panel with base frame and reinstallation.
16M&L for apply two coat of epoxy paint by spray painting m/c on site,including preparation of rusted surface of DG Set, acoustic enclosure of 30/35/40KVA and writing SM No./MES No.complete all as specified and as directed.
17M&L for apply two coat of epoxy paint by spray painting m/c on site,including preparation of rusted surface of DG Set, acoustic enclosure of 62.5/63/82.5/100 KVA and writing SM No./MES No.complete all as specified and as directed.
18M&L for disconnecting alternator, 3 phase, 4 wire, 50Hz, 0.8PF, 415V, AC, 63kVA capacity, insulation, 50 cycles 1500RPM, self excited, self regulated, brushless type, at any position / location, collecting and transporting to workshop, taking out burnt winding, rewinding with new super enemelled copper wire as per original gauge, including providing insulating materials viz. cotton tape, packing, sleeves, etc. and varnishing by vacuum impregnation and baking of coil, duly re-fixing, bringing in at site, connecting all electrical connections, commissioning and testing 63/62.5KVA complete all as specified and as directed
19S&F in repairs changeover switch, on/off load, 4 Pole, 125Amps capacity, fixed in existing panel board all as specified and as directed.
20S&F in repairs changeover switch, on/off load, 4 Pole, 160Amps capacity, fixed in existing panel board all as specified and as directed.
21S&F in repairs changeover switch, on/off load, 4 Pole, 200Amps capacity, fixed in existing panel board all as specified and as directed.
22S&F in repairs Motor Protection Circuit Breaker (MPCB), 3 pole, 415 volts, 25/34 KW, 50 KA breaking capacity with instantaneous trip-rotary type all as specified and directed.
23S&F in repairs MCCB, 4 pole, 415 volts, 125 Amps, 25KA breaking capacity with adjustable thermal settings and adjustable magnetic settings all as specified and directed.
24S&F in repairs MCCB, 4 pole, 415 volts, 160Amps, 25KA breaking capacity with adjustable thermal settings and adjustable magnetic settings all as specified and directed.
25S&F in repairs MCCB, 4 pole, 415 volts, 200Amps, 25KA breaking capacity with adjustable thermal settings and adjustable magnetic settings all as specified and directed.
26Supply only Distilled Water for batteries
27M&L for preparation of old painted surfaces steel by brushing, greasy spots with thinner and apply two coats of spray painting with super enameled grey colour paint of approved and writing the MES /SM No with white paint as directed to Servo Voltage Stabilizer.indoor/outdoorinstalled at various different locations complete all as specified and directed at site.
28Disconecting the LT incoming and outgoing main cables of any size, opening of thevoltage stablizer capacity of 3 x 20KVA , draining out the oil into a cleaned container ( container shall be arranaged by the contractor ). Lifting up dimmer and transformer with help of tripoid and chain pulley etc (TheT & P shall be arranged by contractor ), checking of all the parts ,cleaning and servicing of the inner surface of the voltage stabilizer, dimmer, transformers coil and allied parts including replacememnt of minor parts like nut bolts ,connecting wires ,rubber seals /packing etc. and reassembling the stablizer complete (in reverse order). Refilling oil after dehydration andfiltration by centrifuging machine including testing of samples before and after dehydrations and filtration complete, reconnecting the supply complete all as specified and directed. Note: (i) The cost of Major parts repair or replacement will be measured and paid separately. (ii) Cost of decaning, dismantling coil any connection, testing and inner tank painting of stabilizer deemed to be inclusive
29M&L for changing of burnt copper coil by new copper coil of voltage stabilizer 3x20 KVA complete with insuating material for core assembly purpose all as specified and directed Note : Cost of decaning, dismantling coil any connection, testing and inner tank painting of stabilizer deemed to be inclusive
30S&F in repairs step synchronous motor of high torque single phase AC supply and shall have in start/stop, reverse characterstics & take very low current all as specified and directed. Make : AE/Volina
31Supply and fix in repair dimmer-stat/ variable voltage transformer type copper wound on high grade crgo/foroidel core of capacity 40 KVA all as specified and directed. Make : AE/Volina
32Supply and fix in repair dimmer-stat/ variable voltage transformer type copper wound on high grade crgo/foroidel core of capacity 20 KVA all as specified and directed.
33Supply and topup of transformer/ voltage stabilizer oil having dielectric strength 60KV as per IS complete all as specified and directed. Note : Oil shall be filled in the stabilizers to be repaired or installed at site at different locations.
34M&L for digital card With high low cut off display Microprocessor based Auto manual function Both Buck and boost Single display for both input and output all as specified.
35M&L for rewinding of electric motor of Cap 15 to 20 HP three phase 415 volts by removing burnt copper winding wire, cleaning of slots and insertion of insulating paper in the slots in appropriate size and rewinding with super enameled copper wire of suitable size superior quality of insulating material, winding, varnishing and drying, and refixing back after rewinding, replacement of connection plate and making necessary electric connection complete all as specified and directed.
36All as per serial item No. 35 but capacity of 10 to 12.5HP
37All as per serial item No. 35 but capacity of 5 to 7.5HP
38All as per serial item No. 35 but capacity of 0.5 to 1HP
39Repair/Overhauling of pump 7.5 to 20HP taking out impeller, shaft, stuffing box re-assembling the same after replacing the defective parts & carrying out the necessary repair remetalling, turning polishing the pump shaft including replacement of steel studs nuts/ bolts replacement of GM bush, ball bearing, stuffing box greasing etc and installation at site, checking of smooth functioning complete all as specified and directed. Note : -(i) The complete job includes making good the existing pumps water leak proof ,including gland/ packing etc. (ii) cost of spare parts except GM bush, Impeller, stuffing box and ball bearing shall be included in the quoted rate by the contractor repair of pumpset.
40S & F bearing for 7.5 to 20HP monoblock pump set complete all as specified and directed. Make:- SKF/NBC
41S & F Impeller for monoblock pump capcity 7.5 to 15HP complete all as specified and directed.
42S & F Stuffing box alongwith pressure plate and hexa nuts, studs, gland packing as per existing make complete all as specified and directed.
43S & F Gun metal Bush suitable for monoblock pump set complete all as specified and directed.
44M&L for Repair/Overhauling of pump set 3 to 5HP including replacement of GM bush, ball bearing if required, re-metaling, turning & polishing of pump shaftetc and testingcommissioning and installation at site complete all as specified and directed. Note : -(i) The complete job includes making good the existing pumps water leak proof ,including gland/ packing etc. (ii) Spare parts i.e. GM bush, shaft sleeve and ball bearing will be measured and paid separately under relevent items. (iii) Item No 24 to 28 & 29, Dismantling of pumpset from site , disconnecting & refitting of waterr inlet & outlet, Decoupling of pump and motor and reinstallation at site deemed tobe included in unit rate.
45S & F bearing for 3 to 5HP monoblock pump set complete all as specified and directed. Make:- SKF/NBC
46S & F Impeller suitable for 3 to 5HP monoblock pump set complete all as specified and directed.
47S & F Stuffing box alongwith pressure plate and hexa nuts, studs, gland packing etc as per existing make complete all as specified and directed.
48S & F Gun metal Bush suitable for 3 to 5HP monoblock pump set complete all as specified and directed.
49Supply and lifting of column pipe, flanged 100mm/80mm bore with submersible cable from bore hole of tube well, pump set of any capacity and lowering after repair in borewell complete all as specified and directed by Engr-in-Charge. Note: (i) Lifting & lowering of pump set upto 120mtrs deep will be deemed to be included in unit rate. (ii) Lifting & lowering of pump set to be completed out within 24hrs from intimation. (iv) Rubber gasket, nuts & bolts for replacement deemed to be included in unit rate.
50Opening of submersible motor for rewinding with PVC coated copper winding wire as per existing gauge insulation material,after stripping of existing worn out winding, M&L for sealing kit, O- ring, Gasket, water drain plug, sand guard, cable packing ring, cable gland ring, upper/lower bearing, adopter piece, motor key, upper lower flange, neck ring, suction case, Hex bolt, Circlip washer, Motor coupling, thurst plate,motor bush etc complete, reassembling with pump set of the following capacities :-
5135/40HP
5220HP to 25HP
531.0HP singlePhase submersible/ sludge pump
54M&L for Repair/Overhauling of submersible pump set including replacement ofHex bolt, Circlip washer, bowl stud, pump shaft, rotor bleach, pump bush etc complete andreassembling pump set of the following capacities:- Note : Impeller shall be measured and paid seperately however labour rates inclusive of quoted rate.
5535/40HP
5620HP to 25HP
571.0HP single Phase submersible/ sludge pump
58Supply only impellerof existing make and type for the submersible pump ofcapacity upto 35 HP
59Supply only PVC insulated cable submersible flat copper 3 core 16Sqmm1100 volt grade. Make : RR kable, L&T, Havells
60Supply only PVC insulated cable submersible flat copper 3 core 10Sqmm1100 volt grade. Make : RR kable, L&T, Havells
61Supply only PVC insulated cable submersible flat copper 3 core 6Sqmm1100 volt grade. Make : RR kable, L&T, Havells
62Supply only galvanized iron column pipe 100mm heavy grade (approximately 3mtr length) each duly flanged at both ends by welding with slots for housing two Nos submersible cable and holes for fixing nut bolts complete as specified and directed Make : TATA/Jindal/ Surya prakash
63Supply only galvanized iron column pipe 80mm heavy grade (approximately 3mtr length) each duly flanged at both ends by welding with slots for housing two Nos submersible cable and holes for fixing nut bolts complete as specified and directed Make : TATA/Jindal/ Surya prakash
64M&L for installing, 1HP sludge pump, ISI marked, including necessary accessories required for fixing accessories nylon rope of suitable size for carrying the pump in sludge well, including taking out existing unserviceable pump set from sludge well, and disposing off complete all as specified and as directed Make : Crompton/ Kirloskar/ KSB
65S&F and install chemical dozing pump of capacity 5LPH, maximum pressure 5.5kg/sqcm, stroke speed 100 duly fixed with suction/delivery pipes, duly synchronosing with the present system and fixed including disposing off old/unserviceable pump complete all as specified and as directed. Make : Toschon Jesco M/s Sathya sai aqua pure/ Decrin
66Supply, installation of pump set submersible type suitable for upto 100mm bore well, head 50mtrs, Discharge 30 LPM, Operating Voltage Range 160-240V single phase, 50Hz complete all as specified and as directed
67S&F FASD three phase submersible pump controller comprises of power contactor, over load relay, single phase preventor, Voltmeter of suitable capacity, three phase indicator lamp etc. complete with copper wiring housed inenclosure for capacity 50HP including proper fixing arrangement, copper cable thimble etc and including taking out old unserviceable starter andall as specified and directed
68S&F FASD three phase submersible pump controller comprises of power contactor, over load relay, single phase preventor, Voltmeter of suitable capacity, three phase indicator lamp etc. complete with copper wiring housed inenclosure for capacity 30HP including proper fixing arrangement, copper cable thimble etc and including taking out old unserviceable starter andall as specified and directed
69S&F single phase submersible pump controller comprises of suitable power contactor, over load relay, Start and Run capactor, Volt/Ammeter of suitable capacity etc. complete with copper wiring housed inenclosure suitable for submersible motor capacity 1HP including proper fixing arrangement, copper cable thimble etc complete all as specified and directed Make: L&T model No MR-G2 Or equivqlent in Crompton/Schnieder/ Seimens.
70S&F in replacement ofDischarge pressure gauges 100 mm nominal dia with control valve, socket, union and adopter, range 0-300 PSI fixed with 150 mm long, 15mm dia GI pipe medium grade with suitable arrangement for fixing on 80/100/150/200 mm DI/CI by using clamps, etc, including taking down existing unserviceable item complete all as specified and directed.
71Supply only calcium hypochlorite granules containing 65% free chlorine in 45 kg container complete all as specified and directed. Note : (i) Disinfectant will be brought out site in sealed container. (ii) Disinfectant will be of Approved Make as per E-in-C branch
72S&F Double tank type Electronic Chemical Dosing system consist of service tank 150 ltrs capacity comprising agitator 0.25hp three phase motor 990 RPM with SS sweep blade with Electronic dosing pump 230 V AC 50HZ capacity upto 10LPH @5kg/cm2pressure,pump head PP with Glass filled , Teflon Diaphragm. With suction and Discharge tubing 3mtrs .along with PVC Injector with NRV complete and preparation tank 150ltrs conical type comprising agitator 0.25hp three phase motor 990RPM with SS sweep blade complete. Make:- Sathya Sai Model No:- SSAPS/CDSET/10 DT or Jesco Toschon or equivalent model
73S&F DOL starter of any type and supply and fixing of 415 volt 3 phase suitable for upto 5 HP monoblock pump set and including taking down existing unserviceable starter. Make : BCH/ Siemens/GE/ABB/L&T/CG
74S&F butterfly valve (manual) size 150mm with CI body SS disc, insulated nitrile rubber seal & O ring PN 1.6 pressure rating for for water distribution lines including taking out unsv valve complete all as specified and directed. Make : Castle/ Zoloto/ Kirloskar/ L&T
75S&F butterfly valve (manual) size 100mm with CI body SS disc, insulated nitrile rubber seal & O ring PN 1.6 pressure rating for for water distribution lines including taking out unsv valve complete all as specified and directed. Make : Castle/ Zoloto/ Kirloskar/ L&T
76S&F butterfly valve (manual) size 80mm with CI body SS disc, insulated nitrile rubber seal & O ring PN 1.6 pressure rating for for water distribution lines including taking out unsv valve complete all as specified and directed. Make : Castle/ Zoloto/ Kirloskar/ L&T
77S&F butterfly valve (manual) size 50mm with CI body SS disc, insulated nitrile rubber seal & O ring PN 1.6 pressure rating for for water distribution lines including taking out unsv valve complete all as specified and directed. Make : Castle/ Zoloto/ Kirloskar/ L&T
78S&F cast iron non return valve 80 mm size with flap & sheet having both flanged & drilled ends including joints & jointing material complete and dismantling of old unsv NRV all as directed by Engr-in-Charge. Make : Zoloto, Kirloskar, Leader, L&T.
79S&F cast iron non return valve 100 mm size with flap & sheet having both flanged & drilled ends including joints & jointing material complete and dismantling of old unsv NRV all as directed by Engr-in-Charge. Make : Zoloto, Kirloskar, Leader, L&T.
80S&F cast iron non return valve 150mm size with flap & sheet having both flanged & drilled ends including joints & jointing material complete and dismantling of old unsv NRV all as directed by Engr-in-Charge. Make : Zoloto, Kirloskar, Leader, L&T.
81S&F cast iron sluice valve 150mm size, PN-1.6 with tensile steel spindle, iron wheel, having both flanged & drilled ends, M&L for joints and jointing material complete including taking down old unsv valve all as directed. Make : Zoloto, Kirloskar, Leader, L&T.
82S&F cast iron sluice valve 100mm size, PN-1.6 with tensile steel spindle, iron wheel, having both flanged & drilled ends, M&L for joints and jointing material complete including taking down old unsv valve all as directed. Make : Zoloto, Kirloskar, Leader, L&T.
83S&F cast iron sluice valve 80mm size, PN-1.6 with tensile steel spindle, iron wheel, having both flanged & drilled ends, M&L for joints and jointing material complete including taking down old unsv valve all as directed. Make : Zoloto, Kirloskar, Leader, L&T.
84S&F foot valve, 50/80mm dia size, one side flanged, including providing rubber gaskets of suitable size, nuts, bolts, washers, etc. and dsconnecting and taking down exact sizes unserviceable foot valve complete all as specified and as directed. Make : Leader, Kesin, Kartar.
85S&F foot valve, 100mm dia size, one side flanged, including providing rubber gaskets of suitable size, nuts, bolts, washers, etc. and dsconnecting and taking down exact sizes unserviceable foot valve complete all as specified and as directed. Make : Leader, Kesin, Kartar.
86Supplying and laying synthetic rubber insulated mats of size 2x1m, 2mm thick for voltage upto 3.3 kV for electrical purpose as per IS 15652-2006, suitable for safety from electrical shock complete all as specified and as directed
87Attending day to day complaints pertains to Electric driven motors and LT panels, Starter panels of any capacity as and when required with skilled Electrician and helper, with necessary T&P for checking the equipment at existing location and find out the faults/ defects and rectify the defects in situ, cleaning/ normal maintanance to the euipments (including fixing lugs, nuts, bolts, etc as required on site) complete to make the equipment functional in all respect complete all as spceified anddirected by Engr-in-charge. Note : (i) Spare parts wiil be measured and paid separately.
88Supply only following spare parts of Starter panels/ LT panels etc. all as specified and directed.
89Indicating lamp Make - L&T/ BCH/ C&S
90Voltmeter 0 – 500 V. Make - L&T/ BCH/ C&S
91Ammeter 0 – 150 A. Make - L&T/ BCH/ C&S
92Single phase preventer system of supply 415 Volt 50 Hz. Make - Minilec/ L&T/ BCH/ C&S
93Three phase preventer system of supply 415 Volt 50 Hz VMR 3P (PROTON) (model No PR-07T
94Start/ Stop switch. Make - L&T/ BCH/ C&S
95Power contactors as per existing make. Make : L&T (MNX 70)/ BCH (MCE15MO Series-A1)/ C&S/ Havells
96Star-delta Electronic timers. Make - L&T BCH/ C&S
97Overload relay range of 9-125A. Make - L&T/ BCH/ C&S
98Copper thimble 6Sqmm
99Copper thimble 10/16Sqmm
100Copper thimble 25Sqmm
101Copper thimble 50/70Sqmm
102Attending complaint of repair of chemical dozing pump,detection of fault and rectification of the defects at site and comprising of replacement ofspare parts kit, pipe, foot valve, Injector nozzle, NRV, filter etc.complete all as specified and directed.
103Supply, lowering and packing pea gravel of size 2mm to 5mm size as per IS ofnatural shaps brought directly from the riverbed pouring around casing pipe and slotted pipes in the borewell complete all as specified and directed. Note: - For the purpose of measurement gravel brought by the contractor shall be stacked properly at site & measurement of stacks shall be recorded before use and after use (left unused) to arrive at the net quantity of gravel used.
104M&L for Development of tube well by 250 cfm and 600 PSI till clear water is obtained, including stabilization of existing bore well all as specified and directed.
105Yield test of the existing Borewell as specified and directed to determine the safe capacity of borewell by the continuous pumping for 16 hrs Note : cost of arrangement for pumps, T&P etc. deemed to be included in unit rate.
106Chemical and Biological testing of water samples from approved laboratories to ensure potability of water as per IS complete all as specified and as directed
107S&F in replcement of Agitator for mixing of hypo-chlorine powder granules, stainless steel mixing rod, 1 phase electric driven motor of capacity 0.5 HP, stand for fixing of Agitator system on chemical dozing tank complete with electrical connections connecting all as specified and directed.
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy