Annual Comprehensive Maintenance Of Fire Detection System Annual Comprehensive Maintenance Of Fire Detection System Installed At Different Building In The Campus Of Ipgmer_Sskm Hospital Kolkata And Its Annex Hospital And Institute Of Psychiatry Kolkata Un, kolkata-West Bengal

Public Works Department-PWD has published Annual Comprehensive Maintenance Of Fire Detection System Annual Comprehensive Maintenance Of Fire Detection System Installed At Different Building In The Campus Of Ipgmer_Sskm Hospital Kolkata And Its Annex Hospital And Institute Of Psychiatry Kolkata Un. Submission Date for this Tender is 14-07-2022. Flame Detectors Tenders in kolkata West Bengal. Bidders can get complete Tender details and download the document.




Tender Notice

32798778
Annual Comprehensive Maintenance Of Fire Detection System Annual Comprehensive Maintenance Of Fire Detection System Installed At Different Building In The Campus Of Ipgmer_Sskm Hospital Kolkata And Its Annex Hospital And Institute Of Psychiatry Kolkata Un
Open Tender
Indian
West Bengal
kolkata
14-07-2022

Tender Details

Annual Comprehensive Maintenance Of Fire Detection System Annual Comprehensive Maintenance Of Fire Detection System Installed At Different Building In The Campus Of Ipgmer_Sskm Hospital Kolkata And Its Annex Hospital And Institute Of Psychiatry Kolkata Under Sskm H Electrical Sub_Division P.W.Dte.

Key Value

Document Fees
Refer document
EMD
INR 32000.0 /-
Tender Value
Refer document

BOQ Items

Name of Work: Annual comprehensive maintenance of Fire Detection System installed at different building in the campus of IPGME&R-SSKM Hospital,Kolkata & its Annex Hospital and Institute of Psychiatry, Kolkata under SSKM (H) Electrical Sub-Division, P.W.Dte. (For the period of one year).
Sl. No. Item Description
1Day to day preventive & corrective maintenance of the entire Fire Detection system installed at different buildings within the premises of IPGME&R-SSKM Hospital and it"s Annex Hospitals by engaging 1no. skilled and 1 no. un-skilled person in each shift having adequate knowledge & skill in fire detection system as per terms & condition. Rate should be quotated Per Operator/Per Month basis only for this Item
2Replacementcost for following supply & installation ofspare parts (Consumable spares & Emergency spares) as and when required for annual preventive and corrective maintenance of Fire Detection System. (As per attached Annexure I&II)
3Supply, Installation, Testing & Commissioningof Microprocessor based Intelligent, addressable expandable and fully networkable fire alarm 4 loop control panel( VDS / UL /ERTL / LPCB / FM approved ) suitable for the devices as stated in the previous items of this BOQ along with 20% spare capacity witheach loop loading not exceeding 80% of the full capacity of detectors and devices taken together, complying to IS 2189:2008 or its latest amendments, and with minimum 600 character alpha - numericliquid crystal display. The panel shall be soft addressable type and shall be able to give pin point location of all fire/ fault conditions. Further, the panel must be able to automatically switch off respective control switches whenever any alarm is triggered. The Panel should be able to store sufficient numbers of log events in its Memory as per recommended standards.(Make:Siemens)
4Supply, Installation, Testing & Commissioning Microprocessor based Intelligent, addressable expandable and fully networkable fire alarm 2 loop control panel( VDS / UL /ERTL / LPCB / FM approved ) suitable for the devices as stated in the previous items of this BOQ along with 20% spare capacity witheach loop loading not exceeding 80% of the full capacity of detectors and devices taken together, complying to IS 2189:2008 or its latest amendments, and with minimum 600 character alpha - numericliquid crystal display. The panel shall be soft addressable type and shall be able to give pin point location of all fire/ fault conditions. Further, the panel must be able to automatically switch off respective control switches whenever any alarm is triggered. The Panel should be able to store sufficient numbers of log events in its Memory as per recommended standards. (Make: Esser)
5Supply, Installation, Testing & Commissioning analog Addressable Intelligent multi sensor detector (VDS/UL/FM/ULC aproved) with inbuilt optical smok sensors as well as additional heat detector sensor with decentralise intelligence, soft addressable photo thermal type with inbuilt fault isolator as per NFPAstyle 7 wiring complete with base having IP as per recommended standard (Make: Siemens)
6Supply, Installation, Testing & Commissioning analog Addressable Intelligent multi sensor detector (VDS/UL/FM/ULC aproved) with inbuilt optical smok sensors as well as additional heat detector sensor with decentralise intelligence, soft addressable photo thermal type with inbuilt fault isolator as per NFPAstyle 7 wiring complete with base having IP as per recommended standard (Make: Esser)
7Supply, Installation, Testing & Commissioning Addressable Heat Detector (Fixed temperature cum rate of rise)( VDS / UL / FM / ULC approved ) with twistlockable removal base,built - in fault isolator, drift compensation feature etc including connections as per specifications complete as reqd and havingIP as per recommended standard (Note : Detectors without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for every group ofaddressable devices ( Numbers of addressable devices in a group will be as per latest recommended standards )without any additional cost).(Make: Siemens)
8Supply, Installation, Testing & Commissioning Addressable Heat Detector (Fixed temperature cum rate of rise) ( VDS / UL / FM / ULC approved ) with twistlockable removal base,built - in fault isolator, drift compensation feature etc including connections as per specifications complete as reqd and havingIP as per recommended standard (Note : Detectors without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for every group ofaddressable devices ( Numbers of addressable devices in a group will be as per latest recommended standards )without any additional cost). (Make: Esser)
9Supply, Installation, Testing & Commissioning Addressable Loop Powered Hooter (sound output of minimum 90 db )cum strobe (strength of light 10 cd)complete with inbuilt isolator & IP65 base and( VDS / UL / FM / ULC approved) approved.(Make: Siemens)
10Supply, Installation, Testing & Commissioning Addressable Loop Powered Hooter (sound output of minimum 90 db )cum strobe (strength of light 10 cd)complete with inbuilt isolator & IP65 base and( VDS / UL / FM / ULC approved) approved. (Make: Esser)
11Supply, Installation, Testing & Commissioning Addressable Manual Call Point(VDS /UL / FM / ULC approved) soft addressable type within built fault isolatoras per NFPA style 7 wiring complete asrequired. (Make: Siemens)
12Supply, Installation, Testing & Commissioning Addressable Manual Call Point(VDS /UL / FM / ULC approved) soft addressable type within built fault isolatoras per NFPA style 7 wiring complete asrequired(Make: Esser)
13Supplying, installation, testing and commissioning of LED type Response Indicator (VDS / UL / FM / ULC approved) having 2 Nos. red coloured LED lamps including connections etc. (Make: Siemens)
14Supply, Installation, Testing & Commissioning of LED type Response Indicator (VDS / UL / FM / ULC approved) having 2 Nos. red coloured LED lamps including connections etc. (Make: Esser)
15Supply, Installation, Testing & Commissioning of LED type relay Modules (VDS / UL / FM / ULC approved)
16S&Fof MCP Glass in place of damaged one.
17S&F UPS Battery
1812Volt,12Ah SMF
1912Volt, 7Ah SMF
20Supply & Laying of 2 core 1.5 sq.mm FRLS shielded copper cable (for loop)(make: Finolex/RR Kable/Polycab)
21Supply & Laying of 2 core 1.5 sq.mm FRLS shielded copper cable (for loop)(make: Finolex/RR Kable/Polycab)
22Rate should be quotatedinclusive of LWC and all other related related taxes & duties