Repair/Maintenance Of Fire Fighting Wet Riser Pipe Line System At Ch (Ec) And Ii Line Under Ge Alipore Kolkata, kolkata-West Bengal

Military Engineer Services-MES has published Repair/Maintenance Of Fire Fighting Wet Riser Pipe Line System At Ch (Ec) And Ii Line Under Ge Alipore Kolkata. Submission Date for this Tender is 09-12-2022. Pipe Laying Tenders in kolkata West Bengal. Bidders can get complete Tender details and download the document.




Tender Notice

34977566
Repair/Maintenance Of Fire Fighting Wet Riser Pipe Line System At Ch (Ec) And Ii Line Under Ge Alipore Kolkata
Open Tender
Indian
West Bengal
kolkata
09-12-2022

Tender Details

Repair / Maintenance Of Fire Fighting Wet Riser Pipe Line System At Ch ( Ec ) And Ii Line Under Ge Alipore Kolkata

Key Value

Document Fees
INR 500 /-
EMD
INR 69500.0 /-
Tender Value
INR 34.75 Lakhs /-

BOQ Items

Name of Work: REPAIR/MAINTENANCE OF FIRE FIGHTING WET RISER PIPE LINE SYSTEM AT CH (EC) AND II LINE UNDER GE ALIPORE KOLKATA
Sl. No. Item Description
1Testing ,inspecting with operating of fire fighting pumping installation installed at Main pump house for CH(EC), including testing of riser,hydrant ,hose reel workng with minor repair of all parts involved for smooth operation/function of plantincluding greasing, cleaning, adjustment, minor repairs of nuts, bolts, washers etc of centrifugal fire fighting & jockey pump sets etc with other related equipments of the pump house/ installations alongwith valves including cleaning of inside and outside areas of the respective pump houses, , maintenance of suction and delivery pipe lines, primary fill up of priming tanks at Main pump house fire fighting installation consist of (i) 60 HP electric driven centrifugal pump set- 01 No complete all as specified and directed.
2All as per item No 1 here-in-beforebut locationDefi Tech Bldg fire fighting installation consist of (i) 2850 LPM, 70 m head electric driven centrifugal pump set- 02 Nos (ii) 900 LPM, 30 m head electric driven booster pump centrifugal type- 01 Nos (iii) 2850 LPM, 70 m head IC Engine driven centrifugal pump set- 01 No (iv) 2850 LPM, 70 m head jockey pump set - 01 No complete all as specified and as directed.
3All as per item No 1 here-in-beforebut location, New pump house fire fighting installation consist of (i) 100 HP electric driven centrifugal pump set- 03 Nos (ii) 82.5 BHP IC Engine driven centrifugal pump set- 01 No (iii) 25 HP jockey pump set - 0 No (iv) 20 HP jockey pump set - 01 No complete all as specified and as directed.
4All as per item No 1 here-in-beforebut location,MAP Phase I pump house fire fighting installation consist of (i) 75 HP electric driven centrifugal pump set- 01 No (ii) 92 BHP IC Engine driven centrifugal pump set- 01 No (iii) 20 HP jockey pump set - 01 No complete all as specified and as directed.
5All as per item No 1 here-in-beforebut location,MAP PH-II Fire fighting(i) main nhydrant pump 37 KW-01 No (ii) Jockey pump 9.3KW-1 No ,(iii)IC Engine driven centrifugal pump set- 01 No complete all as specified and as directed.
6Material and labour for thefollowing items for maintanance of IC Engine pump set :-
7Greaves lub oil ,10 Ltr
8Lubrication oil filter and element
9Filter element with O ring
10Fuel insrt with o ring
11Fuel Off sol,12V DC with fine
12Coolant additive
13Battery cable 2 PC set
14Oil pressure switch
15Tempreture switch
16Supply, installation and testing of battery charger suitable for 150 AH battery complete all as specified and as directed.
17Supply, installation and testing of 12 V DC battery 150AH complete all as specified and as directed.
18Excavation in trenches n.exc 1.5 mtr wide and n.exc1.5 mtr in depth for foundation etc or for shaft, wells, man holes, pier holes etc. getting out soft/loose/soil. complete all as specified and as directed.
19Returning, filling in, including spreading levelling, watering and well ramming in layers not exc. 25 cm complete all as specified and as directed.
20Removing excavated material n.exc 50 mtr and depositing where directed at a level n.exc, 1.5 mtr above the starting point complete all as specified and as directed.
21Taking up unserviceable MS Pipeboth end flanged 150 mm dia from trencehes/floor/wall including all fittings. complete all as specified and as directed.
22Taking up unserviceable MS Pipeboth end flanged 100 mm dia from trencehes /floor/wall including all fittings. complete all as specified and as directed.
23Taking up unserviceable MS Pipeboth end flanged 80 mm dia from trencehes /floor/wall including all fittings. complete all as specified and as directed.
24Supply and fixing of MS ERW pipes 150 mm diaFlanged type IS-1239 heavy grade laid in ground complete with all fittings, bends including necessary connectionscutting of existing pipe complete all as specified and as directed.
25Supply and fixing of MS ERW pipes 100 mm dia flange type IS-1239 heavy grade laid in ground complete with all fittings,bends including necessary connectionscutting of existing pipe complete all as specified and as directed.
26Supply and fixing of MS ERW pipes 80 mm dia flange type IS-1239 heavy grade laid in ground complete with all fittings,bends including necessary connectionscutting of existing pipe complete all as specified and as directed.
27Supply and fixing in repair of MS ERW pipes 25 mm dia IS-1239 heavy grade laid in ground complete with all fittings,bendsincluding necessary connectionscutting of existing pipe complete all as specified and as directed.
28Material and labour in repair for flanged joints of MS pipes 150 mm dia with rubber or fibre board gasket, bolts etc complete all as specified and directed.
29Material and labour in repair for flanged joints of MS pipes 100 mm dia with rubber or fibre board gasket, bolts etc complete all as specified and directed.
30Material and labour in repair for flanged joints of MS pipes 80 mm dia with rubber or fibre board gasket, bolts etc complete all as specified and as directed.
31Material and labour in repair for MS clamp for fixing 150 mm dia riser line including drilling hole to the wall and fixing nut bolt,washer,gasket etc. complete all as specified and as directed.
32Supply and fixingin repair MS bend 150 mm dia,flange type with holes,gasket,nut bolts etc
33Supply and fixing in repairMS bend 100 mm dia,flange type with holes,gasket,nut bolts etc complete all as specified and as directed.
34Supply and fixing in repair MS bend 80 mm dia,flange type with holes,gasket,nut bolts etc complete all as specified and as directed.
35Taking down Centrifugal pump set from existing position for carrying out for repair worksat work shop andre-assembling, re-installing the pump set in original position for pump capacity 75 HP. complete all as specified and as directed. Note: Spare parts,winding wire required for renewal shall be measured and paid separately.
36All as item No 26 here-in-beforebut for fire fighting pump capacity 20HP. complete all as specified and as directed.
37Dismantling and opening the motor from pump set in existing position for carrying out rewinding work with new super enamelled copper wire of suitable gauge as per existing and heat varnishing complete with all other material required for rewinding by carrying the motor to outside the cantonment area, re-assembling and refixing the same with pump in original position for the following capacity of motor :-
38(a) 75 HP 3 Phase .
39(b) 20 HP 3 phase .
40Supply and fixing of following spare parts for pump set including motor complete for 20 HP centrifugal pump:-
41(a) Impeller CI
42(b) Pump shaft
43(c) Neck ring
44(d) Shaft Sleeve
45(e) Bearings No 6305/6306/6309 as per site Make : SKF or equivalent
46Supply and fixing of following spare parts for pump set including motor complete for 75 HP centrifugal pump:-
47(a) Impeller CI
48(b) Pump shaft
49(c) Neck ring
50(d) Shaft Sleeve
51(e) Bearings No 6305/6306/6309 as per site Make : SKF or equivalent
52Supply and fixing in repair Gun-metal, globe or gate valves, 20 mm dia size with iron wheel head, screwed both ends for iron pipe and fixed complete all as specified and as directed.
53Supply and fixing in repair stainless steel 63 mm steel fire hydrant valve conforming to IS-908 single headed with double locked adapter with iron wheel including gasket,nut&bolts etc. for fixing in high rise building complete all as specified and as directed.
54Supply and fixing in repair stainless steel 63 mm steel fire hydrant valve double headed conforming to IS-908with double locked adapter with iron wheel including gasket,nut&bolts etc. for fixing in stand post at the bottom of above buildings complete all as specified and as directed.
55Supply and fixing in repair MS blank flange having suitable Nos of holes and including all necessary jointing materials complete all as specified and as directed.
56Supply and fixing in repairRubber hose reel of 20 mm dia and 30 m long with MS make hose reel drum set with necessary accessories conforming to IS:884, like connector, adaptor and ss shut off nozzle complete all as specified and as directed.
57Supply and fixing in repairbranch pipe and stainless steel nozzle for 20 mm dia hose real conforming to IS 903 complete all as specified and as directed.
58Supply and fixing in repairvalve sluice flange type for fire fighting conforming to IS-14846 of class 1.6 PN complete of size 150 mm dia complete all as specified and as directed.
59Supply and fixing in repair valve sluice flange type for fire fighting conforming to IS-14846 of class 1.6 PN complete of size 80 mm dia complete all as specified and as directed.
60Supply and fixing in repair gate valve for fire fightingcomplete of size 25 mm dia complete all as specified and as directed.
61Material and labour in repair for painting hose box, MS pipes with two coats of synthetic enamel paint red in colour over a coat of red oxide primer after removing/scrubbing old painted / rusted surface complete all as specified and as directed.
62Supply and fixing in repair Branch pipe gun metal 63 mm and nozzle confirming to IS 903 with all jointing materials. complete all as specified and as directed.
63Supply and fixing in repair 63 mm dia and 15 m long RRL canvas hose conforming to IS 636 complete including male& female coupling. complete all as specified and as directed.
64Material and labour in repair for CI fitting such as Tee, bend, taper, Tail pieces and type upto 150mm bore pipe complete all as specified and as directed.
65Supply and fixing in repair Foot Valve/Strainer CI conforming to IS 4038,complete of size 150 mm dia complete all as specified and as directed.
66Supply and fixing in repair Foot Valve/Strainer CI conforming to IS 4038,complete of size 80 mm dia complete all as specified and as directed.
67Supply and fixing in repair double flanged single door type swing check reflux (Non return) with by pass arrangement valve in repair confonning to IS-5312 of size 150 mm including necessary flange , nut bolts washer and gasket etc. complete all as specified and as directed.
68Supply and fixing in repair double flanged single door type swing check reflux (Non return) with by pass arrangement valve in repair confonning to IS-5312 of size 100 mm including necessary flange , nut bolts washer and gasket etc.complete all as specified and as directed.
69Supply and fixing in repair double flanged single door type swing check reflux (Non return) with by pass arrangement valve in repair confonning to IS-5312 of size 80 mm including necessary flange , nut bolts washer and gasket etc. complete all as specified and as directed.
70Supply and fixing in repair Butterfly Valve, of size 150mm dia conforming to IS 13095, flanged ends,drilled type with steel spindle including nuts, bolts, washers and jointing materials complete all as specified and as directed.
71Supply and fixing in repair Butterfly Valve, of size 100mm dia conforming to IS 13095, flanged ends,drilled type with steel spindle including nuts, bolts, washers and jointing materials complete all as specified and as directed.
72Supply and fixing in repair Butterfly Valve, of size 80mm dia conforming to IS 13095, flanged ends,drilled type with steel spindle including nuts, bolts, washers and jointing materials complete all as specified and as directed.
73Supply and fixing in repair for fire fighting hose box made of 18 gauge MS sheet 800 mm x 600 mm x 250 mm with double door with 4 mm thick glasses and door frame made of 16 mm gauge MS sheet painted fire red out side and brilliant white inside yardincluding dismantking of unserviceable hose box complete all as specified and as directed.
74Supply and fixing in repair Gun metal four way Fire brigade inlet to hydrent ring with 63 mm dia instantaneous type inlet and 150 mm dia flanged outlet conforming to IS 904 with blank cap and chain complete all as specified and as directed.
75Supply and fixing of the following Items for Fire Fighting Alarm System complete all as specified and as directed.
76(i) Material and labourin repair for sounder and flasher EN-54 suitable for addressable fire panel complete all as specified and as directed. Make- Hochiki
77(ii)Supply and fixing in repair multi detectors with acc-en intelligent multi sensorComplying with and type certified to EN - 54all as specified and as directed. Make Hochiki/Honey well/Appolo
78(iii)Material and labour in repair of manual call point suitable for existing addressable fire alarm panel all as specified and directed. Make:- Hochiki/Honey well/Appolo
79(iv)Material and labour in repair for commissioninginstalling ,testing of network cardfor latitude panel-addressablefor connecting the existing repeater panel suitable for existing panel. complete all as specified and as directed. Make:- Hochiki/Honey well/Appolo
80(v)Supply, Installation Testing Commissioning Testing of Networkable Analogue Addressable Fire Alam Control Panel. The Panel Shall be compliant with EN54-4 and approved by LPCB. The Fire Alarm control Panel should have 4 loops & shall have expandable capacity to 8/ loops. The panel must have full colour 800 x 480 LCD with resistive touch screen and automatic backlight dimming. The panel must also have the capability to take addressable intelligent wire and wireless devices on same loop. Each loop shall have a capacity of 127 analogue addressable devices and 127 base sounders/Base sounder beacons. The panel shall have an event log of minimum 10,000 events @ 1 second resolution, Filterable and Printable. The panel shall have three access levels. Panel Shall support filterable and printable. The panel shall have three access levels, Panel shall support upto 500 cause & Effects entries, with upto 20,000 inputs controlling & 20,000 controlling outputs across the network. The panel shall have capability for peer to peer networking through Rs 485 network card. The panel must have 4 inbult programmable sounder circuits, each circuits rated at 2.5A . The panel must have inbuilt 3 programmable inputs and 5 inbuilt programmable relay outputs. The panel shall have up to sub-addressable 512 programmable inputs/outputs via optional Rs 485 COMMS serially connected expansion cards. The panel shall have 240V AC power supply alongwith suitable size capacity of battery with automatic Battery Charger. The panel shall be fully expandable via common plug in loop driver boards, The user shall have a choice of using the panel with 5.25 Amp o 10.25 Amp power supply unit which is inbult in the FACP and should be approved to EN54-4. The panel shall have configurable via USB port to PC or memory stick. The panel shall have dedicated Rs 232 serial port for optional printer. Approved by EN54. complete all as specified and as directed. Make HochikiModel No.Latitude 4 Loop EN54 or equivalent Honey well/Appolo
81Material and labour for fire fighting submain wiring with copper conductor from Ground floor to Top Floor forMCP/Hooter/Control Pannel Board(Control panel Board to Each MCP located at Each floor and hooter)includingappropriate size of PVC casing capping with all accessoriese such as tees, bends, elbows, reducers, bell mouth tube ends, couplers, lock nuts, saddles, pipe hooks etc. for surface/concealed wiring as per existing including 2x1.5 sq. mm + 1x1.5 sq. mm earth wire 1.5 sqmm PVC insulated copper cable 1100 Volts grade.including taking down unserviceable existing wiring. complete all as specified and as directed. Note : 3RM of copper cable and 1RM PVC casin capping shall be constituted as unit rate.
82Supply and fixing in repair sheet glass ordinary quality with 4 mm thickness for fire cabinet box. complete all as specified and as directed.
83Supply and fixing in repair CI screwed end single Air valve size 20 mm diaas per IS:14845, PN-1.6,complete all as specified and as directed.
84Supply and fixing in repair Sprinkler glass bulb type (Standard response) as per S:15106/TAC guidelines 68 degree temperature rating pendent type complete all as specified and as directed.
85Material and labour in repair Rotational moulded polyethylene water storage tanks 2000 ltrs (cylindrical vertical with closed top) hoisted and fixed in position and tapping both tank by 80mm pipe. complete all as specified and as directed.
86Material and Labour for valve pit of size 100cmx100mmx100 cm , PCC (1:2:4) type B0 (using 12.5mm graded stone aggregate )15 cm thickness,with 35x35 mm size angle section for fixing of covered plate5 mm thickness steel ,all as necessary for fixing of butter fly /sluice valve of size 150 mm /100 mm size complete all as specified and directed.
87Material and labour for earthing complete with galvanized steel earth plate electrode 600mmx600mmx6mm thick burried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of earth plate not less than 1.5m below normal ground level connected with galvanized iron earth strip 32 x 6 mm by means of bolts, nuts, check nuts and washers of galvanized iron or steel complete with 40mm dia GI light grade protection pipe, 20mm dia GI medium grade watering pipe with funnel including charcoal, dust, salt, PCC M-15 type B1 in pit with angle iron (25x25x3)mm frame work with precast RCC (1:2:4) type B-1 (using 20mm graded stone aggregate) cover reinforced with 8mm dia TMT bars @ 150mm C/C both ways and 12mm dia MS fabricated handle, test point etc. in and including light grade GI protection pipe 40mm bore up to 5m length for drawing in earth lead wire, all as shown in electric plate No. 3 of SSR Part-I complete with necessary earth work in any type of soil, removal of soils to a distance not exc. 50m and testing on completion. complete all as specified and as directed.
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail