}

Repairs And Maint To Internal Wiring, Dg Set And Rewinding Of Ceiling Fans, Air Circulators, Wall Mounting Fans, Geysers, Refrigerators And Acs At Pcda Office Bldg Sec-9A And Dad Residential Colony Sec- 35B Under Ge Chandigarh, chandigarh-Chandigarh

Military Engineer Services-MES has published Repairs And Maint To Internal Wiring, Dg Set And Rewinding Of Ceiling Fans, Air Circulators, Wall Mounting Fans, Geysers, Refrigerators And Acs At Pcda Office Bldg Sec-9A And Dad Residential Colony Sec- 35B Under Ge Chandigarh. Submission Date for this Tender is 29-08-2022. Electrification Work Tenders in chandigarh Chandigarh. Bidders can get complete Tender details and download the document.




Tender Notice

33462793
Corrigendum : Repairs And Maint To Internal Wiring, Dg Set And Rewinding Of Ceiling Fans, Air Circulators, Wall Mounting Fans, Geysers, Refrigerators And Acs At Pcda Office Bldg Sec-9A And Dad Residential Colony Sec- 35B Under Ge Chandigarh
Open Tender
Indian
Chandigarh
chandigarh
29-08-2022

Tender Details

Repairs And Maint To Internal Wiring, Dg Set And Rewinding Of Ceiling Fans, Air Circulators, Wall Mounting Fans, Geysers, Refrigerators And Acs At Pcda Office Bldg Sec-9A And Dad Residential Colony Sec- 35B Under Ge Chandigarh

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 22-Aug-2022 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 29-08-2022

Key Value

Document Fees
INR 500 /-
EMD
INR 80000.0 /-
Tender Value
INR 40 Lakhs /-

BOQ Items

Name of Work :REPAIRS AND MAINT TO INTERNAL WIRING, DG SET AND REWINDING OF CEILING FANS, AIR CIRCULATORS, WALL MOUNTING FANS, GEYSERS, REFRIGERATORS AND ACS AT PCDA OFFICE BLDG SEC-9A AND DAD RESIDENTIAL COLONY SEC- 35B UNDER GE CHANDIGARH
Sl. No. Item Description
1Taking down carefully aluminum/copper point wiring (light, fan, socket or power) complete along with fittings such as switches, ceiling roses, pendants, regulators sockets etc, and removing from site and making good disturbed surfaces of walls, floors etc all as directed by Engineer in Charge.
2Taking down existing unserviceable MCB DB along with MCBS completeby disconnecting all as directedby Engineer in Charge.
3Taking down existing unserviceable T/Light fitting any type & Capacity
4Taking down existing unserviceable sub main wiring with upto 2/3 core 1.5 to 6Sqmm aluminum/Copper cable all as directed by Engineer in Charge.
5M&L Point wiring with 1.5 sq mmcopper conductor FRLS(multistrand) PVC insulatedISI marked unseathed cable in and including concealed , non metalic rigid PVC conduit medium grade ISI marked, conduit not less than 19 mm with all fittings& other accessories and also includingPVC insulated ISI marked unseathed FRLS cable of size 1.5 sq mm copper conductor as earth wire to common earth dolly including concealed in wall,mild steel Box, 1.6mm thick with 3mm thick plastic laminated sheet as required at site suitable for modular switches, sockets, fan regulatoretc for One light point controlled by one way switch complete all as specified. Note : cable Colour should beas per IS code.
6All as per item No 5 above but One ceiling /exhaust fan point controlled by one, one way 5 Amps switch
7All as per item No 5 above but One 3 pin socket outlet 5 Amps on independent board
8All as per item No 5 above but One 3 pin socket outlet 5 Amps on same board
9All as per item No 5 above but One light point controled by two, two way 5 Amps switches.
10All as per item No 5 above but One bell/ buzzer point controled by one bell push on same board with other switches or on independent board.
11M&L for Point wiring complete with 2.5 Sqmm single core, PVC insulated unsheathed, FRLS cable, 1100 volts grade, multistranded copper conductor, drawn through and including rigid non metallic PVC conduit and conduit accessories fixed on surface of wall/ceilings or concealed etc., including provision of PVC insulated 2.5 Sqmm FRLS cable with copper conductor for earth continuity and connected to common earth dolly and metal boxes concealed in wall , modular cover plates with frames on top for housing the switches, socket outlet etc., all as specified and as directed for one switch socket outlet 16 Amps on independent board.
12M&L for Sub main wiring/power wiring complete with two runs of 4.0 Sqmm, single core, PVC insulated, unsheathed FRLS cable, 1100 Volts grade, multistranded with copper conductor, drawn through and including suitable size ofrigid non metallic PVC conduit pipe and accessories on surface wall/floors/concealed etc., with one run of PVC insulated, 4.0Sqmm FRLS copper conductor for earth continuity all as specified and as directed.NOTE :- Tworuns of main copper conductor, one run of copper conductor for earth continuity and one run of conduit shall be measured as one unit length & cable Colour should be as per IS code.
13All as per item No 12 here in above but with 2x6 Sqmm for phase and neutral and 1x6 Sqmm for earth wire complete. Make : Polycab / Finolex / havells/Palaza.
14M&L for 3x1.5 Sqmm PVC insulated, unsheathed FRLS cable, 1100 Volts grade, multistranded with copper conductor drawn in the existing metal/ PVC conduit & Casing cappingincluding connecting of the ends into the switch / socket/ DB complete all as specified and as directed.Note : Three runs of cable measured as one unit.
15All as per Item No 14 here in above but size 3x2.5 Sqmm.
16All as per Item No 14 here in above but size 3x4 Sqmm.
17All as per Item No 14 here in above but size 3x6 Sqmm.Note for Sl No 14 to 17 : Make of PVC cables : inolex/Polycab,Havells,Make of PVC Conduit : Mecury/Sudhaker/Avon Plast
18Supply and fixing switch piano flush type single pole one way 5 amps 230 volts complete all as specified and as directed.Make:- Anchor/SSK/Legrand/Indoasian
19Supply and fixingsocket piano flush type universal 2 in 1,3 pin 5 Amps, 230 volts complete all as specified and as directed.Make :- Anchor/SSK/Legrand/Indoasian
20Supply and fixing switch piano flush type single pole one way 15 amps 230 volts complete all as specified and as directed. Make:- Anchor/SSK/Legrand/Indoasian
21Supply and fixingsocket flush type universal 2 in 1, 3 pin 5 &15 Amps, 230 volts complete all as specified and as directed.Make :- Anchor/SSK/Legrand/Indoasian
22Supply and Fixing Ceiling rose 3 terminal 5 Amps 230 volts PVC/Polycarbonate, insulated body complete all as specified and as directed.Make : Anchor/SSK/Legrand/Indoasian
23Supply and Fixing step type electronic fan regulator of capacity 100 watts 230 volts for ceiling / exhaust fan flush type all as specified and as directed. .Make :- Anchor/SSK/Legrand/Indoasian
24Supply and FixingDing Dong Bell AC. 230 volts complete all as specified and as directed. Make :- Anchor/SSK/Legrand/Indoasian
25Supply & Fixing 6 Amps 1 way one module switch complete all as specified and as directed. Make :- Anchor/SSK/Legrand/Indoasian
26Supply & Fixing 6 Amps 2 way one module switch complete all as specified and as directed. Make :- Anchor/SSK/Legrand/Indoasian
27Supply & Fixing 16 Amps one way one module switch complete all as specified and as directed. Make:- Anchor/SSK/Legrand/Indoasian
28Supply & Fixing 6 Amps bell push one module switch complete all as specified and as directede. Make :- Anchor/SSK/Legrand/Indoasian
29Supply & Fixing 6 Amps 2/3 pin socket two module complete all as specified and as directed.Make :- Anchor/SSK/Legrand/Indoasian
30Supply & Fixing modular multi socket outlet 6A/16 Amps 2/3 Pin socket 2 module complete all as specified and as directed.Make :- Anchor/SSK/Legrand/Indoasian
31S&F PVC casing caping of size 20mm including cut to shape and size to match the existing conduits suitable for LT electric supply along with necessary fixing arrangements including disconnection and removing the unserviceable PVC casing caping complete.
32All as per Item No 31 here in above but of size 25mm
33S&F MCB DB, SPN, 6 way with 200 Amps rated copper bus bar with mild steel sheet enclosure, vertical, double door type suitable for fixing MCBs including connecting etc., complete all as specified and as directed.
34S&F MCB DB, SPN, 8 way with 200 Amps rated copper bus bar with mild steel sheet enclosure, vertical, double door type suitable for fixing MCBs including connecting etc., complete all as specified and as directed.
35S&F MCB DB, SPN, 12 way with 200 Amps rated copper bus bar with mild steel sheet enclosure, vertical, double door type suitable for fixing MCBs including connecting etc., complete all as specified and as directed.
36S&F MCB DB, TPN, 4 way with 200 Amps rated copper bus bar with mild steel sheet enclosure, vertical, double door type suitable for fixing MCBs including connecting etc. complete all as specified and as directed.
37S&F MCB DB, TPN, 8 way with 200 Amps rated copper bus bar with mild steel sheet enclosure, vertical, double door type suitable for fixing MCBs including connecting etc. complete all as specified and as directed.
38S&F MCB DB, TPN, 12 way with 200 Amps rated copper bus bar with mild steel sheet enclosure, vertical, double door type suitable for fixing MCBs including connecting etc. complete all as specified and as directed.
39S&F MCB SP 6-32 Amps 230 volts 10 KA ISI marked completeall as specified and directed by Engg-in-Charge.
40All as per Item No 39 here in above but of capacity MCBSPN 40 Amps
41All as per Item No 39 here in above but of capacity MCBSPN 63 Amps
42All as per Item No 39 here in above but of capacity MCBDP 63 Amps
43All as per Item No 39 here in above but of capacity MCBTPN 40 Amps
44All as per Item No 39 here in above but of capacity MCBTPN 63 Amps
45S&F Single pole and neutral enclosure with a two pin earth plug and socket complete controlled by one single pole MCB 20 Amps 240 Volts, including taking outunserviceable MCB plug and socket unitcomplete all as specified and as directed.Note for Item No 33 to 45 : Make : IndoAsian/Siemens/ Scheneider/Legrand
46S&F in repair batten forLED tube light 1X18/20 watts LED, 230Volt energy efficient, industrial batton type, powder coated, CRC Sheet complete with all as accessories internally pre wired and including connecting up with three core twisted flexible copper conductor cable with suitable size Complete all as specified and as directed. MAKE:Philips/Wipro/C&S/Crompton
47Supply and fixing in repair LED tube rod 1X18/20 watts (retrofit LED tube) energy saving, recess / surface mounted luminaire suitable for fix in the batten fitting 1x18W to 20W, complete all as specified and directed by Engineer in Charge.
48S&F as in repair batten for LED tube light 1X9/10/12 watts LED, 230Volt energy efficient, industrial batton type, powder coated, CRC Sheet complete with all as accessories internally pre wired and including connecting up with twin core twisted flexible copper conductor cable with suitable size Complete all as specified and as directed. Make : Philips/Wipro/C&S/Crompton
49Supply and fixing in repair LED tube rod 1X9/10/12 watts (retrofit LED tube) energy saving, recess / surface mounted luminaire suitable for fix in the batten fitting 1x9/10W, complete all as specified and directed by Engineer in Charge. MAKE: Crompton/Havells/Philips
50Disconnection and removing the u/s light fitting from the false ceiling carefully and S&F LED (2X2) indirect light fitting circular shape 36 Watts 230 volts with internally pre-wired and including connecting up with three core twisted flexible copper conductor cable with suitable size compelte all as specified and directed. MAKE :- Philips/Wipro/C&S/Crompton
51Disconnection and removing the u/s light fitting from the Surface mountend ceiling carefully and S&F LED (2X2) indirect light fitting circular shape 36Watts, 230 volts with internally pre-wired and including connecting up with three core twisted flexible copper conductor cable with suitable size compelte all as specified and directed.
52Supply and fixing in repairSurface mounted LED (1X4)Panel indirect light fitting 40Watts, 230 voltswith internally pre-wired and including connecting up with three core twisted flexible copper conductor cable with suitable size compelte all as specified and directed. MAKE :- C&S/Crompton/Philips
53S&F Ceiling mounted Slim design LED recessed round Downlight with Superior light output and internal driver 18 Watts 230 volts with internally pre-wired and including connecting up with two core twisted flexible copper conductor cable with suitable size compelte all as specified and directed. MAKE :- Philips/Wipro/C&S/Crompton
54Supply and fixing in repair Ceiling mounted Slim design LED recessed Square Downlight with Superior light output and internal driver 18 Watts 230 voltswith internally pre-wired and including connecting up with two core twisted flexible copper conductor cable with suitable size compelte all as specified and directed. MAKE :- Philips/Wipro/C&S/Crompton
55Supply and fixing in repair FloodSlim LED light output and internal driver 150 Watts, 230 voltswith internally pre-wired and including connecting up with two core twisted flexible copper conductor cable with suitable size compelte all as specified and directed. MAKE :- Philips/Wipro/C&S/Crompton
56Supply and Fixing lamp holder, angular type, PVC/ polycarbonate with back plate of capacity 5 Amps 230 volts suitabel for general lighting system complete all as specified and as directed. Make : Anchor/Cona/Leader/Bajaj
57S&F LED lamp/T lamp 9/10 watts complete all as specified and as directed. MAKE : Philips/Wipro/Halonex/Crompton
58Supply and fix in repair MCCB 3 pole 125 Amps 25 KAcomplete with and including suitable size ofMS box with locking arrangementflushed in wall complete all as specified and as directed.
59All as per Item No 58 here in above but of capacity MCCB 160Amp, 25KA
60All as per Item No 58 here in above but of capacity MCCB 250Amp, 35KA
61Supply and fix in repair MCCB 4 pole 200 Amps 35 KAcomplete with and including suitable size ofMS box with locking arrangementflushed in wall complete all as specified and as directed.
62All as per Item No 61 here in above but of capacity MCCB 250Amp, 35KA
63All as per Item No 61 here in above but of capacity MCCB 125Amp, 35KA
64M&L for earthing with GI earth plate electrode 60cm x 60cm x 6.0 mm thick burried directly in ground vertically to depth of not less than 2.25 mtr deep below normal ground level with top edge of the plate not less than 1.5 mtr below ground level connected to GI earth wire of 4.0 mm dia by means of bolts, nuts, washers of GI and provision of earth lead, GI protection pipe with 15mm light grade galvanized including necessary earth work in any type of soil, PCC 1:3:6type CI (using 20mm graded stone aggregate) earth chamber and 1:2:4 type B1 RCC cover fitted with50mm thick with 6mm dia MS bars complete all as shown in SSR Pt - 1 electrical plate No 3. Note : Qoted rate deemed to include the cost or excavation and earth work PCC Chamber, funnel cover etc. complete all as specified and directed by Engg-In-Charge
65Supply and fix in repair decorative Post top LED 40Watt for 360* indirect light with IP 65 protection230 voltswith internally pre-wired and including connecting up with two core twisted flexible copper conductor cable with suitable size compelte all as specified and directed.
66Taking down ceiling fans of 1200 to 1400mm sweep and make after disconnecting from ceiling rose, opening up, including greasing and overhauling after replacing unserviceable spairs like bearings, bushes, capacitors, ms clamp,rubeer reels with nut, bolt split pin, andshaft, sleeves, rewinding, testing, rehanging and making connection to ceiling rose Completeall as specified and as directed by Engineer-in-charge.Note: (i)Spares for replacement shall be measured and paid for seprately as supply only under respective items of BOQ. (ii)Technician of contractor shall visit door to door and attend complaintsin respective bldg in Md Accn and obtain thre signatures of user after satisfactory complition of work
67Taking down exhaust fans of any sweep and make after disconnecting, opening up, including greasing and overhauling after replacing unserviceable spairs like bearings, bushes, capacitors, ms clamp, nut, bolt and split pin, andshaft. sleeves, rewinding, testing, refixing andmaking connection to ceiling rose Completeall as specified and as directed by Engineer-in-charge. Note: (i)Spares for replacement shall be measured and paid for seprately as supply only under respective items of BOQ. (ii)Technician of contractor shall visit door to door and attend complaintsin respective bldg in Md Accn and obtain thre signatures of user after satisfactory complition of work
68Taking down Wall mounted/Pedestal fans of Sweep 300 to 450mm, 230 volts of any make & size after disconnecting, opening up, including greasing and overhauling after replacing unserviceable spairs like bearings, bushes, capacitors, ms clamp, nut, bolt and split pin, andshaft. sleeves, rewinding, testing, refixing andmaking connection Completeall as specified and as directed by Engineer-in-charge. Note: (i)Spares for replacement shall be measured and paid for seprately as supply only under respective items of BOQ. (ii)Technician of contractor shall visit door to door and attend complaintsin respective bldg in Md Accn and obtain thre signatures of user after satisfactory complition of work
69M&L replacement to unserviceable capacitor2.5/3.15 mfd in lieu of provided with new capacitor oil type 2.5/3.15 mfd suitable for 240 volt AC Completeall as specified and as directed by Engineer-in-charge.Make :-DENFOS/ INDOFOS /EPCOS/HAVELLS
70All as item No 69 here in above but of Capacity 4.15 MFD, AC 250 volts
71M&L rewinding toceiling fan motor of1200 to 1400mm sweep windedwith winding machinewith super enameled copper winding wire of existing size includinginsulated sleeves& paper , varnishing with ‘B’ class insulation varnish thimbles, connection with flexible cableof copper conductor cable of size 23/.0076upto connector block ( winding wireexc 350 gm and n-exc 750gm ) Completeall as specified and as directed by Engineer-in-charge.Note:--(i) The cost of cutting & taking out to existing old winding wire shall be deemed tobe included in the unit rate of this item. Nothing extra shall beentertained on this account
72All as item No 71 here in above but for Exhaust fan 225 to 300mm sweep.
73All as item No 71 here in above but for Exhaust fan 350 t0 450mm sweep.
74All as item No 71 here in above but for Pedestal / Wall mounted fan upto 450mm sweep.
75Supply only Ball bearing suitable for celing fans of any sweep.
76Supply only gun metal bushsuitable for celing fans of any sweep.
77Supply only Mild steel shaft suitable for celing fans of any sweep.
78Supply only ball bearing suitable for 225/300/350/450 mm sweepexhaust / pedestal/ wall mountin fan
79Supply only gun metal bushsuitable for 225/300/350/450 mm sweep exhaust / pedestal/ wall mountin
80Supply only mild steel shaft suitable for 225/300/350/450 mm sweep exhaust / pedestal/ wall mounting fan
81M&L for replacement to unserviceable rubber reelswith new suitable for any sweep ceiling fan completeall as specified and as directed by Engineer-in-charge.
82M&L for replacement to unserviceable rusted MS rod up to 3 feetincluding clamp, nut, bolt, washer & split pin suitable for any sweep ceiling fan Completeall as specified and as directed by Engineer-in-charge.
83M&L for replacement to unserviceable PVC canopysuitable for any sweep ceiling fancompleteall as specified and as directed by Engineer-in-charge.
84M&L for replacement to unserviceable fan blades (set of three blades) suitable for 1200/1400/1500mm sweep ceiling fans complete all as specified and as directed by Engineer-in-charge.
85Preparation surfaces, cleaning thoroughly with kerosene oilceiling fans 1200mm/1400mm/1500mm sweep to remove only dust and any type of spots and painted withsynthetic enamelpaint of existing colour with help ofspray gunmachine, including writing MES No, complete all as specified and as directed by Engineer-in-charge.
86M&Llathe work for taking out bush from the lower body part of ceiling/Exhaust fan and replacing it with suitable size of ball bearingas per matching size to shaft making necessary bearing boring, cutting, greasing, polishing of shaft completeall as specified and as directed by Engineer-in-charge.Note : - Supply & fixing to Bearing shall be measured and paidseparately under respective item of this Schedule.
87Disconnecting & taking down unserviceable geyser of 25/50 litre capacity of any make from the wall and opening carefully including descaling the inner surface by scrapping, carrying out soldering/ brazing/gaswelding to prevent the leakage, filling of glass wool & replacement of any other defective spares ,including replacement of required number ofstainless steel screws, nuts & bolts,assembling the the same after repair work and fixing inits orginal place, connecting to water mains and electric supply, testing after repairs, complete all as specified andas directed by Engineer-in-charge. Note :spare parts and glass wool shall be measured and paidsepartaly under respective items of BOQ.
88Replacement of unserviceable Geyser thermostat switch any type/size with new thermostat switch ISI marked of range 0-100 degree centigrade, adjustable between 70 to 100 degree centigrade with necessary washer, screws nut etccomplete and all as specified
89Supply only glass wool of good quality as approved for 25 litre capacity of geyser complete all as specified and as directed by Engineer-in-Charge.
90All as per above item No 89 here-in-before but 50 litre capacity.
91S&F replacement of unserviceable Stain lesssteel inner tank of 25 liter capacity geysers of existing make & model including testing after assembling & fixed at site complete all as specified and as directed by Engineer-in-Charge.
92All as per above item No 91 here-in-before but 50 ltr capacity.
93Replacement of unserviceable heating element with new heating elements screw/or stud type ISI marked 2000 watt 230 volts AC single phase including necessary washer, screw, nuts bolts etc complete and all as specified.
94All as per above item No 93 here-in-before but 1500 watt.
95Replacement of unserviceable Safety valve
96Replacement of unserviceable indicator lamp assy with new indicator lamp assy 230 volts square or round suitable for any type or make of Geyser including connecting complete and all as specified
97Replacement of unserviceable 23 to 30 cm long ,10 mm boreC.P Connection with brass union
98Replacement of unserviceable Gun metal non return valve ,15 mm bore
99Replacement of unserviceable 45 cm long , 15mm bore PVC connection pipe with brass union both ends for hot and cold water fixed to GI Pipe complete and all as specified
100Replacement of unserviceable Apparatus plate for Syphon Assy for 25 litre
101Replacement of unserviceable Apparatus plate for Syphon Assy 50 litre
102Replacement of bottom/top plates made out of MS sheet of 1mm thick made to shape of required size factory made complete fitted with machining screws duly painted with synthetic enamelled white paint complete and all as specified.
103Replacement of 3-Pin plug top, 16 Amp, 230volt AC
104Replacement of Rubber "O" ring /gasket for 25 ltrs
105M&L for preparation of surface of geyser of 25 ltrs capacity of any make by scrapping to existing paint, filling cavities with filler (Putty) after cleaning of dust etc and applyingsynthetic enamel paint over a coat of red oxide primer with spray gun and writing the MES No with black paint complete all as specified and as directed by Engineer-in-Charge.
106M&L for preparation of surface of geyser of 50 ltrs capacity of any make by scrapping to existing paint, filling cavities with filler (Putty) after cleaning of dust etc and applying synthetic enamel paint over a coat of red oxide primer with spray gun and writing the MES No with black paint complete all as specified and as directed by Engineer-in-Charge.
107S&F replacement of unserviceable cable with flexible PVC insulatedcopper conductor cable 3 core of size 40/0.0076for Geysersof any capacitycomplete all as specified and as directed by Engineer-in-Charge .Make :POLYCAB/ FINOLEX / HAVELLS
108Cutting chasing inbrick walls for GI tubing 15/20mm bore including making good with cement mortar 1:3, cutting not exceeding 10cm girth complete all as specified and directed by Engineer-in-charge
109S&F sheet metal enclosure with single pole and neutral with two pin and earth plug socket including 20Amp 240 Volt includingMCB SP,20Amp(C-series) as in repair complete all as specified and as directed by Engineer-in-Charge. Make : Standard/Havells/Anchor.
110S&F for 15mm bore stop valve cast copper alloy chromium plated fancy type, high pressure with crutch or butterfly handle screwed both ends for iron pipe or union and fixed as in repair complete all as specified and as directed by Engineer-in-Charge.Make :Leader/Prayag
111S&F for 20mm borestop valve cast copper alloy, high pressure with crutch or butterfly handle screwed both ends for iron pipe or union and fixed as in repair complete all as specified and as directed by Engineer-in-Charge.Make :LEADER/PRAYAG
112S & F for 15mm bore steel water tubingmedium grade, galvanised with all fittings and fixturefixed & concealed inwall/ceiling or laid in floors including taking out unserviceable pipe complete all as specified and directed by Engineer-in-charge.
113Disconnecting, opening and taking out unserviceable sealed compressor ofwater cooler of capacity 150/180 litres and replaced with new sealed compressor of existing capacity& model including soldering of liquid /gas pipe ,cleaning the system arresting the leakage etccomplete all as specified and as directed by Engineer-in-charge. Make : SRI-RAM/ TAKAM SHAH/ KIRLOSKER.
114All as per above item No 113 hereinbefore butwater cooler of capacity 40/80 litres.Note for item No 113 & 114: (i) Contractor shall be produced original purchase voucher of original manufacturer /authorized dealer and test certificate shall be of original manufacturer to the department along with payment of RAR/Final bill.(ii) Recharging of refrigerant gas shall be measured &paid separately underrespective item of BOQ.
115Cleaning the system with CTC and charging the refrigerant gas R-22/134 including replacing strainer and rectification of leakage ofthe system from water cooler of150 litres capacity complete all as specified and as directed by Engineer-in-charge.
116All as per above item No 115 here-in-before butwater cooler of capacity 40/80 litres
117S&F forinternal wiring forwater coolers 150/80/40 ltr capacity with PVC insulatedunsheathed flexible copper conductor cablesingle core size 40/0.0076fixed with terminal clips etc including replacement of screws, washers etc required for fastening tobody etc complete all as specified and as directed by Engineer-in-charge. Make :- HAVELLS/ POLYCAB/FINOLEX
118S&F replacement of unserviceable starting relay assemblywith new starting relay assembly suitable forwater cooler of 150 litre capacity as per exisitng makeComplete all as specified and as directed by Engineer-in-Charge
119All as per above item No 118 hereinbefore butwater cooler of capacity 40/80 liter
120S&F replacement of unserviceable over load protector with new over load protector suitable forwater cooler of 150 litre capacity as per exisitng makeComplete all as specified and as directed by Engineer-in-Charge.
121All as per above item No 120 hereinbefore butwater cooler of capacity 40/80 litre
122S&F replacement of unserviceable fan motor with new fan motor suitable for water cooler of 150 litre capacity as per exisitng make Complete all as specified and as directed by Engineer-in-Charge. Make :-- COOL-HOME/ AUE
123All as per above item No 122 hereinbefore butwater cooler of capacity 40/80 liter
124Replacement to unserviceable Condenser unit with new condenser unit of existing make and model suitable for water cooler of capacity 150/180 liters, complate all as specified and as directed.
125All as per above item No 124 here in before but water cooler of capacity 40/80Liters.
126M&L 15 mm bore self closing tap push typecast copper alloy chromium plated fixed to water cooler as in repair Complete all as specified and as directed by Engineer-in-Charge.
127M&L cleaning to water coolers upto 150 ltrs capacity internal & external surfaces of suitable repairs tobody & stop leakage etc, replacing unserviceable nut bolts & washers etc including preparation of external surfaces andbottom bodyandpainted withanticorrosive synthetic enamel paint withhelp of spray gunmachine and writing SM / MES No in 5cm height Complete all as specified and as directed by Engineer-in-Charge.
128All as per above item No 127 here-in-before butwater cooler of capacity 40/80 liter
129S&F replacement of unserviceablethermo-state switch with new thermo-state switch suitable for water cooleranycapacity as per exisitng make Complete all as specified and as directed by Engineer-in-Charge.
130Disconnecting & opening refrigerator of capacity 180/210/320 litre and taking out unserviceable sealed compressor and replacing with new sealed compressor of existing capacity& model including soldering of liquid /gas pipe ,cleaning the system & the leakage etccomplete all as specified and as directed by Engineer-in-charge.Make :SRI-RAM/ TIKAMSHAH/ KIRLOSKER / WHIRLPOOL .
131Recharging of gas R-10/12/134A in refrigerant cap 180/210/320 litre complete including testing of leakage and testing the unit for satisfactory performance Complete all as specified and as directed by Engineer-in-Charge.
132Replacement offreezer door plastic with tension spring as per existing model suitable 160/210 litre cap.
133Replacement of Door liner ( Plastic ) for upto 310 liter capacity
134Replacement of Door magnetic gaskest for upto 310 litre cap.
135Replacement of Relay box type for any cap.
136S&F replacement of unserviceable over load protectorwith new over load protector suitable forrefrigerator 165 to 310 litre capacity as per existing makeComplete all as specified and as directed by Engineer-in-Charge.
137Disconnection and removing the unserviceable Split AC Outdoor & Indoor Unit/ window type of Capacity 1.5 to 4 Ton capacity from the existing position carefully for finding of the defects and to replace the unserviceable spare parts such as Compressor, Condensor fan mtor, condensor coil, suction & discharge valves, mother plates including carry out leak detection test, Gas charging, servicing such as cleaning and removing the dust particles accumulated in the unit and filters carefully and washing the cooling unit and Indoor unit with water and refixing the same in its original position complete including connecting up of the Copper Tubes and cable connections, testing and commissioning complete all as specified and as directed by Engineer in charge.(i) Cost of spares such as Compressor, Condensor Fan Motor, Condensor Coil, Suction & Discharge valves, mother plates, leak detection test, Gas charging shall be measured and paid separately under the respective Schedule.(ii) Makes & Specifications of the spare parts for replacement should be identical equivalent to the spares suitable for existing ACs.
138Supply only Outdoor hermatically sealed Compressor Unit of Capacity 1.5 TonSingle Phase for Split Type ACs complete all as specified and directed by Engineer in charge. Make : LG/Hitachi/Voltas/Blue Star
139Supply only indoor sealed Compressor Unit of Capacity 1.5 TonSingle Phase for window ACs complete all as specified and as directed. Make : LG/Hitachi/Voltas/Blue Star
140Supply only Outdoor hermatically sealed Compressor Unit of Capacity 2 TonSingle Phase for Split Type ACs complete all as specified and as directed. Make : LG/Hitachi/Voltas/Blue Star
141Supply only indoor sealed Compressor Unit of Capacity 2.0 TonSingle Phase for window ACs complete all as specified and as directed. Make : LG/Hitachi/Voltas/Blue Star
142Supply only sealed Compressor Unit of Capacity 4 TonSingle Phase for Standing Split Type ACs complete all as specified and as directed. Make : LG/Hitachi/Voltas/Blue Star
143Supply only Condensor Fan Motor 230 Volt suitable for 1.5 Ton Outdoor Split Type Air Conditioning Unit complete all as specified and as directed. Make : LG/Hitachi/Voltas/Blue Star
144Supply only Condensor Fan Motor 230 Volt suitable for 2 Ton Outdoor Split Type Air Conditioning Unit complete all as specified and as directed. Make : LG:/Hitachi/Voltas/Blue Star
145Supply only Fan Motor 230 Volt suitable for window type AC of 1.5 Ton capacity complete all as specified and as directed. Make : LG/Hitachi/Voltas/Blue Star
146Supply only Fan Motor 230 Volt suitable for window type AC of 2.0 Ton capacity complete all as specified and as directed. Make : LG/Hitachi/Voltas/Blue Star
147Supply only Fan Motor 230 Volt suitable for Standing Split type AC of 4.0 Ton capacity complete all as specified and as directed. Make : LG/Hitachi/Voltas/Blue Star
148Supply onlyblower motor suitable for Splittype AC of 1.5/2 Ton capacity complete all as specified and as directed. Make : LG/Hitachi/Voltas/Blue Star
149Supply onlyblower motor suitable for windowtype AC of 1.5/2 Ton capacity complete all as specified and as directed. Make : LG/Hitachi/Voltas/Blue Star
150Supply onlyblower motor suitable for Standing Split type AC of 4 Ton capacity complete all as specified and as directed. Make : LG/Hitachi/Voltas/Blue Star
151Supply only Condensor Coil Unit consisting of Copper tubing suitable for 1.5 Ton Outdoor Unit of Split Type Air Conditioning complete all as directed.
152Supply only Condensor Coil Unit made out of Copper tubing suitable for 2 Ton Outdoor Unit of Split Type Air Conditioning complete all as directed.
153Supply only Condensor Coil Unit consisting of Copper tubing suitable for 1.5 Ton Outdoor Unit of window Type Air Conditioning complete all as directed.
154Supply only Condensor Coil Unit consisting of Copper tubing suitable for 2 Ton Outdoor Unit of window Type Air Conditioning complete all as directed.
155Supply only Condensor Coil Unit made out of Copper tubing suitable for 4 Ton Outdoor Unit of Split Type Air Conditioning complete all as directed.
156Supply only PCB/ Mother Board Unit alongwith Remote Control Unitsuitable for 1.5/2/4 Ton Indoor Unit of Split Type Air Conditioning complete all as directed.
157Replacement of broken Fan Blade from the Outdoor units of Split AC Unit 1.5 / 2 /4 Ton Capacity and S&F New Fan Blade Unit complete suitable for existing AC Unit.
158Replacement of running/starting capacitors from the Outdoor units of Split Type AC Unit 1.5/2/4 Ton Capacity and S&F New Capacitors of capacity 36/46/50 MFD, 230 Volts, ISI Marked.
159Replacement of Display Unit for indicating Temperature, Temperature Sensorfor 1.5/2/4 Ton Split AC Unit complete all as directed. Make :- LG/Hitachi/Voltas
160Supply and Charge Refrigerant (R-22)/410a/407C Suitable for existing 1.5 Ton Capacity Split / Window type air conditioning unit complete all as directed.
161Supply and Charge Refrigerant (R-22)/410asuitable for existing 2 Ton Capacity Split / Window type air conditioning unit complete all as directed.
162Supply and Charge Refrigerant (R-22)/410asuitable for existing 4 Ton Capacity Standing Split type air conditioning unit complete all as directed.
163Replacement ofStandard Flexible PVC Drain Pipe of dia 25mm for capacity 1.5 ton, 2.0 ton & 4 Ton capacity complete all as directed.
164Disconnection and removing the old unserviceable Copper Pipe between Indoor & Outdoor Unit and S&F New Copper Pipe of 1/2" dia and connecting alongwith Insulation Sleeves to the existing position incl leak testing complete all as directed by Engineer in charge.
165All as per Item No 164 here in above but size 1/4" dia
166Supply and fix Suction Valvemade of Brass suitable for 1.5 Ton Outdoor Unit of Split Type Air Conditioning complete all as directed.
167Supply and fix Suction Valvemade of Brass suitable for 2 Ton Outdoor Unit of Split Type Air Conditioning complete all as directed.
168Supply and fix Suction Valvemade of Brass suitable for 4 Ton Outdoor Unit of Standing Split Type Air Conditioning complete all as directed.
169Supply and fix Discharge Valvemade of Brass suitable for 1.5 Ton Outdoor Unit of Split Type Air Conditioning complete all as directed.
170Supply and fix Discharge Valvemade of Brass suitable for 2 Ton Outdoor Unit of Split Type Air Conditioning complete all as directed.
171Supply and fix Discharge Valvemade of Brass suitable for 4 Ton Outdoor Unit ofStanding Split Type Air Conditioning complete all as directed.
172Disconnection and Removing the defective / damaged Industrial Plug & Socket Board and supply & fix Industrial Plug & Socket controlled by 01 No 15/16 Amp Single Pole ISI Marked in and including sheet metal enclosure suitable for 1.5/2 Ton capacity
173Disconnection and Removing the Cable connections and Copper Pipe alongwith all connected items carefully from the existing indoor and out door units and Pumpdown the refriegerant from Outdoor Unit of tonnage 1.5/2/4 Ton including stabilizer from the existing positions and shifting the AC unit at new place and refixing the outdoor and indoor units with necessary copper tubingincluding topping up of gas and connecting stabilzer etc for its proper functioning complete all as directed.
174Carried out of Leak Proof Test for detection of leakage of gas from the cooling unit & Copper Tubing for Indoor/Outdoor Unit of Air conditioner, Refrigerator, Water Cooler with liquid nitrogen gas and arresting by gas welding method complete and charging of refrigerant into the Air conditioner/Refrigerator/Water Cooler complete. Note:- 1The leakage to be observed for 24 Hours and after confirmation only the refrigerant is to be provided to the unit. 2The cost of refrigerantwill be measured and paid separately under rhe respective Schedule A Item.
175Disconnection and removing theunserviceable / burnt out Copper Cable between Indoor & Outdoor Unit and S&F PVC Insulated, PVC Sheathed, Multistranded CopperCable 3 Core 4 Sqmm, ISI Marked, 1100 volts Grade and connecting to the unit along with necessary fixing materials complete. Make: Polycab/Finolex/Havells
176Disconnection and removing the unserviceable Engine unit 250 KVA diesel engine carefully from the alternator and transporting the same to the work shop for finding of the defects and servicing/ over hauling of Cylinder Head, Injectors, Fuel Pump, Turbo charger, radiator and self starter including renewal of spares such as Piston with pin, Piston rings, Linners, CR bearings, Valves, Gaskets, O Rings, Injector sleeves, gland nuts, cooling nozzles, air filter, hose pipes, hose clips, oil deisel filter set, radiator coolent, Engine oil, water pump etcand refixing the engine after completion of repairs at work shop at its original position and coupled with the alternator and all other accessories testing and commissioning complete. Note : (1) Over hauling items and spares will be measured and paid separately under respective Sch "A" Items.
177Disconnection and removing the unserviceable alternator suitable for 250 KVAdiesel engine Carefully from the engine and transporting the same to the work shop for rewinding the same with single strand fine enamel copper conductor of same guage weight and tons and keeping the windings into hot air oven till the moisture evaporatesand fixing the same init original position duly painted the alternator after completion of repairs connecting the cables and all the accessories testing and commissioning complete. Note : (1) All the misc items such as impregranted paper, warnising, cotton tape and other misc items required for satisfactory completion of job deemed to be included in the unit rate quoted. (2). Bearings, Terminal block and coupling will be measured and paid separately under respective Sch "A" Items.
178Disconnection and removing the unserviceable Engine unit 62.5 KVA diesel engine carefully from the alternator and transporting the same to the work shop for finding of the defects and servicing/ over hauling of Cylinder Head, Injectors, Fuel Pump, Turbo charger, radiator and self starter including renewal of spares such as Piston with pin, Piston rings, Linners, CR bearings, Valves, Gaskets, O Rings, Injector sleeves, gland nuts, cooling nozzles, air filter, hose pipes, hose clips, oil deisel filter set, radiator coolent, Engine oil, water pump etcand refixing the engine after completion of repairs at work shop at its original position and coupled with the alternator and all other accessories testing and commissioning complete. Note : (1) Over hauling items and spares will be measured and paid separately under respective Sch "A" Items.
179Disconnection and removing the unserviceable alternator suitable for 62.5 KVAdiesel engine Carefully from the engine and transporting the same to the work shop for rewinding the same with single strand fine enamel copper conductor of same guage weight and tons and keeping the windings into hot air oven till the moisture evaporatesand fixing the same init original position duly painted the alternator after completion of repairs connecting the cables and all the accessories testing and commissioning complete. Note : (1) All the misc items such as impregranted paper, warnising, cotton tape and other misc items required for satisfactory completion of job deemed to be included in the unit rate quoted. (2). Bearings, Terminal block and coupling will be measured and paid separately under respective Sch "A" Items.
180Supply only element diesel filter with gasket as per exiting make and model for 62.5 /63KVA, capacity of DG set
181All as per Item No 180 here in above butcapacity of 250KVA
182Supply only Corrosion Resistor filter with gasket as per exiting make and model and CR plate for 62.5KVA to 250 KVA capacity of DG set
183Supply only element bypass filter with gasketas per exiting make and modelfor 62.5 KVA to 250 KVA capacity of DG set
184Supply only inner and outer air cleaner element as per exiting make and model for 62.5 KVA to 250 KVA capacity of DG set
185Replacement of AVR unit and supply , fixing, connecting and testing AVR unit suitable for DG set upto 62.5 KVA capacity Make Kirloskar/National/Universal
186Replacement of AVR unit and supply , fixing, connecting and testing AVR unit as per existing make and model suitable for DG set of 250 KVA capacity. Make Kirloskar/National/ Universal.
187Disconnecting and taking out the radiator of 62.5 KVAto 250 KVA3-phase 50 HZ capacity of DG sets and carrying out to work shop, strip opening completer radiator assembly, cleaning of tubes with using de-scaling solution, including soldering / gas welding of leakage of tubes. Cutting the rusted portion of in let or out let tubes including gas welding of new MS water tubes assembling the complete radiator including replacement of gasket, nut bolts, and testing for making it leak proof including oiling/servicing of water cooling assembly , replacing unserviceable parts, re-assembling and fixing the same in position and testing the system complete all as specified and directed by Engineer-in-Charge.
188All as per Item No 187 here in above butcapacity of 250KVA 3-phase 50 HZ
189Supply only rubber hose pipe set as per exiting make and model complete for 62.5 to 63 KVA DG set suitable for water cooling assembly of DG Set.
190Supply only water pump repair kitas per exiting make and model complete for 250 KVA DG set suitable for water cooling assembly of DG Set.
191Supply onlyimpeller water pumpsetas per exiting make and model complete for 62.5 to 63 KVA DG set suitable for water cooling assembly of DG Set.
192Supply only lubrication oil 20 W- 40 grade for DG set. Make: Kirloskar oil/ SERVO OF IOC/HINDUSTAN PETROLEUM/BPCL/ CASTROL)
193Replacement of asbestos ropes with 12mm dia heat and fire resistance of exhaust pipe of any capacity of DG Set complete all as specified and directed by Engineer in charge.
194Disconnecting and taking out defective battery lead and supplying, fixing, connecting and testing battery lead (Heavy duty) PVC insulated with multi strand copper conductor single core of size 25 Sqmm one side fixed with clamp and other side fixed with brass battery terminal of heavy duty for 2 metre length with battery charging complete all as specified and directed Engineer in charge.
195Supply and filling of inhibitor corrosion (Coolent) suitable for radiators of 62.5 KVA to 250 KVA capacity DG set complete all as specified and directed
196Disconnecting and taking down old unserviceable self starter, 12 Volt DC and dismantling complete for repair, servicing, cleaning, varnishing, oiling, reassembling & testing including replacement of the Following parts as per exiting make and model :- (a) Armature – 01 No (b) Solenoid switch – 01 No. (c) Field coils – 01 No. (d) Commutator – 01 No. (e) Carbon brush – 02 Nos. (f) Bendex assembly – 01 No (g) Tension sleeve – 01 No (h) Gear assly -01 No (j)Wiring circuit complete – 1 Set
197M&L for replacement of unserviceable fuel suction & injector return hose pipe with clamps and banjo washers as per existing make and size suitable for 62.5 to 250 KVA 3 phase 50 HZ capacity of DG sets complete all as specified and directed.
198Taking out water separator & under mentioned unserviceable parts from the DG sets of any capacity and supply and fixing of new Water separator& following parts as per exiting make and model:-
199Oil temperature gauge 40°C to 120°C
200Water temperature gauge 40°C to 120°C
201Oil pressure gauge 0 to 7 kg/cm2
202RPM and Hrs meter complete with chain
203Fuel connector
204Hump hose & bend
205Neon lamp with assly complete
206Ampere meter with lead
207Ignition switch along with duplicate keys
208Toggle switch
209Water safety control
210Oil safety control
211Selector switch three way ON/OFF
212Disconnecting and taking out the exhaust system of DG set of any capacityand carrying out cleaning of choked, carbonized exhaust pipe including exhaust .silencer with de-scaling solution, including soldering / gas welding of leakage of pipe. Cutting the rusted portion of pipes including gas welding of pipes assembling the complete exhaust assembly including replacement of gasket, metallic flexible pipe,nut bolts, and testing for making it leak proof and fixing the same in position and testing the system complete all as specified and directed by Engineer-in-Charge.
213M&L for Cleaning of MS fuel tank of DG sets of various capacity by collecting the fuel in cleaned barrelsand removing sludge deposited/accumulated inside the tank of and disposal of sludge at a distance not exceeding 100 metre and cleaning the tank with kerosene oil , replacement of fuel tank strainer and unserviceable fuel gauge with new PVC fuel level indicator or float gauge and refilling the collected fuel after filtration complete all as specified and directed.
214Disconnecting and taking out of unserviceable turbo drain hose and supply and fixing new turbo drain as per existing make and model suitable for 62.5 KVA to 250 KVA DG sets with clips nuts and bolts complete all as specified and directed by Engineer-in-Charge.
215Disconnecting and taking out of unserviceable fuel suction pipe and supply and fixing new PVC flexible pipeas per existing make and size from fuel tank to fuel filter of DG sets complete all as specified and directed by Engineer-in-Charge.
216Disconnection and taking out of defective battery charger and supply and fixing new battery charger 12/24Volts suitable for charging of two batteries including power transformer, Amp meter, Volt meter along with Selector switch and connected accessoriesall as per specified and directed bu Engineer -in- Charge.
217Disconnecting and taking out old unserviceable belts of the DG set and supply and fixing fan belt of size C-49 suitable for DG set engine operation complete all as specified and directed by Engineer-in-Charge. Make : Fenner/Gemini/Hilton
218All as per Item No 217 here in above but size B-33
219All as per Item No 217 here in above but size B-44
220Disconnecting & taking out of existing AMF panel of any description and in any position, of 62.5 KVA to 250 KVA capacity DG set & opening of AMF Panel, checking AC/DC circuits and replacement of unserviceable control wiring with 1.5 Sqmm, single core, copper conductor, flexible, PVC insulated, unsheathed cablesuitable upto 1100 volts confirming to IS-694, taking out, removing and replacement of unserviceable parts / spares / items, reassembling the panel & fixing the same in position and testing the AMF panel on full load aftercompletion of repairsall as specified and directed by Engineer-in-Charge. Note :The quoted rates of the contractor are deemed toinclude forfixing the serviceable parts in position and replacement of unserviceable parts with new parts.The new replaced parts shall bemeasured and paid for separately under appropriate item of Sch `A’ as `supply only ‘ but quoted rates are inclusive of replacement of small/minor parts such as nuts, bolts, washers/lugs/gasketsetc. all as specified and directed by Engineer-in-Charge
221Supply only the SMPS (Switch mode power supply) /Transformer /Rectifier of12 Volts DC supply & following spares/parts/ components of AMF Panels repaired under Schedule `A’ item No 220above here in before. Note : (i)Fixing & testing element of the following items is deemed to be included in the rates quoted by the contractor for respective Schedule `A’ item. (ii) Contractor shall have no claim on account of variation of quantities of following items or non execution of the item.SMPS (Switch mode power supply) /Transformer /Rectifier of12 Volts DC supply
222Electronic timer, type ET-100, suitable of 240 Volts, 50 Hz, AC supply, for0 -10 seconds (ON delay). Make :L&T/PIC/Aditya Electronic
223Electronic timer, suitable of 240 / 415 Volts, 50 Hz, AC supply, for0-60 seconds (OFF delay). Make :L&T / PIC / Aditya Electronic
224Frequency meter 40-99 HZ with selector switch, 96mm X 96mm electromechanical type Make : AE/IMP/Meco / Simco/Rishab
225Selector switch Trickler/Booster/ for auto manual operation for Battery charger voltmeter& Ammeter.
226Ammeter 0-15 Amps, Electromechanical type suitable for existing CTs Make : AE/IMP/Meco / Simco/Rishab.
227Voltmeter 0-30 Volts, Electromechanical type for measuring DC supply. Make : AE/IMP/Meco / Simco/Rishab
228Bimetal overload relay type MNX with relay range 24 – 40 Amps suitable for 3 phase 415 volts, AC supply Make : L&T /Indoasion/Standard
229Electronic DC timer suitable for 12 Volts DC supply, for 0-60 seconds. (on delay). Make :L&T / PIC / Aditya Electronic
230Under voltage relay suitable for 3 phase 415 volts, AC supply Make : PIC / Aditya Electronic
231Engine starting relay with sequence timer & Master timer suitable for 12 / 24 Volts DC supply. Make : PIC / Aditya Electronic
232Selector switch 4 way for auto manual operation for volt meters & Ammeter.
233Indicating lamps neontype with holderfor 12 / 24 volts DC supply (RYB) Make : L&T/BCH
234Electronic timer, suitable of 240 / 415 Volts, 50 Hz, AC supply, for0-180 seconds (ON delay). Make :L&T / PIC / Aditya Electronic
235Ammeter 0-200 Amp/ 0-150 Amps/ 0-100 Amps,Ectromechanical type suitable for existing CTs of class 1.0 Make : AE/IMP/Meco / Simco/Rishab
236Voltmeter 0-50 Volts, Electromechanical type for measuring DC supply. Make : AE/IMP/Meco / Simco/Rishab
237Voltmeter 0-500 Volts,Electromechanical type, for measuring AC supply Make : AE/IMP/Meco / Simco/Rishab
2383 pole Power contactor current rating AC 3 of MNX 200 Amp, 3 phase 415 Volt. Make : C&S/siemens/L&T/Standard /Legrand
2393 pole Power contactor current rating AC 3 of MNX 400 Amp, 3 phase 415 Volt Make : C&S/siemens/L&T/Standard /Legrand
240PLA relay 12 volt DC 11 pin, 2 change over, cat part No 2C/O-MPC-12 Das per existing make and model.
241HRC fuse for 415 volt,250 Amp rating DIN type
242HRC fuse for 415 volt, 350 TO 400Amp rating DIN type.
243HRC fuse for 415 volt, 350 TO 400Amp rating DIN type.
244SSupply and replace self starter 12Volt DCsuitable for DG set 62.5 Kva to 250 KVA make LUCAS or equivalent make all as directed by engineer in charge.
245Supply only of the shim fuel pump governor& following new partsas per existing make and model suitable for fuel injection pump assembly repaired under Schedule `A" item Note :-Fixing element of these items is included under the rates quoted by the contractor for Schedule `A" items
246Shim fuel pump governor
247Kit injector barrel plunger
248Gasket fuel pump
249Gasket Governor set
250Ball Bearing
251Nozzles with copper washers
252Gasket fuel pump
253Screen filter
254Ball check
255Gasket Injector
256Seal ‘O’ ring
257Shaft fuel pump drive
258Shaft tachometer drive
259Bushing tachometer drive
260Seal key way
261Bearing thrust
262Plug injector orifice
263Screen filter
264Seal dust
265Turbo Charger Repairing Kit
266Disconnection and removing the u/s lead acid batteries 12 volts 180 AH carefully from the 62.50KVA to 250 KVA DG Set and S&F new lead acid batteries 12 volts 180 AH suitable for DG Set62.5 to 250 KVAincluding testing and commissioning complete suitable for DG Set62.5KVA to 250KVA with copper lead..
267Disconnection and removing the u/s fuel injection pump carefully from the 250 KVA DG Set and S&F new fuel injection pump unit suitable for DG Set250 KVA Make: Greaves Model TBD4V12 including testing and commissioning complete
268M&L for earthing complete with galvanized steel earth plate eleteode 600mmX600mmX6mm thick buried directly in ground Verticaly to a depath not less than 2.25mtr deep below normal ground level with top edge of earth plate at a depth of not less than 1.5mtr below normal ground level connected to galvanized iron strip 32mmX6mm by means of bolts, nuts, check nuts and washers made out of galvanized iron and GI earth strip protected by 40MM bore light grade GI Pipe as well as 20mm dia medium grade pipe 1.5mtr fixed with funnel and wire mesh as Specified and connected allas shown in electrical plate No 03 of SSR Part I including necessary earth work and excavation in any type of soil and PCC 1:2:4 type B-1 in chamber and 40mm thick 1:2:4 type B-1 cover slab with 6mm dia mield steel bars at 100mm center to center both way with 6mm dia MS hoks Complate all as Specified and as directed by Engineer in charge. NOTE :-The GI strip 32mmx6mm & 40mm bore light grade GI Pipe up to 7.5mtr deep to be included in the rate quoted by the Complated.
269S&F Aluminium lugs for cable of size70 Sqmm complate all as specified and as directed.
270S&F Aluminium lugs for cable of size95 Sqmm complate all as specified and as directed.
271S&F Indoor TypeLT panel board outdoor type double door surface mounted made out of 3mm thick CRCA sheet Steel for load bearing and 2 mm thick for non load bearing and portions mounted on frame angle iron fo suitable size weather proof/veermin proof shutter type with locking arrangment of cubical type prewired with aluminium extendable busbar 250 Amps for 03 phases and aluminium busbar 250 Amps for neutral including suitable CTs etc and powder coated paint, agle iron frame base of size LT Pannel(100CMX120CMX45CM) with provision for fixing of MCCB"s mounting arrangement shall be adjustabile type,Comprising of following complate all as specified. Make of the Panel board confirming to CPRI specifications only. (i)MCCB250 Amps, Breaking capacity 35 KA,4 pole (Change over switch -1 No In coming) (ii)MCCB 63 Amps,Breaking capacity 25 KA,four pole -3 Nos (outgoing) (iii) 4 Nos Aluminium Bus bar ofCapacity 250 Amps forPhase & Neutral (iv)LED/Neon indicator bulb in RYB Colour - 1 Set. (v)Cable gland with necessary end terminations for incoming and out going cables complete (vi) Indication Lamp set of 3 for RYB & N (vii)Digital Ameter with CTs Units - 01 Set (viii) Digital Voltmeter- 01 Set
272Supply, Installation, Commissioning ant testing of Elecrical control LT Pannel indoor totally enclosed,1100 volts, 50 HZ AC supply, 3 Phase factory made fully compartmentalised made out of 3 mm thick CRCA sheet steel for load bearing and 2 mm thick for non load bearing and portions,complete with powder coated front side openable, front side with double door shutter with locking Arrangement, Wall mounted making necessary cable connection with cable Thimble, Aluminium busbar of capacity 250Amp, MCCB"s Connection shall be with Aluminium bus strip of suitable rating from main busbar, LT Pannel size (100CMX120CMX45CM) MCCB"s mounting arrangement shall be adjustable type,Comprising of following complete all as specified. Make of the Panel board confirming to CPRI specifications only.(i) MCCB250 Amps, Breaking capacity 35 KA,4 pole-1 No (In coming) (ii)4 Nos Aluminium Bus bar ofCapacity 250 Amps forPhase & Neutral (iii) MCB SP 6-32 Amp - 48 N0s(out going) (iv) LED/Neon indicator bulb in RYB Colour - 1 Set. (v) Cable gland with necessary end terminations for incoming and out going cables complete (vi) Indication Lamp set of 3 for RYB & N (vii) Digital Ameter and rotery with CTs Units - 01 Set (viii) Digital Voltmeterand rotary - 01 Set
273Supplying, laying, jointing and testing cable XLPE insulated IS 7098 (Part-I) -1988 marked, screened, PVC sheathed, armoured electric power cable (heavy duty) with aluminium conductor for working voltage upto and including 1100 volts, cross sectional area 3.5 core 70 sqmm laid in trenches/fixed on pole/wall/passed through pipe complete all as specified and directed
274All as per Item No 273 herein above but cable size of 3.5 core 95 sqmm
275Supply only element oil filter with gasket as per exiting make and model for of DG set capacity 62.5 KVA to 250 KVA
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail